Course in
BUILDING ELECTRICAL SYSTEMS
DESIGN & DRAFTING
Prepared By
Eng : AMJED OSMAN ELSAYED MOHAMED
E‐mail: [email protected]
INTRODUCTION
design of the electrical installation in building used to be
simple and straight forward . Such installations generally
included electrical service from an electricity board company ,
power distribution within the building for sockets (receptacles ),
air conditioniong and other electrical loads , lighting and few
specialty system such as fire alram and telephone .
Eng : Amjed Osman Building Electrical Design
Generation , transmission and
distributions of electrical energy
Eng : Amjed Osman Building Electrical Design
Transmission of Electricity
From power station to consumer
Power Station
High Voltage
Generation Distribution
Primary Secondary
Transmission Transmission
11kV, 17kV, 330kV, 60kV, 11kV, 240/415V
22kV, 23kV 500kV 132kV 33kV
Yard Regional Zone Distribution
transformer Substation Substation Substation
Eng : Amjed Osman Building Electrical Design
Distribution of Power
High Voltage and low voltage distribution system
Consumer 1 and 2: 230V two wire
Consumer 3 : 230/400V three wire
Bulk Supply Consumer
Consumer 4 : 230/400V four wire
1 2 3 4
Delta/Star
transformer
Line 1(A)
Line 2(B)
Three phase, high
voltage distribution Line 3(C)
Neutral
Three phase four wire distribution
Three Phase low voltage 230/400V
Star System Eng : Amjed Osman Building Electrical Design
5
Types of phase:‐
There are 3 phase types:
1. Red phase or phase (A)
2. Yellow phase or phase (B)
3. Blue phase or phase (C)
Phase system:
There are 3 types of phase system :
1. One ø system or 1 phase system
2. Tow ø system or 2 phase system
3.Three ø system or 3 phase system
Eng : Amjed Osman Building Electrical Design
Eng : Amjed Osman Building Electrical Design
ELECTRICAL CODES AND STANDARDS:
Electrical codes :‐ the principles used in electrical design and
installation are know as electrical codes.
Examples :
UK‐ UAE‐ QATAR‐ OMAN‐ SUDAN:‐
UK, UAE, Qatar ,Oman, Sudan follow B.S (British standards) know
IEC(International Electrotechnical Commission)
USA‐KSA:‐
USA,KSA follow NEC codes (National electrical codes) which is
chapter no 70 in NFPA book (National fire protection association )
European countries:
European countries follow IEC standards (international electrical
technical commission ).
Eng : Amjed Osman Building Electrical Design
Voltages and codes around the world
U.K → U.K follow B.S codes (also know as IEE regulation )
Normal voltages 230/400V 50Hz.
USA→ USA follow NEC (NFPA 70)
Normal voltage 110/220 60Hz
220/380 60Hz
KSA→ KSA follow NEC (NFPA 70)
Before 2010 KSA was having 2 voltages
127/220 V 60Hz
220/380 V 60 Hz
In 2010 the ministry of electricity decided that new project after
2010 will have only one voltage through out KSA 220/380 60Hz
Eng : Amjed Osman Building Electrical Design
Voltages and codes around the world
UAE → UAE follow B.S
Normal voltage 230/400v 50 Hz
SUDAN → Sudan follow B.S
Normal voltage 240/415v 50 Hz
Qatar → Qatar follow B.S
Normal voltage 240/415v 50Hz
Eng : Amjed Osman Building Electrical Design
SWITCH
used for on or off purpose of small equipment like light – ceiling fan
–exhaust fan - socket – water heaters – washing machine – cooking
range- window and split A/C – small water pumps.etc
Rating of switch : the maximum current which can flow
through switch safety without any damages for switch is know as
rating of switch
Eng : Amjed Osman Building Electrical Design
Standard Rating of Switch
5A
10 A
15 A
20 A
25 A
30A or 32 A
Note
In Gulf we used 10 A switch for light only
In Gulf we used 20 A switch for W/H – W/M etc
Eng : Amjed Osman Building Electrical Design
Types of Switch
One way switch
Two way switch
Intermediate switch
Eng : Amjed Osman Building Electrical Design
One way switch
Eng : Amjed Osman Building Electrical Design
Two way switch
Eng : Amjed Osman Building Electrical Design
Intermediate switch
Eng : Amjed Osman Building Electrical Design
back box
In Gulf they are 2 standard back box size
1. 3×3
2. 6×3
Gang : represents no. of switch in back box
1 Gang 2 gang 3 gang
Eng : Amjed Osman Building Electrical Design
Gang
four gang five gang six gang
4G 5G 6G
Eng : Amjed Osman Building Electrical Design
Sockets
Types of S/O in BS (Sudan , Oman, Qatar, UAE )
3pin → 13A general s/o
→ 15A s/o for A/C
→ 45A flex outlet for W/H , W/M , C/R
K.S.A : S/Os in NEC standard are know as receptacles
Receptacles → 15A/20A , 220 V
Receptacles →15A or 20A , 127 V
Eng : Amjed Osman Building Electrical Design
Sockets
Other classification
1. Single S/O outlet : The back box has only one s/o inside .the
back box size is used 3×3.
