NEW Chapter 13 Generator Protection PDF
NEW Chapter 13 Generator Protection PDF
GENERATOR PROTECTION
• Types Of Faults
Internal Faults
• Differential Protection (Phase Faults)
• Field Grounds
• Setting Example
Synchronous generators for industrial and commercial applications are typically of the non-
unit type (directly connected to the bus vice through a step-up transformer) with ratings
varying from .48-13.8 kV and .5 - 30 MVA.
In medium-sized and large power stations the generators are operated exclusively in unit
connection. In the unit connection the generator is linked to the busbar of the higher
voltage level via a transformer. In the case of several parallel units, the generators are
electrically isolated by the transformers. A circuit-breaker can be connected between the
generator and the transformer.
The task of electrical protection in these systems is to detect deviations from the normal
condition and to react according to the protection concept and the setting. The scope of
protection must be in reasonable relation to the total system costs and the importance of
the system.
Although generators are subject to numerous types of hazards, this chapter will limit
discussion to four types of internal faults and several types of abnormal operating and/or
system conditions. Additional protective schemes, such as overvoltage, out-of-step,
synchronization, etc. should also be considered depending on the cost and relative
importance of the generator.
• Phase and/or ground faults in the stator and associated protection zone
• Field grounds
• Overloads
• Overheating
• Overspeed
• Unbalanced Currents
• Loss of Excitation
• Overvoltage
• Volts → 0
• Power Factor → 0
”
• Current → 10-15 times IFLA (function of X d)
Machine Speed: Because the fault impedance (Z) is normally very small, and the kW out
approaches zero, the generator “sees” the fault as an instantaneous drop in load and
overspeeds in a very short time. All of the prime mover kW input goes to accelerating the
rotor; if left unchecked the turbine blades can be seriously damaged (tearout). Speed
control by the governor cannot react fast enough and therefore relays are used to protect
the generator.
Generator Stability: Faults must be cleared within approximately 0.3 seconds (18 cycles)
to preserve stability. The fault is removed by dropping the generator; for large systems
load shedding is initiated to prevent frequency and voltage drops.
The suggested protection for instantaneous and sensitive protection for generator internal
faults is differential protection (ANSI Device No. 87G), which is very similar to motor
differential protection. A constant percentage, high sensitivity (e.g.,10%) differential
element is recommended. If CT saturation error exceeds 1%, a lower sensitivity (e.g.,
25%) type element should be used. No settings are required for these elements.
Generator differential elements (Figure 13-1) are usually arranged to simultaneously trip
the generator, field circuit, and neutral breakers (if used) through a manually reset lockout
auxiliary relay (ANSI Device No. 86). In some applications, the differential element also
trips the throttle and admits CO2 to the generator for fire protection.
Another alternative differential scheme is to use three zero sequence current transformers
and three type instantaneous trip elements, as shown in Figure 13-5. Although this partial
differential feature protection scheme is more sensitive and less costly (e.g.,6 CTs versus
3 CTs), it does not protect the cables between the generator terminals and the breaker.
The instantaneous element, used in differential manner (ANSI Device No. 87) is typically
set at 0.15A. The zero sequence CTs are usually sized at a 50/5 ratio (most common) with
a 4-inch diameter, or 100/5 ratios are also available with 7 and 14-inch diameters.
A low resistance grounded generator refers to a generator that has substantial impedance
applied at the wye neutral point so that, during a ground fault, a reduced but readily
detectable level of ground current, typically on the order of 100-500A, flows.
The location of the ground fault within the generator winding, as well as the grounding
impedance, determines the level of fault current. Assuming that the generated voltage
along each segment of the winding is uniform, the prefault line-ground voltage level is
proportional to the percent of winding between the fault location and the generator neutral,
VFG in Fig. 13-8. Assuming an impedance grounded generator where (Z0, SOURCE and
ZN)>>ZWINDING, the current level is directly proportional to the distance of the point from
the generator neutral [Fig. 13-8(a)], so a fault 10% from neutral produces 10% of the
current that flows for a fault on the generator terminals. While the current level drops
towards zero as the neutral is approached, the insulation stress also drops, tending to
reduce the probability of a fault near the neutral. If a generator grounding impedance is low
relative to the generator winding impedance or the system ground impedance is low, the
fault current decay will be non-linear. For I1 in Fig. 13-8, lower fault voltage is offset by
lower generator winding resistance. An example is shown in Fig. 13-8(b).
