Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.

1. Material List
Model Qty Description
RXQ32TANYM 2 Cooling only VRV IV STANDARD
RXQ38TANYM 1 Cooling only VRV IV STANDARD
RXQ40TANYM 1 Cooling only VRV IV STANDARD
RXQ52TANYM 4 Cooling only VRV IV STANDARD
FXDQ40NBVE 113 VRV D - Slim Ceiling Mounted Duct
FXMQ100PVE 7 VRV M - Ceiling Mounted Duct
FXMQ125PVE 13 VRV M - Ceiling Mounted Duct
FXMQ140PVE 3 VRV M - Ceiling Mounted Duct
FXMQ200MAVE 1 VRV M - Ceiling Mounted Duct
FXMQ63PVE 1 VRV M - Ceiling Mounted Duct
FXMQ80PVE 16 VRV M - Ceiling Mounted Duct
KHRP26A22T 65 Refnet branch piping kit
KHRP26A33T 19 Refnet branch piping kit
KHRP26A72T 48 Refnet branch piping kit
KHRP26A73T + KHRP26M73TP 14 Refnet branch piping kit
BRC1E62 154 Wired Remote Controller (Navigation Remote
Controller)
BHFP22P100 2 Outdoor unit multi connection piping kit
BHFP22P151 6 Outdoor unit multi connection piping kit
R410A 201.3kg Extra refrigerant charge
Piping 6.4 407.1m
Piping 9.5 342.6m
Piping 12.7 436.8m
Piping 15.9 269.5m
Piping 19.1 272.1m
Piping 22.2 293.2m
Piping 28.6 67.9m
Piping 34.9 39.9m
Piping 38.1 76.5m
Piping 41.3 337.6m

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 1
2.
2.1.1. Out 1 - RXQ38TANYM

Model Qty Description


RXQ38TANYM 1 Cooling only VRV IV STANDARD
FXDQ40NBVE 1 VRV D - Slim Ceiling Mounted Duct
FXMQ100PVE 5 VRV M - Ceiling Mounted Duct
FXMQ125PVE 3 VRV M - Ceiling Mounted Duct
KHRP26A22T 1 Refnet branch piping kit
KHRP26A33T 2 Refnet branch piping kit
KHRP26A72T 4 Refnet branch piping kit
KHRP26A73T + KHRP26M73TP 1 Refnet branch piping kit
BRC1E62 9 Wired Remote Controller (Navigation Remote
Controller)
BHFP22P151 1 Outdoor unit multi connection piping kit
R410A 38.6kg Extra refrigerant charge
Piping 6.4 5.1m
Piping 9.5 50.8m
Piping 12.7 14.7m
Piping 15.9 39.7m
Piping 19.1 5.2m
Piping 22.2 97.8m
Piping 28.6 16.0m
Piping 41.3 85.5m

Standard factory refrigerant charge (5m actual piping length) = 22.7kg


Extra refrigerant charge = 50.8m(ø9.5) × 0.057 + 5.1m(ø6.4) × 0.022 + 85.5m(ø22.2) × 0.36 + 6.4m(ø15.9) × 0.17
+ 9.6m(ø12.7) × 0.11 + A + B = 38.6kg
A [ CR 96%, actual length 108.9m ] = 2.7kg
B [ 38HP ] = 0.0kg

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 2
2.1.2. Out 2 - RXQ32TANYM

Model Qty Description


RXQ32TANYM 1 Cooling only VRV IV STANDARD
FXMQ125PVE 2 VRV M - Ceiling Mounted Duct
FXMQ140PVE 2 VRV M - Ceiling Mounted Duct
FXMQ200MAVE 1 VRV M - Ceiling Mounted Duct
FXMQ63PVE 1 VRV M - Ceiling Mounted Duct
KHRP26A33T 1 Refnet branch piping kit
KHRP26A72T 3 Refnet branch piping kit
KHRP26A73T + KHRP26M73TP 1 Refnet branch piping kit
BRC1E62 6 Wired Remote Controller (Navigation Remote
Controller)
BHFP22P100 1 Outdoor unit multi connection piping kit
R410A 32.9kg Extra refrigerant charge
Piping 9.5 36.5m
Piping 12.7 1.5m
Piping 15.9 37.8m
Piping 19.1 1.3m
Piping 22.2 80.2m
Piping 28.6 7.8m
Piping 38.1 76.5m

