MATLAB Command Window

The document summarizes the results of a power flow analysis using the Newton-Raphson method for a 14 bus system with 20 transmission lines. The system converged in 2 iterations. It then lists the voltage, angle, real and reactive power for each bus and the real and reactive power flows between buses including losses.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
49 views1 page

MATLAB Command Window

The document summarizes the results of a power flow analysis using the Newton-Raphson method for a 14 bus system with 20 transmission lines. The system converged in 2 iterations. It then lists the voltage, angle, real and reactive power for each bus and the real and reactive power flows between buses including losses.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

12/04/17 23:21 MATLAB Command Window 1 of 1

______________________________________________________________
RESULTADOS DO FLUXO DE POTÊNCIA PELO MÉTODO DE NEWTON-RAPHSON
______________________________________________________________
Sistema com 14 barras e 20 linhas
Convergiu em 2 iterações
____________________________________________________
RESULTADOS DAS GRANDEZAS NAS BARRAS
Barra Tipo Tensão Ângulo P Q
-- -- (pu) (graus) (MW) (MVAr)
1 0 1.0600 -0.00 66.9313 5.6841
2 1 1.0450 -1.01 18.3048 -21.1810
3 1 1.0100 -0.89 20.0049 -44.5636
4 2 1.0328 -3.84 -47.7984 3.9189
5 2 1.0419 -3.29 -7.5907 -1.5808
6 1 1.0700 -5.24 30.0114 31.6028
7 2 1.0460 -6.15 -0.0009 0.0146
8 1 1.0900 -6.15 0.0000 27.2256
9 2 1.0261 -7.37 -29.5154 -16.5966
10 2 1.0259 -7.27 -9.0021 -5.7975
11 2 1.0436 -6.37 -3.4925 -1.7946
12 2 1.0532 -6.21 -6.0984 -1.5961
13 2 1.0456 -6.36 -13.4946 -5.7924
14 2 1.0161 -7.96 -14.9029 -4.9970
_________________________________________________________________________
RESULTADOS DOS FLUXOS DE POTÊNCIA
De Para Pkm Qkm Pmk Qmk Pperda Qperda
-- -- (MW) (MVAr) (MW) (MVAr) (MW) (MVAr)
1 2 -37.9138 -14.7462 37.6283 13.8747 -0.2854 -0.8715
1 5 -29.0175 -2.3987 28.6098 0.7158 -0.4077 -1.6829
2 3 -3.0829 -17.7445 2.9433 17.1564 -0.1396 -0.5880
2 4 -29.6555 1.7833 29.1858 -3.2084 -0.4697 -1.4251
2 5 -23.1948 5.2272 22.9000 -6.1273 -0.2948 -0.9001
3 4 -22.9482 21.6334 22.2949 -23.3010 -0.6534 -1.6676
4 5 28.7830 13.0795 -28.9081 -13.4741 -0.1251 -0.3946
4 7 -20.7592 6.1128 20.7592 -7.0310 0.0000 -0.9182
4 9 -11.7061 -1.5937 11.7061 0.8659 0.0000 -0.7278
5 6 -15.0109 11.3697 15.0109 -12.1930 0.0000 -0.8233
6 11 -14.6052 -7.3222 14.3837 6.8585 -0.2214 -0.4637
6 12 -8.8432 -2.8480 8.7505 2.6551 -0.0927 -0.1929
6 13 -21.5740 -9.2397 21.2557 8.6129 -0.3182 -0.6267
7 8 0.0000 26.1266 0.0000 -27.2256 0.0000 -1.0990
7 9 -20.7583 -19.1103 20.7583 18.3098 0.0000 -0.8005
9 10 1.7792 -0.9914 -1.7805 0.9881 -0.0013 -0.0033
9 14 -4.7283 -1.5877 4.6982 1.5238 -0.0300 -0.0639
10 11 10.7826 4.8094 -10.8912 -5.0638 -0.1087 -0.2544
12 13 -2.6522 -1.0590 2.6359 1.0443 -0.0162 -0.0147
13 14 -10.3970 -3.8648 10.2047 3.4732 -0.1924 -0.3916
>>