If 87G feature is provided per Fig. 13-9, relay 51N backs up the 87G, as well as external
relays. If an 87G is not provided or is not sufficiently sensitive for ground faults, then the
51N provides the primary protection for the generator. The advantage of the 87G is that it
does not need to be delayed to coordinate with external protection; however, delay is
required for the 51N. One must be aware of the effects of transient DC offset induced
saturation on CTs during transformer or load energization with respect to the high speed
operation of 87G relays. Transient DC offset may induce CT saturation for many cycles
(likely not more than 10), which may cause false operation of an 87G relay. This may be
addressed by not block loading the generator, avoiding sudden energization of large
transformers, providing substantially overrated CTs, adding a very small time delay to the
87G trip circuit, or setting the feature fairly insensitively.
The neutral CT should be selected to produce a secondary current of at least 5A for a solid
generator terminal fault, providing sufficient current for a fault near the generator neutral.
For example, if a terminal fault produces 1000A in the generator neutral, the neutral CT
ratio should not exceed 1000/5. For a fault 10% from the neutral and assuming I1 is
proportional to percent winding from the neutral, the 51N current will be 0.5A, with a
1000/5 CT.
Machine Characteristics:
• 19.5 MVA, p.f. = 80%, 12.47 kV, FLA = 903 A, X”d = 10.7%, X’d = 15.4%
Fig. 13-13 shows a simple means of detecting phase faults, but clearing is delayed, since
the 51 relay must be delayed to coordinate with external devices. Since the 51 relay
operates for external faults, it is not generator zone selective.
It will operate for abnormal external operating conditions such as remote faults that are not
properly cleared by remote breakers. The 51 pickup should be set at about 175% of rated
current to override swings due to a slow-clearing external fault, the starting of a large
motor, or the re-acceleration current of a group of motors.
Energization of a transformer may also subject the generator to higher than rated current
flow.
The current does not decay as fast for a phase-phase or a phaseground fault and, thereby,
allows the 51 relay more time to trip before current drops below pickup. Fig. 13-14
assumes no voltage regulator boosting, although the excitation system response time is
unlikely to provide significant fault current boosting in the first second of the fault. It also
assumes no voltage regulator dropout due to loss of excitation power during the fault. If the
generator is loaded prior to the fault, prefault load current and the associated higher
excitation levels will provide the fault with a higher level of current than indicated by the
Fig. 13-14 curves. An estimate of the net fault current of a pre-loaded generator is a
superposition of load current and fault current without pre-loading. For example, assuming
a pre-fault 1pu rated load at 30 degree lag, at one second the 3 phase fault value would be
2.4 times rated, rather than 1.75 times rated (1@30°+1.75@90°=2.4@69°). Under these
circumstances, the 51 relay has more time to operate before current decays below pickup.
Figure 13-14. Generator Fault Current Decay Example for 3 Phase and Phase-Phase
Faults at Generator Terminals – with no Regulator Boosting or Dropout during Fault
and no Pre-fault load
For example, the relay might be set for about 175% of generator rated current with rated
voltage applied; at 25% voltage the relay picks up at 25% of the relay setting
(1.75*0.25=0.44 times rated). The voltage controlled approach inhibits operation until the
voltage drops below a preset voltage. It should be set to function below about 80% of rated
voltage with a current pickup of about 50% of generator rated. Since the voltage-controlled
type has a fixed pickup, it can be more readily coordinated with external relays than can
the voltage-restrained type. The voltage-controlled type is recommended since it is easier
to coordinate. However, the voltage restrained type will be less susceptible to operation on
swings or motor starting conditions that depress the voltage below the voltage controlled
undervoltage unit dropout point.
Most large generators are equipped with resistance temperature detectors (RTDs) that are
often used in a bridge circuit to provide sensing intelligence to an indicator or a relay. The
relay has contact-opening torque when the resistance is low, which indicates low machine
o
temperature. When the temperature of the machine exceeds 120 C for class B-insulated
machines, the bridge becomes unbalanced and the contact closes.
