User Manual: HGM8100A Genset Controller (HGM8110A/HGM8120A)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 63

HGM8100A Genset Controller

(HGM8110A/HGM8120A)

(VFD DISPLAY)

USER MANUAL

SMARTGEN (ZHENGZHOU) TECHNOLOGY CO., LTD.


Chinese trademark

English trademark

SmartGen — make your generator smart


SmartGen Technology Co., Ltd.
No.28 Jinsuo Road
Zhengzhou
Henan Province
P. R. China
Tel: 0086-371-67988888/67981888
0086-371-67991553/67992951
0086-371-67981000(overseas)
Fax: 0086-371-67992952
Web: http://www.smartgen.com.cn
http://www.smartgen.cn
Email: [email protected]
All rights reserved. No part of this publication may be reproduced in any material form
(including photocopying or storing in any medium by electronic means or other) without
the written permission of the copyright holder.
Applications for the copyright holder’s written permission to reproduce any part of this
publication should be addressed to Smartgen Technology at the address above.
Any reference to trademarked product names used within this publication is owned by
their respective companies.
SmartGen Technology reserves the right to change the contents of this document without
prior notice.
HGM8110A/8120A Genset Controller
Software Version
Date Version Note
2013-01-29 1.0 Original release.
2013-04-12 1.1 Modify some details.
Modify case dimension; Modify the contents of “Oil Pressure
2013-06-17 1.2
Sensor”
Add “Loss of Speed Signal Shutdown” in output port
2013-11-20 1.3
settings.

2013-12-23 1.4 Add function: Long pressing “ ” button can reset trip
alarm.
Change the “Working Conditions” and “Storage Condition”
2014-10-23 1.5
temperature as (-40~+70)℃
Modify the picture of mask and the graph of controller
2016-09-28 1.6
dimension.

This manual is suitable for HGM8110A/HGM8120A controller only.


Clarification of notation used within this publication.
SIGN INSTRUCTION

Highlights an essential element of a procedure to ensure correctness.


NOTE
Indicates a procedure or practice, which, if not strictly observed, could
CAUTION! result in damage or destruction of equipment.

Indicates error operation may cause death, serious injury and


WARNING! significant property damage.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 3 of 63


HGM8110A/8120A Genset Controller

CONTENT
1 OVERVIEW................................................................................................................ 6

2 PERFORMANCE AND CHARACTERISTICS ........................................................... 7

3 SPECIFICATION ..................................................................................................... 10

4 OPERATION .............................................................................................................11

4.1 KEY FUNCTION .................................................................................. 11


4.2 INDICATOR LIGHT ...............................................................................12
4.3 LCD DISPLAY .....................................................................................13
4.3.1 MAIN DISPLAY ....................................................................................... 13
4.3.2 BASIC PARAMETER .............................................................................. 14
4.3.3 ADVANCED PARAMETERS SETTING .................................................. 16
4.4 AUTOMATIC OPERATION .....................................................................18
4.5 MANUAL OPERATION ..........................................................................20
4.6 GENSET CONTROLLER ATS CONTROL PROCEDURES ...........................21
4.7 VIEWING THE EVENT LOG ...................................................................23

5 PROTECTION ......................................................................................................... 24

5.1 WARNINGS ........................................................................................24


5.2 SHUTDOWN ALARM ............................................................................26
5.3 TRIP AND STOP ALARM .......................................................................28
5.4 TRIP ALARM .......................................................................................29
6 CONNECTING ......................................................................................................... 30

7 SCOPES AND DEFINITIONS OF CONFIGURABLE PARAMETERS .................... 33

7.1 CONTENTS AND SCOPES OF PARAMETERS .........................................33


7.2 ENABLE DEFINITION OF PROGRAMMABLE OUTPUT PORTS...................43
7.2.1 CUSTOM PERIOD OUTPUT .................................................................. 48
7.2.2 CUSTOM COMBINED OUTPUT ............................................................ 49
7.3 DEFINED CONTENTS OF CONFIGURABLE INPUT PORTS (ALL ACTIVE
WHEN CONNECT TO GRAND (B-)) ........................................................50
7.4 SELECTION OF SENSORS ...................................................................53
7.5 CONDITIONS OF CRANK DINSCONNECT SELECTION ............................54

