Power System Protection - Part 07
Power System Protection - Part 07
Differential Protection
(Unit protection)
321
Power System Protection Part – VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
Differential Protection
Differential protection is the best technique in protection. In this type of
protection the electrical quantities entering and leaving the protected zone
or area are compared by current transformers (C.T.s). If the net difference
equal zero, it means no fault exist.
This system is operating in either of the two following principles:
1. Current balance principle.
2. Voltage balance principle.
Differential protection is applicable to all parts of the power system:
1. Generator.
2. Transformers.
3. Motors.
4. Buses.
5. Lines and feeders.
6. Reactors and capacitors
There are two basic types of differential protection:
Current Balance Differential protection
Voltage Balanced Differential Protection
1. Current Balance Differential protection:
Operation during internal and external fault conditions
Fig.1 shows the basic current differential protection based on current
balance principle.
- At normal conditions and for external fault at F, CT1 and CT2
circulate currents at their secondary’s Is1 and Is2 (Is1 =Is2) and no
current flow through the relay (ΔI = Is1 - Is2 = 0), hence the relay will
not operate.
- If fault occurs at point F within the protected zone (internal fault) as
shown in Fig.2, and the fault is fed from both sides, then current
through C.T2 will be reversed. Therefore a current ΔI = Is1 + Is2 will
flow in the operating winding of the relay. This will cause the relay to
trip the circuit breaker connected to the faulty system. Hence the relay
trips when
| Is1 +Is2|>|I| |I|=> pick up current of relay
This form of protection is known as Merz-Price protection.
321
Power System Protection Part – VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
Fig 1
325
Power System Protection Part – VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
321
Power System Protection Part – VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
-Relay may also operate if the fault in feed is from one direction as shown in
fig.3.
321
Power System Protection Part – VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
Fig 4
Fig 5.
321
Power System Protection Part – VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
Figure 6—Basic relay connections (one phase) for fixed percentage restraint
differential relay.
321
Power System Protection Part – VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
At Normal conditions:
The differential current in the operating coil is proportional to Is1-Is2.
Iop = Is1-Is2
The equivalent current in the restrain windings are proportional to
½ ( Is1+Is2) since the two restrain windings are identical.
Irest = ½ ( Is1+Is2)
(mmfop )2 ˃ (mmfr )2
(Is1-Is2) No ˃ ½ ( Is1+Is2) Nr
(Is1-Is2) No ˃ ½ (Is1+Is2) k No
311
Power System Protection Part – VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
Fig.8 Balanced beam relay with restrain. (a) Balanced beam type relay (b)
Schematic
313
Power System Protection Part – VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi
312