Overexcitation can occur due to higher than rated voltage, or rated or lower voltage at less
than rated frequency. For a given flux level, the voltage output of a machine will be
proportional to frequency. Since maximum flux level is designed for normal frequency and
voltage, when a machine is at reduced speed, maximum voltage is proportionately
reduced. A volts/hertz relay (24) responds to excitation level as it affects thermal stress to
the generator (and to any transformer tied to that generator). IEEE C50.13 specifies that a
generator should continuously withstand 105% of rated excitation at full load.
With the unit off line, and with voltage-regulator control at reduced frequency, the
generator can be overexcited if the regulator does not include an overexcitation limiter.
Overexcitation can also occur, particularly with the unit off line, if the regulator is out of
service or defective. If voltagebalance supervision (60) is not provided and a fuse blows on
the regulator ac potential input, the regulator would cause overexcitation. Loss of ac
potential may also fool the operator into developing excessive excitation. The 24 relay can
only protect for overexcitation resulting from an erroneous voltage indication if the 24 relay
is connected to an ac potential source different than that used for the regulator.
Fig. 13-17 shows the 46 relay connection. CTs on either side of the generator can be
used, since the relay protects for events external to the generator. The alarm unit in the
relay will alert the operator to the existence of a dangerous condition.
Figure 13-17 Negative Sequence Current Relay (46) protects against rotor
overheating due to a series unbalance or protracted external fault. Negative
sequence voltage relays (47) (less commonly applied) also responds
A negative sequence overcurrent relay (ANSI Device No. 46) is the recommended
protection for this unbalanced condition.
Generator anti-motoring protection is designed for protection of the prime mover, or the
system, rather than for protection of the generator itself. Motoring results from low prime
mover input to the generator, such as would occur if the steam supply to the turbine or the
oil supply to the diesel were lost. When the prime mover input to the generator cannot
meet all the losses, the deficiency is supplied by the system -- the generator absorbs real
power and reactive power flow (not relevant at this point) may be in or out depending on
the voltage (system excitation). Under motoring conditions, steam turbine blades can
overheat, water wheel turbine blades can cavitate, and fire or possible explosion can result
in a diesel unit.
When the prime mover spins at synchronous speed with no power input, the approximate
reverse power that is required to motor a generator, as a percentage of the nameplate kW
rating, is listed in Table 13-2.
Although there are a number of non-electrical (mechanical) protection schemes for the
generator prime mover, a reverse power relay (ANSI Device No. 32) is used to provide
supplemental protection.
The reverse power relay should have sufficient sensitivity such that motoring power
provides 5-10 times the minimum pickup power of the relay. An induction disc directional
power relay is frequently used to introduce sufficient time delay necessary to override
momentary power surges that might occur during synchronizing. A time delay of 10-15
seconds is typical.
In a steam-turbine, the low pressure blades will overheat with the lack of steam flow.
Diesel and gas-turbine units draw large amounts of motoring power, with possible
mechanical problems. In the case of diesels, the hazard of a fire and/or explosion may
occur due to unburnt fuel. Therefore, anti-motoring protection is recommended whenever
the unit may be connected to a source of motoring power.
Where a non-electrical type of protection is in use, as may be the case with a steam
turbine unit, the 32 relay provides a means of supervising this condition to prevent opening
the generator breaker before the prime mover has shut down. Time delay should be set for
about 5-30 seconds, providing enough time for the controls to pick up load upon
synchronizing when the generator is initially slower than the system.
Since motoring can occur during a large reactive-power flow, the real power component
needs to be measured at low power factors.
Figure 13-20. Reverse-power relay 32-1 prevents load rejection before prime mover
shutdown for selected trips; relay 32-2 operates if motoring is not accompanied by
an 86NE operation
Loss of excitation can, to some extent, be sensed within the excitation system itself by
monitoring for loss of field voltage or current. For generators that are paralleled to a power
system, the preferred method is to monitor for loss of field at the generator terminals.
When a generator loses excitation power, it appears to the system as an inductive load,
and the machine begins to absorb a large amount of VARs. Loss of field may be detected
by monitoring for VAR flow or apparent impedance at the generator terminals.
