Directions:: T-501 Vertical Fixed Roof Residual Fuel Oil No. 6 Jimmy Peress Newark NJ Outdoor Storage Tank
Directions:: T-501 Vertical Fixed Roof Residual Fuel Oil No. 6 Jimmy Peress Newark NJ Outdoor Storage Tank
Fill in pink input cells with specific tank description, dimensions, throughput and paint absorptance factor. For
DIRECTIONS: paint absorptance factor included in Table 1a below.
Tank No. T-501 Tank type Vertical fixed roof Date 03/27/19
Material stored Residual Fuel Oil No. 6 Company Performed by Jimmy Peress
City Newark State NJ
Description Outdoor storage tank
INPUT DATA CALCULATIONS
Symbol Units Symbol Units
Breathing losses
Molecular Weight Tank vapor space volume Vv 6,217.75 ft3
Molecular weight Mv 190.00 Lb/lb-mole Vapor density Wv 1.929E-6 lb/ft3
Tank design data Vapor space expansion facto KE 0.06467
Shell height Hs 40.00 Vented vapor saturation factoKs 0.9999 ft2
Diameter D 20.00 ft
Liquid height Hl 40.00 ft Breathing losses LB 0.28 lb/yr
Avg. Liquid height Hl 20.00 ft
vapor space outage Hvo 20.21 ft Working losses Lw 0.24 lb/yr
Tank volume 94,003 gallons
Turnovers N 10 TOTAL LOSSES LT 0.53 lb/yr
Net throughput Q 940,033 gallons/yr
Tunover factor KN 1.000
Working loss product factor Kp 1.00
Meteorological data Table 1a
Daily ave. ambient temp. TAA 54.75 °F Tank Paint Solar Absorptance
Daily max. ambient temp. TAX 63.38 °F
Daily min. ambient temp. TAN 46.11 °F Solar
Daily ambient temp. range DTA 17.28 °F Tank Paint Absorptance
Tank paint solar absorptance (see adjacent tabl a 0.68 white/white 0.17
Daily total insolation factor I 1,236 Btu/ft2-day Aluminum/Specular 0.39
gray/light 0.54
Liquid bulk temperature TB 57.83 °F Aluminum/Diffuse 0.6
Daily vapor temp. range DTv 35.96 °F grey/medium 0.68
1
Calculations performed on this spreadsheet are taken from the USEPA
AP-42- Section 7.1 Organic Liquid Storage Tanks - January 1996. This
spreadsheet is derived from materials provided by Jimmy Peress, PE,
Tritech Consulting Engineers, 85-93 Chevy Chase Street, Jamaica, NY
11432 USA, Tel - 718-454-3920, Fax - 718-454-6330, e-mail -
[email protected].
Units
Table 1
TANK EMISSION CALCULATION FORM1
( Note - Cells in pink are input cells. All other cells are calculated cells. )
Fill in pink input cells with specific tank description, dimensions, throughput and paint absorptance factor. For
DIRECTIONS: paint absorptance factor included in Table 1a below.
Tank No. T-501 Tank type Vertical fixed roof Date 03/27/19
Material stored Distilllate Fuel Oil NO. 2 Company Performed by Jimmy Peress
City Newark State NJ
Description Outdoor storage tank
INPUT DATA CALCULATIONS
Symbol Units Symbol Units
Breathing losses
Molecular Weight Tank vapor space volume Vv 6,217.75 ft3
Molecular weight Mv 130 Lb/lb-mole Vapor density Wv 1.667E-4 lb/ft3
Tank design data Vapor space expansion facto KE 0.06496
Shell height Hs 40.00 Vented vapor saturation factoKs 0.9925 ft2
Diameter D 20.00 ft
Liquid height Hl 40.00 ft Breathing losses LB 24.40 lb/yr
Avg. Liquid height Hl 20.00 ft
vapor space outage Hvo 20.21 ft Working losses Lw 20.95 lb/yr
Tank volume 94,003 gallons
Turnovers N 10 TOTAL LOSSES LT 45.35 lb/yr
Net throughput Q 940,033 gallons/yr
Tunover factor KN 1.000
Working loss product factor Kp 1.00
Meteorological data Table 1a
Daily ave. ambient temp. TAA 54.75 °F Tank Paint Solar Absorptance
Daily max. ambient temp. TAX 63.38 °F
Daily min. ambient temp. TAN 46.11 °F Solar
Daily ambient temp. range DTA 17.28 °F Tank Paint Absorptance
Tank paint solar absorptance (see adjacent tabl a 0.68 white/white 0.17
Daily total insolation factor I 1,236 Btu/ft2-day Aluminum/Specular 0.39
gray/light 0.54
Liquid bulk temperature TB 57.83 °F Aluminum/Diffuse 0.6
Daily vapor temp. range DTv 35.96 °F grey/medium 0.68
1
Calculations performed on this spreadsheet are taken from the USEPA
AP-42- Section 7.1 Organic Liquid Storage Tanks - January 1996. This
spreadsheet is derived from materials provided by Jimmy Peress, PE,
Tritech Consulting Engineers, 85-93 Chevy Chase Street, Jamaica, NY
11432 USA, Tel - 718-454-3920, Fax - 718-454-6330, e-mail -
[email protected].
