(ED) DMS502B51 (BACnet Gateway) Eng

Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

EEDEN08-204

technical data

air conditioning systems


BACnet Gateway

2e

1 Outline and Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2 System Outline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

3 System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

4 Compatibility with leading BMS systems . . . . . . . . . . . . . . . . . . . . . . . . 4

5 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

6 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

7 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
BACnet Gateway (DMS502A51) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Option DIII board (DAM411B51) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Option Digital Input / Output (DAM412B51) . . . . . . . . . . . . . . . . . . . . . . . . . . 6

8 Communications Check Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7


BAC net object list ................................................... 7

9 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Outline of functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Main functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Names and functions of each part . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Major functions of air-conditioner devices . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

10 Wiring and Setting Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10


System Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
[DIII-NET master] setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
External wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

• VRV® Systems • Network Solution 1


1 Outline and Features


1. Managing the information on 128 groups of air-conditioners (main units only).
2. Up to 256 groups manageable and controllable at once by adding the optional DIII board.
3. Packaging of air-conditioner objects
* Compatible with BACnet (ANSI/ASHRAE-135)
* Compatible with BACnet/IP (ANSI/ASHRAE-135a)
* Compatible with IEIEJ/p-0003-2000 (plan)
(IEIEJ is Institue of Electrical Installation Engineers of Japan)
4. Conforming to European, Oceanian, Safety and EMC rules and regulations.

2 System Outline
DIII-NET
Block
• Optional controllers for centralised control. Zone Zone
Centralised remote control, unified ON/OFF
control

(64 groups)

•BACnet Gateway
HRV
64 groups x 4 = 256 groups (Total heat exchanger)
when the optional DIII Board is used.
Air-conditioning line

Communication line
(Ethernet) Group: Group of units connected by local remote control
Zone: Several groups are registered as a zone by button
• Building central monitor panel operation of the centralised remote control. Control is
then effected by the zone using the centralised remote
control.
Block

Name Functions
BACnet Gateway (DMS502A51) Interface unit to allow communications between VRV® and BMS. BMS ready to run and monitor the air-conditioning systems through BACnet
communications. Up to 128 groups.
Optional DIII board (DAM411B51) Expansion kit, installed on the BACnet Gateway (DMS502A51), to provide 3 more DIII-NET communication ports. Not usable independently. Up to 256
groups.

NOTES

1 A group consists of several indoor units that can be started or stopped simultaneously. As shown in the figure above, a group consists of several
indoor units wired to the same remote control. For units without remote control, each unit is treated as a group.
2 Several groups are registered as a zone with the centralised remote control. By pushing 1 button of the centralised remote control, all groups within
the same zone can be turned on or off simultaneously.
Building management 1 system controls and monitors air-conditioning equipment by the block. A block consists of 1 or more groups (max. 16), and
can be set without regard for the zones mentioned above. You must, how-ever, take the following things into consideration:
3 If the air-conditioning mode is switched, as a premise, permission for cool/heat selection for indoor units (by remote controller or central remote
controller) must be designated within the program.
4 Program status is basically monitored by observing the data of a representative unit. The contents which can be monitored are therefore restricted
if the representative unit is designated as an adaptor, etc.
Block registration is accomplished through signal transmission from the building control system to the cooler-conditioning system. Because
configuration can be changed while receiving power even after operating, mainte-nance from the maker of the air-conditioning equipment is not
required when changing the configuration.

2 • VRV® Systems • Network Solution


3 System Configuration

DI (1)
Outdoor
G unit
DI (2)
F1 F2 F1 F2 F1 F2

maximum of 64 groups

Outdoor
DI (11) unit
G
DI (12)
F1 F2 F1 F2 F1 F2

Air Conditioning maximum of 64 groups


Network Telephone line
Service System
Telephone
Line Phone

For
RS232C-1

maintenance
RS232C-2 100BASE-TX

Central
monitoring
board
10BASE-T

Power supply
100V-240V
Ethernet DAIKIN D-BACS 50/60Hz
BACnet
Client Power
AC100-240V
~
50/60Hz
DIII-1 DIII-2 Di RS485 Do-1 Do-2

Earth leakage breaker


(install for safety)

Outdoor Terminal contact size: M3.5


unit
Power supply
F1 F2 F1 F2 F1 F2 Air conditioner wiring: 2.00mm2
malfunction

BACnet® Interface
malfunction
maximum of 64 groups

Outdoor DIII-4 Force OFF input


unit G
DIII-3 Force OFF input
F1 F2 F1 F2 F1 F2
DIII-2 Force OFF input
G
maximum of 64 groups DIII-1 Force OFF input
C : 1P191170C

