Abstract
This application note serves as a detailed reference of the functionality of the Air Distribution Unit (ADU). It also discusses the use and
implementation of the product in raised floor environments.
Introduction
The Air Distribution Unit (ADU) aids in thermal issues that occur in raised floor IT spaces. These issues include thermal gradient or
mixing of air from floor to ceiling and low static pressures under the raised floor. The ADU fans ensure the distribution of conditioned air
to the IT inlet by pulling airflow into the enclosure and positioning this flow to the equipment inlet.
1
©2006 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,
or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2006-1
How and When to Implement (Raised Floor Only)
Static Pressure Problems
Obstructions such as cabling, piping, or boxes are frequently placed under the raised floor during the life of a facility. These
obstructions were most likely not accounted for in the initial room design and therefore the under-floor distribution of air may
not react as intended. The addition of these obstructions may create a higher pressure drop (ΔP) than the ΔP of the
perforated floor tile. The end result will be a non-uniform distribution of air to the room.
The IT equipment fans will draw the airflow they require from the room even if there is no conditioned air being supplied
through the floor tile. When this occurs, hot aisle air can be pulled over the top of the IT enclosure and used at the IT
equipment inlet. This re-circulation of exhaust air is a major cause of hot spots. The ADU can overcome most under-floor
obstructions by pulling air to the required location under the floor. This changes the flow paths under the raised floor and
distributes the conditioned air from the CRAC (Computer Room Air Conditioner) to the IT enclosure inlet minimizing the
potential for occurrence of hot spots.
Note: Special care must be taken to remove perforated tiles from the front of IT enclosures in this application and replace it
with a standard floor tile. If the perforated tile is left in place, the perforation becomes a point of least resistance and the ADU
could pull room air through the tile. The resulting effect could be a short circuit of air from the adjacent hot aisle.
2
____________________________________________________________________________________________________
©2006 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,
or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2006-1
APC APPLICATION NOTE
or
In properly designed IT space, 2-3 kW load can be cooled without supplemental cooling or air distribution at the enclosure.
One of the reasons this can be achieved is that the kW load is concentrated near the bottom ½ of the enclosure. The air
remains cool at the lower portion of the room unaffected by thermal gradient. When higher loads are spread across the
enclosure, two issues combine to create a hot spot.
The first issue is thermal gradient. Rising air from the hot aisle spreads across the ceiling. When this heated air is not
removed quickly enough from the IT space it mixes with the cold aisle air stream causing mixing. This mixed air is often pulled
into the upper 1/2 to 1/3 of the enclosure and used as inlet air for the IT equipment.
The second issue is the need for additional airflow in higher density applications. As the kW load of equipment increases so
does the need for air to cool that load. IT equipment fans will naturally pull air from the point of least resistance. If the
perforated tile does not supply a curtain of cool air to the entire face of the IT enclosure this demand for airflow will be supplied
by whatever is available at that height in the room. This is when re-circulation from the hot aisle to cold aisle occurs.
Medium densities can be obtained by the use of the ADU with perforated tiles in a properly designed data center. If this
application is to be used then effort must be taken to ensure that the CFM entering the raised floor plenum from the CRACs
exceeds the combined airflow capabilities of the ADU and perforated tiles by 30% due to leakages in the raised floor. Only
when this is the case will the additional airflow required for medium densities at the IT enclosure become attainable.
Conclusions
The ADU should be used if you have a low static pressure issue under the raised floor up to 3kW.
3
___________________________________________________________________________________________________
©2006 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,
or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2006-1
APC APPLICATION NOTE
The ADU can be used to allow for medium density installations in an environment with proper static pressure and airflow
supply from the CRAC. Efforts must be taken to ensure that the flow rates of the CRACs exceed that of the perforated tiles
and ADUs.
The ADU is not recommended for use on non-raised floor.