8 PARAMETER EDITING ........................................................................................... 55

9 SENSORS SETTING ............................................................................................... 57

10 COMMISSIONING ................................................................................................... 58

11 TYPICAL WIRING DIAGRAMS ............................................................................... 59

12 INSTALLATION ....................................................................................................... 61

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 4 of 63


HGM8110A/8120A Genset Controller
12.1 BATTERY VOLTAGE INPUT...................................................................61
12.2 SPEED SENSOR INPUT .......................................................................61
12.3 OUTPUT AND EXPAND RELAYS ............................................................61
12.4 AC INPUT ...........................................................................................62
12.5 WITHSTAND VOLTAGE TEST ................................................................62

13 FACTORY DEFAULT VALUES................................................................................ 63

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 5 of 63


HGM8110A/8120A Genset Controller

1 OVERVIEW

HGM8110A/8120A genset controllers are especially designed for extremely high/low


temperature environment (-40~+70)°C. The controllers can operate reliability in extreme
temperature conditions with the help of VFD display and the components that resist
extreme temperature. All display information is Chinese (English is optional). Operation
information, status information and faults information are all displayed which make
commissioning convenience for factory personnel. Controller can be used under
complex electromagnetic interference environment with the strong ability of
anti-electromagnetic interference. Easy to maintain and upgrade due to the plug-in
terminal.
HGM8110A/8120A genset controllers integrate digitization, intelligentization and network
technology which are used for genset automation and monitor control system of single
unit to achieve automatic start/stop, data measure, alarm protection and “four remote”
(remote control, remote measuring, remote communication and remote regulating).
HGM8110A/8120A genset controllers adopt micro-processor technology with precision
parameters measuring, fixed value adjustment, time setting and set value adjusting and
etc..Majority parameters can be configured from front panel, and all parameters can be
configured by RS485 interface (or RS232) to adjust via PC. It can be widely used in all
types of automatic genset control system with compact structure, advanced circuits,
simple connections and high reliability.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 6 of 63


HGM8110A/8120A Genset Controller

2 PERFORMANCE AND CHARACTERISTICS

♦ HGM8100A series controller has two types:


HGM8110A: ASM (Automatic Start Module),used for single automation systems.
HGM8120A: AMF (Auto Mains Failure), updates based on HGM8110A, moreover, has
mains electric quantity monitoring and mains/generator automatic transfer control
function, especially for automatic system composed by generator and mains.
♦ With ARM-based 32-bit SCM, highly integrated hardware, new reliability level.
♦ Vacuum fluorescent display (VFD), selectable Chinese/English interface which can be
chosen at the site, making commissioning convenience for factory personnel;
♦ Widely temperature range: (-40~70) °C, can be used in extreme temperature
environment.
♦ Suitable for 3-phase 4-wire, 3-phase 3-wire, single phase 2-wire, and 2-phase 3-wire
systems with voltage 120/240V and frequency 50/60Hz;
♦ Collects and shows 3-phase voltage, current, power parameter and frequency of
generator or mains.
Mains
Line voltage (Uab, Ubc, and Uca) V (unit)
Phase voltage (Ua, Ub, and Uc) V (unit)
Frequency f Hz(unit)
Generator
Line voltage (Uab, Ubc, and Uca) V (unit)
Phase voltage (Ua, Ub, and Uc) V (unit)
Frequency f Hz(unit)
Load
3-phase Current Ia, Ib, Ic A (unit)
Active power (P) kW (unit)
Apparent power (S) kVA (unit)
Power factor (λ)
Accumulate total generator power (W) kWh(unit)

♦ For Mains, controller has over and under voltage, over and under frequency, loss of
phase and phase sequence wrong detection functions; For generator, controller has
over and under voltage, over and under frequency, loss of phase, phase sequence

