This document provides instructions for upgrading the operating system and firmware of Premium PLCs and Ethernet modules. The key steps are: 1. Prepare the PC with the Unity software and firmware files needed for the upgrade. 2. Upgrade a PLC from PL7 to Unity by performing three mandatory phases - upgrade to an intermediate OS, power cycle the PLC, then update to the full Unity OS. 3. Procedures are also provided for updating within Unity versions, updating Ethernet modules, and restoring from Unity to PL7 if needed. Precautions are described for connecting the PC and performing the updates.

Uploaded by

Arif karisman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
122 views71 pages

Premium Upgrade Procedure

This document provides instructions for upgrading the operating system and firmware of Premium PLCs and Ethernet modules. The key steps are: 1. Prepare the PC with the Unity software and firmware files needed for the upgrade. 2. Upgrade a PLC from PL7 to Unity by performing three mandatory phases - upgrade to an intermediate OS, power cycle the PLC, then update to the full Unity OS. 3. Procedures are also provided for updating within Unity versions, updating Ethernet modules, and restoring from Unity to PL7 if needed. Precautions are described for connecting the PC and performing the updates.

Uploaded by

Arif karisman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 71

PLC Operating

System

Upgrade and Update Procedure


(Premium Part)

Edition V0.1 - May 2007


Why this Documentation?

Subject of this This user’s guide explains how to upgrade Premium PLC’s Operating System
Chapter but also the firmware of Ethernet modules

Premium PLC’s
 Upgrade a PLC from PL7 to Unity
 Update a PLC from Unity to Unity
 Update Premium ETY modules and embedded Ethernet modules
 Restore PL7 on a Unity processor
Summary

1. Prepare a Premium update .......................................................................................... 6

2. Upgrading a Premium PLC from PL7 to Unity......................................................... 8

3. Updating a Premium PLC from Unity to Unity....................................................... 19

4. Updating Premium PLC with an Ethernet Port ...................................................... 26

5. Updating Premium Co-Processor PLC..................................................................... 28

6. Restoring a Premium PLC from Unity to PL7 ........................................................ 30

Appendix 1 : ETY Module Upgrade Procedure.......................................................... 41

Purpose............................................................................................................................. 41

The upgrade of the ETY and Ethernet Port modules are completed by installing a
single file using the Unity Pro v2.2 or higher OS Loader. Please note that prior
version of the OS Loader are not compatible with this revision of the firmware. You
MUST be at the proper OS Loader revision of 2.2 or higher. .................................... 41

Applicable Modules ........................................................................................................ 41

Resulting Module after upgrade.................................................................................... 41

Overview .......................................................................................................................... 41

Step1 ................................................................................................................................. 41

Step2 ................................................................................................................................. 42

Step3 ................................................................................................................................. 42
........ 43

Step4 ................................................................................................................................. 43

Step5 ................................................................................................................................. 44

Step6 ................................................................................................................................. 46

Step7 ................................................................................................................................. 48

Step1 ................................................................................................................................. 55

Step2 ................................................................................................................................. 55

Step3 ................................................................................................................................. 56

Step4 ................................................................................................................................. 56
Step5 ................................................................................................................................. 57

Step6 ................................................................................................................................. 59

Appendix 3 : FactoryCast ETY 510 Module Upgrade Procedure ............................ 62


1. Prepare a Premium update

Object of this This chapter describes how to prepare a Premium PLC in order to update or
Chapter upgrade PLC’s Operating System and / or Ethernet modules.

Prerequisites This update requires a PC with Unity installed and the binary file containing
the OS firmware to download.

Software The following software are required :


 Unity Version 2.0 mini must be installed on the PC (note that is not
necessary to launch Unity for an OS upgrade).
 The CD “Unity OS firmware” provided with Unity and that contains
all the OS for Quantum and Premium PLC’s or only the specific OS
file for your PLC you previously have downloaded from the Schneider
web site http://www.telemecanique.com
 The OS Loader (installed with Unity). This tool allows the user to
download PLC’s Operating System and Ethernet modules firmware.

Connecting the Although Ethernet allows a remote access via the network and then the
PC to the PLC upload / download procedure, we strongly recommend installing the
to update an processor with the embedded Ethernet module in a system consisting of only
Ethernet the CPU, Power Supply and Rack. Once done,
module  Configure the PLC system with an empty program containing only the
ETY IP address configuration. Note that the ETY module must be on
the same logical Ethernet network than the PC with the OS loader (for
that both IP address, Subnet mask and default gateway must be
compatible)
 Ensure the only devices connected to the Ethernet network are the PC
running the OS loader and the ETY module
 The CPU must be in Stop mode and the ETY module must have no
TCP traffic.

The physical connection between the PC running the OS loader and the ETY
module can be performed :
 by connecting directly a “crossed” Ethernet cable between the PC and
the ETY module
 by connecting the PC and the ETY module with two “non crossed”
Ethernet cables via a Hub
Connecting the Two possibilities can be proposed to connect the PC to the PLC :
PC to the PLC
for an OS 1) Using the RS232 COM port of the PC by connecting the cable
update TSXPCX1031 to the TER port of the Premium PLC. The rotary switch of the
cable must be set on TER DIRECT and the Unitelway driver already installed
on the PC.