2.Double or twin S/O outlet : The back box has two s/o , the
back box size is used 6×3
3.Shaver outlet : (110_ 220 v)
Eng : Amjed Osman Building Electrical Design
Radial circuit
Eng : Amjed Osman Building Electrical Design
Ring circuit
Eng : Amjed Osman Building Electrical Design
flex outlet
Eng : Amjed Osman Building Electrical Design
CILEING ROSE
WIRES AND CABLES:-
Wire : conductor + insulation (small size)
Cables : conductor + insulation + sheath (large size )
Bare conductor : only conductor (no insulation). Ex, over
head lines in Sudan
Units of wires and cables
mm² → Sudan and B.S countries (UAE, K.SA,Qatar)
OR
AWG →(American Wire Gnage )
mm² : it is cross sectional area of conductor without
insulation
Eng : Amjed Osman Building Electrical Design
AWG
Eng : Amjed Osman Building Electrical Design
Equivalent of mm² to AWG
MM² AWG REMARK
1.0 mm² 18 AWG AWG For KSA
1.5 mm² 16 AWG AWG For KSA
2.5 mm² 14 AWG AWG For KSA
4 mm² 12 AWG AWG For KSA
6 mm² 10 AWG AWG For KSA
10 mm² 8 AWG AWG For KSA
16 mm² 6 AWG AWG For KSA
25 mm² 4 AWG AWG For KSA
35 mm² 2 AWG AWG For KSA
50 mm² 1 1/0 AWG AWG For KSA
70 mm² 2/0 AWG AWG For KSA
95 mm² 3/0 AWG AWG For KSA
120 mm² 4/0 AWG AWG For KSA
150 mm² 250 kc MIL AWG For KSA
185 mm² 350 kc MIL AWG For KSA
240 mm² 400 kc MIL AWG For KSA
300 mm² 500 kc MIL AWG For KSA
Eng : Amjed Osman Building Electrical Design
CORE OF CABLES
Core (c) represents the numbers of conductors in the cable , there are two
types of the cable based on the cores of cables
1. Single core cable (1c)
2. Multi core cable
(a) 2 core cable (2c)
Eng : Amjed Osman Building Electrical Design
CORE OF CABLES
(b) Three core cable (3c)
(c)Four core cable (4c)
(d)3 ½ core or 3.5 core
Eng : Amjed Osman Building Electrical Design
Run of cable:-
Run of cable represents the no .of single core or multi core
Always the earth is separate run and 1c only . no multi core for earth
wire
We prefer multi core cables above 6mm², avoid single cables above
6mm²
1.5 mm² → single core (1c)
2.5 mm² → single core (1c)
4 mm² → single core (1c)
6 mm² → single core (1c)
10 mm² → (2c ,3c , 4c, 3.5c)
16 mm² → (2c ,3c , 4c, 3.5c)
25 mm² → (2c ,3c , 4c, 3.5c)
:
:
300 mm² → (2c,3c , 4c, 3.5c)
Eng : Amjed Osman Building Electrical Design
Earth wire sizing
Earth wire is dependent on phase size
Wire or cable size for phase and N Earth wire or cable size
1.0mm² 1.0 mm²
1.5 mm² 1.5 mm²
2.5 mm² 2.5 mm²
4 mm² 4 mm²
6 mm² 6 mm²
10 mm² 10 mm²
16 mm² 16 mm²
25 mm² 16 mm²
35 mm² 25 mm²
50 mm² 25 mm²
70 mm² 35 mm²
95 mm² 50 mm²
120 mm² 70 mm²
150 mm² 95 mm²
185 mm² 95 mm²
240 mm² 120 mm²
300 mm² 150 mm²
Eng : Amjed Osman Building Electrical Design
Conductor materials
1. Copper (cu)
2. Aluminum (al)
Eng : Amjed Osman Building Electrical Design
Insulation materials
1. PVC :(Poly-Viny Chloride)
PVC insulated wires are used for smaller
loads like light , fans , s/o , w/m , w/h , c/r
They can with stand up to 60 C,
2. LSOH : Low Smoke zero Holagen
LSOH insulated wires are used for smaller
loads like lights , fans , s/o , w/h , w/m . c/r .
Eng : Amjed Osman Building Electrical Design
Insulation materials
XLPE : cross linked polyethylene
XLPE insulated cables are used as main
feeder cable (service wire) for DB OR SMDB
OR MCC OR T/F etc. and for heavy mechanical
load like chiller – AHU – Boilers
XLPE cables can with stand up to 90º c
FR : Fire Retardant or MICC (Mincal Insulated Cable
Conductor )
FR cable are professed for emergency load like
lights fire fighting pumps , emergency lights
,fire alarms cables
Eng : Amjed Osman Building Electrical Design
Types power cable :
1.Un armoured cable
2. Armoured cable
a) SWA (Steel Wire Armour )
b) AWA (Aluminum Wire Armour)
c) SSA (Steel Strip Armour )
d) ASA (Aluminum Strip Armour)
Eng : Amjed Osman Building Electrical Design
Voltage classification
H.V → High Voltage (above 1000 v)
M.V → Medium Voltage (250 to 1000v)
L.V → Low Voltage (30 to 250 v)
ELV → Extra Low Voltage (voltage less
than 30 ac or 54 v dc)
Grade of cable
means the with stand voltage whether the
cable is for LV or MV or HV.
