Atlanta Transformer Components
Atlanta Transformer Components
The employees are given training for safe working practices followed
by the safety rules.
Health treatment, which falls under company‘s scope.
Providing safe and modern tools and equipments.
By adopting human and earth friendly technology for the
manufacturing of products.
Atlanta has adopted OHSAS system and has been accredited by OHSAS-
18001:2007.
2 INTRODUCTION OF TRANSFORMERS
Vp = -Np A Vs = -Ns A
E = 4.44×f×N×Bmax×Acore
Where, E = rated coil voltage (volts),
f = operating frequency (hertz),
N = number of turns in the winding,
Bmax = maximum flux density in the core (tesla), and
Acore = cross-sectional area of the core material in Sq.
meters.
VA = 4.44×f×N×Bmax×Acore×J×Acond
Where, N, Bmax, Acore and f are as defined above, J is the current
density (A/ sq. mm), and Acond is the coil cross-sectional area (mm2) in the
core window; of the conducting material for primary winding. J depends
upon heat dissipation and cooling.
Power Transformers
Mobile Transformers
Distribution Transformers
Furnace Transformers
a. Induction Furnace Duty
b. Arc Furnace Duty
Motor Starting Transformers
Neutral Grounding Transformers
Rectifier Duty Transformers
Testing Transformer
C. Reactors
Air Core Reactors
Gap Core Reactors
3 MANUFACTURING PROCESS OF
TRANSFORMER
Winding Construction
Core Assembly
Core & Winding(Coil) Assembly (CCA)
Tapping &Tap Changer
Drying Process
Tank Construction
Tanking & Final Fitting
Fittings & Accessories
Painting
Oil Filling & Filtration
Testing
1) Helical Winding
2) Layer Winding
3) Disc Winding
4) Interleaved Winding
Winding Construction
Core is built with Cold Rolled Grain Oriented Silicon Steel, low loss
silicon steel lamination . Bonded core design/ technique is used to eliminate
hole punching and to minimize fixed losses and Magnetizing Current. Use of
HiB grade & Laser scribed Laminations and Rigid clamps significantly
reduce vibrations and noise level. Cooling ducts are provided in large
transformers for efficient circulation of oil to keep temperature of core well
within limit without affecting the flux distortion and also in the core suitable
insulation paper are inserted between some laminations for the purpose of
reducing eddy currents and also minimizing magnetic short circuit.
Core of the transformer is either in square or rectangular in size. It is
further divided into two parts. The vertical position of the core is limbs and
horizontal position of the core is yoke of the core. Core is made up of
laminations to reduce the eddy current losses get minimized. This
lamination is insulated by using insulations line varnish or thick paper.
Paper insulation is used for low voltage transformer and varnish is used for
high voltage transformer.
The step lap or Mitred joints at the core corners ensure a stream line
magnetic flux path. The core limb are held with resin bonded glass bands to
eliminate limb bolts. Yokes are clamped by solid mild steel plates with yoke
stud ensuring high rigidity for withstanding mechanical socks during
transportation & Short Circuits. The leg core in a which hard wooden bars
are inserted, are tighten with synthetic resin impregnated fibre glass tape.
Core Assembly
L.V. Windings are normally placed near core over insulating cylinder
and oil ducts. HV Windings are assembled co-axially placed with respect to
LV. Spacers between coils are 'T' shaped for added firmness. Coils are
assembled with best insulating materials and are adequately clamped. SPA
methodology is now a day widely adopted to have it's special beneficial
characteristics. The winding is rigidly supported by a common spacer ring of
densified wood at the top and bottom for precise alignment. Well profiled
angled rings are placed between LV & HV windings to reduce voltage stress
level. The ends & tapping leads of all windings are connected by special extra
flexible, insulated copper cables which are rigidly braced in position.
Tap Changer
There are three different drying periods which will occur consecutively
in time:
Above 18% MC the grain drying rate can be increased (that is, drying
will occur faster) by providing a higher temperature or more drying air
without major changes in grain temperature. Below 18%MC increase in
drying air temperature will not increase the drying rate but will increase
grain temperatures and potentially damage the grain. Therefore, higher
drying air temperatures can be used to dry grain quickly down to 18% MC
(to remove "surface moisture") but lower temperatures should be used to
remove internal moisture from the grain.
