(ED) DMS502B51 (BACnet Gateway) Eng
(ED) DMS502B51 (BACnet Gateway) Eng
(ED) DMS502B51 (BACnet Gateway) Eng
technical data
2e
•
2 System Outline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3 System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
5 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
6 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
7 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
BACnet Gateway (DMS502A51) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Option DIII board (DAM411B51) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Option Digital Input / Output (DAM412B51) . . . . . . . . . . . . . . . . . . . . . . . . . . 6
9 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Outline of functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Main functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Names and functions of each part . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Major functions of air-conditioner devices . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2 System Outline
DIII-NET
Block
• Optional controllers for centralised control. Zone Zone
Centralised remote control, unified ON/OFF
control
(64 groups)
•BACnet Gateway
HRV
64 groups x 4 = 256 groups (Total heat exchanger)
when the optional DIII Board is used.
Air-conditioning line
Communication line
(Ethernet) Group: Group of units connected by local remote control
Zone: Several groups are registered as a zone by button
• Building central monitor panel operation of the centralised remote control. Control is
then effected by the zone using the centralised remote
control.
Block
Name Functions
BACnet Gateway (DMS502A51) Interface unit to allow communications between VRV® and BMS. BMS ready to run and monitor the air-conditioning systems through BACnet
communications. Up to 128 groups.
Optional DIII board (DAM411B51) Expansion kit, installed on the BACnet Gateway (DMS502A51), to provide 3 more DIII-NET communication ports. Not usable independently. Up to 256
groups.
NOTES
1 A group consists of several indoor units that can be started or stopped simultaneously. As shown in the figure above, a group consists of several
indoor units wired to the same remote control. For units without remote control, each unit is treated as a group.
2 Several groups are registered as a zone with the centralised remote control. By pushing 1 button of the centralised remote control, all groups within
the same zone can be turned on or off simultaneously.
Building management 1 system controls and monitors air-conditioning equipment by the block. A block consists of 1 or more groups (max. 16), and
can be set without regard for the zones mentioned above. You must, how-ever, take the following things into consideration:
3 If the air-conditioning mode is switched, as a premise, permission for cool/heat selection for indoor units (by remote controller or central remote
controller) must be designated within the program.
4 Program status is basically monitored by observing the data of a representative unit. The contents which can be monitored are therefore restricted
if the representative unit is designated as an adaptor, etc.
Block registration is accomplished through signal transmission from the building control system to the cooler-conditioning system. Because
configuration can be changed while receiving power even after operating, mainte-nance from the maker of the air-conditioning equipment is not
required when changing the configuration.
3 System Configuration
DI (1)
Outdoor
G unit
DI (2)
F1 F2 F1 F2 F1 F2
maximum of 64 groups
Outdoor
DI (11) unit
G
DI (12)
F1 F2 F1 F2 F1 F2
For
RS232C-1
maintenance
RS232C-2 100BASE-TX
Central
monitoring
board
10BASE-T
Power supply
100V-240V
Ethernet DAIKIN D-BACS 50/60Hz
BACnet
Client Power
AC100-240V
~
50/60Hz
DIII-1 DIII-2 Di RS485 Do-1 Do-2
BACnet® Interface
malfunction
maximum of 64 groups
5 Specifications
Item Description
Rated Electrical conditions Rated Voltage and Frequency Single Phase AC 200-240, 50/60 Hz
Rated Power Maximum 20 W
Conditions for Use Power Supply Fluctuation ±10% of the Rated Value
Ambient Temperature -10~+50°C
Ambient Humidity 0~98° (Sweating is not acceptable)
Preservation Temperature -20~+60°C
Performance Insulation Resistance 50MΩ or more by DC500 megohmmeter
Mass 2.8 kg
Components
The following parts are attached to this unit. Make sure to check them before installation.
6 Accessories
Item Description
DIII board DAM411B51 Extension of 2 x DIII lines (2 x 64) indoor units
Digital input /output DAM412B51 For forced shutdown
Interface adapters KRP928A2S For connection to Split units
DTA102A52 For connection to R-22/R-407C Sky Air units
DTA112B51 For connection to R-410A Sky Air units
7 Dimensions
7-1 BACnet Gateway (DMS502A51)
D-SUB 9Pin
(male)
Phone
D-SUB 9Pin
RS232C-1
Di Board
Di Board
(male)
PCMCIA
RS232C-2
100BASE-TX
10BASE-T
BACKUP
DAIKIN D-BACS
Power
OFF ON
POWER
AC100-240V
~
50/60Hz
10 - M2.5
3D056945
7 Dimensions
7-2 Option DIII board (DAM411B51)
This kit is for adding 2 ports to the DIII-NET communication port by installing it on the BACnet Gateway DMS502A51. The kit can not be solely used.