• VRV® Systems • Network Solution 3


4 Compatibility with leading BMS systems


Manufacturer* Type
Andover Controls Continuum ver. 1.6 1.6
Cinmetrics Sauter OPC Server
Honeywell EBI V2.0
Iconix Sauter OPC Server
Invensys
(Sacthwell) System Manager
Polar Soft BACdoor
Johnson Controls Metasys BSI V9.01C
Johnson Controls Metasys N30
Priva
Reliable Systems Mach
Siemens System 600 Apoaee Insight V3.2
Siemens System 600 Apoaee Insight V3.4
Siemens Desigo Insight V1.01
Siemens PX Desigo Insight V2.2
TAC Pacific OPC Server
Trane Tracer Summit
Trend
Tridium Niagara Framework 2.301.321.v1
Trilogy
(*) Please contact your Daikin distributor for further details or other manufacturers concerning compatibility.

5 Specifications
Item Description
Rated Electrical conditions Rated Voltage and Frequency Single Phase AC 200-240, 50/60 Hz
Rated Power Maximum 20 W
Conditions for Use Power Supply Fluctuation ±10% of the Rated Value
Ambient Temperature -10~+50°C
Ambient Humidity 0~98° (Sweating is not acceptable)
Preservation Temperature -20~+60°C
Performance Insulation Resistance 50MΩ or more by DC500 megohmmeter
Mass 2.8 kg
Components
The following parts are attached to this unit. Make sure to check them before installation.

BACnet Gateway Adapter 232C for connection


Installation manual
DMS502A51 with the central monitoring board
and wire clamp materials

4 • VRV® Systems • Network Solution


6 Accessories
Item Description
DIII board DAM411B51 Extension of 2 x DIII lines (2 x 64) indoor units
Digital input /output DAM412B51 For forced shutdown
Interface adapters KRP928A2S For connection to Split units
DTA102A52 For connection to R-22/R-407C Sky Air units
DTA112B51 For connection to R-410A Sky Air units

7 Dimensions
7-1 BACnet Gateway (DMS502A51)

BACnet Gateway outside drawing


(DMS502B51)
24 - M2.5 4 - M3.5
Line

D-SUB 9Pin
(male)
Phone

D-SUB 9Pin
RS232C-1

Di Board

Di Board
(male)

PCMCIA
RS232C-2
100BASE-TX
10BASE-T

BACKUP
DAIKIN D-BACS

Power

OFF ON
POWER
AC100-240V
~
50/60Hz

4 - M3.5 4 - M3.5 3 - M3.5

10 - M2.5

3D056945

• VRV® Systems • Network Solution 5


7 Dimensions
7-2 Option DIII board (DAM411B51)
This kit is for adding 2 ports to the DIII-NET communication port by installing it on the BACnet Gateway DMS502A51. The kit can not be solely used.

(27) (12.7)
Outside dimensions of PCB

Board
30±3

140±1.2

(104.5) Master central setting connector

C : 1P191165B

7-3 Option Digital Input / Output (DAM412B51)

(28.86) (8.5)
Outside dimensions of PCB

30±3
140±1.2

(104.5)