Standard factory refrigerant charge (5m actual piping length) = 20.8kg


Extra refrigerant charge = 36.5m(ø9.5) × 0.057 + 76.5m(ø22.2) × 0.36 + 6.3m(ø15.9) × 0.17 + 1.5m(ø12.7) × 0.11
+ A + B = 32.9kg
A [ CR 99%, actual length 93.4m ] = 2.0kg
B [ 32HP ] = 0.0kg

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 3
2.1.3. Out 3 - RXQ40TANYM

Model Qty Description


RXQ40TANYM 1 Cooling only VRV IV STANDARD
FXMQ125PVE 8 VRV M - Ceiling Mounted Duct
KHRP26A33T 2 Refnet branch piping kit
KHRP26A72T 2 Refnet branch piping kit
KHRP26A73T + KHRP26M73TP 3 Refnet branch piping kit
BRC1E62 8 Wired Remote Controller (Navigation Remote
Controller)
BHFP22P151 1 Outdoor unit multi connection piping kit
R410A 31.9kg Extra refrigerant charge
Piping 9.5 39.4m
Piping 12.7 1.4m
Piping 15.9 32.5m
Piping 19.1 2.4m
Piping 22.2 79.7m
Piping 28.6 3.2m
Piping 34.9 2.4m
Piping 41.3 71.0m

Standard factory refrigerant charge (5m actual piping length) = 23.0kg


Extra refrigerant charge = 39.4m(ø9.5) × 0.057 + 71.0m(ø22.2) × 0.36 + 1.4m(ø12.7) × 0.11 + 2.4m(ø19.1) × 0.26
+ 1.9m(ø15.9) × 0.17 + A + B = 31.9kg
A [ CR 100%, actual length 87.8m ] = 3.0kg
B [ 40HP ] = 0.0kg

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 4
2.1.4. Out 4 - RXQ52TANYM

Model Qty Description


RXQ52TANYM 1 Cooling only VRV IV STANDARD
FXDQ40NBVE 27 VRV D - Slim Ceiling Mounted Duct
FXMQ80PVE 3 VRV M - Ceiling Mounted Duct
KHRP26A22T 15 Refnet branch piping kit
KHRP26A33T 3 Refnet branch piping kit
KHRP26A72T 9 Refnet branch piping kit
KHRP26A73T + KHRP26M73TP 2 Refnet branch piping kit
BRC1E62 30 Wired Remote Controller (Navigation Remote
Controller)
BHFP22P151 1 Outdoor unit multi connection piping kit
R410A 24.6kg Extra refrigerant charge
Piping 6.4 96.6m
Piping 9.5 40.3m
Piping 12.7 99.6m
Piping 15.9 30.0m
Piping 19.1 69.3m
Piping 22.2 7.4m
Piping 28.6 7.6m
Piping 34.9 3.2m
Piping 41.3 58.5m

Standard factory refrigerant charge (5m actual piping length) = 31.4kg


Extra refrigerant charge = 96.6m(ø6.4) × 0.022 + 40.3m(ø9.5) × 0.057 + 61.7m(ø19.1) × 0.26 + 4.6m(ø15.9) × 0.17
+ 3.0m(ø12.7) × 0.11 + A + B = 24.6kg
A [ CR 102%, actual length 79.8m ] = 3.0kg
B [ 52HP ] = 0.0kg

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 5
2.1.5. Out 5 - RXQ52TANYM

Model Qty Description


RXQ52TANYM 1 Cooling only VRV IV STANDARD
FXDQ40NBVE 27 VRV D - Slim Ceiling Mounted Duct
FXMQ80PVE 3 VRV M - Ceiling Mounted Duct
KHRP26A22T 15 Refnet branch piping kit
KHRP26A33T 3 Refnet branch piping kit
KHRP26A72T 9 Refnet branch piping kit
KHRP26A73T + KHRP26M73TP 2 Refnet branch piping kit
BRC1E62 30 Wired Remote Controller (Navigation Remote
Controller)
BHFP22P151 1 Outdoor unit multi connection piping kit
R410A 22.0kg Extra refrigerant charge
Piping 6.4 96.6m
Piping 9.5 40.3m
Piping 12.7 99.6m
Piping 15.9 30.7m
Piping 19.1 58.9m
Piping 22.2 7.4m
Piping 28.6 8.3m
Piping 34.9 3.2m
Piping 41.3 48.1m