2) Using one USB port of the PC as described below. In this case :


 plug the USB – RS485 converter (TSXCUSB485) into the PC’s USB
port
 plug the RJ45 connector of the TSXCRJMD25 cable into the RJ45
port of the TSXCUSB485 converter
 plug the Mini Din connector of the TSXCRJMD25 cable to the TER
port of the Premium PLC.
The rotary switch of the converter must be set on TER DIRECT and the
Unitelway driver (V1.9 minimum) already installed on the PC

Note that the cable TSXPCX3030 (no more commercialized) can be used to
connect the USB port of the PC to the TER port of the PLC.
2. Upgrading a Premium PLC from PL7 to Unity

Object of this This chapter describes how to upgrade a Premium PLC from PL7 to Unity.
Chapter The screens shots given below show how to upgrade a TSX P57 253 (PL7) to
TSX P57 254 (Unity). This procedure is similar for all other type of PLC’s

Warning Upgrading a PLC from PL7 to Unity requires to perform three main phases :

 Phase 1 - Upgrade the PLC to Unity with an intermediate OS


 Phase 2 - Power OFF then ON the PLC
 Phase 3 - Update the Operating system with the appropriate file

Those phases are mandatory and cannot be by-passed.

Each phase is described in the following procedure

Connecting the This phase is fully described in the chapter 1 of this document.
PC to the PLC
Launching the The OS Loader (installed with Unity) allows the user to download the
OS loader Operating System to the PLC. To open it, click on
Start/Program/Schneider-Electric/Unity-PRO/OS loader

Once done, the following screen appears :

Select the com


munication From the main screen of the OS loader, click on the button. The
protocol following screen appears :

To download the operating System into the PLC select the Unitelway

communication protocol (UNITLW01) and click on the button.


Select the
Target Device

On the Device Type field, select Processor

Get the PL7 Knowing which PL7 version is installed on the processor could be useful if
version for any reason a restore function from Unity to PL7 is needed. For that
(optional) proceed as follow :

1
Select the PLC

2 Click on the button to connect the PC to PLC. Once


connected, the yellow TER led of the PLC is flashing.
3 Click on the button to get info from the PLC
The following screen gives to the user some information regarding
the PLC status
 Started, stopped,
 Processor type (in this example : TSX 57253)
 The Hardware identification (for Schneider internal use only)
 The OS version (in this example the OS version is 5.9)

4
Note this version number to avoid compatibility issues between the
5 application program and the OS if for any reason the previous CPU
Os (PL7) has to be restored.
6
Press the button to return back to the OS update process

Select the From the screen described above in the section “Select the Target Device”
Download
Function press the button. A new screen is proposed : select “Download
OS to device”
Select the file to
download Click on the button in order to select the file to download into the
PLC. In this example we will update the OS from TSX P57 253 to TSX P57
254. For that select the folder Premium\Processors_modules\PL7_to_Unity\
and select TSXP57253_to_254 (in your case, select the folder according to
your processor)

For an upgrade from PL7 to Unity two binary files can be selected :
 PL7_to_Unity_254.bin (allows to “format” the processor for Unity)
 TSXP57254M_V240.bin is the OS that will finally be download in the
processor

In our example we have to “format” the processor (remember, we still are in


the Phase 1) then select and Valid “PL7_to_Unity_254.bin”.

Once done click on the button.


Download the Once the previous screen validated, a warning is displayed
intermediate
OS

Click the button. Two screens that give information


regarding the file, the processor and the download are now displayed :

Warning : If the system detects a discrepancy between the hardware or the


OS versions, the download will not be possible. This is indicated by a red

cross and the button becomes not available.

Solve this issue and continue. When the hardware - OS are compatible, click

on the button launches the download of the intermediate OS file


Download the During the download (roughly 15 to 20 mn) the remaining time is displayed
intermediate
OS file (cnt’d)

Warning : During the download, do not power OFF the PLC, neither
disconnect the cable nor shut down the OS loader. If unfortunately it
happens, the PLC may have lost some important files and therefore be unable
to run correctly and must be returned back for repair.

Once the download successfully completed, the screen below is displayed.

Click twice on the button and go to the Phase 2 (Power OFF


then ON or reset the PLC).
Reset the PLC Once the download of the intermediate binary file completed, the PLC has to
be initialized. This task can be performed by one of the two following actions:
 Reset the PLC by pushing on the Reset button located on the PLC’s
power supply (for more information, refer to the PLC technical
documentation
 Power OFF then ON the PLC.
Once the PLC restarted, go to phase 3 : download the final Unity OS file.

Presentation The final binary file “TSXP57254M_V240.bin” (in our example) has to be
downloaded.

For that, follow the same procedure as the one described in the Phase 1.

Download As all the actions necessary to download the final Unity OS have been
procedure already fully described in the Phase 1, they are shortly reminded here after :

1 Open the OS loader (the PC should be still connected to the PLC).

2 Select the Protocol (UNTLW01) – Refer to Phase 1

Select the target device and click on the button. The next
screen appears after few seconds.