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 7 of 63


HGM8110A/8120A Genset Controller
wrong, over and reverse power, over current detection functions;
♦ 3 fixed analog sensors (temperature, oil pressure and liquid level);
♦ 2 configurable sensors can be set as sensor of temperature, oil pressure or fuel level;
♦ Precision measure and display parameters about Engine,
Temp. (WT) °C/°F both be displayed
Oil pressure (OP) kPa/psi/bar all be displayed
Speed (RP)
Voltage of Battery (VB) V (unit)
Voltage of Charger (VD) V (unit)
Hour count (HC) can accumulate to max. 65535 hours.
Start times can accumulate to max. 65535 times.
♦ Protection: automatic start/stop of the gen-set, ATS(Auto Transfer Switch) control with
perfect fault indication and protection function;
Fault display items:
High temperature alarm
High temperature shutdown
Low oil pressure alarm
Low oil pressure shutdown
Over speed shutdown
Low fuel level warn
Battery voltage high warn
Battery voltage low warn
Over current shutdown
Fail to start
Fail to stop
Emergency stop alarm
Oil pressure sensor open circuit shutdown
Temperature sensor open circuit shutdown
♦ All output ports are relay-out;
♦ Parameter setting: parameters can be modified and stored in internal EEPROM
memory and cannot be lost even in case of power outage; most of them can be
adjusted using front panel of the controller and all of them can be modified using PC
via RS485/RS232 ports.
♦ More kinds of curves of temperature, oil pressure, fuel level can be used directly and
HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 8 of 63
HGM8110A/8120A Genset Controller
users can define the sensor curves by themselves;
♦ Multiple crank disconnect conditions (speed sensor, oil pressure, generator frequency)
are optional;
♦ Real time clock and run time accumulation function. 99 pieces of event logs can be
circularly stored and inquired on the spot; also can be print or be inquired via PC.
♦ Scheduled start & stop generator (can be set as start genset once a week/month).
♦ With maintenance function. Actions (warning, shutdown or trip and stop) can be set
when maintenance time out;
♦ Can be used on pumping units and as an indicating instrument (indicate and alarm are
enable only, relay is inhibited );
♦ Accumulative total electric energy. Users can reset it and re-accumulative the value
which make convenience to users to count the total value as their wish.
♦ Widely Power supply range: DC(8~35)V, suitable to12/24V start battery voltage
environment.
♦ With international standard MODBUS communication protocol, better error checking
capability, and with RS232 and RS485(coupling isolation) communication interface,
can realized functions of remote control, remote measuring, remote communication
and remote regulating.
♦ Waterproof security level IP55 due to rubber seal installed between the controller
enclosure and panel fascia;
♦ Metal fixing clips enable perfect in high temperature environment;
♦ Modular design, pluggable connection terminals and embedded installation way;
compact structure with easy mounting.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 9 of 63


HGM8110A/8120A Genset Controller

3 SPECIFICATION

ITEM CONTENT
Operating voltage DC8. 0V to 35. 0V, Continuous Power Supply
Power consumption <6W(Standby mode: ≤3W)
Alternator Input Range
3-Phase 4 Wire AC20V - AC360V (ph-N)
3-Phase 3 Wire AC30V - AC600V (ph- ph)
Single-Phase 2 Wire AC20V - AC360V (ph-N)
2-Phase 3 Wire AC20V - AC360V (ph-N)
Alternator Frequency 50Hz / 60Hz
Speed sensor voltage 1.0V to 24.0V (RMS)
Speed sensor Frequency 10,000 Hz (max)
Start Relay Output 16 A DC28V at DC supply output.
Fuel Relay Output 16 A DC28V at supply output.
Aux. Output 1 16 A DC28V at supply output.
Aux. Output 2 16 A DC28V at supply output.
Aux. Output 3 16 A DC28V at supply output.
Aux. Output 4 16 A AC250V at DC supply output.
Gen Close Relay 16A AC250V passive
Aux. Output 5
Mains Close Relay 16A AC250V passive
Aux. Output 6
Overall Dimensions 243.7mm x 176.2mm x 51.2mm
Panel Cutout 214mm x 160mm
C. T. Secondary 5A (rated)
Temperature: (-40~+70)°C
Working Conditions
Humidity: (20~93)%RH
Storage Condition Temperature: (-40~+70)°C
Protective Level IP55 Gasket
Apply AC2.2kV voltage between high voltage terminal and
Insulation Intensity low voltage terminal;
The leakage current is not more than 3mA within 1min.
Weight 0.80kg

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 10 of 63


HGM8110A/8120A Genset Controller

4 OPERATION

4.1 KEY FUNCTION


Symbol Key Type Description
Stop running generator in Auto/Manual mode; Lamp test
(press at least 3 seconds); Reset alarm in stop mode;
Stop/ Reset
During stopping process, press this button again to stop
generator immediately.