The power diagram (P-Q plane) of Fig. 13-22 shows 40Q characteristic of a typical loss of
field relay with a representative setting, a representative generator thermal capability
curve, and an example of the trajectory following a loss of excitation. The first quadrant of
the diagram applies for lagging power factor operation (generator supplies VARs). The
trajectory starts at point A and moves into the leading power factor zone (4th quadrant)
and can readily exceed the thermal capability of the unit. A trip delay of about 0.2-0.3
seconds is recommended to prevent unwanted operation due to other transient conditions.
A second high speed trip zone might be included for severe underexcitation conditions.
When impedance relaying is used to sense loss of excitation, the trip zone typically is
marked by a mho circle centered about the X axis, offset from the R axis by X'd/2. Two
zones sometimes are used: a high speed zone and a time delayed zone (Figure 13-23)
Rotor thermal capability can also be exceeded for a partial reduction in excitation due to an
operator error or regulator malfunction. If a unit is initially generating reactive power and
then draws reactive power upon loss of excitation, the reactive swings can significantly
depress the voltage. In addition, the voltage will oscillate and adversely impact sensitive
loads. If the unit is large compared to the external reactive sources, system instability can
result.
The differential relay responds to fault contributions from both the generator and the
external system. While the differential relay is fast, the slow decay of the generator field
will cause the generator to continue feeding current into a fault. However, fast relay
operation will interrupt the externalsource contribution, which may be greater than the
generator contribution. Fast disconnection from the external source allows prompt
restoration of normal voltage to loads and may reduce damage and cost of repairs.
The differential relay (87G) may protect for ground faults, depending upon the grounding
impedance. The 51N relay in Fig. 13-25 provides back-up protection for the 87G or will be
the primary protection if the differential relay (87G) is not sufficiently sensitive to the
ground current level.
Fig. 13-25 shows three relays sharing the same CTs with a differential relay. This is
practical with solid state and numeric relays, because their low burden will not significantly
degrade the quality of differential relay protection. The common CT is not a likely point of
failure of all connected relaying. A CT wiring error or CT short is unlikely to disable both
the 87G and 51V relays. Rather, a shorted CT or defective connection will unbalance the
differential circuit and cause the 87G to trip. Independent CTs could be used to provide
improved back-up protection, although this seems to be a minimal advantage here.
However, a separate CT is used for the 51N relay that provides protection for the most
likely type of fault. The reverse power relay (32) in Fig. 13-25 protects the prime mover
against forces from a motored generator and could provide important protection for the
external system if the motoring power significantly reduces voltage or overloads
equipment.
Likewise, the loss-of-field relay (40) has dual protection benefits—against rotor
overheating and against depressed system voltage due to excessive generator reactive
absorption. Thermal relay (49) protects against stator overheating due to protracted heavy
reactive power demands and loss of generator cooling. Even if the excitation system is
equipped with a maximum excitation limiter, a failure of the voltage regulator or a faulty
manual control could cause excessive reactive power output. Frequency relaying (81O/U)
protects the generator from off nominal frequency operation and senses generator
islanding. The under and overvoltage function (27/59) detects excitation system problems
and some protracted fault conditions.
Typical relays include a third harmonic undervoltage function (27-3N), that provides
supervision of the grounding system, protects for faults near the generator neutral, and
detects a shorted or open connection in the generator ground connection or in the
distribution transformer secondary circuit.
Features
Protection and Control
• Generator stator differential • Overexcitation
• Power swing blocking and out-of-step • Phase sequence reversal for pumped
tripping storage
• Networking interfaces – 100Mbit Fiber Optic Ethernet, RS485, RS232, RS422, G.703,
C37.94
• Multiple Protocols - IEC61850, DNP 3.0 Level 2, Modbus RTU, Modbus TCP/IP,
IEC60870-5-104, Ethernet Global Data (EGD)
• Direct I/O – secure, high-speed exchange of data between URs for Direct Transfer Trip
and I/O Extension applications
• Embedded Managed Ethernet Switch with 4 - 100 Mbit Fiber optic ports and 2 copper
ports
• Event Recorder - 1024 time tagged events with 0.5ms scan of digital inputs
- 1 to 60 phasors/sec
Voltage, current, and power metering is built into the relay as a standard feature. Current
parameters are available as total waveform RMS magnitude, or as fundamental frequency
only RMS magnitude and angle (phasor).
