304 Med
304 Med
304 Med
Installation
Operation
Maintenance
E50001-U229-A304-X-US00
IMPORTANT
The information contained herein is general in nature and not intended for specific
application purposes. It does not relieve the user of responsibility to use sound practices in
application, installation, operation, and maintenance of the equipment purchased. Siemens
reserves the right to make changes in the specifications shown herein or to make
improvements at any time without notice or obligations. Should a conflict arise between the
general information contained in this publication and the contents of drawings or
supplementary material or both, the latter shall take precedence.
QUALIFIED PERSON
For the purpose of this manual and product labels, a qualified person is one who is familiar
with the installation, construction, operation, or maintenance of the equipment and the
hazards involved. In addition, this person has the following qualifications:
(a) is trained and authorized to energize, de-energize, clear, ground, and tag circuits
and equipment in accordance with established safety procedures.
(b) is trained in the proper care and use of protective equipment such as rubber
gloves, hard hat, safety glasses or face shields, flash clothing, etc., in accordance
with established safety practices.
(c) is trained in rendering first aid.
GENERAL
These instructions do not purport to cover all details or variations in equipment, nor to
provide for every possible contingency to be met in connection with installation,
operation, or maintenance. Should further information be desired or should particular
problems arise which are not covered sufficiently for the purchaser’s purposes, the matter
should be referred to the local Siemens sales office.
The contents of this instruction manual shall not become part of or modify any prior or
existing agreement, commitment or relationship. The sales contract contains the entire
obligation of Siemens Power Transmission & Distribution, Inc. The warranty contained in the
contract between the parties is the sole warranty of Siemens Power Transmission &
Distribution, Inc. Any statements contained herein do not create new warranties or modify
the existing warranty.
Contents
2
General Description
General
Siemens Type 96H3 and 97H3 vacuum contactors are construction. The Type 96H3 or 97H3 vacuum contactors each
provided for use in Series 81000™ medium-voltage consists of: (1) a low-voltage section which contains the main coil
controllers. These contactors provide the advantage drive and auxiliary contacts; (2) a medium-voltage section which
of long mechanical and electrical life with low houses the vacuum interrupter, and (3) a support structure which
maintenance. They are suitable for loads of all types, provides mounting for the power fuses, control transformer and
including three-phase motors, transformers, primary fuses, and drawout attachments. Since interruption is
capacitors and resistive loads. The overall dimensions accomplished completely within the vacuum interrupters, items
of the vacuum contactor are 18 inches (457mm) such as arc chutes, blowout coils and pole plates are not required
wide by 27.5 inches (699mm) high by 23.87 inches with vacuum contactors. Voltage surge suppressors are sometimes
(606mm) deep. The vacuum contactor with single or furnished at the controller load terminals to limit transient over-
double barrel power fuses can be installed in Series voltages caused by multiple reignitions which may occur due to
81000 Class E2 controllers of either one high (5kV or the use of vacuum interrupters. For application guidelines, refer to
7kV), two high (5kV or 7kV) or three high (5kV) the instruction manual for Series 81000 Controllers -
E50001-U229-A303-X-US00.
Table 1. 96H3 or 97H3 Contactor Ratings
Interrupting Capacity
Contactor Maximum Voltage Enclosed Continuous Unfused Class E1 Fused Class E2 Impulse Level
Type Rating Ampere Rating Controller Controller (BIL) (kV)
(kA) Symmetrical (MVA)
200 @ 2.3kV
96H35
5.0kV 360 5kA 350 @ 4.0kV 60
97H35
400 @ 4.6kV
96H37
7.2kV 360 4.2kA 570 @ 6.6kV 60
97H37
96H37
– – – – – – 4000 5000 4000 24R – – – 1500 200E
97H37
Table 3. Operating Data (Magnetically Held) Table 4. Operating Data (Latched Type)
Rated Voltage 7200V Permissible Switching 60/Hour
Rated Current 400A (open) — 360A (enclosed) Frequency
Permissible Switching Frequency 1200/Hour Mechanical Life 100,000 Operations
Mechanical Life 1,000,000 operations Control Voltage Options 24VDC, 32VDC, 48VDC, 125 VDC,
Available 250VDC, 115VAC, 240VAC
Electrical Life 250,000 operations
Closing Time 150 ms Tripping Voltage 85% Rating DC
Minimum Closing Command Duration 300 ms Tripping Power 500 W
Opening Time 325 ± 75 ms (standard)
(Fast dropout option ≤ 50 ms)
Arcing Time 10-20 ms
Pick-Up Voltage AC or DC, Nominal 85% Rated (Hot) - 70% Rated (Cold)
Drop-Out Voltage AC or DC, Nominal 74 ± 2V
Rated Control Voltage 120-240 V 50/60 Hz
125-250 VDC
Coil Circuit Inrush 600W
Coil Circuit Holding 90W
Auxiliary Contact Arrangement 2 NO - 2 NC
(2 NO + 2 NC for purchaser’s use)
Auxiliary Contact Rating 10A, 600V (NEMA Class A600)
3
General Description
Vacuum
Interrupter Flexible
Conductor
Closing Coil
Rotating Shaft
Aux. Contacts
Electronic Economizer
Mounting Base
Contactor Type
93H3 or 96H3 94H3 or 97H3
Cell modification kit 25-213-200-501
Cell modification kit 25-154-555-805
required. Mount per 25-154-488-424.
required. Mount per 25-213-213-405.