Eng : Amjed Osman Building Electrical Design
Color codes of cable
PHASE In sudan or gulf New color code
countries in europe
Phase (A) or (1) Red Brown
Phase (B) or (2) Yellow Black
Phase (C) or (3) Blue Grey
Neutral Black Blue
Earth Green or Y/G Y/G
Eng : Amjed Osman Building Electrical Design
Final representation of cables
1×4c×10mm² ,XLPE/SWA/PVC.Cu,0.6/1kv + 1×1c×10mm², pvc /pvc ,cu Y/G
1 → run
4c→ core
10mm²→size
XLPE → insulation
SWA→ armour
PVC→ sheath
Cu → conductor material
0.6/1kv → M.V /L.V grade
Earth
1 → run
1c→ core
10mm²→ size
PVC → insulation
PVC→ sheath
Cu → conductor material
Y/G → Earth
Eng : Amjed Osman Building Electrical Design
Electrical faults
Types of electrical faults
Over load
Short circuit
Earth –fault or shock
Over voltage
Under voltage
Eng : Amjed Osman Building Electrical Design
1. Over load
Over load mean current more than rated current of
equipment
Ex : 10 A rated switch
2A→ safe
6A→ safe
10A→ safe
11A→ un safe (over load current)
When over load current passes then the s/w gets
damage.
Eng : Amjed Osman Building Electrical Design
2. Short circuit
When any phase of neutral or any two phase meet
each other then infinite current flows through them.
Usually thousands of current in 1 ms (KA of current
in 1ms ), this increase the temperature is know as
short- circuit condition
Eng : Amjed Osman Building Electrical Design
3.Earth – fault or shock
When any phase meet earth wire or any conducting materials eg
(metals – human body – water – etc. ) some a mount of current
passes in to ground through the earth wire or any conducting material
This current passing to earth from phase wire is know as earth –
leakage current and the fault is know as earth – fault .
Good conductor Bad conductor
Silver (best) wood
Cu and AL Rubber
All metals expect few Plastic – paper – glass
semi‐ conductor
Human body porcelain
Water Air
Eng : Amjed Osman Building Electrical Design
Summary
P – N → Short circuit
P – P → Short circuit
P – E or human body → earth fault –
shock
N – E or human body → No effect
E – human body → No effect
Eng : Amjed Osman Building Electrical Design
Productive devices
The devices which protected from electrical faults are
knows as protective devices
Types of protective devices
1. Fuse → protective from over load only
2. Circuit breaker → protects from over load and s.c
faults
3. RCB or ELCB or GFCI→ protects from earth faults or
shock
4. RCBO or RCCB → protects from over load , s.c and
earth faults
5. UVR (Under Voltage Relay)→ protects from under
voltage
Eng : Amjed Osman Building Electrical Design
Circuit Breaker : The CB is protective devices which can
be operated manually and automatically it trips in case of over load and
short‐ circuit condition
5 A to 40 A MCB (Miniature circuit breaker )
50 A to 600 A MCCB
(Modulate Case circuit breaker )
800 A to 3500 A ACB
(Air Circuit Breaker)
Eng : Amjed Osman Building Electrical Design
Standard of C.B (A) Type of C.B
5 MCB
10 MCB
15 MCB
20 MCB
25 MCB
30 or 32 MCB
40 MCB
50 MCCB
60 or 63 MCCB
80 MCCB
100 MCCB
125 MCCB
150 MCCB
200 MCCB
225 MCCB
250 MCCB
300 MCCB
400 MCCB
500 MCCB
600 MCCB
800 ACB
1000 ACB
1250 ACB
1500 ACB
2000 ACB
2500 ACB
3000 ACB
3500 ACB
Eng : Amjed Osman Building Electrical Design
Standard short – circuit rating of C.B
1. 6KA
2. 10KA
3. 16KA
4. 25KA
5. 35KA
6. 50KA
Eng : Amjed Osman Building Electrical Design
TYPES OF C.B
1.MCB → Miniature Circuit Breaker
2.MCCB→ Modulate Case Circuit Breaker
3.ACB → Air Circuit Breaker
other breaker used in H.V (power plants and s/s )
4.VCB → Vacuum C.B
5. OCB → Oil C.B
6. SF6
Eng : Amjed Osman Building Electrical Design
Types of MCB
B curve MCB
C curve MCB
D curve MCB
Eng : Amjed Osman Building Electrical Design
Types of MCB
Eng : Amjed Osman Building Electrical Design
Application of B,C,D curve MCB
1. B curve MCB is preferred for lighting circuit.
2. C curve MCB is preferred for small heavy like W/H –
W/M – C/R
3.D curve MCB is preferred for machine like (backing
machine ).