For seed purposes, drying air temperatures should never exceed 43ºC,
regardless of the MC, to avoid overheating of the grain which kills the germ.
Exposing paddy to 60ºC for one hour can reduce the seed germination rate
from 95% to 30%. Two hours at 60ºC will reduce the germination rate to
5%.
3.5.4 Tempering
Small capacity tanks are fabricated from sheet steel while larger ones
are assembled with cast aluminium. For cooling purpose the tank is welded
with cooling tubes. These are some types of transformer tanks.
Protection of active part in transformer is very important. While
achieving the optimized size of transformer to suit the site condition for
installation. The main role of the tank is to protect the active part and tank
is manufacture to have sufficient strengths to withstand internal & external
faults that may occur during operation. Tanks are fabricated from low
carbon M.S. Sheet of best quality proceed by qualified welders. The tank is
designed to withstand vacuum and pressure test as per Indian /
International standards. A robust skid under base is provided, and guide
bars are located inside the tank to securely fix the core and windings
assembly in position, and to prevent any movement during transportation.
Dried out Core & Coil Assembly is tightened before application of hot oil
shrinkaging for 24 hours. The oil shrinkaging process avoids looseness of
active parts during it's service at site. At last uniform pressing is done on
Core & Coil Assembly. High mechanical rigidity is achieved by hydraulic
pressing at circulated force and tightening all pressure screws. Pressed Core
& Coil Assembly is put in to the tank with proper locating & locking
arrangements which is of prime importance to achieve high resistivity
against transient damages, vibrations during service and Forces develop
during fault occurrence.
After completion of Core & Coil Assembly insertion in tank, hot, degassed
oil is then allowed into the transformer tank under vacuum. This oil is then
circulated through the transformer and the oil degassing plant until all gas
trapped in the core, windings, and the insulation is removed. This ensures a
high degree of stability in the insulation structure and early attainment of its
mature condition, which would not otherwise be achieved until the
transformer had been in service for some time.
The transformer is made ready for testing after assembly of bushings,
conservators, radiators & all other protective devices .All the joints are
gasketed to avoid leakage with the help of rubberized cork sheets/Nitrite
Rubberized ORing, which can withstand high oil temperature and do not
deteriorate nor contaminate oil in its contact.
Final Fitting
The transformer must be isolated from all time the live lines, before
operating the switch.
Operating the switch when transformer is energized, will damage the
switch contacts due to severe arcing between the contacts and many damage
transformer winding.
When switch handle is provided on the side wall, it is necessary that
switch handle assembly is dismantled before undertaking.
Some times links are provided inside the transformer tank to obtain
required voltage ratio. Links are required to be loosened and fixed in new
required position as given in R & D plate. Links are accessible from the
inspection cover. In case of conservator units, oil level has to be lowered
below the inspection cover before unbolting inspection cover.
For further details, please refer to the attached manual of OLTC and
schematics.
3.8.5 Valves
The wheel valves are used either with female screw threads or with
flanges. These are of gun metal/cast iron type.
Generally, one isolating valve also known as shut off valves is
provided for transformer up to 2000KVA between conservator and buchholz
relay.
The butterfly type cast steel valves with the machined flanges are
used at points of connection between tank and detachable radiators.
3.8.6 Bushings
3.8.6.1 Oil Communicating Type
Generally, condenser bushings are used for 72.5KV and above. These
bushings contain their own oil and are sealed to retain the same. Whenever
these bushings are mounted on bushings pockets or raised truncated
portions, air vent pips are provided for carrying away air or gases from these
pockets to Buchholz relay during service typical assembly.
These bushings are detached from the transformers and dispatched
separately. They are packed as per manufacturer‘s instructions. The draw
through type lead is coiled and kept temporarily below the bushing blanking
plate. The equipment required for mounting the bushings are
(1) Rope slings.