(27) (12.7)
Outside dimensions of PCB
Board
30±3
140±1.2
C : 1P191165B
(28.86) (8.5)
Outside dimensions of PCB
30±3
140±1.2
(104.5)
C : 1P191166C
Unit
Memner Object name
Name Object type Inactive Active
number (XXX: Air Con Logical Group Number)
Text-1 Text-2 Text-3 Text-4
1 Start/stop (setting) (Note 2) Start stop command_XXX BO Stop Operation
2 Start/stop (status) Start stop status_XXX BI Stop Operation
3 Alarm Alarm_XXX BI Normal Malfunction
4 Malfunction code Malfunction code_XXX MI Normal Manufacturer specific
5 Air conditioner mode (Setting) (Note 2) AirConModeCommand_XXX MO Cooling Heating Fan Auto
6 Air-conditioning mode (status) AirConModeStatus_XXX MI Cooling Heating Fan
7 Air flow rate level (setting) (Note 2) Air flowRate command_XXX MO Low High
8 Air flow rate level (status) AirFlowRateStatus_XXX MI Low Gigh
9 Measured room temperature (Note 1) Roomtemp_XXX AI °C
10 Set room temerature (Note 2) TempAdjust_XXX AV °C
11 Filter sign signal FilterSign_XXX BI No Yes
12 Filter sign segnal reset FilterSignReset_XXX BV Reset
13 Remote control enable / disable (start / stop) RemoteControlStart_XXX BV Enabled Disabled
14 Remote control enable / disable (air-conditioning RemoteControlAirConModeSet_XXX BV Enabled Disabled
mode)
15 Blank
16 Remote controller enable / disable (set RemoteControlTempAdjust_XXX BV Enabled Disabled
temperature)
(*)17 Central control ‘lower central control disable) CL_Rejection_XXX BV Enabled Disabled
18 Blank
19 Accumulated power ElecTotalPower_XXX BV Enabled Disabled
20 Communication status CommunicationStatus_XXX BI Normal Communication
communication error
(*)21 Forced system stop SystemForcedOff_XXX BV Clearance Forced stop
22 Air direction (setting) (Note 2) AirDirectionCommand_XXX AV
23 Air direction (status) AirDirectionStatus_XXX AI
24 Forced thermostat disble (setting) ForcedThermoOFFCommand_XXX BO Clearance Set
25 Forced thermostat disable (status) ForcedThermoOFFStatus_XXX BI Clearance Set
26 Energy saving (setting) Energy EfficiencyCommand_XXX BO Clearance Set
27 Energy saving (status) EnergyEfficiencyStatus_XXX BI Clearance Set
28 Thermostat status ThermoStatus_XXX BI OFF ON
29 Compressor status CompressorStatus_XXX BI Stop Operation
30 Indoor fan status IndoorFanStatus_XXX BI Stop Operation
31 Heater operation status HeaterStatus_CCC BI Stop Operation
Central control (lower central control disable) and orced systemm stop are obly available for 000, 064, 128, and 192.
NOTES
1 The room temperature is measured with the suction air. Since the indoor unit fan stops when the thermostat is disabled or the air conditioner is
stopped, or in z special operation such as defrosting, temperature measurement may be affected by the heat exchanger, and may detect and
transmit a different temperature from the actual room temperature, For this reason, this value should be considered as a reference for the room
temperature.
If the building management system manufacturer uses this value for system control (e.g., switching the airconditioning mode or preset
temperature), the manufactureer must take on the whole responsibility.
2 The air conditioner saves the settings for the temperature, start/stop status, air-conditioning mode, air direction, and air flow rate in the nonvolatile
memory each time they are changed, so that the settings will not be lost when a power cut occurs. This nonvolatile memory has a write count limit
and may cause a failure if it is written exceeding the limit count.
Therefore when the temperature, start / stop status, air-conditioning mode, air direction, and air flow rate of each indoor unit are automatically
controlled from the central monitoring panel, be sure that the number of changes for each setting should not exceed 7,000 timer per year.
9 Function
9-1 Outline of functions
• This BACnet Gateway enables interfacing between the VRV® system and central monitoring board.
• Data of up to 256 groups of air conditioner (when the option DIII board is used) are controllable by the BACnet Gateway.
• Air conditioners are operable and the state can be monitored from the central monitoring board by BACnet communication.
DIII Board
This is used when distribution the power
Di Board
(15) 263
(13)
130 DAIKIN D-BACS
CPU ETHER
ALIVE ALRN LINK
Power
68.5 DIII
RCV
ETHER AC100-240V
~
50/60Hz
DIII-1 DIII-2 Di RS485 Do-1 Do-2
Line
Phone
RS232C-1
DIII Board
Di Board
PCMCIA
RS232C-2
275
260
CPU ETHER
100BASE-TX
BACKUP
10BASE-T
Power
RCV
AC100-240V RCV
OFF ON
POWER
DIII ETHER
~
50/60Hz DIII ETHER
DIII-1 DIII-2 Di RS485 Do-1 Do-2
ø10
1P191169C
LED display
CPU ALIVE It flashes when the unit is in normal operation.