C : 1P191166C

6 • VRV® Systems • Network Solution


8 Communications Check Sheet


8-1 BAC net object list

Unit
Memner Object name
Name Object type Inactive Active
number (XXX: Air Con Logical Group Number)
Text-1 Text-2 Text-3 Text-4
1 Start/stop (setting) (Note 2) Start stop command_XXX BO Stop Operation
2 Start/stop (status) Start stop status_XXX BI Stop Operation
3 Alarm Alarm_XXX BI Normal Malfunction
4 Malfunction code Malfunction code_XXX MI Normal Manufacturer specific
5 Air conditioner mode (Setting) (Note 2) AirConModeCommand_XXX MO Cooling Heating Fan Auto
6 Air-conditioning mode (status) AirConModeStatus_XXX MI Cooling Heating Fan
7 Air flow rate level (setting) (Note 2) Air flowRate command_XXX MO Low High
8 Air flow rate level (status) AirFlowRateStatus_XXX MI Low Gigh
9 Measured room temperature (Note 1) Roomtemp_XXX AI °C
10 Set room temerature (Note 2) TempAdjust_XXX AV °C
11 Filter sign signal FilterSign_XXX BI No Yes
12 Filter sign segnal reset FilterSignReset_XXX BV Reset
13 Remote control enable / disable (start / stop) RemoteControlStart_XXX BV Enabled Disabled
14 Remote control enable / disable (air-conditioning RemoteControlAirConModeSet_XXX BV Enabled Disabled
mode)
15 Blank
16 Remote controller enable / disable (set RemoteControlTempAdjust_XXX BV Enabled Disabled
temperature)
(*)17 Central control ‘lower central control disable) CL_Rejection_XXX BV Enabled Disabled
18 Blank
19 Accumulated power ElecTotalPower_XXX BV Enabled Disabled
20 Communication status CommunicationStatus_XXX BI Normal Communication
communication error
(*)21 Forced system stop SystemForcedOff_XXX BV Clearance Forced stop
22 Air direction (setting) (Note 2) AirDirectionCommand_XXX AV
23 Air direction (status) AirDirectionStatus_XXX AI
24 Forced thermostat disble (setting) ForcedThermoOFFCommand_XXX BO Clearance Set
25 Forced thermostat disable (status) ForcedThermoOFFStatus_XXX BI Clearance Set
26 Energy saving (setting) Energy EfficiencyCommand_XXX BO Clearance Set
27 Energy saving (status) EnergyEfficiencyStatus_XXX BI Clearance Set
28 Thermostat status ThermoStatus_XXX BI OFF ON
29 Compressor status CompressorStatus_XXX BI Stop Operation
30 Indoor fan status IndoorFanStatus_XXX BI Stop Operation
31 Heater operation status HeaterStatus_CCC BI Stop Operation
Central control (lower central control disable) and orced systemm stop are obly available for 000, 064, 128, and 192.

NOTES

1 The room temperature is measured with the suction air. Since the indoor unit fan stops when the thermostat is disabled or the air conditioner is
stopped, or in z special operation such as defrosting, temperature measurement may be affected by the heat exchanger, and may detect and
transmit a different temperature from the actual room temperature, For this reason, this value should be considered as a reference for the room
temperature.
If the building management system manufacturer uses this value for system control (e.g., switching the airconditioning mode or preset
temperature), the manufactureer must take on the whole responsibility.
2 The air conditioner saves the settings for the temperature, start/stop status, air-conditioning mode, air direction, and air flow rate in the nonvolatile
memory each time they are changed, so that the settings will not be lost when a power cut occurs. This nonvolatile memory has a write count limit
and may cause a failure if it is written exceeding the limit count.
Therefore when the temperature, start / stop status, air-conditioning mode, air direction, and air flow rate of each indoor unit are automatically
controlled from the central monitoring panel, be sure that the number of changes for each setting should not exceed 7,000 timer per year.

• VRV® Systems • Network Solution 7


9 Function
9-1 Outline of functions
• This BACnet Gateway enables interfacing between the VRV® system and central monitoring board.
• Data of up to 256 groups of air conditioner (when the option DIII board is used) are controllable by the BACnet Gateway.
• Air conditioners are operable and the state can be monitored from the central monitoring board by BACnet communication.

9-2 Main functions


The BACnet Gateway can monitor and control air conditioners from a maximum of 256 groups, on a unit by unit basis.
Major features are listed below.
1. Switches the ON/OFF operation and monitors operational state. 5. Monitors and resets filter clean sign.
2. Monitors indoor units for malfunctions. 6. Switches the operation mode.
3. Monitors and changes temperature. 7. Sets remote control operation
4. Monitors indoor unit temperature. 8. PPD data is available on BMS-system

9-3 Names and functions of each part

RS232C connector for


PC communication
Modem connector for Air Connector for connecting
Conditioning Network with PC for commissioning
Service System LED display
When using Air Conditioning DIII-4 It flashes when it receives/transmits data from/to the
Network Service RCV equipment connected with DIII-4 such as air conditioners
Systemservice, connect it to
the telephone line RS232C connector for central monitoring Terminal block for watt hour meter (option) Terminal block for DII-NET DIII-3 It flashes when it receives/transmits data from/to the
board communication communication (option) RCV equipment connected with DIII-3 such as air conditioners

DIII Board
This is used when distribution the power
Di Board

This connector for connecting with the central


monitoring board using RS232C. supply to indoor units (No Voltage) Terminal block for communication
(option model name: DAM412B51 with air conditoners
(option model name: DAM411B51)

(15) 263
(13)
130 DAIKIN D-BACS
CPU ETHER
ALIVE ALRN LINK

Power
68.5 DIII
RCV
ETHER AC100-240V
~
50/60Hz
DIII-1 DIII-2 Di RS485 Do-1 Do-2
Line
Phone
RS232C-1

