Arc resistant controllers Rockwell Automation has enhanced the safety of its world
recognized medium voltage control products to include an optional arc resistant class of
medium voltage control equipment. ArcShield™ controllers provide the additional arc
resistant safety features required by some industries. Most medium voltage control
products can be provided with the ArcShield enclosure design which meets the arc
resistant testing requirements of IEEE C37.20.7. ArcShield controllers use the same
standard reliable internal components that continue to serve industries world wide.
Built-in DeviceNet
DeviceNet ports in horizontal wireway
• Simplifies installation
• Complex I/O interwiring is reduced to a single DeviceNet cable
• New 8 ampere, Class 1 DeviceNet cabling
• Tested for noise immunity
4
IntelliCENTER Software
• Spare parts lists specific to each unit
• AutoCAD® elevation and one-line drawings
• User manuals specific to each unit
• Event logging, warnings, faults,
parameter edits
IntelliCENTER Software
• Features pre-configured screens for each unit
• Allows MCC monitoring from anywhere in the
user’s facility
• Contains Active X controls to allow easy
integration into RSView
MV SMC FLEX
UNMATCHED INTELLIGENT MOTOR CONTROL
7
ARCSHIELD
®
8
Offering a wide variety of Centerline ArcShield products:
The ArcShield products are available in a
number of different controller configurations.
Side view (common to all products)
Here are just a few of the products available:
• Bulletin 1591A Incoming units
• Bulletin 1512A/AT One high controller
• Bulletin 1512B/BT Two high controller
• Bulletin 1562E MV SMC Flex controller
9
BUILDING BLOCKS
At Rockwell Automation, we are committed to
providing the products and services that our
customers demand. Over the past eighty years,
Allen-Bradley medium voltage Centerline®
controllers have set the standard by which others
are measured. Our unmatched quality and
innovative designs have made us the leader in
medium voltage motor control products.
11
INTELLIGENT
MOTOR CONTROL
MEETING TOMORROW’S MANUFACTURING NEEDS...TODAY
PROTECTION
Thanks to integrated I/O and advanced diagnostic and protection
capabilities, all Intelligent Motor Control products constantly
monitor the motor operation to help you follow performance trends
and take remedial action before potential failures occur. Reduce
unwanted downtime by 75% while increasing overall production
efficiency by 10% or more.
12
COMMUNICATIONS
Because you have a wide range of
application needs, Intelligent
Motor Control offers a variety of
motor control technologies.
COMMUNICATIONS
The key to intelligence in motor control...
Added to those demands is the need for smaller, more flexible medium voltage products that are more
efficient and reduce building and expansion costs.
OEM Frames and components leverage the existing family of motor controllers built by Rockwell
Automation. They also incorporate some of the most fundamental, high volume components available
in our OEM product line for Original Equipment Manufacturers and electrical equipment companies.
Bulletin 1502 vacuum contactors are a comprehensive line of vacuum contactors used as isolating
contactors or as bypass contactors. Light weight and maintainability are but two of the features of this
fixed-mounted design.
Bulletin 1503F OEM components are a series of medium voltage frame-mounted components designed
to mount into new or existing structures or enclosures. These assemblies can also be used to retrofit
existing motor controllers. These products are available as a complete OEM frame or sold individually
as components.