Kit includes new interlock spring and
90H3 Kit includes replacement interlock parts.
replacement mechanical latch. Modified
Modified cell will no longer allow use of
cell will allow use of either 90H3, 93H3, or
90H3 contactor.
96H3 contactor.
4
General Description
5
General Description
9XH3 X 3 X XX X X X X X
6
General Description
Nomenclature
The contactor configuration can be identified through
the nomenclature description shown in Table 7.
Upon receipt of this equipment, an immediate
inspection should be made for any damage which may
have occurred during shipment. The inspection should
include examination of the packaging material and the
contactor. Be sure to look for concealed damage and
do not discard the packaging material. If damage is
found, note damage on “Bill of Lading” prior to
accepting receipt of the shipment, if possible.
7
Installation
Electrical Connections
Inspect all insulated wiring to see that no damage has
Hazardous voltages. occurred. Test the high-voltage wiring for possible
Will cause death, serious injury, or grounds or short circuits.
property damage. An AC dielectric test at 2.25 times the nominal system
Disconnect, ground, and lockout incoming power voltage plus 2000 volts, applied for one minute
and control voltage sources before beginning between phases and from all phases to ground is the
work on this or any other electrical equipment. preferred method. Be sure to disconnect any devices
Installation should be performed only by
(control power transformer, etc.) from the circuit which
qualified personnel. could be damaged by the test voltage. If a hi-pot tester
is not available, then a Megger* test at 1000 volts is a
Introduction suitable second choice.
Before performing any installation activities:
• Test all power terminals to verify that incoming
power has been disconnected. Use only approved Hazardous voltages.
high-voltage test equipment to check voltage on
Can cause death or serious injury.
power terminals. Do not attempt to measure high-
voltage (over 600 volts) with a volt-ohm meter. Dielectric or Megger testing should only
be conducted by qualified personnel. Refer
• Check all control and secondary circuit terminals with a
to instructions provided with the testing
voltmeter to make certain that all sources of incoming equipment for safety instructions.
control and secondary voltage have been disconnected.
• Connect safety grounds to power terminals after the
system has been de-energized, and prior to working Note: Do not use DC high potential testers
on the equipment. incorporating half-wave rectification.
These devices produce high peak voltages.
• Perform all disconnecting, grounding, and lockout
operations in accordance with established These high voltages will produce X-ray radiation.
safety procedures. These devices also show erroneous readings of
leakage current when testing vacuum interrupters.
• Follow the procedure outlined in the Pre-
Energization Check section of this manual before
Make sure that all current-carrying parts outside the
power is restored.
contactor have adequate current-carrying capacity and
Site Preparation and Mounting are correctly insulated in accordance with the
Installation shall be in accordance with the National requirements of the National Electrical Code (NEC). All
Electrical Code (NFPA 70) and NEMA Standards. The electrical connections should be made carefully per the
contactor enclosure should be installed in a clean, dry, wiring diagram furnished with the equipment. Tighten
heated location with good ventilation. It should be all lugs to recommended torque values (refer to Table
readily accessible for cleaning and inspection and should 10). If crimp type terminals have been furnished, use
be carefully set up and leveled on its supporting only the crimping tools recommended by the
foundation and secured in place. All adjustments have manufacturer of the terminal.
been made at the factory before shipping and generally Latched Contactors
no change is required. See that all contact surfaces are
An extension is required to extend 3.62” (91.9mm)
clean and smooth, and that current-carrying parts are
from the auxiliary trip lever for a latched contactor used
not damaged.
in bottom compartments. All latched contactors shipped
* Megger is a registered trademark of Megger Group, Ltd. in bottom compartment have an extension attached to
the auxiliary trip lever perpendicular to the door. For
contactors shipped in middle or top compartments, or
shipped separately, the extensions are attached to the
auxiliary trip lever and in parallel to the door. When
contactors are shipped separately and are to be used in
a bottom compartment, the extension must be
assembled to the auxiliary trip lever per Figure 3.