Diagnostic features include an event recorder capable of storing 1024 time-tagged events,
oscillography capable of storing up to 64 records with programmable trigger, content and
sampling rate, and data logger acquisition of up to 16 channels, with programmable
content and sampling rate. The internal clock used for time-tagging can be synchronized
with an IRIGB signal or via the SNTP protocol over the Ethernet port. This precise time
stamping allows the sequence of events to be determined throughout the system. Events
can also be programmed (via FlexLogic™ equations) to trigger oscillography data capture
which may be set to record the measured parameters before and after the event for
viewing on a personal computer (PC). These tools significantly reduce troubleshooting
time and simplify report generation in the event of a system fault.
A faceplate RS232 port may be used to connect to a PC for the programming of settings
and the monitoring of actual values.
Ideally, the CTs should be selected so the generator nominal current is 80 to 85% of CT
primary. The following settings are entered for the example system. The M5 bank and the
ground CT input on each of the groups are unused in this example.
1. CT accuracy errors
2. CT saturation
The characteristic allows for very sensitive settings when fault current is low and less
sensitive settings when fault current is high and CT performance may produce incorrect
operate signals.
• Stator Diff Line End Source: This setting selects the source connected to CTs in the
end of the machine stator winding closest to the load and furthest from the winding
neutral point. Both line and neutral-side CTs should be wired to measure their currents
in the same direction with respect to the neutral point of the winding.
• Stator Diff Neutral End Source: This setting selects the source connected to CTs in the
end of the machine stator winding furthest from the load and closest to the winding
neutral point. Both line and neutral-side CTs should be wired to measure their currents
in the same direction with respect to the neutral point of the winding.
• Stator Diff Pickup: This setting defines the minimum differential current required for
operation. This setting is based on the amount of differential current that might be seen
under normal operating conditions. A setting of 0.1 to 0.3 pu is generally
recommended.
• Stator Diff Slope 1: This setting is applicable for restraint currents from zero to
STATOR DIFF BREAK 1, and defines the ratio of differential to restraint current above
which the element will operate. This slope is set to ensure sensitivity to internal faults at
normal operating current levels. The criteria for setting this slope is to allow for
maximum expected CT mismatch error when operating at the maximum permitted
current. This maximum error is generally in the range of 5 to 10% of CT rating.
• Stator Diff Break 1: This setting defines the end of the Slope 1 region and the start of
the transition region. It should be set just above the maximum normal operating current
level of the machine.
• Stator Diff Slope 2: This setting is applicable for restraint currents above the STATOR
DIFF BREAK 2 setting when the element is applied to generator stator windings. This
slope is set to ensure stability under heavy external fault conditions that could lead to
high differential currents as a result of CT saturation. A setting of 80 to 100% is
recommended.
The transition region (as shown on the characteristic plot) is a cubic spline,
automatically calculated by the relay to result in a smooth transition between STATOR
DIFF SLOPE 1 and STATOR DIFF SLOPE 2 with no discontinuities.
SATURATION DETECTION:
External faults near generators typically result in very large time constants of DC
components in the fault currents. Also, when energizing a step-up transformer, the inrush
current being limited only by the machine impedance may be significant and may last for a
very long time. In order to provide additional security against maloperations during these
events, the G60 incorporates saturation detection logic. When saturation is detected the
element will make an additional check on the angle between the neutral and output
current. If this angle indicates an internal fault then tripping is permitted.
GENERATOR UNBALANCE
THEORY OF OPERATION
The generator unbalance element protects the machine from rotor damage due to
excessive negative-sequence current.
The element has an inverse time stage which is typically used for tripping and a definite
time stage typically used for alarm purposes. The inverse time stage operating
characteristic is defined by the following equation:
• Gen Unbal Inom: This setting is the rated full load current of the machine. • GEN
UNBAL STG1 PICKUP: This setting defines the pickup of the stage 1 element
expressed as a percentage of the nominal current as specified by GEN UNBAL
INOM setting. It is typically set at the maximum continuous negative sequence
current rating of the machine.
Chapter 13 Page 50 Generator Protection
• Gen Unbal Stg1 K-Value: This setting is the negative sequence capability constant.