Standard factory refrigerant charge (5m actual piping length) = 31.4kg


Extra refrigerant charge = 96.6m(ø6.4) × 0.022 + 40.3m(ø9.5) × 0.057 + 51.3m(ø19.1) × 0.26 + 5.3m(ø15.9) × 0.17
+ 3.0m(ø12.7) × 0.11 + A + B = 22.0kg
A [ CR 102%, actual length 70.1m ] = 3.0kg
B [ 52HP ] = 0.0kg

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 6
2.1.6. Out 6 - RXQ52TANYM

Model Qty Description


RXQ52TANYM 1 Cooling only VRV IV STANDARD
FXDQ40NBVE 27 VRV D - Slim Ceiling Mounted Duct
FXMQ80PVE 3 VRV M - Ceiling Mounted Duct
KHRP26A22T 15 Refnet branch piping kit
KHRP26A33T 3 Refnet branch piping kit
KHRP26A72T 9 Refnet branch piping kit
KHRP26A73T + KHRP26M73TP 2 Refnet branch piping kit
BRC1E62 30 Wired Remote Controller (Navigation Remote
Controller)
BHFP22P151 1 Outdoor unit multi connection piping kit
R410A 20.4kg Extra refrigerant charge
Piping 6.4 96.7m
Piping 9.5 40.3m
Piping 12.7 99.7m
Piping 15.9 30.7m
Piping 19.1 52.8m
Piping 22.2 7.4m
Piping 28.6 8.3m
Piping 34.9 3.2m
Piping 41.3 42.0m

Standard factory refrigerant charge (5m actual piping length) = 31.4kg


Extra refrigerant charge = 96.7m(ø6.4) × 0.022 + 40.3m(ø9.5) × 0.057 + 45.2m(ø19.1) × 0.26 + 5.3m(ø15.9) × 0.17
+ 3.0m(ø12.7) × 0.11 + A + B = 20.4kg
A [ CR 102%, actual length 64.0m ] = 3.0kg
B [ 52HP ] = 0.0kg

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 7
2.1.7. Out 7 - RXQ52TANYM

Model Qty Description


RXQ52TANYM 1 Cooling only VRV IV STANDARD
FXDQ40NBVE 27 VRV D - Slim Ceiling Mounted Duct
FXMQ80PVE 3 VRV M - Ceiling Mounted Duct
KHRP26A22T 15 Refnet branch piping kit
KHRP26A33T 3 Refnet branch piping kit
KHRP26A72T 9 Refnet branch piping kit
KHRP26A73T + KHRP26M73TP 2 Refnet branch piping kit
BRC1E62 30 Wired Remote Controller (Navigation Remote
Controller)
BHFP22P151 1 Outdoor unit multi connection piping kit
R410A 17.9kg Extra refrigerant charge
Piping 6.4 96.7m
Piping 9.5 40.3m
Piping 12.7 99.7m
Piping 15.9 30.7m
Piping 19.1 43.3m
Piping 22.2 7.4m
Piping 28.6 8.3m
Piping 34.9 3.2m
Piping 41.3 32.5m

Standard factory refrigerant charge (5m actual piping length) = 31.4kg


Extra refrigerant charge = 96.7m(ø6.4) × 0.022 + 40.3m(ø9.5) × 0.057 + 35.7m(ø19.1) × 0.26 + 5.3m(ø15.9) × 0.17
+ 3.0m(ø12.7) × 0.11 + A + B = 17.9kg
A [ CR 102%, actual length 54.5m ] = 3.0kg
B [ 52HP ] = 0.0kg

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 8
2.1.8. Out 8 - RXQ32TANYM

Model Qty Description


RXQ32TANYM 1 Cooling only VRV IV STANDARD
FXDQ40NBVE 4 VRV D - Slim Ceiling Mounted Duct
FXMQ100PVE 2 VRV M - Ceiling Mounted Duct
FXMQ140PVE 1 VRV M - Ceiling Mounted Duct
FXMQ80PVE 4 VRV M - Ceiling Mounted Duct
KHRP26A22T 4 Refnet branch piping kit
KHRP26A33T 2 Refnet branch piping kit
KHRP26A72T 3 Refnet branch piping kit
KHRP26A73T + KHRP26M73TP 1 Refnet branch piping kit
BRC1E62 11 Wired Remote Controller (Navigation Remote
Controller)
BHFP22P100 1 Outdoor unit multi connection piping kit
R410A 13.0kg Extra refrigerant charge
Piping 6.4 15.4m
Piping 9.5 54.7m
Piping 12.7 20.7m
Piping 15.9 37.4m
Piping 19.1 39.1m
Piping 22.2 6.2m
Piping 28.6 8.4m
Piping 34.9 24.7m