Start Start genset in Manual/Test mode.

Pressing this key will set the module into manual mode.
Manual mode /
In setting parameter status, press this key will decrease
Config. ‘-’
setting value.
Pressing this key will set the module into test mode (only
Test mode/
for HGM8120A). In setting parameter status, press this
Config. ‘+’
key will increase setting value.
Pressing this key will set the module into auto mode. In
Auto mode/Confirm setting parameter status, press this key will right shift
cursor or confirm setting value.
Pressing this key will view shutdown history records.
Again pressing this key will exit.
Event log
When there is trip alarm occurs, pressing and holding
this button for more than 3 seconds can reset the alarm.
Screen scroll in parameters interface or event log
Page Down
interface;

NOTE: In manual mode, pressing and simultaneously will force


generator to crank. Successful start will not be judged according to crank disconnect
conditions, operator will have to crank the starter motor manually; when operator decides
that the engine has fired, he/she should release the button and start relay will be
deactivated, safety on delay will start.

NOTE: Pressing and holding for more than 3 seconds enters basic parameter
configuration menu;

NOTE: Pressing and enters advanced parameter configuration menu;

WARNING: Default password is 00318, user can change it in case of others change
the advanced parameters setting. Please clearly remember the password after changing. If
you forget it, please contact Smartgen services.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 11 of 63


HGM8110A/8120A Genset Controller
4.2 INDICATOR LIGHT
Alarm indicator:

Alarm Type Alarm Indicator


Warning Slow flashing (1 time per sec)
Trip Alarm Slow flashing (1 time per sec)
Shutdown Alarm Fast flashing (5 times per sec)
Trip and Stop Alarm Fast flashing (5 times per sec)
Genenerator normal light:It is light on when generator is normal; flashing when
generator state is abnormal; off when there is no generator power.
Mains normal light:It is light on when mains is normal; flashing when mains state is
abnormal; off when there is no mains power.
Generator close light: It is light on when generator close; off when generator open.
Mains close light: It is light on when mains close; off when mains open. (HGM8120A)

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 12 of 63


HGM8110A/8120A Genset Controller
4.3 LCD DISPLAY
4.3.1 MAIN DISPLAY

Main screen is used to display real time data of all parameters, use to scroll the
screen.
★Status, including as below,
Status of genset, mains (HGM8120A), and ATS
★Mains, including as below
Phase voltage, Line voltage, frequency

NOTE: HGM8110A has no mains status screen.


★Gen, including as below,
Phase voltage, Line voltage, frequency
★Load, including as below,
Current, each phase and total active power (positive and negative), total apparent power,
average power factor (positive and negative), accumulated energy (kWh, kVarh, kVAh).

Note: When mains close indicator lights, count active and inactive power, apparent
power, power factor, but accumulate electric energy. Counting the generator active and
reactive power, apparent power, power factor, and accumulate electric energy under other
conditions.

NOTE: Power factor shows as following,

Remark:
P stands for active power
Q stands for inactive power

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 13 of 63


HGM8110A/8120A Genset Controller
Power Active
Conditions Inactive power Remark
factor power
Load is inductive resistance.
COS>0L P>0,Q>0 Input Input

Load is capacitance resistance.


COS>0C P>0,Q<0 Input Output
Load equal to one under excitation
COS<0L P<0,Q>0 Output Input
generator
Load equal to one over excitation
COS<0C P<0,Q<0 Output Output
generator.