This value is normally provided by the generator manufacturer (refer to ANSI
C50.13 for details).
• Gen Unbal Stg1 Tmin: This is the minimum operate time of the stage 1 element.
The stage will not operate before this time expires. This is set to prevent false trips
for faults that would be cleared normally by system protections.
• Gen Unbal Stg1 Tmax: This is the maximum operate time of the stage 1 element.
This setting can be applied to limit the maximum tripping time for low level
unbalances.
• Gen Unbal Stg1 K-Reset: This setting defines the linear reset rate of the stage 1
element. It is the maximum reset time from the threshold of tripping. This feature
provides a thermal memory of previous unbalance conditions.
• Gen Unbal Stg2 Pickup: This setting defines the pickup of the stage 2 element
expressed as a percentage of the nominal current as specified by GEN UNBAL
INOM setting. The definite time element would normally be used to generate an
alarm to prompt an operator to take some corrective action. The stage 2 element
would typically be set at a safe margin below the stage 1 pickup setting.
• Gen Unbal Stg2 Pkp Delay: This is the minimum operate time of the stage 2
element. This is set to prevent nuisance alarms during system faults.
Stage 1 of the generator unbalance element is typically used to trip the generator. In this
example, the I2 capability of the machine is 8% and the I22T capability is 10. The generator
nominal current is:
The minimum operate time of stage 1 will be set to 0.25 seconds, the maximum operating
time will be 10 minutes, and the reset time will be set to 4 minutes. Stage 2 is typically set
lower than stage 1 with a time delay to prevent nuisance alarms for external faults that are
normally cleared by system protection. For the application example, the pickup setting is:
Pickup=70% × I2 capability=0.70 × 8% = 5.6%
LOSS OF EXCITATION
THEORY OF OPERATION
The operating characteristic is shaped out of two offset mho circles shifted down along the
imaginary axis as shown below.
The stage 1 characteristic is typically set to detect a loss of excitation for load conditions of
30% of the nominal or higher.
This is achieved with a mho element with a diameter equal to the base impedance of the
machine and an offset equal to half the machine transient reactance (X′d).
The stage 1 element should be time delayed to allow for blocking by the VT fuse failure
element (50 ms).
Stage 2 Settings:
The stage 2 characteristic is typically set to detect a loss of excitation for all load
conditions. This is achieved with a mho element with a diameter equal to the synchronous
reactance of the machine and an offset equal to half the machine transient reactance (X′d).
During stable power swing conditions the positive-sequence impedance may momentarily
enter the stage 2 characteristic. For security of the function under such conditions, it is
recommended to delay stage 2 by a minimum of 0.5 seconds.
The voltage supervision setting will be determined by a system study and may be disabled
on either element if required. VT fuse failure should supervise this element.
If none of these curve shapes is adequate, FlexCurves™ may be used to customize the
inverse time curve characteristics.
The Definite Time curve is also an option that may be appropriate if only simple protection
is required.
to the time multiplier (TD MULTIPLIER) setting value. For example, all times for a
multiplier of 10 are 10 times the multiplier 1 or base curve values. Setting the multiplier to
zero results in an instantaneous response to all current levels above pickup.
Time overcurrent time calculations are made with an internal ‘energy capacity’ memory
variable. When this variable indicates that the energy capacity has reached 100%, a time
overcurrent element will operate. If less than 100% energy capacity is accumulated in this
variable and the current falls below the dropout threshold of 97 to 98% of the pickup value,
the variable must be reduced. Two methods of this resetting operation are available:
“Instantaneous” and “Timed”. The “Instantaneous” selection is intended for applications
with other relays, such as most static relays, which set the energy capacity directly to zero
when the current falls below the reset threshold. The “Timed” selection can be used where
the relay must coordinate with electromechanical relays.
The IEEE time overcurrent curve shapes conform to industry standards and the IEEE
C37.112-1996 curve classifications for extremely, very, and moderately inverse. The IEEE
curves are derived from the formulae:
Two methods of resetting operation are available: “Timed” and “Instantaneous” (refer to
the Inverse Time overcurrent curves characteristic sub-section earlier for details on curve
setup, trip times, and reset operation). When the element is blocked, the time accumulator
will reset according to the reset characteristic. For example, if the element reset
characteristic is set to “Instantaneous” and the element is blocked, the time accumulator
will be cleared immediately.