DIII Board
Di Board

PCMCIA
RS232C-2

275

260

CPU ETHER
100BASE-TX

BACKUP
10BASE-T

ALIVE ALRM LINK


DAIKIN D-BACS
CPU ETHER
ALIVE ALRM LINK

Power
RCV
AC100-240V RCV
OFF ON
POWER

DIII ETHER
~
50/60Hz DIII ETHER
DIII-1 DIII-2 Di RS485 Do-1 Do-2

Power supply switch


Terminal block for DII-NET Turn this switch to
communication ON when using
Terminal block for
Terminal block for force Power supply
communication with air
stop input of indoor unit terminal block
conditoners
This is used when stopping the Earth terminal block
Connect the lines with
Connector for BACnet indoor units compulsorily by Make sure to connect AC100-240V
communication contact input (No Voltage) the earth wire
This connector is used for
communicating with a client by Terminal block for contact output 4.5
BACnet communication system Do-1: ON when the unit malfunctions R2.25
9

Do-2: ON when an air conditioner


malfunctions

ø10

Detailed drawing of fixing hole

1P191169C

LED display
CPU ALIVE It flashes when the unit is in normal operation.
CPU ALRM It flashes when the unit is abnormal operation.
D III -1 It flashes when it receives/transmits data from/to the equipment connected with DIII-1
such as air conditioners
DIII-2 It flashes when it receives/transmits data drom/to the equipment connected with DIII-2
such as air conditioners
Ether RCV It flashes when it receives/tranmits data from/to BACnet client.
Ether link It lights when the 10BASE-T acable or 100BASE-TX cable
RS485 (TxD) This LED display cannot be used with this unit
RS485 (RxD) This LED display cannot be used with this unit
RS232C-1 (TxD) It flashen when it tramits data to PC
RS232C0-1 (RxD) It flashen when it receives data from PC
RRS232C-2(TxD) It flashes when it tranmits data to the central minitoring board.
RS232C-2(RxD) It flashes when it receives data from the central minotoring board.

8 • VRV® Systems • Network Solution


9 Function
9-4 Major functions of air-conditioner devices
Air-conditioning equipment

Function Interface adapter Wiring adapter Remarks


VRV Inverter
for Sky Air series HRV for other
series
(SA Heat Pump) air-conditioners
Start/stop control and monitoring 0 0 0 0

Air-conditioner error notification 0 0 0 0

Indoor air temperature monitoring 0 0 Χ Χ

Temperature setting and monitoring 0 0 16~32 Χ Χ

Air-conditioning mode switching is effective only for indoor


Air-conditioning mode setting and monitoring 0 0 Χ Χ
units for which cool/heat selection is permitted.
*1 Remote control mode setting and monitoring 0 0 Χ Χ

Filter sign monitoring and reset 0 Χ Χ Χ

Cumulative power value monitoring 0 Χ Χ 0

Thermostat status monitoring 0 Χ Χ Χ

Compressor operation status monitoring 0 Χ Χ Χ

Indoor fan operation status monitoring 0 Χ Χ Χ

Heater operation status monitoring 0 Χ Χ Χ

Air direction setting and monitoring 0 Χ Χ Χ

Air flow rate setting and monitoring 0 Χ Χ Χ

Forced thermostat off setting and monitoring 0 *2 Χ Χ Χ

Forced thermostat on setting and monitoring 0 *2 0 *2 Χ Χ

Energy efficiency command (Setting temperature 0 Χ Χ Χ


shift)

NOTES

1 *1: Remote control mode is for acceptance or rejection of on/off operation, temperature setting and air conditioning mode setting by remote control.
2 *2: If set locally, the host is not notified. Thus, monitoring cannot be accomplished from the host.
3 The meaning of 0, Χ are as follows
0: Possible functions
Χ: Impossible functions

• VRV® Systems • Network Solution 9


10 Wiring and Setting Procedures


10 - 1 System Wiring

DI (1)
Outdoor
G unit
DI (2)
F1 F2 F1 F2 F1 F2

maximum of 64 groups

Outdoor
DI (11) unit
G
DI (12)
F1 F2 F1 F2 F1 F2

Air Conditioning
Network maximum of 64 groups
Telephone line
Service System
Telephone
Line Phone

For
RS232C-1

maintenance
RS232C-2 100BASE-TX

Central
monitoring
board
10BASE-T

Power supply
100V-240V
Ethernet DAIKIN D-BACS 50/60Hz
BACnet
Client Power
AC100-240V
~
50/60Hz
DIII-1 DIII-2 Di RS485 Do-1 Do-2

Earth leakage breaker


(install for safety)

Outdoor Terminal contact size: M3.5


unit
Power supply
F1 F2 F1 F2 F1 F2 Air conditioner wiring: 2.00mm2
malfunction

BACnet® Interface
malfunction
maximum of 64 groups

Outdoor DIII-4 Force OFF input


unit G
DIII-3 Force OFF input
F1 F2 F1 F2 F1 F2
DIII-2 Force OFF input
G
maximum of 64 groups DIII-1 Force OFF input
C : 1P191170C

10 - 2 [DIII-NET master] setting


Make sure to connect the unit with [DIII-NET master]. Do not remove the master central setting connector.
Remove the master central setting connectors of the centralised management controllers or ON/OFF controllers when using togheter with other
centralised controllers such as centralised management controllers or ON/OFF controllers.