Eng : Amjed Osman Building Electrical Design
MCCB(Modulate Case circuit breaker )
Rating 50 to 600A
Types of MCCB
1. Adjustable MCCB
here we can set the tripping value normally
2. Fixed or un adjustable MCCB
Eng : Amjed Osman Building Electrical Design
ACB : Air Circuit Breaker
Rating 800 to 3500A
1.Motorized with drawable ACB :
Here the start and stop push buttons are
operated by a motor which is required to
be energized and after it is off we can with
draw the ACB to avoid are flash
2.Motorized non_ with draw able ACB
Here the start and stop push buttons are
operated by a motor which is required to
be energized and after it is off/on we need
to with raw ACB
Eng : Amjed Osman Building Electrical Design
RCD or ELCB or GFCI
B.S (Sudan and UAE,Qatar)
→RCD (Residual Current Devices )
→ELCB (Earth Leakage Circuit Breaker)
NEC (KSA)
→ GFCI : Ground fault Circuit Breaker
Eng : Amjed Osman Building Electrical Design
Working principle of RCD
The RCD continuously monitors the current difference
between phase and neutral . if the leakage current is equal
to sensitivity of RCD then the RCD is trip
Recommended sensitivity of RCD :
For lights use 100 mA RCD (0.1A)
For sockets use 30 mA RCD (0.03A)
For W/H- W/M- C/R use 30 mA (0.03A)
For A/C use 100mA RCD (0.1A)
For under water lighting use 10mA RCD (0.001A)
Note: the RCD is provide with a test buttons to verity that RCD
is working propyl
Eng : Amjed Osman Building Electrical Design
Working principle of RCD
No .of poles :
Since neutral is compulsory in RCD we have
1. Two poles RCD
2. Four poles RCD
Eng : Amjed Osman Building Electrical Design
RCCB or RCBO :
RCCB
Residual Current Circuit Breaker
RCBO
Residual CB with over current
protection (over load & S.C)
Note
RCCB or RCBO protects from all 3 faults (over load , S.C and earth
fault)Since this technology is now they are very less used
Eng : Amjed Osman Building Electrical Design
RCCB or RCBO
Ex : (C 40A - 100ma - 10KA)
C → type of RCBO
40 A→ rating of RCBO
100mA → sensitivity of MCBO
10KA→ short- circuit rating
Note
In UAE they have both CB and RCD for all lights and W/H.
S/O , A/C
In Qatar RCD are minatory for S/O , W/H , W/M only not
require for lights and A/C.
In KSA RCD are not used GFCI are minatory only for
equipment inside bath room and kitchen.
Eng : Amjed Osman Building Electrical Design
Isolator or disconnect switch (D/S):
Isolator or D/S is not a protective devices is it doesn’t trip in case of
any fault it is only meant for on and off purpose
It can look similar to CB with handle side handle or rotary handle
Note
In sudan and B.S countries the isolator is
used as main breaker knows as (main isolator )
inside the DB or final DB
Always install D/S near to every heavy
mechanical equipment such as chiller , AHU ,
Motor and pumps , lights for maintains
and repair purpose
Eng : Amjed Osman Building Electrical Design
STANDARD ISOLATOR RATING
1. 20 A 18. 600 A
2. 25 A 19. 800 A
3. 30 A 20. 1000 A
4. 40 A 21. 1250 A
5. 50 A 22. 1500 A
6. 60 A 23. 2000 A
7. 80 A 24. 2500 A
8. 100 A 25 3000 A
9. 125 A 26 3500 A
10. 150 A
11. 220 A
12. 225 A
13. 250 A
14. 300 A
15. 350 A
16. 400 A
17. 500 A
Eng : Amjed Osman Building Electrical Design
DB (NEC)
Eng : Amjed Osman Building Electrical Design
DB (B.S)
Eng : Amjed Osman Building Electrical Design
DB (B.S)
SMDB
Eng : Amjed Osman Building Electrical Design
STANDARD ISOLATOR RATING
NO .OF POLES FOR ISOLATOR DB:
2P 4P
No.of poles D/S near the heavy mechanical equipment
SPN for single phase equipment
TPN for three phase equipment
Eng : Amjed Osman Building Electrical Design
Wires and cables insulation methods
Majorly the wires of cables are said to be installed in two methods
Cable in air (2) Cable in ground
No Methods for cable in Methods for cable in
Air ground
1 Free in Air Directly buried or directly
laid under ground cable
2 conduit Duct bank or electrical
ducts
3 Cable trunking Cable tranch
4 Cable tray
5 Cable ladder
Eng : Amjed Osman Building Electrical Design
Conduit: (electrical pipe)
Material of conduit
PVC
Metallic
GI/GS→ Galvanized Iron/
Galvanized Steel
Eng : Amjed Osman Building Electrical Design
Conduit: (electrical pipe)
Material of conduit :
EMT→ Electrical Metallic Tubes
RGS/RGI →Rigid Galvanized Steel/
Rigid Galvanized Iron
Note
PVC conduits are used as connected conduit inside the wall , slabs ,
and floor screed.
