Compressor Tecumseh AE4440Y-AA1A
Compressor Tecumseh AE4440Y-AA1A
Compressor Tecumseh AE4440Y-AA1A
1/15/2019
Product Description
Type: Reciprocating
Application: HBP/CBP - High/Commercial
Back Pressure
Refrigerant: R-134a/R-513A
Voltage/Frequency: 115V ~ 60Hz
Version: N/A
Product Specifications
Performance
Refrigeration Capacity Input Power Efficiency EVAP TEMP COND AMBIENT RETURN LIQUID
Condition Test Voltage Btu/h kcal/h W W Btu/Wh kcal/Wh W/W TEMP TEMP GAS TEMP
ASHRAE 115V ~ 60HZ 4528 1141 1327 611 7.4 1.87 2.17 7.2°C (45°F) 54°C (130°F) 35°C (95°F) 35°C (95°F) 46°C (115°F)
(R-513A)
ARI (R-513A) 115V ~ 60HZ 4213 1062 1234 610 6.91 1.74 2.02 7.2°C (45°F) 54°C (130°F) 35°C (95°F) 18.3°C 46°C (115°F)
(65°F)
ASHRAE 115V ~ 60HZ 4350 1096 1275 550 7.91 1.99 2.32 7.2°C (45°F) 54°C (130°F) 35°C (95°F) 35°C (95°F) 46°C (115°F)
(R-134a)
General
Evaporating Temp. Range: -15°C to 15°C (5°F to 59°F)
Motor Torque: High Start Torque (HST)
Compressor Cooling: Fan
Mechanical
Weight: 10
Weight Unit of Measure: KG
Displacement (cc): 10.33
Oil Type: Polyolester
Viscosity (cSt): 32
Oil Charge (cc): 284.9
Electrical
Voltage Range (50 Hz): N/A
Voltage Range (60 Hz): 103-127
Locked Rotor Amps (LRA): 32
Rated Load Amps (RLA 50 Hz): 0
Rated Load Amps (RLA 60 Hz): 5.82
Max. Continuous Current (MCC in Amps): 8.81
Motor Resistance (Ohm) - Main: 1.65
Motor Resistance (Ohm) - Start: 3.44
Motor Type: CSIR
Overload Type: N/A
Relay Type: N/A
Agency Approval
CE Listed, SASO Listed, cURus Recognized
Performance Data Sheet
AE4440Y-AA1A
General Information
Model AE4440Y-AA1A Refrigerant R-134a/R-513A
Test Condition ARI (R-134a) Performance Test Voltage 115V ~ 60HZ
Return Gas 4.4°C (40°F) RETURN GAS Motor Type CSIR
Performance Information
Condensing Temperature (°F)
Evap Temp (°F)
80 90 100 110 120 130 140 150
Value = C1 + C2 * Te + C4 * Te^2 + C7 * Te^3 + (C3 + C5 * Te + C8 * Te^2) * Tc + (C6 + C9 * Te) * Tc^2 + C10 * Tc^3
Te = Evaporator Temperature
Tc = Condensing Temperature
Performance Data Sheet
AE4440Y-AA1A
General Information
Model AE4440Y-AA1A Refrigerant R-134a/R-513A
Test Condition ARI (R-134a) Performance Test Voltage 115V ~ 60HZ
Return Gas 18.3°C (65°F) RETURN GAS Motor Type CSIR
Performance Information
Condensing Temperature (°F)
Evap Temp (°F)
80 90 100 110 120 130 140 150
Value = C1 + C2 * Te + C4 * Te^2 + C7 * Te^3 + (C3 + C5 * Te + C8 * Te^2) * Tc + (C6 + C9 * Te) * Tc^2 + C10 * Tc^3
Te = Evaporator Temperature
Tc = Condensing Temperature
Performance Data Sheet
AE4440Y-AA1A
General Information
Model AE4440Y-AA1A Refrigerant R-134a/R-513A
Test Condition ASHRAE (R-134a) Performance Test Voltage 115V ~ 60HZ
Return Gas 35°C (95°F) RETURN GAS Motor Type CSIR
Performance Information
Evap Condensing Temperature (°C)
Temp (°C) 30 35 40 45 50 55 60 65
Watts (Power) 307 318 328 337 344 348 348 344
-15
Amps 4.35 4.40 4.45 4.50 4.53 4.54 4.53 4.48
Watts (Power) 337 350 363 376 387 395 400 401
-10
Amps 4.50 4.57 4.63 4.70 4.76 4.81 4.83 4.82
Watts (Power) 355 371 386 401 415 426 435 440
-6.7
Amps 4.61 4.68 4.76 4.85 4.93 5.00 5.05 5.07
Watts (Power) 364 381 398 414 429 443 453 460
-5
Amps 4.66 4.74 4.83 4.93 5.02 5.10 5.16 5.20
Watts (Power) 389 409 430 451 471 490 506 519
0
Amps 4.81 4.91 5.03 5.16 5.28 5.41 5.51 5.60
Watts (Power) 409 433 458 484 510 535 557 578
5
Amps 4.93 5.06 5.21 5.37 5.54 5.71 5.87 6.01
Watts (Power) 416 442 469 498 526 553 579 603
7.2
Amps 4.97 5.12 5.28 5.47 5.65 5.84 6.02 6.19
Watts (Power) 423 451 482 513 545 576 606 633
10
Amps 5.02 5.18 5.37 5.57 5.79 6.00 6.22 6.42
Watts (Power) 429 463 498 536 574 612 649 684
15
Amps 5.05 5.25 5.48 5.73 6.00 6.27 6.54 6.80
Value = C1 + C2 * Te + C4 * Te^2 + C7 * Te^3 + (C3 + C5 * Te + C8 * Te^2) * Tc + (C6 + C9 * Te) * Tc^2 + C10 * Tc^3
Te = Evaporator Temperature
Tc = Condensing Temperature
Performance Data Sheet
AE4440Y-AA1A
General Information
Model AE4440Y-AA1A Refrigerant R-134a/R-513A
Test Condition ASHRAE (R-134a) Performance Test Voltage 115V ~ 60HZ
Return Gas 35°C (95°F) RETURN GAS Motor Type CSIR
Performance Information
Condensing Temperature (°F)
Evap Temp (°F)
100 110 120 130 140
Value = C1 + C2 * Te + C4 * Te^2 + C7 * Te^3 + (C3 + C5 * Te + C8 * Te^2) * Tc + (C6 + C9 * Te) * Tc^2 + C10 * Tc^3
Te = Evaporator Temperature
Tc = Condensing Temperature
Performance Data Sheet
AE4440Y-AA1A
General Information
Model AE4440Y-AA1A Refrigerant R-134a/R-513A
Test Condition ASHRAE (R-513A) Performance Test Voltage 115V ~ 60HZ
Return Gas 35°C (95°F) RETURN GAS Motor Type CSIR
Performance Information
Condensing Temperature (°F)
Evap Temp (°F)
80 90 100 110 120 130 140 150
Value = C1 + C2 * Te + C4 * Te^2 + C7 * Te^3 + (C3 + C5 * Te + C8 * Te^2) * Tc + (C6 + C9 * Te) * Tc^2 + C10 * Tc^3
Te = Evaporator Temperature
Tc = Condensing Temperature