Description of Features • IntelliVAC™ control module for each vacuum contactor, mounted
in low voltage panel, with advanced features:
Designed for Safety, Convenience and Reliability – Universal input voltage (110-240V AC, 50/60 Hz or 100-250V DC)
– Selectable vacuum contactor drop-out time and consistent pick-
The Allen-Bradley medium voltage controller offers: up time
• Three isolated compartments: – Altitude compensation
- Power bus – Power loss ride-through (TDUV) – may require additional
- Low voltage hardware (external capacitor)
- Power cell – Anti-kiss and anti-plugging protection
• Large swing-out low voltage panel painted white for high visibility – Delayed motor re-start and temporary motor jog function
• Test circuit and plug for remote control power supply – One device is suitable for all contactors and control schemes
• External operating handle to operate the isolation switch
• Bolted power cell door(s)
Input Voltage
• Centerline® horizontal power bus with removable cover plates for
• 2400V, 3300V, 4200V, 6600V or 6900V AC (+5/-10%)
accessibility
• 3 phase 50/60 Hz (± 3%)
• 1/4” x 2” continuous copper ground bus
• Line, load and control wire conduit openings with removable cover
Ambient Temperature
plates at the top or bottom of the structure
• Base mounting sill channels with mounting holes and removable • 0°C to 40°C (32°F to 104°F) with relative humidity of
up to 95% (non-condensing)
lifting means
• Hybrid epoxy powder paint finish
Enclosure Types
• NEMA Type 1 – General purpose (IP10)
Controller Standard Features
• NEMA Type 1 w/g – General purpose with gasket (IP21)
• NEMA Class E2 design • NEMA Type 12 – Dust-tight and drip proof (IP52)
• Removable lifting angles or brackets • NEMA Type 3R – Non walk-in weatherproof (IP34)
• Non-removable sill channels • Arc Resistant (NEMA Type 12) – Accessibility Type 2
• Removable backplates – Tested per IEEE C37.20.7-2001
• Top or bottom plates to accommodate cable entry/exit
• Tin-plated copper horizontal power bus located in an isolated Standards
compartment • Canadian Standards Association (CSA),
• A ¼” x 2” continuous bare copper ground bus Industrial Control Equipment C22.2 No. 14 and TIL D-21
• A main non-load break isolation switch with visible blades • American Nation Standards Institute (ANSI),
and shutter mechanism, and operating handle Instrument Transformers C57.13
• Mechanical and electrical interlocks between isolation switch, • Institute of Electrical & Electronic Engineers (IEEE)
vacuum contactor and MV door • National Electrical Code (NEC)
• Vacuum contactor(s) • Occupational Safety & Health Act (OSHA)
• Three (3) current limiting power fuses for NEMA Class E2 operation • Guide for Harmonic Control and Reactive
• Three (3) current transformers Compensation of Static Power Converters (IEEE 519-1992)
• Control circuit transformer with primary and secondary fuses • National Electrical Manufacturers Association (NEMA),
• A low voltage control panel Medium Voltage Controllers Rated 1501 to 7200 V AC ICS 3-2
• Space for necessary auxiliary control and metering devices (formerly ICS 2-324)
• Polycarbonate viewing window in power cell door • Underwriters Laboratories, Inc. (UL),
High Voltage Industrial Control Equipment 347
• European Directives for EMC
Ground Bus
• Continuous bare copper ground bus 6 x 52 mm (1/4 in x 2 in)
as standard
• #8 - #1/0 AWG or #6 – 250 MCM mechanical lug
supplied at the incoming end of the lineup
Current Transformers
• Three (3) current transformers are supplied as standard
for overload protection and metering
• Five (5) amp secondary output
Visible Isolation
• When in the open position, a visible barrier isolates the power cell
from the power bus compartment
• Status of the isolation switch can be viewed through a window in
the power cell door
Vacuum Contactor
• Modular design for simplified maintenance and reliability
• Fixed mounted design eliminates hot spots and
reduces maintenance
• Visible contact wear indicator eliminates the need for special tools
Isolated Compartment
• All low voltage components are located in the low voltage panel
• Low voltage panel interior painted white for better visibility
• Power cell, low voltage panel, and bus compartment are isolated
from each other for better fault containment
• IntelliVAC control module
Specifications
CONTROL M-INTELLIVAC
POWER
FUSE 7 + - 8
OPEN
9 + - 10
CLOSE
OVERLOAD START
STOP
16 CONTACTOR
STATUS
15
MODULE 14
STATUS
13
CAPACITOR
(OPTIONAL)
1 - 4
EC TCO
2 + 3
MOV
M
11 6 M
AUX CCO
12 5
CONFIGURATION
DIP SWITCHES
INPUT POWER
L1 G L2/N
Applications
Medium Voltage (1,000 to 7,200 V) vacuum switching for:
• Motor Starters (asynchronous, synchronous)
– Full voltage
– Reduced voltage
– Variable frequency drives
• Transformer feeder units
• Capacitors
Product Approvals
• UL347
• CSA 22.2 No. 14 and TIL D-21
• IEC 60470
• CE Mark
Modular Construction
• Designed to be interchangeable with other contactors of the same
Description of Features rating
The Allen-Bradley vacuum contactors are designed as fixed • Horsepower rated devices are located elsewhere in the power cell,
mounted devices for heavy-duty industrial performance. This design not on the contactor
eliminates the worries typically associated with drawout contactors. • Easily removed for maintenance and repair
The compact design of the contactor eliminates the need for it to be Vacuum Bottles
removed from the power cell. Also there are no drawout stab and
finger assemblies, which require routine maintenance. • Designed to industry specifications
• Arcing confined inside vacuum bottle for ionized gas protection
The Series E contactors are designed for operation with Rockwell • Mounted on the front of the contactor for visible inspection
Automation’s IntelliVAC control module. • Contact wear indicators located on the bottle eliminates the need
for special tools
• Excellent dielectric recovery provides high switching frequency
Advantages
• Lightweight, compact design Long Electrical and Mechanical Life
• High interrupting capability • 1,000,000 electrical operations (400 A)
• Low chop current • 2,500,000 mechanical operations (400 A)
• Visual contact wear indicator (no measurement tools required)
• Provisions for mechanical interlocking (to isolation switch)
• Excellent dielectric recovery allowing for high switching frequency
• Single coil/core magnet assembly (800 A only)
• Control power transformer primary fuse holders (400 A only)
• Minimal maintenance required
• All major components are easily accessed from the front
• Mechanical latch design (optional)
• Easily integrated into control circuit with quick connector and wire
harness (optional)
• Designed to complement the advanced features of the IntelliVAC
contactor control module
Specifications
Converter Modules
• Compact Three-Phase current transformer modules
• Provides electrical isolation
• Six current ranges
• 0.5 to 2.5 A
• 2.5 to 20 A
• 20 to 180 A
• 160 to 630 A
• Compatibility with MCS PLUS Bulletin 100-D contactors
Engineered Features
• Reinforced cabinet and power cell door closure mechanism
• Multi-point latching mechanism, reinforced cross bracing and
Description of Features gasket sealing
• Reinforced back plates – added support plates secured with mul-
The Allen-Bradley Centerline ArcShield arc resistant controller provides tiple bolts provide increased rigidity and security
rugged process control for applications requiring a higher level of • Reinforced low voltage panel to withstand arc flash energy and
personnel protection. ArcShield products are compliant to the IEEE shield maintenance personnel while working in the isolated low
C37.20.7 standard, and provide Type 2 protection during an arc flash. voltage compartment
• Arc “Pressure Relief” vent to safely vent arc gases and material
The ArcShield controller safely redirects the arc flash energy out the
away from personnel during an arc flash
top of the unit and away from personnel. This level of protection is
also maintained when the low voltage door is open for maintenance • Available with removable arc exhaust plenum
purposes.
Specifications
Description of Features
• Fixed mounted vacuum contactors (FORWARD and REVERSE)
• Three-pole, gang-operated, non-load break isolating switch with an
external operating handle, fully interlocked with main contactor and
power cell doors
• A polycarbonate viewing window in the power cell door to view the
position of the isolating switch
• Three (3) R-rated current-limiting power fuses
• Three (3) current transformers
• Control power transformer with primary and secondary fuses
• Segregated low voltage panel to house standard and optional
hardware for unit control and monitoring
• IntelliVAC™ control module for each vacuum contactor, mounted
in low voltage panel, with advanced features:
• Additional low voltage control panel accessories including:
– “NORMAL-OFF-TEST” circuit
– receptacle for external test power supply
400 amp
– set of control circuit terminal blocks
• Available for motor loads
• Plugging or anti-plugging duty
• Mechanically and electrically interlocked contactors
Specifications
Description of Features
• Fixed mounted vacuum contactor
• Three-pole, gang-operated, non-load break isolating switch with an