8
Installation
Pre-Energization Check
5º - 6º 5º - 6º
Trip Lever Actuator
on Inside Hazardous voltages.
of Door
Will cause death, serious personal injury or
property damage.
9
Installation
RUN TEST C
CXFU Push to Test
A X 12
C L2
B X RL
RUN TEST
L1
C X
X= Contacts Closed
C B
RSI TFU 8 9
A
6 115V. or 230V.
Test Power
Legend
CPT . . . .Control Power Transformer START
CXFU . .Fuse for CPT Sec. STOP 1 2 3 OL
LSI . . . . .Line Switch Interlock MR
M . . . . . .Main Contactor MR
MR . . . . .Master Relay 10 A M B
11
M CC . . .Main Contactor Magnet Coil
14 13
RL . . . . .High Voltage Light
MR 15 F D 13
A1 A2
DC Drive Unit
1 1 2 2
M
CC
M
CC
Additional Auxiliary Contacts
M M M M
84 83 43 44 21 22 32 31
G H I J K L M N
12 13 14 15 16 17 18 19
Figure 4. Series 81000 Controller with Type 96H3 or 97H3 Magnetically-Held Contactor
10
Installation
X= Contacts Closed
C B
RSI TFU
8 9
A
6 115V. or 230V.
Test Power
LM A1 A2
TX
Legend 43 44
CPT . . . .Control Power Transformer TRIP (+)
CXFU . .Fuse for CPT Sec. 15 F AC AC
Rec.
LSI . . . . .Line Switch Interlock -1
LM . . . . .Main Contactor (Latched Type)
(-)
REC . . . .Rectifier
RL . . . . .High Voltage Light
RSI . . . . .Racking Switch Interlock TX TX
T . . . . . .Trip Coil T
TFU . . . .Fuse for Test Power 44 43 13 14
TX . . . . .Trip Aux. Relay
LM CC . .Main Contactor Magnet Coil
CLOSE
24 O D 13
A1
DC Drive Unit A2
1 1 2 2
LM
CC Mech. Trip
LM
CC
Additional Auxiliary Contacts
LM LM LM LM
13 14 84 83 21 22 32 31
B A G H K L M N
5 4 12 13 16 17 18 19
Figure 5. Series 81000 Controller with Type 96H3 or 97H3 Contactor with Mechanical Latch, and Electrical Trip from AC Source
11
Installation
X= Contacts Closed
C B RSI TFU 8 9 J3
A
115V. or 230V.
6
Test Power
(+)
AC AC
Rec.
15 -1
Legend Rc 19
(-)
CAP . . . .Capacitor
CPT . . . .Control Power Transformer F 43 LM 44 A1 A2
TX J
CXFU . .Fuse for CPT Sec.
LSI . . . . .Line Switch Interlock TX LM CAP
13 14 E1
LM . . . . .Main Contactor (Latched Type) T
Rb . . . . .Bleeding Resistor 44
Rc . . . . .Charging Resistor AC
REC . . . .Rectifier Rb
(+) REC -2 (-)
RL . . . . .High Voltage Light TRIP
RSI . . . . .Racking Switch Interlock
T . . . . . .Trip Coil
TFU . . . .Fuse for Test Power CLOSE 16 G H 17
LM CC . .Main Contactor Magnet Coil 84 LM4 83
Maintain
Contact If Used
CLOSE
4 O D 13
A1 A2
DC Drive Unit
1 1 2 2
Additional Auxiliary Contacts LM
CC Mech. Trip
LM LM LM LM LM
13 14 84 83 21 22 32 31 CC
B A G H K L M N
5 4 12 13 16 17 18 19
Figure 6. Series 81000 Controller with Type 96H3 or 97H3 Contactor with Mechanical Latch, and Electrical Trip from AC Capacitor Source
12
Maintenance
• Check all control and secondary circuit terminals The maintenance tasks in Table 8 must be performed regularly.
with a voltmeter to make certain that all sources
of incoming control and secondary voltage have • Blown Fuse Trip Mechanism Checks
been disconnected.
• Vacuum Contactor Inspection
• Connect safety grounds to power terminals after • Main Contacts Inspection
the system has been de-energized, and prior to
working on the equipment. • Closing Coil Check
• Perform all disconnecting, grounding, and • Latch Mechanism Check
lockout operations in accordance with established • Mechanical Interlock Checks
safety procedures. • Fuse Clip Inspection
• Follow the procedure outlined in the Pre- • Check of Terminals and Joints
Energization Check section of this manual before • Periodic Cleaning
power is restored.