Units
Table 1
TANK EMISSION CALCULATION FORM1
( Note - Cells in pink are input cells. All other cells are calculated cells. )
Fill in pink input cells with specific tank description, dimensions, throughput and paint absorptance factor. For
DIRECTIONS: paint absorptance factor included in Table 1a below.
Tank No. T-501 Tank type Vertical fixed roof Date 03/27/19
Material stored Gasoline (RVP 9) Company Performed by Jimmy Peress
City Newark State NJ
Description Outdoor storage tank
INPUT DATA CALCULATIONS
Symbol Units Symbol Units
Breathing losses
Molecular Weight Tank vapor space volume Vv 6,217.75 ft3
Molecular weight Mv 67 Lb/lb-mole Vapor density Wv 5.849E-2 lb/ft3
Tank design data Vapor space expansion facto KE 0.23798
Shell height Hs 40.00 Vented vapor saturation factoKs 0.1629 ft2
Diameter D 20.00 ft
Liquid height Hl 40.00 ft Breathing losses LB 5,144.50 lb/yr
Avg. Liquid height Hl 20.00 ft
vapor space outage Hvo 20.21 ft Working losses Lw 7,348.37 lb/yr
Tank volume 94,003 gallons
Turnovers N 10 TOTAL LOSSES LT 12,492.88 lb/yr
Net throughput Q 940,033 gallons/yr
Tunover factor KN 1.000
Working loss product factor Kp 1.00
Meteorological data Table 1a
Daily ave. ambient temp. TAA 54.75 °F Tank Paint Solar Absorptance
Daily max. ambient temp. TAX 63.38 °F
Daily min. ambient temp. TAN 46.11 °F Solar
Daily ambient temp. range DTA 17.28 °F Tank Paint Absorptance
Tank paint solar absorptance (see adjacent tabl a 0.68 white/white 0.17
Daily total insolation factor I 1,236 Btu/ft2-day Aluminum/Specular 0.39
gray/light 0.54
Liquid bulk temperature TB 57.83 °F Aluminum/Diffuse 0.6
Daily vapor temp. range DTv 35.96 °F grey/medium 0.68
1
Calculations performed on this spreadsheet are taken from the USEPA
AP-42- Section 7.1 Organic Liquid Storage Tanks - January 1996. This
spreadsheet is derived from materials provided by Jimmy Peress, PE,
Tritech Consulting Engineers, 85-93 Chevy Chase Street, Jamaica, NY
11432 USA, Tel - 718-454-3920, Fax - 718-454-6330, e-mail -
[email protected].
Units
Table 1
TANK EMISSION CALCULATION FORM1
( Note - Cells in pink are input cells. All other cells are calculated cells. )
Fill in pink input cells with specific tank description, dimensions, throughput and paint absorptance factor. For
DIRECTIONS: paint absorptance factor included in Table 1a below.
Tank No. T-501 Tank type Vertical fixed roof Date 03/27/19
Material stored Gasoline (RVP 13) Company Performed by Jimmy Peress
City Newark State NJ
Description Outdoor storage tank
INPUT DATA CALCULATIONS
Symbol Units Symbol Units
Breathing losses
Molecular Weight Tank vapor space volume Vv 195.33 ft3
Molecular weight Mv 62 Lb/lb-mole Vapor density Wv 8.129E-2 lb/ft3
Tank design data Vapor space expansion facto KE 0.39416
Shell height Hs 20.00 Vented vapor saturation factoKs 0.2049 ft2
Diameter D 5.00 ft
Liquid height Hl 20.00 ft Breathing losses LB 468.06 lb/yr
Avg. Liquid height Hl 10.00 ft
vapor space outage Hvo 10.05 ft Working losses Lw 217.29 lb/yr
Tank volume 2,938 gallons
Turnovers N 7 TOTAL LOSSES LT 685.35 lb/yr
Net throughput Q 20,000 gallons/yr
Tunover factor KN 1.000
Working loss product factor Kp 1.00
Meteorological data Table 1a
Daily ave. ambient temp. TAA 54.75 °F Tank Paint Solar Absorptance
Daily max. ambient temp. TAX 63.38 °F
Daily min. ambient temp. TAN 46.11 °F Solar
Daily ambient temp. range DTA 17.28 °F Tank Paint Absorptance
Tank paint solar absorptance (see adjacent tabl a 0.68 white/white 0.17
Daily total insolation factor I 1,236 Btu/ft2-day Aluminum/Specular 0.39
gray/light 0.54
Liquid bulk temperature TB 57.83 °F Aluminum/Diffuse 0.6
Daily vapor temp. range DTv 35.96 °F grey/medium 0.68
1
Calculations performed on this spreadsheet are taken from the USEPA
AP-42- Section 7.1 Organic Liquid Storage Tanks - January 1996. This
spreadsheet is derived from materials provided by Jimmy Peress, PE,
Tritech Consulting Engineers, 85-93 Chevy Chase Street, Jamaica, NY
11432 USA, Tel - 718-454-3920, Fax - 718-454-6330, e-mail -
[email protected].
Units