Standard factory refrigerant charge (5m actual piping length) = 20.8kg


Extra refrigerant charge = 15.4m(ø6.4) × 0.022 + 54.7m(ø9.5) × 0.057 + 24.7m(ø19.1) × 0.26 + 5.3m(ø12.7) × 0.11
+ 3.2m(ø15.9) × 0.17 + A + B = 13.0kg
A [ CR 102%, actual length 46.5m ] = 2.0kg
B [ 32HP ] = 0.0kg

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 9
3. Piping Diagrams
Pipes marked with * in the diagrams must be connected to the device with a reducing joint.

3.1. Piping Out 1


Out 1
RXQ38TANYM
RXQ18TAYM RXQ12TAYM RXQ8TAYM

15.9×28.6 12.7×28.6 9.5×19.1


15.9×28.6
BHFP22P151

85.5m 4.8m 8.3m 5.2m


22.2×41.3 * 15.9×28.6 12.7×28.6 9.5×19.1
KHRP26A73T + KHRP26A72T KHRP26A72T KHRP26A22T
KHRP26M73TP

1.3m 2.6m 5.1m


9.5×15.9 9.5×15.9 6.4×12.7
T1/1.07 T1/1.08 T1/1.09
5.4m FXMQ125PVE FXMQ125PVE FXDQ40NBVE
9.5×22.2
KHRP26A33T

1.9m 5.2m
9.5×15.9 9.5×15.9
T1/1.05 T1/1.06
1.6m 1.3m FXMQ100PVE 6.9m FXMQ100PVE
15.9×28.6 12.7×28.6 9.5×22.2
KHRP26A72T KHRP26A72T KHRP26A33T

9.5m 0.9m 1.7m 10.3m


9.5×15.9 9.5×15.9 9.5×15.9 9.5×15.9
T2/1.01 T2/1.02 T2/1.03 T2/1.04
FXMQ100PVE FXMQ100PVE FXMQ125PVE FXMQ100PVE

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 10
3.2. Piping Out 2
Out 2
RXQ32TANYM
RXQ18TAYM RXQ14TAYM

15.9×28.6 12.7×28.6

BHFP22P100

76.5m 1.8m 4.6m 1.5m


22.2×38.1 * 15.9×28.6 15.9×28.6 12.7×28.6
KHRP26A73T + KHRP26A72T KHRP26A72T KHRP26A72T
KHRP26M73TP

3.9m 7.5m 1.3m 9.1m


9.5×15.9 9.5×15.9 9.5×19.1 9.5×15.9
T3/1.03 T3/1.04 T3/1.05 T3/1.06
3.7m FXMQ125PVE FXMQ140PVE FXMQ200MAVE FXMQ125PVE
9.5×22.2
KHRP26A33T

2.1m 8.9m
9.5×15.9 9.5×15.9
T3/1.01 T3/1.02
FXMQ140PVE FXMQ63PVE

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 11
3.3. Piping Out 3
Out 3
RXQ40TANYM
RXQ16TAYM RXQ12TAYM RXQ12TAYM

12.7×28.6 12.7×28.6 12.7×28.6


15.9×34.9
BHFP22P151

71.0m 1.9m 0.5m 1.9m 1.4m 3.9m


22.2×41.3 * 19.1×34.9 19.1×34.9 15.9×28.6 12.7×28.6 9.5×22.2
KHRP26A73T + KHRP26A73T + KHRP26A73T + KHRP26A72T KHRP26A72T KHRP26A33T
KHRP26M73TP KHRP26M73TP KHRP26M73TP