The PHASE TOC1 PICKUP setting can be dynamically reduced by a voltage restraint
feature (when enabled). This is accomplished via the multipliers (Mvr) corresponding to the
phase-phase voltages of the voltage restraint characteristic curve (see the figure below);
the pickup level is calculated as ‘Mvr’ times the PHASE TOC1 PICKUP setting. If the
voltage restraint feature is disabled, the pickup level always remains at the setting value.
System backup protection is implemented using a phase time overcurrent element with
voltage restraint enabled. The NEUTRL source will be chosen for this element. The pickup
of this element should be set at a safe margin above the maximum load expected on the
machine.
The selection of all standard curves (and FlexCurves™) is allowed for easy coordination
with system relaying. For the example system, an IEEE extremely inverse curve will be
used and a setting will be chosen such that the operate time for a three phase fault on the
high side of the transformer is 0.75 seconds. For simplicity, the power system contribution
is not considered.
Since this element will coordinate with system protections a timed reset is chosen. The
element must be blocked for a VT fuse failure. The neutral source will be chosen
This function provides time-delayed protection for system faults that have not been cleared
by system protections and to provide backup protection for stator faults.
The “Line” source will be used in this example to permit the application of a forward and
reverse zone. The memory duration will be left at the default setting (10 cycles).
Zone 1 will look forward and cover the GSU and the transmission line leaving the station.
Zone 3 will look in the reverse direction and cover the stator winding. Zone 2 will not be
used in this example. Both the VTs and the CTs are located on the low voltage side of the
GSU. The transformer vector diagram (see Figure 13-31) shows this transformer to be
Yd1. Consequently, due to the location of instrument transformers, Dy11 is chosen for both
the XFMR VOL CONNECTION and XFMR CUR CONNECTION settings. There are no
transformers in the reverse direction. Therefore “None” is chosen for both of the zone 3
transformer connection settings. The reach of the zone 1 element will be set at 120% of
impedance of the GSU and the transmission line. In the instance that there are multiple
lines and/or multiple generators, the zone 1 reach must be increased to compensate for
the infeed effect.
The zone 3 reach will be set at 120% of the generator transient reactance. The time delay
of this element should be compared to the generator decrement curve to verify the
adequacy of this setting.
An mho shape has been chosen for this example. Therefore, the quadrilateral settings are
left at their default values.
Note: Most generators produce enough third-harmonic voltage for proper application of the
64G2 element; however, some generators (e.g., those with 2/3 pitch winding) may not. In
those cases the element based on the third-harmonic voltage, such as the 64G2, cannot
be used for 100 percent Stator Ground Protection.
This function detects stator ground faults in all but the bottom 5–10 percent of the
generator winding. In this area close to the generator neutral, the neutral voltage does not
increase significantly during a generator ground fault. The G60 relay uses the third-
harmonic voltage differential element to detect faults in this area.
The following formula is used to create an adaptive operating quantity based on the
amount of third harmonic that appears at the generator terminals.
where: VN(3rd) is a magnitude of the 3rd harmonic in the voltage measured at the
machine neutral point measured via an auxiliary channel of the VT bank, and V0(3rd) is a
magnitude of the 3rd harmonic in the zero-sequence voltage measured at the machine
terminals.
This element requires wye-connected VTs for measurement of the third harmonic in
the zero-sequence voltage at the generator output terminals.
Consider the figure shown below. In the case of a high impedance grounded machine, the
neutral resistor is typically chosen such that power dissipated in the resistor during a single
line to ground fault is approximately equal to the reactive power produced by the zero
sequence capacitance of the stator winding and the GSU LV winding (X0c ). At power
system frequencies, the neutral resistance is therefore equal to Xoc / 3, and at 3 x Fn, the
neutral resistance is Xoc
The per-unit V/Hz value is calculated using the maximum of the three-phase voltage inputs
or the auxiliary voltage channel Vx input, if the Source is not configured with phase
voltages. To use the V/Hz element with auxiliary voltage, set SYSTEM SETUP
SIGNAL SOURCES SOURCE 1(6) SOURCE 1(6) PHASE VT to “None” and
SOURCE 1(6) AUX VT to the corresponding voltage input bank. If there is no voltage on
the relay terminals in either case, the per-unit V/Hz value is automatically set to “0”. The
per unit value is established as per voltage and nominal frequency power system settings
as follows:
1. If the phase voltage inputs defined in the source menu are used for V/Hz operation,
then “1 pu” is the selected SYSTEM SETUP → AC INPUTS →↓ VOLTAGE BANK
N →↓ PHASE VT N SECONDARY setting, divided by the divided by the SYSTEM
SETUP →↓ POWER SYSTEM → NOMINAL FREQUENCY setting.