3
Click on the button and select (for our example) the file
“TSXP57254M_V240.bin” located on the CD OS. Then valid this
screen

Select the operation to perform (Download OS to device) and press

on the button

Download At this stage, and as no functional Operating System is present in the


procedure PLC the screen displays the string ??? in the field “OS Version” and
(cnt’d)
an error message. Click to validate this message

Then click on the button.


Click on and validate the warning message displayed on
the screen to launch the download of the final OS file.

Download During the download (roughly 35 to 45 mn) the remaining time is


procedure displayed
(cnt’d)

Warning : During the download, do not power OFF the PLC,


neither disconnect the cable nor shut down the OS loader. If
unfortunately it happens, the PLC may have lost some important files
8 and therefore be unable to run correctly and must be returned back for
repair.
Once the download successfully completed, the screen below is
displayed.

Click twice on the button to exit the OS loader tool.


9 Reset or power OFF then ON the PLC.
Checking If needed, you can check the new CPU version. For that
version (not  Open the OS loader tool,
mandatory)  Select the protocol (UNITLW01),

 Click on
 Click on .

In our example, the CPU has been upgraded to TSX P57 254M and the OS
version is 2.31 40.
3. Updating a Premium PLC from Unity to Unity
Object of this This chapter describes how to update a Premium PLC from Unity version >=
Chapter V2.0 to a more recent one. Note that the update from Unity V1.0 to V2 and
above is not provided.
The screens shots given below show how to update a TSX P57 454 processor.

Connecting the This phase is fully described in the chapter 1 of this document
PC to the PLC

Launching the The OS Loader (installed with Unity allows the user to download the
OS loader Operating System to the PLC. To open it click on Start/Progam/Schneider-
Electric/Unity-PRO/OS loader

Once done, the following screen appears :


Select the com
munication From the main screen of the OS loader, click on the button. The
protocol following screen appears :

To download the operating System into the PLC select the Unitelway

communication protocol (UNITLW01) and click on the button.

Select the
Target Device

On the Device Type field, select Processor

Get the Unity Before the update, knowing which Unity version is already installed on the
version processor could be useful if for any reason a restore function is needed. For
(optional) that proceed as follow :

1
Select the PLC

2 Click on the button to connect the PC to PLC. Once


connected, the yellow TER led of the PLC is flashing.
3 Click on the button to get info from the PLC
The following screen gives to the user some information regarding
the PLC status
 Started, stopped, Not Configured, ……..
 Processor type (in this example : TSX P57 454M)
 The Hardware identification (for Schneider internal use only)
 The OS version (in this example the OS version is 2.1)

Note this version number to avoid compatibility issues between the


5 application program and the OS if the previous version has to be
restored.
6
Press the button to return back to the OS update process

Select the From the screen described above in the section “Select the Target Device”
Download
Function press the button. A new screen is proposed : select “Download
OS to device”
Select the file to
download Click on the button in order to select the file to download into the
PLC. In this example we will update the TSX P57 454 OS from version 2.31
to V2.40. For that select the folder :
Premium\Processors_modules\Unity_Upgrade\ and select TSXP57254 (in
your case, select the folder according to your processor)

Then, select the binary file “TSXP57454M_V240.bin”

Once done click on the button.


Download the Once the previous screen validated, two screens display the current OS
OS version, the processor and the OS file to download :

Warning : If the system detects a discrepancy between the hardware or the


OS versions, the download will not be possible. This is indicated by a red

cross and the button becomes not available.

Solve this issue and continue. When the hardware - OS are compatible, click

on the button and validate the warning message displayed on the


screen to launch the download of the OS file.
Download the During the download (roughly 45 to 55 mn) the remaining time is displayed
OS file (cnt’d)

Warning : During the download, do not power OFF the PLC, neither
disconnect the cable nor shut down the OS loader. If unfortunately it
happens, the PLC may have lost some important files and therefore be unable
to run correctly and must be returned back for repair.

Once the download successfully completed, the screen below is displayed.

Click twice on the

Reset the PLC Once the download of the OS file completed, the PLC has to be initialized.
This task can be performed by one of the two following actions:
 Reset the PLC by pushing on the Reset button located on the PLC’s
power supply (for more information, refer to the PLC technical
documentation
 Power OFF then ON the PLC.
Checking If needed, you can check the new CPU version. For that
version  Open the OS loader tool,
(optional)  Select the protocol (UNITLW01),

 Click on ,
 Click on .

In our example the processor TSX P57 454M has been updated to the version
2.40-46.
4. Updating Premium PLC with an Ethernet Port

Object of this This chapter describes how to update a Premium PLC with an Ethernet port
Chapter module. This procedure is applicable to the following modules :
 TSX P57 2623M
 TSX P57 3623M
 TSX P57 1634M
 TSX P57 2634M
 TSX P57 3634M

The screens shots given below show how to update a TSX P57 1634M.

Warning For updating Premium PLC’s with an Ethernet port embedded it is imperative
that the update be carried out in the following order :
 Update the Ethernet module (Phase 1)
 Update the PLC Operating System (Phase 2)

Update the This phase is fully described in the Appendix 1 of this document.
Ethernet
module Once done update the PLC Operating System.
Updating the As the ETY port is now updated it is time to update the processor according
Processor to the latest version available. This download does not need an Ethernet
connection but the PC has to be connected to the TER port of the processor.