external operating handle, fully interlocked with main contactor and
power cell doors
• A polycarbonate viewing window in the power cell door to view the
position of the isolating switch
• Three (3) R-rated current-limiting power fuses
(R-rated power fuses used for 450 A, 600 A and 800 A starters)
• Three (3) current transformers
• Control power transformer with primary and secondary fuses
• Segregated low voltage panel to house standard and optional
hardware for unit control and monitoring
• IntelliVAC™ control module for each vacuum contactor, mounted
in low voltage panel, with advanced features:
• Additional low voltage control panel accessories including:
400 Amp – “NORMAL-OFF-TEST” circuit
– receptacle for external test power supply
– set of control circuit terminal blocks
• 1-high structure design for one complete motor controller
• Available in optional ArcShield enclosure
• Also available as “Prepared Space” (Bulletin 1512AP, 200A and
400A only) or Starter Kits (Bulletin 1512AS)
Specifications
Description of Features
• Fixed mounted vacuum contactor
• Three-pole, gang-operated, non-load break isolating switch with an
external operating handle, fully interlocked with main contactor and
power cell doors
• A polycarbonate viewing window in the power cell door to view the
position of the isolating switch
• Three (3) E-rated current-limiting power fuses
(R-rated power fuses used for 450 A, 600 A and 800 A starters,
and for 400 A 6600V/6900V starters)
• Three (3) current transformers
• Control power transformer with primary and secondary fuses
• Segregated low voltage panel to house standard and optional
hardware for unit control and monitoring
• IntelliVAC™ control module for each vacuum contactor, mounted
in low voltage panel, with advanced features:
400 Amp • Additional low voltage control panel accessories including:
– “NORMAL-OFF-TEST” circuit
– receptacle for external test power supply
– set of control circuit terminal blocks
• 1-high structure design for one complete transformer controller
• Available in optional ArcShield enclosure
• Also available as “Prepared Space” (Bulletin 1512AP, 200 A and
400 A only) or Feeder Kits (Bulletin 1512AU)
Specifications
Description of Features
• Fixed mounted vacuum contactor
• Three-pole, gang-operated, non-load break isolating switch with an
external operating handle, fully interlocked with main contactor and
power cell doors
• A polycarbonate viewing window in the power cell door to view the
position of the isolating switch
• Three (3) R-rated current-limiting power fuses
• Three (3) current transformers
• Control power transformer with primary and secondary fuses
• Segregated low voltage panel to house standard and optional
hardware for unit control and monitoring
• IntelliVAC™ control module for each vacuum contactor, mounted
in low voltage panel, with advanced features:
• Additional low voltage control panel accessories including:
– “NORMAL-OFF-TEST” circuit
– receptacle for external test power supply
400 Amp – set of control circuit terminal blocks
• 2-high structure design for two complete motor controllers
• Available in optional ArcShield enclosure
• Also available as “Prepared Space” (Bulletin 1512BP) and Starter
Kits (Bulletin 1512BS)
Specifications
Specifications
Description of Features
• Fixed mounted vacuum contactor
• HIGH and LOW speed settings for two-speed separate winding,
Bulletin 1522E starter
• HIGH/LOW speeds and HIGH SPEED SHORTING settings for
two-speed consequent pole, Bulletin 1522F/G starter
• Three-pole, gang-operated, non-load break isolating switch with an
external operating handle, fully interlocked with main contactor and
power cell doors
• A polycarbonate viewing window in the power cell door to view the
position of the isolating switch
• Three (3) R-rated current-limiting power fuses
• Six (6) current transformers
• Control power transformer with primary and secondary fuses
• Segregated low voltage panel to house standard and optional
hardware for unit control and monitoring
400 A • IntelliVAC™ control module for each vacuum contactor, mounted
in low voltage panel, with advanced features:
• Additional low voltage control panel accessories including:
– “NORMAL-OFF-TEST” circuit
– receptacle for external test power supply
– set of control circuit terminal blocks
• Constant or variable torque, and constant horsepower applications
Specifications
Metering
• Access locally using the controller’s built-in LCD display, or
remotely through the communication port
• Three-phase voltage
• Three-phase current
• Three-phase power (MW, MWh, power factor)