2.0m 1.9m 7.3m


9.5×15.9 9.5×15.9 9.5×15.9
T4/1.06 T4/1.07 T4/1.08
4.8m FXMQ125PVE FXMQ125PVE FXMQ125PVE
9.5×22.2
KHRP26A33T

5.9m 1.8m 5.1m 2.9m 3.8m


9.5×15.9 9.5×15.9 9.5×15.9 9.5×15.9 9.5×15.9
T4/1.01 T4/1.02 T4/1.03 T4/1.04 T4/1.05
FXMQ125PVE FXMQ125PVE FXMQ125PVE FXMQ125PVE FXMQ125PVE

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 12
3.4. Piping Out 4
Out 4
RXQ52TANYM
RXQ18TAYM RXQ18TAYM RXQ16TAYM

15.9×28.6 15.9×28.6 12.7×28.6


19.1×34.9
BHFP22P151

58.5m 3.2m 3.2m 0.6m 0.4m 1.7m 0.8m


19.1×41.3 19.1×34.9 15.9×28.6 12.7×28.6 12.7×28.6 9.5×15.9 9.5×15.9
KHRP26A73T + KHRP26A73T + KHRP26A72T KHRP26A72T KHRP26A72T KHRP26A22T KHRP26A22T
KHRP26M73TP KHRP26M73TP

3.4m 2.3m 6.2m


6.4×12.7 6.4×12.7 6.4×12.7
T5/1.08 T5/1.09 T5/1.10
2.5m 2.5m FXDQ40NBVE 2.8m FXDQ40NBVE 1.7m FXDQ40NBVE
9.5×22.2 9.5×19.1 9.5×15.9 9.5×15.9
KHRP26A33T KHRP26A22T KHRP26A22T KHRP26A22T

5.1m 2.6m 1.4m 2.9m 3.1m 2.3m 4.4m


6.4×12.7 6.4×12.7 9.5×15.9 6.4×12.7 6.4×12.7 6.4×12.7 6.4×12.7
T5/1.01 T5/1.02 T5/1.03 T5/1.04 T5/1.05 T5/1.06 T5/1.07
0.7m 0.6m FXDQ40NBVE 0.4m FXDQ40NBVE 1.7m FXMQ80PVE 0.8m FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE
15.9×28.6 12.7×28.6 12.7×28.6 9.5×15.9 9.5×15.9
KHRP26A72T KHRP26A72T KHRP26A72T KHRP26A22T KHRP26A22T

3.4m 2.3m 6.2m


6.4×12.7 6.4×12.7 6.4×12.7
T6/1.18 T6/1.19 T6/1.20
2.5m 2.5m FXDQ40NBVE 2.8m FXDQ40NBVE 1.7m FXDQ40NBVE
9.5×22.2 9.5×19.1 9.5×15.9 9.5×15.9
KHRP26A33T KHRP26A22T KHRP26A22T KHRP26A22T

5.1m 2.6m 1.4m 2.9m 3.1m 2.3m 4.4m


6.4×12.7 6.4×12.7 9.5×15.9 6.4×12.7 6.4×12.7 6.4×12.7 6.4×12.7
T6/1.11 T6/1.12 T6/1.13 T6/1.14 T6/1.15 T6/1.16 T6/1.17
0.7m 0.6m FXDQ40NBVE 0.4m FXDQ40NBVE 1.7m FXMQ80PVE 0.8m FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE
15.9×28.6 12.7×28.6 12.7×28.6 9.5×15.9 9.5×15.9
KHRP26A72T KHRP26A72T KHRP26A72T KHRP26A22T KHRP26A22T

3.4m 2.3m 6.2m


6.4×12.7 6.4×12.7 6.4×12.7
T7/1.28 T7/1.29 T7/1.30
2.5m 2.5m FXDQ40NBVE 2.8m FXDQ40NBVE 1.7m FXDQ40NBVE
9.5×22.2 9.5×19.1 9.5×15.9 9.5×15.9
KHRP26A33T KHRP26A22T KHRP26A22T KHRP26A22T

5.1m 2.6m 1.4m 2.9m 3.1m 2.3m 4.4m


6.4×12.7 6.4×12.7 9.5×15.9 6.4×12.7 6.4×12.7 6.4×12.7 6.4×12.7
T7/1.21 T7/1.22 T7/1.23 T7/1.24 T7/1.25 T7/1.26 T7/1.27
FXDQ40NBVE FXDQ40NBVE FXMQ80PVE FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 13
3.5. Piping Out 5
Out 5
RXQ52TANYM
RXQ18TAYM RXQ18TAYM RXQ16TAYM