GI/GS or RGI/RGS are used as exposed conduits or the wall , or slab
in India and B.S countries (Qatar , UAE ,Oman)
EMT conduits are used as exposed conduits on the wall or slab in
KSA
Eng : Amjed Osman Building Electrical Design
Standard size of conduits
½ ´´ → 16 mm
¾´´ → 20 mm
1´´ → 25mm
1¼´´→ 32 mm
2´´ → 50 mm
3´´ → 75 mm
4´´ → 100 mm
Note
½ ´´ conduits are not recommended
¾´´ (20 mm) 0r 1´´ (25 mm) conduit can be use for wiring
lighting
1´´ (25 mm) or (32mm) conduit can be used for wiring of s/o ,
w/h , w/m , c/r , pumps and low current system like fire alarms
wires , CCTV telephone and TV wires.
Eng : Amjed Osman Building Electrical Design
Conduits accessories
Coupler : coupler used to join 2conduts
Bends : In gulf countries bends are made
at site in the same coduit using PVC bending
Eng : Amjed Osman Building Electrical Design
circular JB
is fixed near to every light point , ceiling and exhaust and smoke electors
Types of JB circular JB
One way two way through two way angle
two way U three way four way
Eng : Amjed Osman Building Electrical Design
Junction box
octagonal JB
back bax : are used for s/o flex outlet etc
adapter : use for fixing conduit to the back box
Eng : Amjed Osman Building Electrical Design
Standard mounting heights of wiring
accessories
All switches → 1250 mm AFFL (After Finish Floor
Level) Light , fan , w/h , w/m .
Sockets →450 mm AFFL
Tel/sockets →450 mm AFFL
Sockets in kitchen → 250 mm above kitchen plat
form
s/o for w/h , w/m , A/C , near the equipment
Eng : Amjed Osman Building Electrical Design
Standard mounting heights of wiring
accessories
Eng : Amjed Osman Building Electrical Design
conduiting
laying of conduit is knows as coduiting there are three stages for
conduiting
Conduiting in slab
Eng : Amjed Osman Building Electrical Design
Conduiting in wall
Eng : Amjed Osman Building Electrical Design
Conduiting in floor
Eng : Amjed Osman Building Electrical Design
Cable trunking
Cable trunking is used to carry branch of wires (many wires )
Materials' :
1. PVC cable trunking
2. Metallic cable trunking
Eng : Amjed Osman Building Electrical Design
Standard size of cable trunking
1. 50mm ×50mm (5cm×5cm)
2. 100mm ×100mm (10cm×10cm)
3. 150mm ×150mm (15cm×15cm)
4. 200mm ×200mm (20cm×20cm)
5. 250mm ×250mm (25cm×25cm)
6. 300mm ×300mm (30cm×30cm)
7. 400mm ×400mm (40cm×40cm)
8. 500mm ×500mm (50cm×50cm)
Note: other combination are also available
ex : 300mm×100mm
Eng : Amjed Osman Building Electrical Design
Installation methods of cable trunking
The cable trunking can be installed is three method as per
requirements
On the surface of the wall
Hanging from slab
Under floor trunking
Eng : Amjed Osman Building Electrical Design
CABLE TRAY
Cable tray is used to carry heavy cable
Types of cable tray:
1. Perforated cable tray :
is preferred for carraying power cables
2. Plain cable tray :
can be used for low current system
like TV , CCTV ,FF
Eng : Amjed Osman Building Electrical Design
Materials of cable tray
1. No PVC
2. Metallic
(a) Galvanized cable tray (b) Hot dip galvanized cable
Eng : Amjed Osman Building Electrical Design
Standard cable tray size
1) 50mm ×50mm (5cm×5cm)
2) 150mm ×150mm (15cm×15cm)
3) 200mm ×100mm (20cm×10cm)
4) 250mm ×100mm (25cm×10cm)
5) 300mm ×100mm (30cm×10cm)
6) 400mm ×100mm (40cm×10cm)
7) 500mm ×100mm (50cm×10cm)
8) 600mm×100mm (60cm×10cm)
9) 800mm×100mm (80cm×10cm)
10) 900mm×100mm (90cm×10cm)
Note: if more than 900mm cable tray is required then use two
cable tray parally
Eng : Amjed Osman Building Electrical Design
Cable tray installation
Cable tray can be installed in three methods :
1. On the surface of wall
2. Hanging from cable
3.Floor mounted (on the floor )
Eng : Amjed Osman Building Electrical Design
Cable laying methods on cable tray
There are three methods of cable laying on cable tray
Flat formation – touching
Flat formation – spacing
Trefoil formation (only for single core cables )
Eng : Amjed Osman Building Electrical Design
Cable ladder
Cable ladder are preferred only for vertical installation only in
electrical shaft or riser
Cable installation in ground :