• Elapsed time
• Motor thermal capacity usage
• Motor speed (with optional use of tachometer input)
Diagnostics
• Line Fault • Undervoltage
• Power Loss • Jam
• Voltage Unbalance • Overtemperature
• Current Unbalance • Stall
• Ground Fault • Open Gate
• Communication Fault • Overload
• Phase Reversal • Underload
• Extensive Starts per hour
Bulletin 1562E
Combination Controller Communication (optional)
• DeviceNet™
• ControlNet™
• EtherNet/IP
Description of Features • Profibus DP
• Remote I/O
• RS485-DF1
Optimized Performance, Safety, Convenience
and Reliability Programming
The Rockwell Automation MV SMC Flex Smart Motor Controller • Three-level menu structure (using standard languages)
offers: • Built-in LCD display and keypad
• Multiple languages: English, French, German, Italian, Mandarin,
Portuguese, Spanish
Standard Control Module
• Optional Human Interface Modules (DPI-based)
• Soft Start – with Selectable Kickstart • Configurable with DriveTools™ programming software
• Soft Stop
• Current Limit Start – with Selectable Kickstart
• Linear Speed Acceleration* – with Selectable Kickstart Vacuum Contactor
• Linear Speed Deceleration* • Fixed mounted vacuum contactor is standard
• Dual Ramp – with Selectable Kickstart • Main contactor for unit isolation (1562E)
• Full Voltage • Bypass contactor removes SCR Power Stack from circuit, once at
• Preset Slow Speed full voltage
* requires motor tachometer – Eliminates heat generated by SCRs - improves efficiency
– Protects SCRs from voltage and current transients
• Contactor can be provided with IntelliVAC™ solid-state control
Optional Control Module
• Pump Control (eliminates water hammer) Complete Package
– separate start and stop profiles • Quick shipment of several standard configurations
– Bulletin 1560E retrofit controller (does not include isolation
Motor Protection switch, main contactor, power fuses and control transformer)
– Bulletin 1562E combination controller
• Electronic motor overload protection Class 10, 15, 20 and 30 or
• Available with optional equipment
OFF
• Ready for immediate installation
• Complete installation documentation
• Built to Rockwell Automation quality standards and ISO9001:2000
• Fully load tested with a three-phase MV motor
Specifications
Description of Features
• Fixed mounted vacuum contactor
• (1S, FORWARD, REVERSE and RUN) settings, with closed
transition operation, Bulletin 1576 Reversing starter
• (1S, 2S and RUN) settings, with closed transition operation,
Bulletin 1572 Non-reversing starter
• Three-pole, gang-operated, non-load break isolating switch with an
external operating handle, fully interlocked with main contactor and
power cell doors
• A polycarbonate viewing window in the power cell door to view the
position of the isolating switch
• Three (3) R-rated current-limiting power fuses
• Three (3) current transformers
• Control power transformer with primary and secondary fuses
• Segregated low voltage panel to house standard and optional
hardware for unit control and monitoring
400 Amp
• IntelliVAC™ control module for each vacuum contactor, mounted
in low voltage panel, with advanced features:
• Additional low voltage control panel accessories including:
– “NORMAL-OFF-TEST” circuit
– receptacle for external test power supply
– set of control circuit terminal blocks
• NEMA medium duty, dry type, three (3) winding autotransformer
with 50, 65 and 80% taps. The 65% tap shall be used unless
otherwise specified.
Specifications
Description of Features
• Fixed mounted vacuum contactors (START and RUN) with closed
transition operation
• Three-pole, gang-operated, non-load break isolating switch with an
external operating handle, fully interlocked with main contactor and
power cell doors
• A polycarbonate viewing window in the power cell door to view the
position of the isolating switch
• Three (3) R-rated current-limiting power fuses
• Three (3) current transformers
• Control power transformer with primary and secondary fuses
• Segregated low voltage panel to house standard and optional
hardware for unit control and monitoring
• IntelliVAC™ control module for each vacuum contactor, mounted
in low voltage panel, with advanced features:
• Additional low voltage control panel accessories including:
– “NORMAL-OFF-TEST” circuit
– receptacle for external test power supply
– set of control circuit terminal blocks
• NEMA medium duty, dry type, three (3) winding reactor with 50,
65 and 80% taps. The 65% tap shall be used unless otherwise
specified.
Specifications
1591A
Specifications
Note: A 44-inch incomer is only available when a 3000A power bus is used.