• Dielectric Test
General • Maintenance Tasks in Manual for Series 81000
For the safety of maintenance personnel as well as Controllers, E50001-U229-A303-X-US00
13
Maintenance
Machine
Screw
Support
Tray
1 Switch
Contacts Close
Plunger
2
4
3
Stop
Insert
3/16” (4.8mm)
Shim
Direction
Electromagnet
Closing Coil • Year or
Every
20,000
Armature and
Core • • Operations
Latch
Mechanism
Trip Coil
•
(Note 2) Roller
• • • •
Mechanical
Interlock Bolt
Interlock
Check
And
Interlock Arm
• • •
(97H3 Only)
Others
Bolts and Nuts
•
Insulated Wire •
Notes: 1. The life expectancy of the electrical parts (vacuum interrupter, auxiliary switch) is 250,000 operations.
2. The life expectancy of the latch mechanism for latched contactors is 100,000 operations.
3. When the contactor is not protected by current limiting fuses, the vacuum interrupters should be replaced if they have
interrupted fault currents at or near their maximum (unfused) interrupting rating.
15
Maintenance
3. Check the vacuum interrupter for integrity of the Fuse Clip Inspection
vacuum. With the contactor open, apply 18kV AC Closely examine fuse clips. If there is any sign of
between the upper and lower terminals for one overheating or looseness, check the spring pressure or
minute. If the interrupter withstands this test, it is tightness of clamps.
acceptable. If voltage breakdown occurs, the
interrupter must be replaced.
Replace the fuse clips if the spring pressure compares
unfavorably with that of other similar fuse clips. Make
sure that fuses are completely inserted.
Hazardous voltage.
Floor
(Bottom of Wheel)
Standard Torque 2/3 Standard Torque 1/2 Standard Torque 1/2 Standard Torque
Thread Size Metal-to-Metal Metal-to-Insert Compound-to-Insert Compound-to-Compound
(in-lbs/Nm) (in-lbs/Nm) (in-lbs/Nm) (in-lbs/Nm)
Vacuum Interrupter Replacement Procedure 2. Loosen and remove the M8 nut (4.4.2), holding the
When a vacuum interrupter has reached a specified movable contact (4.1.1) of the vacuum interrupter
life (250,000 operations) or when it is damaged, it is with an open end 17mm wrench to avoid damage
to the interrupter bellows.
recommended that it be replaced. If the contactor is
not protected by current limiting fuses, the vacuum 3. Remove two M5 hex head bolts (4.2.1) and remove
interrupters should be replaced if they have latch (4.2.3).
interrupted fault currents at or near their maximum 4. Loosen and remove M8 hex head bolt (6.2) of
(unfused) interrupting rating. upper terminal.
5. Remove vacuum interrupter and attached
The replacement vacuum interrupter kit (serial no. components from the contactor housing.
31670936 and up) consists of a vacuum interrupter 6. Loosen locknut (4.3.2), holding the movable
(4.1), a flexible shunt connector (5), contact washers contact (4.1.1) of the vacuum interrupter with an
(4.3.1, 5.3 and 6.1), and an adjusting tool. open end 17mm wrench to avoid damage to the
interrupter bellows.
The replacement vacuum interrupter kit (up to serial
7. Unscrew the insulator (4.4) from the movable
no. 31670935) consists of a vacuum interrupter (4.1), contact (4.1.1).
flexible shunt connector and insulator assembly as well
as washer (4.4.4), and spring (4.4.3), spacer tube All of the parts removed should be retained, as they
(4.4.5), washer (4.4.6), lockwasher (4.4.7), nut will be reused in the new assembly, except for the
(4.4.2), contact washers (6.1 and 5.3), and an following items: vacuum interrupter (4.1), flexible
adjusting tool. shunt connector (5), contact washers (6.1, 5.3 and
4.3.1), and lockwasher (4.4.7).
The replacement of vacuum interrupters should be Removing the Interrupter (Up to serial no 31670935)
performed as follows:
1. (Refer to Figure 11.) Loosen the M8 hex head bolt
(5.1) which secures the flexible shunt connection
to the contactor housing, and remove.
Hazardous voltages.
2. Loosen and remove the M8 nut (4.4.1), holding the
Will cause death or serious injury. movable contact (4.1.1) of the vacuum interrupter
Before replacing vacuum interrupters, with an open end 17mm wrench to avoid damage
remove the contactor from the controller to the interrupter bellows.
compartment to ensure that all high-voltage
sources are disconnected. 3. Loosen and remove the M8 nut (4.4.2), while
continuing to hold the movable contact (4.1.1) of
Low-voltage test power is required during the the vacuum interrupter to prevent bellows damage.
reinstallation of new vacuum interrupters, so
exercise caution. 4. Remove two M5 hex head bolts (4.2.1) and remove
latch (4.2.3).
Removing the Interrupter (Serial no. 31670936 and up) 5. Loosen and remove M8 hex head bolt (6.2) of
1. (Refer to Figure 11.) Loosen the M8 hex head bolt upper terminal.