15.9×28.6 15.9×28.6 12.7×28.6


19.1×34.9
BHFP22P151

48.1m 3.2m 3.9m 0.6m 0.4m 1.7m 0.8m


19.1×41.3 19.1×34.9 15.9×28.6 12.7×28.6 12.7×28.6 9.5×15.9 9.5×15.9
KHRP26A73T + KHRP26A73T + KHRP26A72T KHRP26A72T KHRP26A72T KHRP26A22T KHRP26A22T
KHRP26M73TP KHRP26M73TP

3.4m 2.3m 6.2m


6.4×12.7 6.4×12.7 6.4×12.7
T9/2.18 T9/2.19 T9/2.20
2.5m 2.5m FXDQ40NBVE 2.8m FXDQ40NBVE 1.7m FXDQ40NBVE
9.5×22.2 9.5×19.1 9.5×15.9 9.5×15.9
KHRP26A33T KHRP26A22T KHRP26A22T KHRP26A22T

5.1m 2.6m 1.4m 2.9m 3.1m 2.3m 4.4m


6.4×12.7 6.4×12.7 9.5×15.9 6.4×12.7 6.4×12.7 6.4×12.7 6.4×12.7
T9/2.11 T9/2.12 T9/2.13 T9/2.14 T9/2.15 T9/2.16 T9/2.17
0.7m 0.6m FXDQ40NBVE 0.4m FXDQ40NBVE 1.7m FXMQ80PVE 0.8m FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE
15.9×28.6 12.7×28.6 12.7×28.6 9.5×15.9 9.5×15.9
KHRP26A72T KHRP26A72T KHRP26A72T KHRP26A22T KHRP26A22T

3.4m 2.3m 6.2m


6.4×12.7 6.4×12.7 6.4×12.7
T10/2.28 T10/2.29 T10/2.30
2.5m 2.5m FXDQ40NBVE 2.8m FXDQ40NBVE 1.7m FXDQ40NBVE
9.5×22.2 9.5×19.1 9.5×15.9 9.5×15.9
KHRP26A33T KHRP26A22T KHRP26A22T KHRP26A22T

5.1m 2.6m 1.4m 2.9m 3.1m 2.3m 4.4m


6.4×12.7 6.4×12.7 9.5×15.9 6.4×12.7 6.4×12.7 6.4×12.7 6.4×12.7
T10/2.21 T10/2.22 T10/2.23 T10/2.24 T10/2.25 T10/2.26 T10/2.27
0.7m 0.6m FXDQ40NBVE 0.4m FXDQ40NBVE 1.7m FXMQ80PVE 0.8m FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE
15.9×28.6 12.7×28.6 12.7×28.6 9.5×15.9 9.5×15.9
KHRP26A72T KHRP26A72T KHRP26A72T KHRP26A22T KHRP26A22T

3.4m 2.3m 6.2m


6.4×12.7 6.4×12.7 6.4×12.7
T8/2.08 T8/2.09 T8/2.10
2.5m 2.5m FXDQ40NBVE 2.8m FXDQ40NBVE 1.7m FXDQ40NBVE
9.5×22.2 9.5×19.1 9.5×15.9 9.5×15.9
KHRP26A33T KHRP26A22T KHRP26A22T KHRP26A22T

5.1m 2.5m 1.4m 2.9m 3.1m 2.3m 4.4m


6.4×12.7 6.4×12.7 9.5×15.9 6.4×12.7 6.4×12.7 6.4×12.7 6.4×12.7
T8/2.01 T8/2.02 T8/2.03 T8/2.04 T8/2.05 T8/2.06 T8/2.07
FXDQ40NBVE FXDQ40NBVE FXMQ80PVE FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 14
3.6. Piping Out 6
Out 6
RXQ52TANYM
RXQ18TAYM RXQ18TAYM RXQ16TAYM

15.9×28.6 15.9×28.6 12.7×28.6


19.1×34.9
BHFP22P151

42.0m 3.2m 3.9m 0.6m 0.4m 1.7m 0.8m


19.1×41.3 19.1×34.9 15.9×28.6 12.7×28.6 12.7×28.6 9.5×15.9 9.5×15.9
KHRP26A73T + KHRP26A73T + KHRP26A72T KHRP26A72T KHRP26A72T KHRP26A22T KHRP26A22T
KHRP26M73TP KHRP26M73TP