2. When the auxiliary voltage Vx is used (regarding the condition for “None” phase
voltage setting mentioned above), then the 1 pu value is the SYSTEM SETUP →AC
INPUTS →↓ VOLTAGE BANK N AUXILIARY VT N SECONDARY setting
divided by the SYSTEM SETUP →↓ POWER SYSTEM → NOMINAL FREQUENCY
setting.
3. If V/Hz source is configured with both phase and auxiliary voltages, the maximum
phase among the three voltage channels at any given point in time is the input
voltage signal for element operation, and therefore the per-unit value will be
calculated as described in Step 1 above. If the measured voltage of all three phase
voltages is 0, than the perunit value becomes automatically 0 regardless of the
presence of auxiliary voltage.
The element has a linear reset characteristic. The reset time can be programmed to match
the cooling characteristics of the protected equipment. The element will fully reset from the
trip threshold in VOLTS/HZ T-RESET seconds. The V/Hz element may be used as an
instantaneous element with no intentional time delay or as a Definite or Inverse timed
element.
• DEFINITE TIME: T(sec.) = TD Multiplier. For example, setting the TD Multiplier set
to 20 means a time delay of 20 seconds to operate, when above the Volts/Hz
pickup setting. Instantaneous operation can be obtained the same way by setting
the TD Multiplier to “0”.
THEORY OF OPERATION
This element provides protection against energization while the generator is at standstill or
reduced speed. The feature is armed using either the AND or OR combination of the
undervoltage and machine off-line conditions, selected with the
ACCDNT ENRG ARMING MODE setting (see below). The undervoltage condition is
determined from the measured voltages. The machine off-line status is indicated by a
dedicated FlexLogic™ operand. Once armed, the accidental energization feature operates
upon detecting an overcurrent condition in any of the stator phases.
• ACCDNT ENRG ARMING MODE: This setting specifies whether the feature gets armed
by either of the undervoltage or machine off-line conditions (“UV or Off-line” value), or by
both the conditions (“UV and Off-line” value). In both cases, the element is armed after 5
seconds of the appropriate condition and de-armed 250 ms after the arming condition (UV
and/or Off-line) ceases.
The “UV or Off-line” selection shall be made when the VTs are on the power system side
of the disconnecting device.
If this is the case, the measured voltages may be normal regardless of the status of the
protected machine, thus the need for an OR condition. The “UV or Off-line” value provides
protection against poor synchronization. During normal synchronization, there should be
relatively low current measured. If however, synchronization is attempted when conditions
are not appropriate, a large current would be measured shortly after closing the breaker.
Since this feature does not de-arm immediately, but after a 250 ms time delay, this will
result in operation under imprecise synchronization.
The ACCDNT ENRG OC PICKUP setting can control the required precision of
synchronization.
The “UV and Off-line” value shall be made when the VTs are on the generator side of the
disconnecting device. If this is the case, both the undervoltage and machine off-line
conditions are required to indicate that the protected generator is not energized.
• ACCDNT ENRG OC PICKUP: This setting specifies the current level required to operate
the armed Accidental Energization element. If any of the phase current is above the
ACCDNT ENRG OC PICKUP level, the feature operates.
• ACCDNT ENRG UV PICKUP: This setting specifies the voltage level required to arm the
Accidental Energization element.
All of the line-to-line voltages must drop below the ACCDNT ENRG UV PICKUP level in
order to detect the undervoltage condition. The setting is entered in voltage pu values. As
• ACCDNT ENRG OFFLINE: This setting specifies the FlexLogic™ operand indicating that
the protected generator is off-line