(5.1) which secures the flexible shunt connection 6. Remove vacuum interrupter and attached
to the contactor housing, and remove. components from the contactor housing.
Retain following parts for reuse: bolts (6.2, 5.1 and 4.2.1),
washers (4.2.2 and 5.2), nut (5.4) and latch (4.2.3).
17
Maintenance
6.2
6.1
6
33 4
4.3 4.4.2
4.4.1
T D
4.2.4 3
4
4.2.1 5.1 Detail “A” T D
4.2.2 5.2
1 . . . . . .Contactor Housing
4.2.3 5
3 . . . . . .Drive Lever
5.3 4.1 . . . . .Vacuum Interrupter
4.1.1 4.1.1 . . .Movable Contact
5.4 4.2.1 . . .Hex Head Bolt (M5)
4.3.1 4.2.2 . . .Washer
4.2.3 . . .Latch
4.4
4.2.4 . . .Bearing
4.3.2 4.4.4
4.3.1 . . .Contact Washer
4.4.5
4.3.2 . . .Nut
4.4.3
4.4 . . . . .Insulator
4.4.6
4.4.1 . . .Locknut
4.4.7 4.4.2 . . .Nut
3 4.4.3 . . .Compression Spring
4.4.2 4.4.4 . . .Washer
See Detail “A” For 4.4.5 . . .Spacer Tube
Serial No. Up To 4.4.6 . . .Washer
31670935. 4.4.7 . . .Lock Washer
5 . . . . . .Flexible Shunt Connector
5.1 . . . . .Hex Head Bolt (M5)
5.2 . . . . .Washer
5.3 . . . . .Contact Washer
5.4 . . . . .Nut
6 . . . . . .Upper Terminal
6.1 . . . . .Contact Washer
6.2 . . . . .Hex Head Bolt (M5)
Installing the New Interrupter (Serial No. 31670936 & up) 5. Insert assembly into contactor housing (1), while passing lower
1. (Refer to Figures 11 and 12) Screw locknut (4.3.2) articulated bolt through drive lever (3) and flexible shunt
and contact washer (4.3.1) onto insulator (4.4), slip connector (5) through the opening in the rear of the housing (1).
flexible shunt connector (5) onto articulated bolt on 6. Install latch (4.2.3) with hex head bolt M5 (4.2.1) and
the upper end of the insulator (4.4), slip bearing washer (4.2.2).
(4.2.4) onto movable contact (4.1.1) of vacuum 7. Secure vacuum interrupter (4.1) to the upper terminal (6), using
interrupter (4.1). hex head bolt M8 (6.2) and contact washer (6.1).
2. Screw vacuum interrupter (4.1) onto articulated bolt 8. Secure flexible shunt connector (5) to housing using hex head
on the upper end of the insulator (4.4). bolt M8 (5.1), washer (5.2), nut (5.4) & contact washer (5.3).
3. Preset assembly to size (16 to 16.5mm) as shown in Torque to 10-14 Nm (88-124 in-lbs.).
Figure 12, and secure it in correct adjustment using Installing the New Interrupter (Up to Serial No. 31670935)
nut (4.3.2). Do not fully tighten nut (4.3.2) at this
time. Nut (4.3.2) will be fully tightened in final Follow the procedure in the preceding section, steps 4-8. Steps 1-3
position during the “Drive Connection and are not required as the replacement kit includes a preset assembly
Adjustment” procedure. comprised of the vacuum interrupter (4.1), flexible shunt connector
(5), and insulator (4.4).
4. Slip washer (4.4.4), spacer tube (4.4.5) and
compression spring (4.4.3) onto lower articulated
bolt of insulator (4.4)
18
Maintenance
0.63-0.65”
(16.0-16.5mm)
Hazardous voltage.
4 4.1
1.4mm factory. Verify this dimension if contactor does not
(0.055 in.) properly latch. Adjust actuator or auxiliary trip lever
3
7.4 mounting location as needed. See Figure 3 to
identify actuator, auxiliary trip lever, and other
7 6.3
latch components. If this condition is satisfied,
5 next, mechanically (manually) operate the actuator
1.1 + 1.2 and verify that the contactor opens. Repeat this
1.3 sequence of tests approximately 20 times to verify
7.1 correct operation.
16. (Electrical trials) Reapply control power to the main
6.2
coil to close the contactor. The mechanical latch
7.3 should correctly latch and hold the contactor in the
2
closed (ON) position after control power is removed
6 from the main coil. If this condition is satisfied, next,
6.1
apply the correct control power voltage for the
mechanical latch trip coil (often different from the
main coil control power voltage). Control power
7.2 should be applied to the mechanical latch trip coil
for at least 0.1 second, but not for longer than one
9 second, or damage to the mechanical latch trip coil
will result. Verify that the contactor opens when the
9.1 mechanical latch is operated electrically. Repeat this
sequence of tests approximately 20 times to verify
7.1 correct operation.