The update procedure is fully described in the chapter 3 of this document and
will not be repeated here. Please refer to this chapter.

Update the processor according to its type. Note that in our example (ETY
Port TSX P57 1634M) the file will be downloaded from the following
directory : Premium\Processors_modules\Unity_Upgrade\ :
5. Updating Premium Co-Processor PLC

Object of this This chapter describes how to update a Premium Co-Processor PLC with an
Chapter Ethernet port module. This procedure is applicable to the following modules :
 TSX P57 4634M
 TSX P57 5634M
 TSX P57 6634M

The screens shots given below show how to update a TSX P57 5634M.

Warning For updating Premium Co-Processor PLC’s with an Ethernet port embedded
it is imperative that the update be carried out in the following order :
 Update the Ethernet module (Phase 1)
 Update the PLC Operating System (Phase 2)

Update the This phase is fully described in Appendix 2 of this document.


Ethernet
module Once done update the PLC operating system.
Updating the As the Ethernet module of the Premium Co-Processor is now updated it is
Processor time to update the Co-Processor according to the latest version available. This
download does not need an Ethernet connection but the PC has to be
connected to the TER port of the processor

The update procedure is fully described in the chapter 3 of this document and
will not be repeated here.

Update the processor according to its type. Note that in our example (TSX
P57 5634M) the file will be downloaded from the following directory :
Premium\Processors_modules\Unity_Upgrade\ :
6. Restoring a Premium PLC from Unity to PL7

Object of this This chapter describes how to restore a Premium PLC from Unity to PL7. The
Chapter screens shots given below show how to restore a TSX P57 254 (Unity) to
TSX P57 253 (PL7).

Warning Restoring a PLC from Unity to PL7 requires to perform three main phases :

 Phase 1 – Restore the PLC to PL7 with an intermediate OS


 Phase 2 - Power OFF then ON the PLC
 Phase 3 – Restore the PL7 Operating System with the appropriate file

Those phases are mandatory and cannot be by-passed.

Each phase is described in the following procedure

Connecting the This phase is fully described in the chapter 1 of this document.
PC to the PLC
Launching the The OS Loader (installed with Unity allows the user to download the
OS loader Operating System to the PLC. To open it click on Start/Progam/Schneider-
Electric/Unity-PRO/OS loader

Once done, the following screen appears :

The next steps are fully described later in this document.

Select the com


munication From the main screen of the OS loader, click on the button. The
protocol following screen appears :

To download the operating System into the PLC select the Unitelway

communication protocol (UNITLW01) and click on the button.


Select the
Target Device

On the Device Type field, select Processor

Select the
Download From the screen described above press the button. A new screen
Function is proposed : select “Download OS to device”
Select the file to
be downloaded Click on the button in order to select the file to download into the
PLC. In this example we will restore the OS from TSX P57 254 to TSX P57
253 version V5.9. For that select the folder :
Premium\Processor_modules\Unity_to_PL7\ :

Then select TSXP57254_to_253 (in your case, select the folder according to
your processor)

Select the OS version to download (V5.9 in our example)

Valid the choice SV5.9


Select the file to To restore the OS from Unity to PL7, two binary files can be sectioned :
be downloaded  Unity_to_PL7_253.bin (allows to “format” the processor to PL7)
(cnt’d)  TSXP57253_V59.bin is the OS that will finally be download in the
processor

In our example we have to “format” the processor (remember, we still are in


the Phase 1) then select and Valid “Unity_to_PL7_253.bin”.

Once done click on the button.


Download the Once the previous screen validated a warning is displayed
intermediate
OS

Click the button. Two screens that give information


regarding the file, the processor and the download are now displayed :

Warning : If the system detects a discrepancy on the hardware or on the OS


version, the download will not be possible. This is indicated by a red cross

and the button becomes not available.

Solve this issue and continue. When the hardware - OS are compatible, click

on the to launch the download of the intermediate OS file


Download the During the download (roughly 30 to 40 mn) the remaining time is displayed
intermediate
OS file (cnt’d)

Warning : During the download, do not power OFF the PLC, neither
disconnect the Ethernet cable nor shut down the OS loader. If
unfortunately it happens, the PLC may have lost some important files and
therefore be unable to run correctly and must be returned back for repair.

Once the download successfully completed, the screen below is displayed.

Click twice on the button and go to the Phase 2 (Power OFF


then ON or reset the PLC).
Reset the PLC Once the download of the intermediate binary file completed, the PLC has to
be initialized. This task can be performed by one of the two following actions:
 Reset the PLC by pushing on the Reset button located on the PLC’s
power supply (for more information, refer to the PLC technical
documentation
 Power OFF then ON the PLC.
Once the PLC restarted, go to Phase 3 : download the final PL7 OS

Presentation The final binary file “TSXP57XXX_VZZ.bin” where XXX represents the
processor type (253, 353, 453, ….) and ZZ the OS version, has to be
downloaded.

For that, follow the same procedure as the one described in the Phase 1.

Download As all the actions necessary to download the final PL7 OS have been already
procedure fully described in the Phase 1, they are shortly reminded here after :

1 Open the OS loader (the PC should be still connected to the PLC)

2 Select the Protocol (UNTLW01) – Refer to Phase 1

Select the target device and click on the button. The next
screen appears after few seconds.