10 • VRV® Systems • Network Solution


10 Wiring and Setting Procedures


10 - 3 External wiring
Everything relating with field wiring must be supplied in the field.

10 - 3 - 1.Ethernet communication wiring


Field supplied
DMS502B51 HUB
BACnet
Ethernet 10BASE-T straight cable client
10BASE-T

10 - 3 - 2.DIII-NET wiring
DMS502A51 Outdoor
unit Recommended wire size 0.75~1.25mm2
Polarity: No

Outdoor F1 F2 F1 F2 F1 F2 F1 F2
Polarity: No unit

F1 F2 F1 F2 F1 F2 F1 F2
Terminal contact size: M3.5

DAM411B51 (Option) Outdoor


Polarity: No unit Recommended wire size 0.75~1.25mm2

Outdoor F1 F2 F1 F2 F1 F2 F1 F2
Polarity: No unit

F1 F2 F1 F2 F1 F2 F1 F2
Terminal contact size: M3.5

CAUTIONS

1 Do not use multicore cables with three or more cores.


2 Use wires of sizes between 0.75 mm2 and 1.25 mm2.
3 Wire length: Max 1,000 m
4 Do not bind the wire for DIII-NET
5 Wirings for DIII-NET must be isolated from the power lines.

• VRV® Systems • Network Solution 11


10 Wiring and Setting Procedures


10 - 3 External wiring

10 - 3 - 3.Do-1 and 2

DMS502A51
Recommended wire size 0.75~2 mm2
Lamp or the like

Lamp or the like


No voltage contact output contact specification is as follows
Do-1 : ON when the unit malfunctions : Allowable current 10m A~1 A
Do-2 : ON when an air conditioner malfunctions : Allowable voltage MAX, AC250 V
Wiring length : Max. 150 m
Terminal contact size : M4

Main specifications
Temperature range -10~50°C
Humidity range 0~98% (No frost formation)
Power supply 1~AC200-240V 50/60Hz
Power consumption Max.20 W
Weight 4.0 Kg

12 • VRV® Systems • Network Solution


2e

Daikin’s unique position as a manufacturer of air Daikin Europe N.V. is approved by LRQA for its The present publication is drawn up by way of information only and
conditioning equipment, compressors and Quality Management System in accordance with the does not constitute an offer binding upon Daikin Europe N.V.. Daikin
refrigerants has led to its close involvement in ISO9001 standard. ISO9001 pertains to quality Europe N.V. has compiled the content of this publication to the best
environmental issues. For several years Daikin assurance regarding design, development, of its knowledge. No express or implied warranty is given for the
has had the intension to become a leader in the manufacturing as well as to services related to the completeness, accuracy, reliability or fitness for particular purpose of
Prepared in Belgium by Lannoo (www.lannooprint.be), a company whose concern for

provision of products that have limited impact product. its content and the products and services presented therein.
on the environment. This challenge demands Specifications are subject to change without prior notice. Daikin
Responsible Editor: Daikin Europe N.V., Zandvoordestraat 300, B- 8400 Oostende

the eco design and development of a wide Europe N.V. explicitly rejects any liability for any direct or indirect
range of products and an energy management damage, In the broadest sense, arising from or related to the use
system, resulting in energy conservation and a and/or interpretation of this publication. All content is copyrighted
reduction of waste. ISO14001 assures an effective environmental by Daikin Europe N.V..
management system in order to help protect human
health and the environment from the potential
the environmont is set in the EMAS and ISO 14001 systems.

impact of our activities, products and services and to


EEDEN08-204 • 01/2008 • Copyright © Daikin

assist in maintaining and improving the quality of the


environment.
The present publication supersedes EEDEN07-200

Daikin units comply with the European


regulations that guarantee the safety of
the product.

Naamloze Vennootschap
Zandvoordestraat 300
B-8400 Oostende, Belgium
VRV®products are not within the scope of the
www.daikin.eu Eurovent certification programme.
BTW: BE 0412 120 336
RPR Oostende

ÈEEDEN08-204aËÍ

You might also like