1.4
6.3
6.1
7.3
20
Maintenance
Main (Magnet) Coil Replacement 8. Note: The washer (8.8) mounted between the
The magnet coil configuration employs a pair of magnet magnet core (8.6) and the magnet angle (8.4) is
coils for each contactor. If it should become necessary to needed for installing the new magnet coil. There is
one washer (8.8) per magnet coil.
replace either of the magnet coils, replace both coils as
a set. To replace the magnet coils, remove the drawout 9. The magnet core (8.6) is also to be reused.
contactor carriage from the controller enclosure, and 10. Washers (8.3.1), (8.2.1), and (8.5.1) should be
disconnect all sources of power. For non-drawout type discarded and replaced with the new washers in
contactors, disconnect and ground all sources of power, the replacement magnet coil kit.
and remove the contactor from the enclosure. The 11. (Replacing the magnet coils) Install the new
replacement procedure is as follows (refer to Figure 14 magnet coils (8.1), reversing the action in the
and Figure 15) previous step. Install each magnet coil over the
1. (Removal of the magnet coils) Disconnect the leads magnet core (8.6) on the magnet angle (8.4),
of the magnet coils (8.1). using bolt (8.5), new washer (8.5.1), and washer
2. Remove the mounting bolts (8.2) which secure the (8.8). Torque to 157-192 in-lbs (18- 22 Nm).
magnet system (8) to the contactor mounting base 12. Align the magnet coils (8.1) into correct position so
(2). (Note: On early model drawout contactors, that the magnet core (8.6) is free to move, and
holes to allow access to the mounting bolts (8.2) secure the magnet coils (8.1) in position using
are not provided. If access holes are not present, plate (7). Torque to 39- 48 in-lbs (4.5-5.5 Nm).
contact Siemens Field Service for assistance in 13. Install bolts (8.3) with new washers (8.3.1). Torque
replacing main magnet coils). to 157-192 in-lbs (18-22 Nm).
3. Remove the magnet system (8) from the contactor 14. Slide the magnet system (8) into the contactor
by sliding the assembly out the rear of the contactor. from the rear.
4. Do not loosen or adjust items 8.10, 8.11, 8.12, 15. Secure the magnet system (8) to the contactor
or 8.13. mounting base (2) using bolts (8.2) and new
5. Remove the bolts (8.3) at the rear side of the washers (8.2.1). Tighten loosely, but allow some
magnet angle (8.4). movement between the magnet system (8) and the
6. Loosen, but do not remove, plate (8.7). contactor mounting base (2).
7. Remove the mounting bolt (8.5) at the rear side of 16. Connect the leads from the new magnet coils (8.1)
the magnet angle (8.4). to the correct terminals on the contactor.
8.1 8.7
8.1 8.8 8.13
8.10
8.3
8.6 8.3.1
8.5
8.5.1
8.4
8.11 8.4
8.12
21
Maintenance
17. To continue the installation, the contactor must be Be sure that the wires are attached to the correct
closed. This requires application of control power terminals of the correct auxiliary switch block.
to the main coil. Use appropriate precautions to 6. When all wires are properly secured, slide the
avoid injury or shock when control power is applied auxiliary switch blocks with the wires attached into
to the contactor. the proper location on the contactor drawout
18. (Alignment) Apply control power and switch the carriage, and align the auxiliary switch blocks to
contactor to the closed (ON) position. The the mounting holes in the contactor housing (1).
contactor should close correctly, and the closing 7. Install lower auxiliary switch block (10.2) to the
process will cause the magnet system (8) to lower position on the contactor housing (1) using
properly align with the magnet plate (8.9). M3 x 35 screws. To install one of the screws, it will
19. While the contactor is closed, torque the mounting be necessary to rotate the actuator arm (7).
bolts (8.2) to 157-192 in-lbs (18-22 Nm). While 8. Install upper auxiliary switch block (10.1) to the
tightening the mounting bolts, assure that proper upper position on the contactor housing (1) using
alignment between the magnet system (8) and the M3 x 35 screws.
magnet plate (8.9) is maintained.
9. Reposition the actuator arm (7) and secure it to the
20. (Electrical trials) Apply control power and switch the shaft with screw (3), and torque to 5.5-6.5 Nm (96-
contactor to the closed (ON) position. The contactor 114 in-lbs).
should close correctly and without unusual
hesitation. Verify that the contactor opens when the 10. To continue the installation, the contactor must be
control power is removed. Repeat this test closed. This requires application of control power to
approximately 20 times to verify correct operation the main coil. Use appropriate precautions to avoid
injury or shock when control power is applied to
the contactor.