there are three methods of cable tray installation in ground
1.Directly buried or directly laid under ground
2.Duct bank or electrical duct
3.Cable trench
Eng : Amjed Osman Building Electrical Design
Cable installation in ground
1.Directly buried or directly laid under ground
Eng : Amjed Osman Building Electrical Design
2.Duct bank or electrical duct
Eng : Amjed Osman Building Electrical Design
3.Cable trench
Eng : Amjed Osman Building Electrical Design
Coordination with mechanical system
1. HAVC (Heating Ventilation and Air Conditioning )
2. Plumbing
a) water supply
b) drainage
3. Fire fighting
4. Conveyors like ,lifts scalolar
5. Swimming pool.
Eng : Amjed Osman Building Electrical Design
Types of HVAC system
1. Window A/C
2. Split A/C
Eng : Amjed Osman Building Electrical Design
3.VRV or VRF system
Eng : Amjed Osman Building Electrical Design
4. Package A/C
Eng : Amjed Osman Building Electrical Design
5. Central A/C – VAV system
Eng : Amjed Osman Building Electrical Design
6. Chilled water system
Eng : Amjed Osman Building Electrical Design
Plumbing system
1. Water supply
2. Drainage system
Eng : Amjed Osman Building Electrical Design
Fire fighting system
Duty and stand by pumps
Eng : Amjed Osman Building Electrical Design
Plumbing system
Lift :
The installation works of lift etc is done by separate
contractor know as lift contractor
The elect.engineer has to provide a D/S inside the lift
room for supply to the lift system
Summing pool : are usually done by separate contractor
knows as swimming pool contractor .
Sometimes the elec. Engineer has to supply electricity to
under water lights which is done at voltage not greater
than 30 v a.c the lights shall be provide with 10ma RCD.
Eng : Amjed Osman Building Electrical Design
Panel board
An enclosure with protection devices such as C.B and
RCD knows as panel board .
Ex : DB – SMDB – MCC – MDB (All are panel board)
Switch gear : a panel board including instruments is
knows as switch gear.
Ex : MDB – MCC
Eng : Amjed Osman Building Electrical Design
MCC (motor control center )
MCC is a panel board to which major mechanical motors
or loads are connected.
MCC has measuring indicating remote start indicates.
Ex : MCC panel has ammeter voltmeter frequency meter
power factor meter , phase indicators motor run off trip
indicating lamps auto , manual selector switch CB and
motor starters with remote terminal blocks.
Eng : Amjed Osman Building Electrical Design
Panel board
The panel board and switch gear (DB- SMDB – MDB –
MCC ) are manufactured in separate factories knows as
switch gear manufacturing company and these panel
boards are delivered at site for installation
Well – know switch gear companys :
1. ABB
2. Schneider electric
3. Mitsubishi
4. Merlin gerin
5. Siemens
6. L&T
Eng : Amjed Osman Building Electrical Design
Bus duct system
Note : bus duct has a housing with bus bar insulated , bus bar is used
to carry current of very high ratings ,
ex : above 600A only
STANDARD BUS DUCT RATING:
600A
800A
1000A
1230A
1500A
2000A
2500A
3000A
3500A
Bus way or bus duct riser : is used for power distribution inside the
high building for each house
Eng : Amjed Osman Building Electrical Design
IP PROTECTION
IP →Ingress Protection or International Protection
IP is the number assigned to the electrical equipment and
motors installed outside the building or in wall areas to protection
from water and dust and object
No Protection form object and Protection form water
dust
0 Not protect Not protect
1 Hand protect Vertical water
2 Finger protect 15º
3 Tool protect 60º
4 Wire protect Splashing of water
5 Dust protect Low jets of water
6 Complete protect High jets of water
7 Immession
8 Complete submersible
Eng : Amjed Osman Building Electrical Design
TRANSFORMES
Types of transformer
1. steps up transformer
2. step down transformer
Types base on phase system
single phase
three phase
Types of transformer base on poling
oil cooled transformer
air cooled transformer
Eng : Amjed Osman Building Electrical Design
TRANSFORMES
Note:
for indoor transformer use air cooled transformer
for outdoor transformer use oil cooled transformer
in gulf countries the transformer are indoor type
installed in separate room ex substation room or
transformer room
oil cooled transformer are not referred inside the
building .
air cooled transformer are used inside building
unit of transformer is KVA
Eng : Amjed Osman Building Electrical Design
TRANSFORMES
STANDARD RATING OF TRANSFORMER
1) 50 KVA
2) 60KVA
3) 80KVA
4) 100KVA
5) 150KVA
6) 250KVA
7) 315KVA
8) 500KVA
9) 630KVA
10) 800KVA
11) 1000KVA
12) 1500KVA
13) 2000KVA
14) 2500KVA
15) 3000KVA
16) 3500KVA
Eng : Amjed Osman Building Electrical Design
TRANSFORMES
Need of transformer
Gulf countries
Transformer is not require for building whose
total max demand less than 400kva
If the total max demand is greater than 400kVA
then we require transformer
Max permit transformer size 2500kVA
Sometimes is 3000kVA
Eng : Amjed Osman Building Electrical Design
TRANSFORMES
Steps to calculate the transformer size :
1.Consider
Total max demand of MDB = KW
2.Total max demand of MDB in KVA = KW/cosø = KVA
3.Add 10% as future load
Total max demand with future load in KVA = kVA ×1.10
4. Transformer size = Total max demand with future load in KVA
Transformer load (90%)
Then select the standard size
Eng : Amjed Osman Building Electrical Design
TRANSFORMES
Ex : calculate the Transformer size for project inside whose max demand is
100kw
Solution :
Total max demand of MDB = 100 KW
1.Total max demand of MDB in KVA = KW/cosø = 100/0.8=125KVA
2. Add 10% as future load
3. Total max demand with future load in KVA =125 kVA ×1.10=137.5KVA
4. Transformer size = Total max demand with future load in KVA
Transformer load (90%)
= 137.5Kva/.90 = 157.7Kva
Standard T/F size = 250KVA / air cooled
11kv/440v / indoor T/F
Y/▲ / z% = 5%
3ø, 4 wires 50 Hz
Eng : Amjed Osman Building Electrical Design
Capacitor bank
Types of load:
1.Resistive load: current is in phase with voltage
2.Inductive load: current lags voltage
3.Capacitive load: current leads voltage
Phase angle: angle between voltage and current
Note: All loads in our daily life are resistive – inductive loads, ex
(tube light,bulb, motor and pumps ,w/h, w/m , r/c).