3
Click on the button and select (for our example) the file
TSXP57253_V59.bin located on the CD OS. Then valid this screen

Select the operation to perform (Download OS to device) and press

on the button

Download At this stage, and as no functional Operating System is present in the


procedure PLC the screen displays the string “ ???” in the field “OS Version”
(cnt’d)
and an error message. Click to validate this message

Then click on the button.


Click on and validate the warning message displayed on
the screen to download the final OS file.

During the download (roughly 10 to 15 mn) the remaining time is


displayed

Warning : During the download, do not power OFF the PLC,


neither disconnect the Ethernet cable nor shut down the OS
loader. If unfortunately it happens, the PLC may have lost some
8 important files and therefore be unable to run correctly and must be
returned back for repair.

Once the download successfully completed, the screen below is


displayed.

Click twice on the button to exit the OS loader tool.


9 Reset or power OFF then ON the PLC.
Checking If needed, you can check the new CPU version. For that
version  Open the OS loader tool,
(optional)  Select the protocol (UNITLW01),

 Click on ,
 Click on .

In our example, the CPU has been restored to TSX P57 253 and the OS
version is V5.9
Appendix 1 : ETY Module Upgrade Procedure
Purpose
The upgrade of the ETY and Ethernet Port modules are completed by installing a
single file using the Unity Pro v2.2 or higher OS Loader. Please note that prior
version of the OS Loader are not compatible with this revision of the firmware.
You MUST be at the proper OS Loader revision of 2.2 or higher.

Applicable Modules
TSXETY4102 V2.0 or V2.1
TSXETY4103 V3.0 or higher
TSXP572623M Ethernet Port
TSXP573623M Ethernet Port
TSXP571634M Ethernet Port
TSXP572634M Ethernet Port
TSXP573634M Ethernet Port

Resulting Module after upgrade


TSXETY4103 BootRom V3.1, Exec V4.0
TSXP571634M Ethernet Port BootRom V3.1, Exec V4.0
TSXP572634M Ethernet Port BootRom V3.1, Exec V4.0
TSXP573634M Ethernet Port BootRom V3.1, Exec V4.0

Overview
The upgrade of an ETY module is a multi-step process. Two components must
be considered to be upgraded, the BootRom and the Exec version. Steps 6, 7
and 8 describe the various files used to upgrade the modules. Not all steps may
be required depending on the version of the ETY module before this upgrade
procedure is started.

Note - For Premium configurations, it is imperative that the update be carried out
in the following order:
- Update of ETY network modules or Ethernet coprocessors for TSX P57
2623M / TSX P57 3623M / TSX P57 1634M /TSX P57 2634M / TSX P57 3634M
PLCs,
- Update of PLC processors.

Step1
Ensure the ETY module to be upgraded is listed in the Applicable Modules
section of this document. Refer to the ETY module web pages for version
numbers.

Step2
Install the ETY module in a system consisting of only the PLC CPU, Power
Supply, Rack and ETY module. Configure the PLC system with an ‘empty’
program containing only the ETY IP address configuration.
Ensure the ETY module is installed in a PLC rack with a configured IP address.
Ensure the only devices connected to the Ethernet network are the PC running
the OS Loader and the ETY module.
The CPU module must be in STOP mode and the ETY must have NO TCP
traffic.

Step3
Ensure the PC is running OS Loader V2.2 or higher. To identify this, the first
screen of the OS Loader should look like the screen bellow.
Select ‘Next’
Step4
Select the FTP Driver.
Select ‘Next’
Step5
Select ‘Direct Device’ and enter the device IP address and select Connect. If
requested enter the module’s MAC address, the MAC address can be found on
the front of the module.
Select ‘Next’
Step6
Select Operation ‘Download OS to Device’
Select the filename to download based on the Current Module Version in the
following table.
If module not listed proceed to Step7.
If module is listed select the correct file and click ‘Next’.

Current Module File to Select Resulting Module


Version
TSXETY4102 Premium\Ethernet_modul TSXETY4103 Boot V2.1
Exec V2.0 or V2.1 es\Pl7_to_Unity\TSXETY4 Exec V3.0
102_to_4103\TSXETY410
3_V300.bin
TSXP572623M Premium\Processor_modu TSXP572634M Ethernet
Ethernet Port les\Pl7_to_Unity\TSXP572 Port Boot 2.1 Exec V3.0
623_to_2634\Eth_OS\TSX
P572634_EtyPort_V300.bi
n
TSXP573623M Premium\Processor_modu TSXP573634M Ethernet
Ethernet Port les\Pl7_to_Unity\TSXP573 Port Boot 2.1 Exec V3.0
623_to_3634\Eth_OS\TSX
P573634_EtyPort_V300.bi
n

The following Screen will appear


Ensure that both the Hardware ID and OS Version are followed by a green tick.
Select ‘Next’ and then ‘Download’
After the download is completed the following screen will appear.
If this screen does not appear recheck each step and contact your local
Schneider office for assistance if required.
Select ‘Close’ and ‘Back’ in the OS Loader.
Exit the OS loader.
Allow the module 60 seconds to complete any actions and power cycle the
module to allow the new exec to be loaded.
Restart this procedure from Step 1 and continue to Step7.