3.4m 2.3m 6.2m


6.4×12.7 6.4×12.7 6.4×12.7
T13/3.28 T13/3.29 T13/3.30
2.5m 2.5m FXDQ40NBVE 2.8m FXDQ40NBVE 1.7m FXDQ40NBVE
9.5×22.2 9.5×19.1 9.5×15.9 9.5×15.9
KHRP26A33T KHRP26A22T KHRP26A22T KHRP26A22T

5.1m 2.6m 1.4m 2.9m 3.1m 2.3m 4.4m


6.4×12.7 6.4×12.7 9.5×15.9 6.4×12.7 6.4×12.7 6.4×12.7 6.4×12.7
T13/3.21 T13/3.22 T13/3.23 T13/3.24 T13/3.25 T13/3.26 T13/3.27
0.7m 0.6m FXDQ40NBVE 0.4m FXDQ40NBVE 1.7m FXMQ80PVE 0.8m FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE
15.9×28.6 12.7×28.6 12.7×28.6 9.5×15.9 9.5×15.9
KHRP26A72T KHRP26A72T KHRP26A72T KHRP26A22T KHRP26A22T

3.4m 2.3m 6.2m


6.4×12.7 6.4×12.7 6.4×12.7
T12/3.18 T12/3.19 T12/3.20
2.5m 2.5m FXDQ40NBVE 2.8m FXDQ40NBVE 1.7m FXDQ40NBVE
9.5×22.2 9.5×19.1 9.5×15.9 9.5×15.9
KHRP26A33T KHRP26A22T KHRP26A22T KHRP26A22T

5.1m 2.6m 1.4m 2.9m 3.1m 2.3m 4.4m


6.4×12.7 6.4×12.7 9.5×15.9 6.4×12.7 6.4×12.7 6.4×12.7 6.4×12.7
T12/3.11 T12/3.12 T12/3.13 T12/3.14 T12/3.15 T12/3.16 T12/3.17
0.7m 0.6m FXDQ40NBVE 0.4m FXDQ40NBVE 1.7m FXMQ80PVE 0.8m FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE
15.9×28.6 12.7×28.6 12.7×28.6 9.5×15.9 9.5×15.9
KHRP26A72T KHRP26A72T KHRP26A72T KHRP26A22T KHRP26A22T

3.4m 2.3m 6.2m


6.4×12.7 6.4×12.7 6.4×12.7
T11/3.08 T11/3.09 T11/3.10
2.5m 2.5m FXDQ40NBVE 2.8m FXDQ40NBVE 1.7m FXDQ40NBVE
9.5×22.2 9.5×19.1 9.5×15.9 9.5×15.9
KHRP26A33T KHRP26A22T KHRP26A22T KHRP26A22T

5.1m 2.6m 1.4m 2.9m 3.1m 2.3m 4.4m


6.4×12.7 6.4×12.7 9.5×15.9 6.4×12.7 6.4×12.7 6.4×12.7 6.4×12.7
T11/3.01 T11/3.02 T11/3.03 T11/3.04 T11/3.05 T11/3.06 T11/3.07
FXDQ40NBVE FXDQ40NBVE FXMQ80PVE FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 15
3.7. Piping Out 7
Out 7
RXQ52TANYM
RXQ18TAYM RXQ18TAYM RXQ16TAYM

15.9×28.6 15.9×28.6 12.7×28.6


19.1×34.9
BHFP22P151

32.5m 3.2m 3.9m 0.6m 0.4m 1.7m 0.8m


19.1×41.3 19.1×34.9 15.9×28.6 12.7×28.6 12.7×28.6 9.5×15.9 9.5×15.9
KHRP26A73T + KHRP26A73T + KHRP26A72T KHRP26A72T KHRP26A72T KHRP26A22T KHRP26A22T
KHRP26M73TP KHRP26M73TP

3.4m 2.3m 6.2m


6.4×12.7 6.4×12.7 6.4×12.7
T16/4.28 T16/4.29 T16/4.30
2.5m 2.5m FXDQ40NBVE 2.8m FXDQ40NBVE 1.7m FXDQ40NBVE
9.5×22.2 9.5×19.1 9.5×15.9 9.5×15.9
KHRP26A33T KHRP26A22T KHRP26A22T KHRP26A22T