Hence capacitor bank are required which are connected to MDB
,which improves the over all power factor of the system .
Sudan PF = 0.80 (low PF)
Final PF = 0.98 or 0.96 (improve p.f)
Eng : Amjed Osman Building Electrical Design
Capacitor bank
Note
Capacitor bank is not require for single phase equipment or for
small project
Capacitor bank required for project involving three phase
equipment or here phase motors or MCC panels and this
capacitor bank is connected to MDB.
Unity of capacitor bank:
KVAR (Kilo – Volt – Ampere – Reactive)
Formula to calculate capacitor bank:
Capacitor bank (KVAR)
Max demand of MDB in KW {tan(cos-¹ø1) – tan (cos-¹ø2)}
Where
Ø1 → initial power factor = 0.8
Ø2 → final power factor = 0.98
Eng : Amjed Osman Building Electrical Design
Capacitor bank
Types of capacitor bank:
1.Fixed capacitor bank
2.APFC (Automatic Power Factor Corrector)
APFC: in this types the capacitor
are automatic , they become on
and off depending on the load
Ex: If full load then all capacitor are on
If half load then few capacitor are on
If no load then very few capacitor on
Eng : Amjed Osman Building Electrical Design
standard capacitor bank
1. 10 KVAR 17. 300 KVAR
2. 15 KVAR 18. 375 KVAR
3. 20 KVAR 19. 420 KVAR
4. 25 KVAR 20. 540 KVAR
5. 35 KVAR 21. 750 KVAR
6. 40 KVAR
7. 50 KVAR
8. 75 KVAR
9. 100 KVAR
10. 125 KVAR
11. 135 KVAR
12. 150 KVAR
13. 175 KVAR
14. 200 KVAR
15 225 KVAR
16. 275 KVAR
Eng : Amjed Osman Building Electrical Design
Capacitor bank
Eng : Amjed Osman Building Electrical Design
EMERGENCY BACK UP SYSTEM
UPS / Inverter
(Un interrupted Power Supply)
DG (Disel Generator )
or stand by generator
Eng : Amjed Osman Building Electrical Design
UPS / Inverter
UPS →Un interrupted Power Supply
Eng : Amjed Osman Building Electrical Design
UPS / Inverter
UPS is used for back up of electronic equipment ,ex(computer,
CCTV)
Inverter is used for back up of electrical and electronic
equipment's
Ex → electrical (fans – lights - w/m )
Ex → electronic (computer – CCTV )
Unit of UPS/Inverter → KVA (Kilo – Volt – Ampere )
Eng : Amjed Osman Building Electrical Design
Standard of UPS /Inverter
1. 0.5 KVA
2. 085 KVA
3 1 KVA
4. 1.4 KVA
5. 2 KVA
6. 3 KVA
7. 3.5 KVA
8. 5 KVA
9. 7.5 KVA
10. 10 KVA
11. 20 KVA
12. 25 KVA
13. 30 KVA
14. 40 KVA
15. 50 KVA
16. 65 KVA
17. 80 KVA
18. 100 KVA Eng : Amjed Osman Building Electrical Design
UPS / Inverter
Step to calculate UPS/inverter size:
1.Calculate the total load in KW
2.Calculate the total load in KVA
3. UPS/Inverter size = total load in KVA
UPS/Inverter loading
= total load in KVA
0.80 (80% or 85% loading)
4. select the standard size
Eng : Amjed Osman Building Electrical Design
UPS / Inverter
Wattages of load:
1. Tube lights = 40 w
2. Ceiling fans = 80 w
3. Computer
(a)CRT computer = 300 w
(b)LCD computer = 200 w
(c)LED computer = 160 w
4. printer = 200 w
5. router = 50 w
6. (6) EPBAX = 50 w
7. (7) CCTV = 50 w
Eng : Amjed Osman Building Electrical Design
Diesel generator
The diesel generator can be connected in two methods
1.C.O.S (Change Over Switch ) manually operated
switching
2. A.T.S (Auto Transfer Switch ) automatic switching
Units of generator → KVA
Eng : Amjed Osman Building Electrical Design
C.O.S (Change Over Switch ) manually operated
Eng : Amjed Osman Building Electrical Design
A.T.S (Auto Transfer Switch ) automatic switching
Eng : Amjed Osman Building Electrical Design
Diesel generator
Standard generator size
1. 10 KVA 16. 400 KVA
2. 20 KVA 17. 500 KVA
3. 30 KVA 18. 600 KVA
4. 40 KVA 19. 630 KVA
5. 50 KVA 20. 750 KVA
6. 63 KVA 21. 800 KVA
7. 75 KVA 22. 1000 KVA
8. 100 KVA 23. 1250 KVA
9. 125 KVA 24. 1500 KVA
10. 132 KVA 25. 1800 KVA
11. 160 KVA 26. 2000 KVA
12. 200 KVA 27. 2500 KVA
13. 225 KVA
14. 250 KVA
15. 300 KVA
Eng : Amjed Osman Building Electrical Design
Diesel generator
Step to calculate generator size:
1. Calculate the total load in kw = (SMDB Comm)
2. Total load in KVA = kw /cosø = KVA
3. Generator size = = total load in KVA