Step7
Select the filename to download based on the Current Module Version in the
following table.

Current Module File to Select Resulting Module


Version
TSXETY4103 Premium\Ethernet_module TSXETY4103 Boot V3.1
Boot V2.1 and s\Pl7_to_Unity\TSXETY41 Exec V3.0
Exec V3.0 02_to_4103\TSXETY4103
_V310_BOOT.bin
TSXP571634M Premium\Processor_modul TSXP571634M Ethernet
Ethernet Port es\Unity_Upgrade\TSXP57 Port Boot 3.1 Exec V3.0
Boot V2.1 and 1634\Eth_OS\TSXP57163
Exec V3.0 4_EtyPort_V310_BOOT.bi
n
TSXP572634M Premium\Processor_modul TSXP572634M Ethernet
Ethernet Port es\Pl7_to_Unity\TSXP5726 Port Boot 3.1 Exec V3.0
Boot V2.1 and 23_to_2634\Eth_OS\TSXP
Exec V3.0 572634_EtyPort_V310_BO
OT.bin
TSXP573634M Premium\Processor_modul TSXP573634M Ethernet
Ethernet Port es\Pl7_to_Unity\TSXP5736 Port Boot 3.1 Exec V3.0
Boot V2.1 and 23_to_3634\Eth_OS\TSXP
Exec V3.0 573634_EtyPort_V310_BO
OT.bin

If module not listed proceed to Step8.


If module is listed select the correct file and click ‘Next’.
The following screen will appear.
Ensure that the Hardware ID and OS Versions are both followed by green ticks. If
an error message regarding hardware ID is received ensure you have completed
all previous steps correctly and contact your local Schneider office for assistance
if required.

Click ‘Next’ and ‘Download’

Following the download the screen above will appear.


Select close and exit the OS Loader.
Allow the ETY module at least 60 seconds to reboot and implement the new Boot
Files. This process will be complete once the module again shows the ‘RUN’ and
‘STS’ LED’s on solid for at least 30 seconds continuously.
If the RUN and STS LED’s do not come on continuously after 2 minutes but
instead the RUN led is flashing and the STS led is on or the RUN, STS and ERR
led's are flashing power cycle the module. After completion restart this procedure
and proceed to Step8.

Step8

Select the filename to download based on the Current Module Version in the
following table.
Current Module File to Select Resulting Module
Version
TSXETY4103 Boot Premium\Ethernet_modul TSXETY4103 Boot V3.1
V3.1, Exec V3.0 or es\Unity\TSXETY4103\TS Exec V4.0
higher XETY4103_V400.bin

Comment:
TSXETY 4103
Boot V3.1, Exec
V3.0 can be
directly upgraded
to Exec V4.0. If
users want to use
an early version, it
also can be
upgraded directly.

TSXP571634M Premium\Processor_modu TSXP571634M Ethernet


Ethernet Port Boot les\Unity_Upgrade\TSXP5 Port Boot V3.1 Exec
V3.1 and Exec 71634\Eth_OS\TSXP5716 V4.0
V3.0 or higher 34_EtyPort_V400.bin

Comment:
TSXP571634M
Ethernet Port Boot
V3.1 Exec V3.0
can be directly
upgraded to Exec
V4.0. If users want
to use an early
version, it also can
be upgraded
directly.
TSXP572634M Premium\Processor_modu TSXP572634M Ethernet
Ethernet Port Boot les\Unity_Upgrade\TSXP5 Port Boot V3.1 Exec
V3.1 and Exec 72634\Eth_OS\TSXP5726 V4.0
V3.0 or higher 34_EtyPort_V400.bin

Comment:
TSXP572634M
Ethernet Port Boot
V3.1 Exec V3.0
can be directly
upgraded to Exec
V4.0. If users want
to use an early
version, it also can
be upgraded
directly.
TSXP573634M Premium\Processor_modu TSXP573634M Ethernet
Ethernet Port Boot les\Unity_Upgrade\TSXP5 Port Boot V3.1 Exec
V3.1 and Exec 73634\Eth_OS\TSXP5736 V4.0
V3.0 or higher 34_EtyPort_V400.bin

Comment:
TSXP573634M
Ethernet Port Boot
V3.1 Exec V3.0
can be directly
upgraded to Exec
V4.0. If users want
to use an early
version, it also can
be upgraded
directly.
If module is listed select the correct file and click ‘Next’.
The following screen will appear.

Ensure that the Hardware ID and OS Versions are both followed by green ticks.
Ensure that the Device Boot Loader Version is V3.1. If an error message
regarding hardware ID is received ensure you have completed all previous steps
correctly and contact your local Schneider office for assistance if required.

Click ‘Next’ and ‘Download’

Following the transfer the following screen will appear.

53/69
Select ‘Close’ and exit the OS loader.
Allow the ETY module at least 60 seconds to reboot and implement the new
Exec Files. This process will be complete once the module again shows the
‘RUN’ and ‘STS’ LED’s on solid for at least 30 seconds continuously.
If the RUN and STS LED’s do not come on continuously after 2 minutes but
instead the RUN led is flashing and the STS led is on or the RUN, STS and ERR
led's are flashing power cycle the module.