(2) Flexible steel wire approx 2mm in diameter, of suitable length.
Cable boxes are designed for receiving & protecting cables ends.
Insulating paper is most hygroscopic & all paper insulated cable ends must
be protected by suitable insulating compound. These cable boxes are
provided with brass wiping glands & designed with clearances insides the
box suitables for compound filling. The cable box in such case must be filled
with compound as marked as indicated in the drawling.
Cable boxes of PVC are XLPE cables are designed with air clearances
and hence these boxes are not required to be filled with compound.
Cable boxes of 3.6 KV & above are provided with detachable gland
plates. Earthing terminals are also provided on these cable boxes for
earthing the amounting of individual cable when cable boxes are provided
with disconnecting chambers they permit removal of transformers for
servicing without disturbing cable terminations.
3.8.8 Bus-duct\trunkings
conservator falls to a low level. This Protection feature and clear visibility
justify the cost of MOG on a bigger transformer.
3.9 Painting:-
All the Transformers are supplied with first filling of oil conforming to IS
335. Before filling, oil is heated, filtered and vacuum treated in filter
machine to remove any foreign particles, moisture and air.
Oil Filling
3.11 Testing:-
For this test rated phase to neutral voltage is applied across the
object. A coupling capacitor (having low inductance) is connected across the
test object which converts the input currents to low output voltage. The
output of this coupling capacitor is fed to the PD measuring instrument
which gives the PD value in Pico Coulomb and also indicates the discharges
on the sinusoidal waveform. The most important requirement for this test is
a PD free power source transformer. The circuit for PD testing is shown in
figure below
CONNECTIONN SCHEME
The test is for verifying whether the temperature rise limits of the
windings , as agreed at the time of the enquiry, are respected. The test can
be carried out by means of two different methods:
Simulated loading method (in accordance with. IEC 60726 p.21.1.3)
The method used is defined at the time of the enquiry.
CONNECTION SCHEME
4.1 Installation
4.1.1 Location
4.1.2 Foundation
Keep the main tank in its permanent position of operation. Lock the
rollers to prevent any accidental movement on rails. Draw an oil sample from
the botton of the tank and test it for Break-Down-Voltage (BDV).
4.1.6 Bushing
Clean the bushings and check that there are no hair-cracks or other
damages. Test IR value of each bushing with a 500V Megger. It should be
100 M ohms or greater. Note details of Bushings in the ―Commissioning
Report.‖ Mount all the bushings as described in 2.6. Ensure that the test tap
cap is fully tightened, thus positively grounding the same. Adjust the Arcing
Horn Gaps in accordance with the Insulation Co-ordination Note these
values in the ―Commissioning Report‖.
Note details of ―Buchholz Relay‖ for the transformer and of ―Oil Surge
Relay‖ for the OLTC in the ―Commissioning Report.‖ Buchholz Relay floats
are tied to prevent transit damage. They should be released. Also if ‗ Test‘
lever is provided, it should be in the working position. Mount the ―Buchholz
Relay‖ and the shut off valves as described in 2.10 Similarly mount ―Oil
Surge Relay‖.
4.1.9 Breathers
4.1.10 Radiators
(vi) Oil might seep through the tank side radiator valves and be retained
by the blanking plates. This oil should be collected in a clean
container at the time of removing top and bottom blanking plates.
(vii) Bring the radiator flanges close to the flanges on the tank. Ensure
that tank gasket is in position. Fit by means of bolts, nuts spring
washers etc.
(viii) Open the bottom radiator valve using the operating handle. Gradually
unscrew the air release plug on the top of the radiator, until air starts
escaping. Air release plug should not be removed from the engaging
threads as it would be difficult to control oil coming out of it. Oil from
main tank will now flow in the radiator, driving out air form air
release plug. When oil comes out steadily form the air release plug
and no more air comes through, close the air release plug. Open the
top radiator valve. Oil level in the conservator would now have fallen.
Check that there is no oil leakage from the radiator itself and the
gasketted joints. Restore the oil level and assemble the next radiator
in the same manner.