5.1m 2.6m 1.4m 2.9m 3.1m 2.3m 4.4m


6.4×12.7 6.4×12.7 9.5×15.9 6.4×12.7 6.4×12.7 6.4×12.7 6.4×12.7
T16/4.21 T16/4.22 T16/4.23 T16/4.24 T16/4.25 T16/4.26 T16/4.27
0.7m 0.6m FXDQ40NBVE 0.4m FXDQ40NBVE 1.7m FXMQ80PVE 0.8m FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE
15.9×28.6 12.7×28.6 12.7×28.6 9.5×15.9 9.5×15.9
KHRP26A72T KHRP26A72T KHRP26A72T KHRP26A22T KHRP26A22T

3.4m 2.3m 6.2m


6.4×12.7 6.4×12.7 6.4×12.7
T15/4.18 T15/4.19 T15/4.20
2.5m 2.5m FXDQ40NBVE 2.8m FXDQ40NBVE 1.7m FXDQ40NBVE
9.5×22.2 9.5×19.1 9.5×15.9 9.5×15.9
KHRP26A33T KHRP26A22T KHRP26A22T KHRP26A22T

5.1m 2.6m 1.4m 2.9m 3.1m 2.3m 4.4m


6.4×12.7 6.4×12.7 9.5×15.9 6.4×12.7 6.4×12.7 6.4×12.7 6.4×12.7
T15/4.11 T15/4.12 T15/4.13 T15/4.14 T15/4.15 T15/4.16 T15/4.17
0.7m 0.6m FXDQ40NBVE 0.4m FXDQ40NBVE 1.7m FXMQ80PVE 0.8m FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE
15.9×28.6 12.7×28.6 12.7×28.6 9.5×15.9 9.5×15.9
KHRP26A72T KHRP26A72T KHRP26A72T KHRP26A22T KHRP26A22T

3.4m 2.3m 6.2m


6.4×12.7 6.4×12.7 6.4×12.7
T14/4.08 T14/4.09 T14/4.10
2.5m 2.5m FXDQ40NBVE 2.8m FXDQ40NBVE 1.7m FXDQ40NBVE
9.5×22.2 9.5×19.1 9.5×15.9 9.5×15.9
KHRP26A33T KHRP26A22T KHRP26A22T KHRP26A22T

5.1m 2.6m 1.4m 2.9m 3.1m 2.3m 4.4m


6.4×12.7 6.4×12.7 9.5×15.9 6.4×12.7 6.4×12.7 6.4×12.7 6.4×12.7
T14/4.01 T14/4.02 T14/4.03 T14/4.04 T14/4.05 T14/4.06 T14/4.07
FXDQ40NBVE FXDQ40NBVE FXMQ80PVE FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE FXDQ40NBVE

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 16
3.8. Piping Out 8
Out 8
RXQ32TANYM
RXQ18TAYM RXQ14TAYM

15.9×28.6 12.7×28.6

BHFP22P100

24.7m 3.8m 1.1m 8.5m


19.1×34.9 12.7×28.6 9.5×22.2 9.5×19.1
KHRP26A73T + KHRP26A72T KHRP26A33T KHRP26A22T
KHRP26M73TP

8.3m 1.2m 2.7m 6.2m


9.5×15.9 9.5×15.9 9.5×15.9 9.5×15.9
T18/1.01 T18/1.02 T18/1.03 T18/1.04
3.2m 1.5m FXMQ140PVE 3.9m FXMQ100PVE FXMQ80PVE FXMQ80PVE
15.9×28.6 12.7×28.6 9.5×15.9
KHRP26A72T KHRP26A72T KHRP26A22T

2.5m 4.9m
6.4×12.7 6.4×12.7
T17/5.26 T17/5.27
5.0m 5.9m FXDQ40NBVE FXDQ40NBVE
9.5×22.2 9.5×19.1
KHRP26A33T KHRP26A22T

1.7m 2.7m 6.2m


9.5×15.9 9.5×15.9 9.5×15.9
T17/5.23 T17/5.24 T17/5.25
1.3m FXMQ100PVE FXMQ80PVE FXMQ80PVE
9.5×15.9
KHRP26A22T

6.2m 1.9m
6.4×12.7 6.4×12.7
T17/5.21 T17/5.22
FXDQ40NBVE FXDQ40NBVE

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 17

You might also like