Verify the Boot and Exec versions by viewing the web pages or connecting again
with the OS Loader.

54/69
Appendix 2: Premium CoPro Ethernet Port Upgrade
Procedure
Applicable Modules
TSXP574634M
TSXP575634M
TSXP576634M

Overview
The upgrade of the CoPro Ethernet Port is complete by installing a single file
using the Unity Pro v2.2 or higher OS Loader. Please note that prior version of
the OS Loader are not compatible with this revision of the firmware. You MUST
be at the proper OS Loader revision of 2.2 or higher.

Note: the CPU exec MUST be at OS2.0 or higher before the Ethernet port is
upgraded. If the CPU is not at this revision level the Ethernet port of the CoPro
will not be configured and it will default to its “default IP address” (as defined by
the MAC address).

Special Case: channel not configured


If the Ethernet channel is not configured in the Unity Pro application, it takes the
IP address built from its MAC address:
085.016.xxx.yyy where xxx and yyy are the last two numbers of the MAC
address.
Example:
The MAC address is (in hexadecimal): 00 80 F4 01 12 20
In this case the default IP address is (in decimal): 085.016.018.032

Step1
Ensure the CoPro Ethernet port to be upgraded is listed in the Applicable
Modules section of this document. Refer to the CoPro Ethernet port web pages
for version numbers.

Step2
Install the CoPro module in a system consisting of only the PLC CPU, Power
Supply, and Rack. Configure the PLC system with an ‘empty’ program containing
only the module’s Ethernet link IP address configuration.
Ensure the CoPro Ethernet port has a configured IP address.

55/69
Ensure the only devices connected to the Ethernet network are the PC running
the OS Loader and the CoPro Ethernet port module.
Step3
Ensure the PC is running OS Loader V2.2 or higher. To identify this, the first
screen of the OS Loader should look like the screen bellow.
Select ‘Next’

Step4
Select the FTP Driver.
Select ‘Next’

56/69
Step5
Select ‘Direct Device’ and enter the device IP address and select Connect. If
requested enter the module’s MAC address, the MAC address can be found on
the front of the module.
Select ‘Next’

57/69
58/69
Step6
Select Operation ‘Download OS to Device’
Select the filename to download based on the Current Module Version in the
following table.

Current Module File to Select Resulting Module


Version
TSXP574634M Premium\Processor_modules\Un Eth Embedded link
V2.1 ity_Upgrade\TSXP57x634\Eth_O V2.5
S\TSXP574634_EthCopro_V250.
bin
TSXP574634M Premium\Processor_modules\Un Eth Embedded link
V2.2 ity_Upgrade\TSXP57x634\Eth_O V2.5
S\TSXP574634_EthCopro_V250.
bin
TSXP574634M Premium\Processor_modules\Un Eth Embedded link
V2.4 ity_Upgrade\TSXP57x634\Eth_O V2.5
S\TSXP574634_EthCopro_V250.
bin

Current Module File to Select Resulting Module


Version
TSXP575634M Premium\Processor_modules\Un Eth Embedded link
V2.1 ity_Upgrade\TSXP57x634\Eth_O V2.5
S\TSXP575634_EthCopro_V250.
bin
TSXP575634M Premium\Processor_modules\Un Eth Embedded link
V2.2 ity_Upgrade\TSXP57x634\Eth_O V2.5
S\TSXP575634_EthCopro_V250.
bin
TSXP575634M Premium\Processor_modules\Un Eth Embedded link
V2.4 ity_Upgrade\TSXP57x634\Eth_O V2.5
S\TSXP575634_EthCopro_V250.
bin

Current Module File to Select Resulting Module


Version
TSXP576634M Premium\Processor_modules\Un Eth Embedded link
V2.4 ity_Upgrade\TSXP57x634\Eth_O V2.5
S\TSXP576634_EthCopro_V250.
bin

If module is listed select the correct file and click ‘Next’.

59/69
The following Screen will appear

Ensure that both the Hardware ID and OS Version are followed by a green tick.
Select ‘Next’ and then ‘Download’
After the download is completed the following screen will appear.

60/69
Select ‘Close’ and exit the OS loader.
Allow the CoPro Ethernet port at least 60 seconds to reboot and implement the
new Exec Files. This process will be complete once the module again shows the
‘RUN’ and ‘STS’ LED’s on solid for at least 30 seconds continuously.
If the RUN and STS LED’s do not come on continuously after 2 minutes but
instead the RUN led is flashing and the STS led is on or the RUN, STS and ERR
led's are flashing power cycle the module.

Verify the Boot and Exec versions by viewing the web pages or connecting again
with the OS Loader.

61/69
Appendix 3 : FactoryCast ETY 510 Module Upgrade
Procedure

Purpose
The upgrade of the ETY 510 module is completed by installing a single file using
the Unity Pro v2.2 or higher OS Loader. Please note that prior version of the OS
Loader are not compatible with this revision of the firmware. You MUST be at the
proper OS Loader revision of 2.2 or higher.