Set the ‗Alarm‘ & ‗Trip‘ contacts of O.T.I & W.T.I. at required values.
O.T.I. setting as A=85 C & T=95 C W.T.I. setting of A-95 C & T+ 105 C are
considered good. They can be worked out to suit local conditions.
When Cable Boxes are provided they should be mounted and cable
terminations done. Oil filled cable-boxes should be duly filled with oil. In
case of ―Bus-Duct‖ connections, transformer is provide with a flange to
receive the bus-duct. Due connection and fitting should be done to over-
head line by a terminal connector.
Taking usual precaution, draw oil samples from Bottom & Top of
main tank and from OLTC. They should be tested for BDV. If they meet the
requirements of I.S. 1866 for new transformers, no further processing is
required. However if they do not meet the requirements, oil needs to be
filtered till the required BDV is obtained. Note the BDV values in the
―Commissioning Report‖.
4.2 Commissioning
Ratio between all the three corresponding H.V. & L.V. phases is to be
measured on all taps. It is desirable to do this test by a Ratio-meter. But if it
is not available, a simple test of measuring voltages can also serve the
purpose.
Referring to R&D plate, fine out which terminals of H.V. & L.V.
correspond to one phase e.g. for a vector Group of Dyn-11, H.V. Terminals
1U, 1V, & L.V. terminals 2U, 2N correspond to U phase. Apply single phase,
415 V or 240 V, AC., 50 Hz to H.V. side and measure voltage on the L.V.
side. Measure these voltages on all taps and note them in ―Commissioning
Report‖ Repeat for the other two phase. These observations should indicate a
consistent trend of variation in line with the details given in R&D Plates.
Numerical values should approximately check with the voltage ratio
Apply 415 volts, 2 phase, AC. to the H.V. terminals, keeping the L.V.
terminals open and tapping switch in the normal position. Measure the 3
line currents, if possible simultaneously, otherwise one after the other.
Because the 3 phases of the magnetic circuit of the core are not similar, the
3 line currents will be approximately equal & v phase current around 80% of
either of them. If H.V. is delta connected, V & W phase currents will be
approximately equal and U phase current around 110 %
In case of Power Transformers, such a test is done, some times, along
with routine tests at the manufacturer works. When done at site and results
compared with the factory test confirms that there are no transit damages to
the core and windings. Note the observations in the ―Commissioning Report‖.
For the H.V. side voltage and the % impedance, it would be possible to
calculate the current which would flow in the H.V. side, with 415V applied to
it, while keeping L.V. side shorted. If the 415 V source can feed that current,
a short-circuit test can be carried out.
This test would confirm proper contact engagement at all tap
positions. Apply 3 ph. 415 V, 50 Hz to H.V. side, keeping L.V. side shorted.
Measure the 3 line currents at all tap positions. If the switch is an OFF-
CIRCUIT switch, supply has to be disconnected before changing tap. Note
the observations in the ―Commissioning Report‖. Note also details of OLTC, if
any.
A Consistent trend indicates healthiness. If short-circuit test is not
possible due to limitation of source, carry out one tap changing operation
over the entire range increasing as well as decreasing. Check the other
modes of OLTS operation and note in ―Commissioning Report‖.
(1) Its voltage ratio is same as the existing transformer on all tappings.
(2) Its % Impedance is within +1% of value of existing transformer.
4.5 Energising
When all the pre-commissioning tests are found satisfactory and all
the check points are confirmed the transformer can be energized on No load.
It is preferable to keep settings of all protective relays to the minimum. The
transformer should be allowed to run on No-Load for about 3 hours. During
this period, the transformer should be observed for any abnormality in the
hum and gas collection in the Buchholz Relay. Sometimes during this
period, trapped air is released and gets accumulated in Buchholz Relay.