generator loading (0.80)
4. Select the standard generator size
Eng : Amjed Osman Building Electrical Design
Electrical instruments (testing and
commission):
1. Voltmeter
2. Ammeter
3. Energy meter or Kwh meter
4. P.F meter
5. Frequency
6. Phase indicators
7. Multi meter
Eng : Amjed Osman Building Electrical Design
Earthing and lighting protection
system
Earthing : connection of wire to the ground is knows as
earthing
Types of earthing conductor:
1.Earth continuity conductor (ECC) or protection earth conductor
2.Main earth conductor
3.Equipment bonding conductor
1.Earth continuity conductor (ECC) or protection earth
conductor:
The earth wire passing to final loads and DB to SMDB or
MDB is knows as ECC.
2.Main earth conductor:
The earth wire connected to ground is knows as main earth
conductor usually it is connected to MDB.
Eng : Amjed Osman Building Electrical Design
Earthing and lighting protection
system
3.Equipmential bonding conductor
Every metallic part in the electrical installation shall be
connected to ground (earth)
Eng : Amjed Osman Building Electrical Design
Earthing and lighting protection
system
Types of earth pits:
1.Pipe earthing
Eng : Amjed Osman Building Electrical Design
Earthing and lighting protection system
2. Electrode earthing
Eng : Amjed Osman Building Electrical Design
Lighting protection system
lighting protection system is building above 15 meter
Eng : Amjed Osman Building Electrical Design
Lighting protection system
Eng : Amjed Osman Building Electrical Design
lighting system
lamp → any device which gives light is knows as lamp
types of lamp:
1.Incandescent lamps
2.Fluorescent lamps
a) CFL (compact Fluorescent lamps)
b)tube
Eng : Amjed Osman Building Electrical Design
Types of lamp
3.Mercury vapor lamps
4.Metal halide lamps
5.HPS(High Pressure Sodium)
6.Halogen lamps
Eng : Amjed Osman Building Electrical Design
Types of lamp
Note:
Incandescent lamps are not recommended as their
efficiency is very low (high input current , low output
current
For indoor purpose the best lamps are fluorescent lampsas
their efficiency is very good (less input current or power
high out put light
The M.V lamps and metal ,HPS lamps are preferred for
out door street light.
Lamp input: is measured in watts
Ex : tube light(40w,36w) or CFL (24w , 36w)
Lamp output: lamp output is measured in lumens .
Eng : Amjed Osman Building Electrical Design
Luminaire or lighting fixture
Lamp fixed on a frame or reflectors is knows as luminaire
Illumination:
The lumen output of any luminaire falling on asq.meter
room area is knows as illumination
It is measured is
1.Lux (Lx) if the room dimensions are in meter
2.Foot candle (F.C) if the room dimension are in feets
Relation between LUX and F.C:
1 LUX = 0.1 F.C
1F.C = 10 LUX
Eng : Amjed Osman Building Electrical Design
Recommended lux level for different
rooms by IENSNA
IENSNA: Illumination Engineer Society North America
Bedroom = 50 lux = 5 FC
Hall = 150 lux = 15 FC
Kitchen = 300 lux = 30 FC
Bathroom =100 lux = 10 FC
Coefficient of utilization (Cu):
The Cu depends on the reflection factors of ceiling wall
and floor colors . also it depends on the work plane height
Note:
for manual calculation consider cu = 45%
Eng : Amjed Osman Building Electrical Design
Lamp lumen factor (LLF)
Lamp lumen factor (LLF) or lumen loss factor(LLF)
or maintenance factor (MF):
Ex : tube light (40 w)
Today → 2450 lumens
After 3 years→ less than 2450 lumens
The LLF depends on cleaning of luminaire
Note
For manual calculation for 3 years maintence consider
LLF= 0.67
Eng : Amjed Osman Building Electrical Design
Formula
Formula to calculate no.of luminaire in room:
No.of lamps = (lux or FC)× room area
( luminaire )×(lumens ×cu × LLF)
Cu = .45
LLF = 0.67
Eng : Amjed Osman Building Electrical Design
Arrangement of luminaire: (x=2x)
X → distance from wall to luminaire
2X→distance between luminaire to luminaire
Eng : Amjed Osman Building Electrical Design