Applicable Modules
TSXETY5102 V2.0 or V2.1
TSXETY5103 V3.0 or higher

Resulting Module after upgrade


TSXETY5103 BootRom V3.1, Exec V4.0

Overview
The upgrade of an ETY module is a multi-step process. Two components must
be considered to be upgraded, the BootRom and the Exec version. Steps 6, 7
and 8 describe the various files used to upgrade the modules. Not all steps may
be required depending on the version of the ETY module before this upgrade
procedure is started.

Note
OS Version numbers displayed in screenshots of following steps are only
examples.

Step1
Ensure the ETY module to be upgraded is listed in the Applicable Modules
section of this document. Refer to the ETY module web pages for version
numbers.

Step2
Install the ETY module in a system consisting of only the PLC CPU, Power
Supply, Rack and ETY module. Configure the PLC system with an ‘empty’
program containing only the ETY IP address configuration.

62/69
Ensure the ETY module is installed in a PLC rack with a configured IP address.
Ensure the only devices connected to the Ethernet network are the PC running
the OS Loader and the ETY module.
The CPU module must be in STOP mode and the ETY must have NO TCP
traffic.

Step3
Ensure the PC is running OS Loader V2.2 or higher. To identify this, the first
screen of the OS Loader should look like the screen bellow.
Select ‘Next’

Step4
Select the FTP Driver.
Select ‘Next’

63/69
Step5
Select ‘Direct Device’ and enter the device IP address and select Connect. If
requested enter the module’s MAC address, the MAC address can be found on
the front of the module.
Select ‘Next’

64/69
65/69
Step6
Select Operation ‘Download OS to Device’
Select the filename to download based on the Current Module Version in the
following table.

Current Module File to Select Resulting Module


Version
Premium\Ethernet_modules\Pl7_to_U TSXETY5103 Boot V2.1 Exec
TSXETY5102 Exec
nity\TSXETY5102_to_5103\TSXETY5 V3.0
V2.0 or V2.1
103_V300.bin

If device name is TSXETY5103 proceed to Step8.


If module is listed select the correct file and click ‘Next’.

The following Screen will appear

Ensure that both the Hardware ID and OS Version are followed by a green tick.
Select ‘Next’ and then ‘Download’
After the download is completed the following screen will appear.

66/69
If this screen does not appear recheck each step and contact your local
Schneider office for assistance if required.
Select ‘Close’ and ‘Back’ in the OS Loader.
Exit the OS loader.
Allow the module 60 seconds to complete any actions and power cycle the
module to allow the new exec to be loaded.
Restart this procedure from Step 1 and continue to Step7.

Step7
Select the filename to download based on the Current Module Version in the
following table.

Current Module File to Select Resulting Module


Version
TSXETY5103 Boot Premium\Ethernet_modules\Pl7_t TSXETY5103 Boot V3.1 Exec
V2.1 and Exec V3.0 o_Unity\TSXETY5102_to_5103\T V3.0
SXETY5103_V310_BOOT.bin

If module not listed proceed to Step8.


If module is listed select the correct file and click ‘Next’.
The following screen will appear.

67/69
Ensure that the Hardware ID and OS Versions are both followed by green ticks. If
an error message regarding hardware ID is received ensure you have completed
all previous steps correctly and contact your local Schneider office for assistance
if required.

Click ‘Next’ and ‘Download’

68/69
Following the download the screen above will appear.
Select close and exit the OS Loader.
Allow the ETY module at least 60 seconds to reboot and implement the new Boot
Files. This process will be complete once the module again shows the ‘RUN’ and
‘STS’ LED’s on solid for at least 30 seconds continuously.
If the RUN and STS LED’s do not come on continuously after 2 minutes but
instead the RUN led is flashing and the STS led is on or the RUN, STS and ERR
led's are flashing power cycle the module. After completion restart this procedure
and proceed to Step8.

Step8
Select the filename to download based on the Current Module Version in the
following table.

69/69
Current Module File to Select Resulting Module
Version
TSXETY5103 Boot V3.1, Premium\Ethernet_modules\Pl7_to_ TSXETY5103 Boot V3.1 Exec
Exec V3.0 or higher Unity\TSXETY5102_to_5103\TSXET V4.0
Y5103_V400.bin
Comment: TSXETY 5103
Boot V3.1, Exec V3.0 can OR
be directly upgraded to
Premium\Ethernet_modules\Unity\T
Exec V4.0. If users want
SXETY5103\TSXETY5103_V400.bin
to use an early version, it
also can be upgraded
directly.

If module is listed select the correct file and click ‘Next’.


The following screen will appear.

Ensure that the Hardware ID and OS Versions are both followed by green ticks. Ensure
that the Device Boot Loader Version is V3.1. If an error message regarding hardware ID
is received ensure you have completed all previous steps correctly and contact your
local Schneider office for assistance if required.

Click ‘Next’ and ‘Download’

Following the transfer the following screen will appear.


Select ‘Close’ and exit the OS loader.
Allow the ETY module at least 60 seconds to reboot and implement the new Exec Files.
This process will be complete once the module again shows the ‘RUN’ and ‘STS’ LED’s
on solid for at least 30 seconds continuously.
If the RUN and STS LED’s do not come on continuously after 2 minutes but instead the
RUN led is flashing and the STS led is on or the RUN, STS and ERR led's are flashing
power cycle the module.

Verify the Boot and Exec versions by viewing the web pages or connecting again with
the OS Loader.

71/69