Hazardous voltage.
Hazardous voltage.
23
Maintenance
SIEMENS
1 . . . . . . . . .Contactor Housing
11.1 11.2 11 11.3 8.1 8..1 . . . . . . .Magnet Coils
11 . . . . . . . .Electronic Economizer
11.1 . . . . . . .Cover
11.2, 11.3 . .Screws
24
Maintenance After a Fault
Inspection
The following areas should be inspected after a fault
Hazardous voltages. has occurred.
Will cause death, serious injury, or
property damage. Enclosures
Disconnect, lockout, and ground incoming power External evidence of enclosure deformation usually is
and control voltage sources before beginning indicative of damage within. Extensive damage will
work on this or any other electrical equipment.
require replacement of the enclosure parts and the
Maintenance should be performed only by enclosed equipment. Insure that door mounted
qualified personnel.
equipment and safety interlocks function properly.
Verify that hinge and latch integrity is maintained.
Introduction
Terminals and Internal Conductors
Before performing any maintenance:
Replace all damaged parts which show evidence of
• Test all power terminals to verify that incoming
discoloration, melting or arcing damage. Special
power has been disconnected. Use only approved
attention should be paid to the stab (disconnect) fingers.
high-voltage test equipment to check voltage on
power terminals. Do not attempt to measure high- Overload Relays
voltage (over 600 volts) with a volt-ohm meter. The complete overload relay must be replaced if
• Check all control and secondary circuit terminals burnout of the heater element has occurred. Any
with a voltmeter to make certain that all sources indication of an arc striking or burning the overload
of incoming control and secondary voltage have relay also requires replacement of the relay. If there is
been disconnected. no visual indication of damage that would require
• Connect safety grounds to power terminals after replacement, contact operation must be verified by
the system has been de-energized, and prior to electrically or mechanically tripping and resetting the
working on the equipment. overload relay.
• Perform all disconnecting, grounding, and lock- Fuse Holders
out operations in accordance with established Replace fuse holders if the insulation mounts, barriers,
safety procedures. or fuse clips show signs of damage, deterioration,
• Follow the procedure outlined in the Pre- heating, distortion or looseness.
Energization Check section of this manual before
Fuses
power is restored.
Always replace all three fuses in a three phase circuit
General even though only one or two are open circuited since
The excessive currents occurring during a fault may internal damage suffered by fuses not replaced could
result in structure, component and/or conductor result in nuisance shut-down later. Perform the “Pre-
damage due to mechanical distortion, thermal Energization Check” procedures detailed in the
damage, metal deposits, or smoke. After a fault, Installation section of this manual before restoring the
repair the cause of the fault, inspect all equipment equipment to service.
per NEMA Standards Publication No. ICS2 Annex A
and make any necessary repairs or replacements
prior to placing the equipment into service again. Be
sure that all replacements (if any) are of the proper
rating and are suitable for the application. If in
doubt, consult your Siemens representative.
25
Troubleshooting
26
Troubleshooting
Table 11.Troubleshooting
Phenomenon Possible Causes Corrective Action
If inspection and/or corrective
Will not Does Not Open Overheated Overheated Latch Is Not Survey main circuit without voltage
action is difficult, inform
close (Latch Type) Trip Coil Main Coil Engaged Remove all power before inspecting
Siemens immediately
Decrease the voltage drop to
• • • Control power supply voltage
is too low
increase the voltage to 90% or
more of the rating.
• • • Poor connection and/or loose screw Ensure that the connection is tight
• • Mechanism jammed
Lubricate corresponding portion or
remove cause of jam
27
28
25 (Bø Only) Transformer Leads
18 17 8 23
Parts
30
28 Control Wire
Harness
29
CPT
13 13
26
21 21
16 16
6 6
37, 36 11
12 12
11 11
25 25
33
31 Vacuum 22 Vacuum 22
38
Contactor Contactor
26 32 41
41 28, 29, 30 28, 29, 30
13
Front View R.H. Side View (96H3) R.H. Side View (97H3)
Parts
Table 12. Type 96H35 or 97H35 (5kV) Contactor (Refer to Figure 18)
Contactor Quantities
Item Description Part Number
Drawout Stationary
1 LH Side Rail 25-154-488-560 1 –
2 RH. Side Rail 25-154-488-559 1 –
3 Contactor Mtg. Tray 25-154-521-554 1 –
4 LH Side Plate 25-154-488-571 1 –
5A RH Side Plate 25-154-488-572 1 (96H3 Only) –
5B RH Side Plate 25-154-488-598 1 (97H3 Only) –
6 Insulator Molding 25-407-783-005 2 –
7A CPT Mounting Plate 25-154-488-566 1 (96H3 Only) –
7B CPT Mounting Plate 25-154-488-595 1 (97H3 Only) –
8 CPT Fuse Block 25-154-247-061 1 –
9 Wheel 18-658-134-345 4 –
10 Wheel Shaft 25-154-301-034 3 –
* Kit 25-154-654-001 for 3TL8 contactor serial number 31670936 and higher. For 3TL8 contactor serial number up to
31670935, use kit 25-154-654-005.