Note:
1. Input active power, generator or mains supply electricity to load.
2. Output active power, load supply electricity to generator or mains.
3. Input reactive power, generator or mains send reactive power to load.
4. Output reactive power, load send reactive power to generator or mains.
★Engine, including as below,
Speed, engine temperature, engine oil pressure, liquid (fuel) level, flexible sensor 1, flexible
sensor 2, battery voltage, charger voltage, accumulated run time, accumulated start times.
★Alarm:
Display all kinds of alarm information, such as Gen Overvolts, Gen Undervolts, Gen Over
Frequency, Gen Under Frequency and so on.
★Event log
Records all start/stop events (shutdown alarm, trip and stop alarm, manual /auto start or
stop) and the real time when alarm occurs.
Example:

Gen Load
UL-L 0 0 0V Current 0.0 0.0 0.0A
UL-N 0 0 0V Power 0.0kW 0.0 kVA
F = 0.0Hz 0rpm cosΦ = 0.00 0.0 kVar
Stop Mode Gen Overvolts Warn

4.3.2 BASIC PARAMETER


Basic parameters setting Including as following,
★ Mains Rated Voltage (HGM8120A)
★ Mains Rated Frequency (HGM8120A)
★ Crank Disconnect

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 14 of 63


HGM8110A/8120A Genset Controller
★ Flywheel Teeth
★ Gen Rated Speed
★ Gen Rated Voltage
★ Gen Rated Frequency
★ CT Ratio
★ Rated Current
★ Rated Power
★ Battery Voltage
★ Date and Time
★ Start Delay
★ Stop Delay
★ Pre-heat Delay
★ Cranking Time
★ Crank Rest Time
★ Safety On Delay
★ Start Idle Time
★ Warming Up Time
★ Cooling Time
★ Stop Idle Time
★ ETS Solenoid Hold
★ Fail to Stop Delay
★ After Stop Time
Example:
Basic Parameter Settting
Form1: are used for changing the setting
>Return
> Mains Rated Frequency contents. to enter settings (form2), to exit
> Crank Disconnect
settings menu.

Crank Disconnect
Form 2:Press to enter settings (form 3); press
2:Speed sensor + Gen freq.
or or to return to previous menu. (Form

1).

Crank Disconnect
Form 3: are used for changing the setting
2:Speed sensor + Gen freq.
contents. Confirm setting (form 2), exit

setting (form 2).

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 15 of 63


HGM8110A/8120A Genset Controller
4.3.3 ADVANCED PARAMETERS SETTING
Advanced parameter setting Including as following,
★ Mains settings
★ Timer settings
★ Engine settings
★ Generator settings
★ Load settings
★ Switch settings
★ Analog sensor settings
★ Input port settings
★ Output port settings
★ Module settings
★ Scheduling and maintenance settings
Example,
Advanced Parameters Setting
Form1: are used for changing the setting
>Mains
>Timers contents. to enter settings (form2), to exit
>Engine
>Generstor settings menu.

Engine Setting
Form 2: are used for changing the setting
>Return
>AC Systerm contents (form 3). Select “Return” and press to
>Poles
>Rated Voltage return to previous menu (form 1). Press also can

return to previous menu (form 1)

Generator Setting
Form 3: are used for changing the setting
>Gen Undervolt Shutdown
> Gen Overfreq. Shutdown contents. Confirm setting (form 4), exit
> Gen Underfreq. Shutdown
> Gen Overvolt Warn setting (form 1).

Overvolt Warn
Form 4: Press to enter settings (form 5); Press
Sel: Disable
Set Value: 00110% or or to return to previous menu. (Form
Return Value: 00108%
Delay: 00005 3).

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 16 of 63


HGM8110A/8120A Genset Controller
Overvolt Warn
Form 5: are used for changing the setting
Sel: Disable
Set Value: 00110% contents ( form 6). Confirm setting (form 7),
Return Value: 00108%
return to previous menu (form 4)
Delay: 00005

Overvolt Warn
Form 6: are used for changing the setting
Sel: Disable
Set Value: 00110% contents ( form 5). Confirm setting (form 7),
Return Value: 00108%
return to previous menu (form 4)
Delay: 00005

Overvolt Warn
Form 7: are used for changing the setting
Sel: Enable
Set Value: 00000 contents (form 5). Confirm setting, return to
Return Value: 00108%
Delay: 00005 previous menu (form 4).