Description of Features
• Main load break switch for switching primary power source
• Feeder load break switch for switching other loads
• Isolation between upper and lower power cells
• The operating handle is fully interlocked with the power cell door
• Provisions on the operating handle for key interlocking
• A polycarbonate viewing window in the power cell door to view the
position of the isolation handle
• Protective guard over the line terminals, inside the power cell, to
barrier off medium voltage when the power door is open
• Feeders for 2-high structures
• Bulletin 1592BF – fused load break switch, designed as a feeder
for 2-high structures
• Bulletin 1592F/M – fused load break switch, designed for feeder
and mains
• Bulletin 1594F/M – non-fused load break switch, designed for
feeder and mains
Specifications – 1592BF
Description of Features
• Fixed mounted vacuum contactor for Non-reversing Bulletin 1912B
• Fixed mounted vacuum contactors (FORWARD and REVERSE)
for reversing Bulletin 1906B
• For constant speed applications
• Available with or without static exciter
• Three-pole, gang-operated, non-load break isolating switch with an
external operating handle, fully interlocked with main contactor and
power cell doors
• A polycarbonate viewing window in the power cell door to view the
position of the isolating switch
• Three (3) R-rated current-limiting power fuses
• Three (3) current transformers
• Control power transformer with primary and secondary fuses
• Segregated low voltage panel to house standard and optional
hardware for unit control and monitoring
• IntelliVAC™ control module for each vacuum contactor, mounted
in low voltage panel, with advanced features:
• Additional low voltage control panel accessories including:
– control circuit fusing
– “NORMAL-OFF-TEST” circuit
– receptacle for external test power supply
– set of control circuit terminal blocks
• Synchronous control package:
– Field application and protection relay (SyncPro standard)
– Field application control pilot relays
– Field excitation switch (2-pole contactor standard, when optional
Exciter is not provided as part of the unit)
– Field discharge resistor bank
Specifications – 1906B
Specifications – 1912B
Description of Features
• Fixed mounted vacuum contactor for Non-reversing Bulletin 1912L
• Fixed mounted vacuum contactors (FORWARD and REVERSE)
for reversing Bulletin 1906L
• For constant speed applications
• Three-pole, gang-operated, non-load break isolating switch with an
external operating handle, fully interlocked with main contactor and
power cell doors
• A polycarbonate viewing window in the power cell door to view the
position of the isolating switch
• Three (3) R-rated current-limiting power fuses
• Three (3) current transformers
• Control power transformer with primary and secondary fuses
• Segregated low voltage panel to house standard and optional
hardware for unit control and monitoring
• IntelliVAC™ control module for each vacuum contactor, mounted
in low voltage panel, with advanced features:
• Additional low voltage control panel accessories including:
– control circuit fusing
– “NORMAL-OFF-TEST” circuit
– receptacle for external test power supply
– set of control circuit terminal blocks
• Provisions for optional factory or customer supplied field exciter
(contact Cambridge to ensure low voltage panel space is available
for customer supplied field exciter.)
Specifications – 1906L
Specifications – 1912L
Protection/Control
• Squirrel-cage winding protection
• Field winding application control
• Incomplete sequence
• Field voltage failure
• Auto load
• Stall protection
• Pull-out protection (power factor)
• Restart lockout
Display/Metering
• Detected fault conditions
• Slip frequency and starting time during start-up
• Power factor
• Enter/view setpoints through the DTAM
Description of Features
Specifications
Approximate Dimensions
(1901-AND, Open Type)
18.02 [458]
.38 [10]
16.75 [425]
20.00 18.95
[508] [481]
13.29
[338]
6.12
.63 [16] 13.75
13.75 [349]
[349] .36 [9] dia. [155]
(4) Mounting Holes
T C R ACC POS
4 5 6 DEC
PREV
N M . I
1 2 3 ± F( )
ESC
:
0 SHIFT ENTER
Option
Cards
RTD Scanner
Module
Core Balance
Current
Transformer
47
SUPPORT AND MAINTAIN YOUR INVESTMENT
You can maximize the life of your investment by aligning your Medium Voltage solutions with a strategic
approach to maintenance. By including the right combination of predictive, preventive and reactive methods
and Rockwell Automation® Services & Support, you can get the most out of your automation assets.
Start-U
Up & Commissioning
Decrease Installation and continuous support for your motor control applications
Time To Install
Training
Instructors and self paced materials for troubleshooting and programming
Ease
Troubleshooting Network Validation
DeviceNet™ configuration and diagnostics for networked products
Technical Support
For stand alone products and integrated systems
Reduce Costs
Allen-Bradley, ArmorStart, Compact I/O, DeviceLogix, DriveLogix, FORCE Technology, IntelliCENTER, PowerFlex, Rockwell Automation, SMC-Flex, SynchLink and XM
are trademarks of Rockwell Automation. Trademarks not belonging to Rockwell Automation are proerty of their respective companies.
Medium Voltage Products, 135 Dundas Street, Cambridge, ON, N1R 5X1 Canada, Tel: (1) 519.740.4100, Fax: (1) 519.623.8930, www.ab.com/mvb
Publication 1500-SG001A-EN-P - September 2006 Copyright © 2006 Rockwell Automation, Inc. All rights reserved. Printed in Canada