CPU ALRM It flashes when the unit is abnormal operation.
D III -1 It flashes when it receives/transmits data from/to the equipment connected with DIII-1
such as air conditioners
DIII-2 It flashes when it receives/transmits data drom/to the equipment connected with DIII-2
such as air conditioners
Ether RCV It flashes when it receives/tranmits data from/to BACnet client.
Ether link It lights when the 10BASE-T acable or 100BASE-TX cable
RS485 (TxD) This LED display cannot be used with this unit
RS485 (RxD) This LED display cannot be used with this unit
RS232C-1 (TxD) It flashen when it tramits data to PC
RS232C0-1 (RxD) It flashen when it receives data from PC
RRS232C-2(TxD) It flashes when it tranmits data to the central minitoring board.
RS232C-2(RxD) It flashes when it receives data from the central minotoring board.
9 Function
9-4 Major functions of air-conditioner devices
Air-conditioning equipment
NOTES
1 *1: Remote control mode is for acceptance or rejection of on/off operation, temperature setting and air conditioning mode setting by remote control.
2 *2: If set locally, the host is not notified. Thus, monitoring cannot be accomplished from the host.
3 The meaning of 0, Χ are as follows
0: Possible functions
Χ: Impossible functions
DI (1)
Outdoor
G unit
DI (2)
F1 F2 F1 F2 F1 F2
maximum of 64 groups
Outdoor
DI (11) unit
G
DI (12)
F1 F2 F1 F2 F1 F2
Air Conditioning
Network maximum of 64 groups
Telephone line
Service System
Telephone
Line Phone
For
RS232C-1
maintenance
RS232C-2 100BASE-TX
Central
monitoring
board
10BASE-T
Power supply
100V-240V
Ethernet DAIKIN D-BACS 50/60Hz
BACnet
Client Power
AC100-240V
~
50/60Hz
DIII-1 DIII-2 Di RS485 Do-1 Do-2
BACnet® Interface
malfunction
maximum of 64 groups
10 - 3 - 2.DIII-NET wiring
DMS502A51 Outdoor
unit Recommended wire size 0.75~1.25mm2
Polarity: No
Outdoor F1 F2 F1 F2 F1 F2 F1 F2
Polarity: No unit
F1 F2 F1 F2 F1 F2 F1 F2
Terminal contact size: M3.5
Outdoor F1 F2 F1 F2 F1 F2 F1 F2
Polarity: No unit
F1 F2 F1 F2 F1 F2 F1 F2
Terminal contact size: M3.5
CAUTIONS
10 - 3 - 3.Do-1 and 2
DMS502A51
Recommended wire size 0.75~2 mm2
Lamp or the like
Main specifications
Temperature range -10~50°C
Humidity range 0~98% (No frost formation)
Power supply 1~AC200-240V 50/60Hz
Power consumption Max.20 W
Weight 4.0 Kg
Daikin’s unique position as a manufacturer of air Daikin Europe N.V. is approved by LRQA for its The present publication is drawn up by way of information only and
conditioning equipment, compressors and Quality Management System in accordance with the does not constitute an offer binding upon Daikin Europe N.V.. Daikin
refrigerants has led to its close involvement in ISO9001 standard. ISO9001 pertains to quality Europe N.V. has compiled the content of this publication to the best
environmental issues. For several years Daikin assurance regarding design, development, of its knowledge. No express or implied warranty is given for the
has had the intension to become a leader in the manufacturing as well as to services related to the completeness, accuracy, reliability or fitness for particular purpose of
Prepared in Belgium by Lannoo (www.lannooprint.be), a company whose concern for
provision of products that have limited impact product. its content and the products and services presented therein.
on the environment. This challenge demands Specifications are subject to change without prior notice. Daikin
Responsible Editor: Daikin Europe N.V., Zandvoordestraat 300, B- 8400 Oostende
the eco design and development of a wide Europe N.V. explicitly rejects any liability for any direct or indirect
range of products and an energy management damage, In the broadest sense, arising from or related to the use
system, resulting in energy conservation and a and/or interpretation of this publication. All content is copyrighted
reduction of waste. ISO14001 assures an effective environmental by Daikin Europe N.V..
management system in order to help protect human
health and the environment from the potential
the environmont is set in the EMAS and ISO 14001 systems.
Naamloze Vennootschap
Zandvoordestraat 300
B-8400 Oostende, Belgium
VRV®products are not within the scope of the
www.daikin.eu Eurovent certification programme.
BTW: BE 0412 120 336
RPR Oostende
ÈEEDEN08-204aËÍ