Overvolt Warn
Form 8: are used for changing the setting
Sel: Enable
Set Value: 0000 contents. Confirm setting (form 4), return
Return Value: 00108%
Delay: 00005 to previous menu (form 4).

NOTE: Pressing and holding for a long time can exit setting directly during setting.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 17 of 63


HGM8110A/8120A Genset Controller
4.4 AUTOMATIC OPERATION

Press , its indicator lights, and controller enters Auto mode.


Starting Sequence,
1. HGM8120A: When Mains is abnormal (over and under voltage, over and under
frequency), it enters into mains “abnormal delay” and VFD display count down time.
When mains abnormal delay is over, it enters into “start delay”;
2. HGM8110A: Generator enters into “start delay” as soon as “Remote Start” is active.
3. “Start Delay” timer is shown on VFD display.
4. When start delay is over, preheat relay outputs (if this be configured), “preheat delay
XX s” is shown at the bottom line of VFD.
5. When preheat delay is over, fuel relay outputs 1s and then start relay output; if engine
crank fails during “cranking time”, the fuel relay and start relay deactivated and enter
into “crank rest time” to wait for next crank.
6. If engine crank fails within setting times, the controller sends Fail to Start signal and Fail
To Start message appears on VFD alarm page.
7. In case of successful crank attempt, “safety on” timer starts. During this period, low oil
pressure, high water temperature, under speed, charge failure alarms and Aux. input (if
configured) are disabled. As soon as this delay is over, “start idle delay” is initiated (if
configured).
8. During “start idle delay”, under speed, under frequency, under voltage alarms are
inhibited. When this delay is over, “warming up delay” starts (if configured).
9. When “warming up delay” is over, if generator state is normal, its indicator will be
illuminated. If voltage and frequency has reached on-load requirements, the closing
relay will be energised, generator will accept load, generator power indicator will turn
on, and generator will enter Normal Running state; if voltage and frequency are
abnormal, the controller will initiate alarm (alarm type will be displayed on VFD display).

NOTE: In case of “Remote Start (off Load)”, the procedure is the same, except for step
NO. 9: the closing relay will NOT be energised, generator will NOT accept load.
Stopping Sequence
1) HGM8120A:If mains turns normal during genset is running, enter into mains voltage
“normal delay” and its indicator illuminates after mains is confirmed normally, “Start
delay” is beginning.
2) HGM8110A:Genset enters into “stop delay” as soon as “Remote Start” input is

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 18 of 63


HGM8110A/8120A Genset Controller
inactive.
3) HGM8120A: After stop delay ends, enter “cooling time”, and generator close relay is
disconnected, after “switch transfer delay”, mains close relay output, mains is on-load,
generator power supply indicator is extinguishing, and mains power supply indicator is
illuminates.
4) Idle relay is output when the controller enters “idle stop delay”.
5) Enter into “ETS delay” and ETS relay is active. Fuel relay output is disconnected.
6) Genset can automatically judge if it is steady when the controller enters “Genset after
stop time”.
7) After genset stops steadily, enter generator standby status; if genset does not stop,
then controller will alarm (VFD screen display stop failure warn).
8) Enter “generator at rest” as soon as “after stop time” is over.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 19 of 63


HGM8110A/8120A Genset Controller
4.5 MANUAL OPERATION

1) HGM8120A: “Manual Mode” is active when press key and its indicator illuminates.
Press key, then controller enters “Test Mode” and indicator illuminates. Under the
both modes, press key to start genset, and it automatically detects if it starts
successfully and accelerate high speed running. With high temperature, low oil
pressure, over speed and abnormal voltage during diesel genset running, controller
can protect genset to stop effectively and quickly (please refer to No.4~9 of Starting
Sequence for more details). Under “Manual Mode ”, genset on-load is decided by
whether mains are normal or not. If mains are normal, loading switch isn’t transferred;
while mains are abnormal, loading switch is transferred into generator’s side. Under
“Test Mode “, after genset runs well in high speed, no matter mains is normal or
not, loading switch must be transferred into Generator’s side.
2) HGM8110A: “Manual Mode” is active when press key, and its indicator is
illuminates. Then press key to start generator, it automatically detects if it is started
successfully and genset automatically accelerates high speed running. With high
temperature, low oil pressure, over speed and voltage abnormal during diesel genset
running, controller can protect genset to stop effectively and quickly (please refer to
No.4~9 of Starting Sequence for more details). After genset runs well in high speed,
controller will send signal of Generator close.
3) Manual stop: press key can shutdown the running genset (please refer to No.3~7
of Stopping Sequence for more details).