At the end of this 3 hours period, transformer should be de-energised
and air released from Bushings, Bushing pockets, Buchholz Relay, Main
tank cover, Radiators etc. The transformer should, then, be energized again
and then relays set at their desired setting. Transformer should then be
grandually loaded reaching full load in about 3 hours time. During the
period and for further 3 hours, (i.e. total of 6 hours) transformer should be
under observation. Check that all instruments, O.T.I & W.T.I, M.O.G. are
reading properly and that all radiators are uniformly hot. Check that there is
no gas collection in Buchholz Relay. If everything is found in order, the
transformer can continue working.
The ―Commissioning Report‖ should be duly signed by the Authorised
representatives of all the participating organizations.
5.1 OPERATION
5.2 Maintenance
5.2.1 General
5.2.2 OIL
It id recommended that the core and windings are removed from the
tank for visual inspection as per the maintenance schedule given.
Depending upon the arrangement provided, tap switch handle, connections
to bushings etc. may have to be disconnected before lifting up core and
wings assembly
The windings should be examined and if sludge has been deposited
it should be washed away with oil jet. Any loose nut and bolt should be
tighterned.
Adjust the rods/coil clamping screws provided to remove any
slackness of windings. This is important as slackness in winding will
permit movement of coils under the action of Short Circuits forces and
repeated coil movement can wear out insulation and give rise to a fault.
The pipe work should be inspected for leakages, which may be due, to
bad seated joints, joints should be re-made and leakage stopped.
5.2.10 Bushing
5.3.1 CURRENTTRANSFORMER
Zinc oxide gapless arresters or metal oxide arrester. There are gapless
& consist of zinc-oxide dises in series zone arresters have. Superior V/I
characteristic & higher energy absorption level and they are preferred for
EHV & HVDC installations.
5.4.2 Impurities
5.4.5 Breather
5.4.6 Oil
5.4.7 Temperature
When the transformer is installed & put in service for the first time,
the oil temperature must be taken at interval of about 2 hours for the first
two days.
The temperature of oil may than be checked for further 2 or 3 days
during these hours to see whether the same temperature is reached every
day. If the temperature remains below 70`c the temperature may be checked
one 9 month or so unless the load increases or weather gats considerable
hot. In case of temperature exceeds 70`c more frequeat checking of
temperature is required.
From time to time the transformer should be taken out of service for a
complete examination & over hall, which should include lifting or core &
winding from the tank for inspection.
1 2 3 4 5
(ii)
Explosion
- Replace if cracked or
vent
broken.
driving
mecha
nism.
breather.
(vii) Check -
Ventilators that air
passages are
(In
free.
case of
indoor
transformers)
Gauge freedom of
movement.
(ix) - Take
Earth suitable action if
earth resistance is
Resista
high.
nce
transfo
rmers
6 CONCLUSION
The training of which manufacturing of transformer company was
very help full to me. It has improved my theoretical concept of transformer.
We also know that a transformer is a device that transfers electrical
energy from one circuit to another through inductively coupled conductors—
the transformer's coils. A varying current in the first or primary winding
creates a varying magnetic flux in the transformer's core and thus a
varying magnetic field through the secondary winding. This varying magnetic
field induces a varying electromotive force (EMF), or "voltage", in the
secondary winding. This effect is called inductive. The training was more
than hope to me and also help me to understand about manufacturing of
transformer more.
7 Reference
Basic Electrical Engineering, by R.P. Ajwaliya
Chapter No. 14
Page No.367 to 415
8 BIBLIOGRAPHY
www.atlantaeletrcals.com
http://seminarprojects.com/Thread-construction-of-
transformer
http://www.most.gov.mm/techuni/media/EP_03041_6.pdf
http://www.energymanagertraining.com/CodesandManualsCD-
5Dec%2006/BEST%20PRACTICE%20MANUAL-
TRANSFORMERS.pdf
http://tad-
electronics.com/files/Download/The_J%26P_Transformer_Book
_12E.pdf
http://www.powerlinker.org/htm/SFRA.pdf
http://www.powersystemconsultant.com/htm/PARTIAL%20DIS
CHARGE.pdf
http://www.carroll-
meynell.com/pdf/Cast%20Resin%20Testing.pdf
http://www.carroll-
meynell.com/pdf/Cast%20Resin%20Testing.pdf