29
30
25 (Bø Only) Transformer Leads
18 17 8 23
Parts
30
28 Control Wire
Harness
29
CPT
13 13
43 (97H3) 1 26
2 35 34
L.H. Side View
7A (96H3)
Rear View 7B (97H3)
Fuse Holder Required
with 2-barrel Fuse Only 37 Fuse Holder Required 37
5A (96H3) 36 with 2-barrel Fuse Only 36
4 16 5B (97H3) 31, 32, 33 24 6 12 25 31, 32, 33 24 6 12 25
21 21
Figure 19. 96H37 or 97H37 Vacuum Contactor (7.2kV with 18R-24R Fuses)
16 16
6 6
37, 36 11
12 12
11 11
25 25
33
31 Vacuum 22 Vacuum 22
38
Contactor Contactor
26 32 41
41 28, 29, 30 28, 29, 30
13
Front View R.H. Side View (96H3) R.H. Side View (97H3)
Parts
Table 13. Type 96H37 or 97H37 (7.2kV) Contactor 18R - 24R Fuses (Refer to Figure 19)
Contactor Quantities
Item Description Part Number
Drawout Stationary
1 LH Side Rail 25-154-488-560 1 –
2 RH. Side Rail 25-154-488-559 1 –
3 Contactor Mtg. Tray 25-154-521-554 1 –
4 LH Side Plate 25-154-488-571 1 –
5A RH Side Plate 25-154-488-572 1 (96H3 Only) –
5B RH Side Plate 25-154-488-598 1 (97H3 Only) –
6 Insulator Molding 25-407-783-005 2 –
7A CPT Mounting Plate 25-154-488-566 1 (96H3 Only) –
7B CPT Mounting Plate 25-154-488-595 1 (97H3 Only) –
8 CPT Fuse Block 25-154-247-061 1 –
9 Wheel 18-658-134-345 4 –
10 Wheel Shaft 25-154-301-034 3 –
* Kit 25-154-654-001 for 3TL8 contactor serial number 31670936 and higher. For 3TL8 contactor serial number up to
31670935, use kit 25-154-654-005.
31
32
25 (Bø Only) 18 17 8 23 Transformer Leads
Parts
36, 37
30 28
Control Wire
Harness
29
CPT
13
13
2 35 43 (97H3) 34 1 26
7A (96H3) L.H. Side View
Rear View 7B (97H3)
5A (93H3)
4 16 5B (94H3) 31, 32, 33 36 6 12 25 31, 32, 33 6 12 25
21 21
Figure 20. 96H37 or 97H37 Vacuum Contactor (7.2kV with 2R-12R Fuses)
16 16
11 24 6 24 6
11 12 11 12
25 25
33 22 22
31 Vacuum Vacuum
38 Contactor Contactor
26 32
41 41
28, 29, 30
13 28, 29, 30
Front View R.H. Side View (96H3) R.H. Side View (97H3)
Parts
Table 14.Type 96H37 or 97H37 (7.2kV) Contactor 2R - 12R Fuses (Refer to Figure 20)
Contactor Quantities
Item Description Part Number
Drawout Stationary
1 LH Side Rail 25-154-488-560 1 –
2 RH. Side Rail 25-154-488-559 1 –
3 Contactor Mtg. Tray 25-154-521-554 1 –
4 LH Side Plate 25-154-488-587 1 –
5A RH Side Plate 25-154-488-557 1 (96H3 Only) –
5B RH Side Plate 25-154-488-598 1 (97H3 Only) –
6 Insulator Molding 25-407-783-005 2 –
7A CPT Mounting Plate 25-154-488-566 1 (96H3 Only) –
7B CPT Mounting Plate 25-154-488-595 1 (97H3 Only) –
8 CPT Fuse Block 25-154-247-061 1 –
9 Wheel 18-658-134-345 4 –
10 Wheel Shaft 25-154-301-034 3 –
* Kit 25-154-654-001 for 3TL8 contactor serial number 31670936 and higher. For 3TL8 contactor serial number up to
31670935, use kit 25-154-654-005.
33
All statements, technical information and recommendations
contained herein are based on information and tests we
believe to be reliable. The accuracy or completeness hereof is
not guaranteed. Since conditions of use are outside our
control, the user should determine the suitability of the
product for its intended use and assumes all risk and liability
whatsoever in connection herewith.
www.usa.siemens.com/energy