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 20 of 63


HGM8110A/8120A Genset Controller
4.6 GENSET CONTROLLER ATS CONTROL PROCEDURES
1. HGM8120A ATS CONTROL PROCEDURES
1) If input port is configured as Closed Auxiliary (Mains Closed Auxiliary/ Gen
Closed Auxiliary)
A. If “Open breaker detect” is “SELECT Enable”
When transferring load from mains to generator, controller begins detecting “fail to transfer”,
then the open delay and transfer rest delay will begin. When detecting time out, if switch
open failed, the generator will not switch on, otherwise, generator switch on. Detecting
transfer failure while generator switch on. When detecting time out, if switch on fail, it is
need to wait for generator to switch on. If transfer failed and warning “SELECT Enable”,
there is alarming signal whatever switch on or off failure.
The way to transfer from generator load to mains load is as same as above.
B. If “Open breaker detect” is “SELECT Disable”
Mains load is transferred into generator load, after the delay of switch off and transfer
interval, generator switch on. Detecting transfer fail while generator switch on. After
detecting time out, if switch on fail, then wait for generator switch on. If transfer fail and
warning “SELECT Enable”, there is alarming signal.
2) If input port is not configured as Close Mains Auxiliary
Mains load is transferred into generator load, after switch off and transfer interval delay,
generator switch on.
The way to transfer generator load to mains load is as same as above.
2. HGM8110A ATS CONTROL PROCEDURES
1) If input port is configured as Gen Closed Auxiliary
A. If “Open breaker detect” is “SELECT Enable”
Generator load is transferred into generator un-load, after the delay of switch off, detecting
transfer failure while switch off output. When detecting time out, if switch off failed, it will
wait for switch off. Otherwise, switch off is completed.
Generator unload is transferred into generator load, after the delay of switch on, detecting
transfer failure while switch on outputting. When detecting time out, if switch on failed, it will
wait for switch on. Otherwise, switch on is completed.
If transfer failed and warning “SELECT Enable”, there is alarming signal whatever switch
on or off failure.
B. If “Open breaker detect” is “SELECT Disable”

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 21 of 63


HGM8110A/8120A Genset Controller
Generator load is transferred into generator unload, after the delay of switch off, switch off
is completed.
Generator unload is transferred into generator load, after the delay of switch on, detecting
transfer failure while switch on outputting. When detecting time out, if switch on failed, to
wait for switch on. Otherwise, switch on is completed.
If transfer failure warning is “SELECT Enable”, there is warning signal that “switch on fail”.
2) If input port is not configured as Gen Closed Auxiliary
Generator un-load is transferred into generator load, close generator output.
Generator load is transferred into generator un-load, open generator output.
NOTE:
When using ATS of no interposition, switch off detecting should “SELECT Disable”;
When using ATS of having interposition, switch off “SELECT Disable” or “SELECT Enable”
both are OK. If choose “SELECT Enable”, switch off output should be configured;
When using AC contactor, switch off “SELECT Enable” is recommended.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 22 of 63


HGM8110A/8120A Genset Controller
4.7 VIEWING THE EVENT LOG

In the control panel, press key to view previous running records of the controller,

including all start/stop records (shutdown, trip and stop, manual/auto start/stop) and

corresponding time. Press key to view records backward. Again press key to

return real time display status of the controller. HGM8100A controller can save recent 99

pieces event log records.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 23 of 63


HGM8110A/8120A Genset Controller

5 PROTECTION

5.1 WARNINGS
When controllers detects the warning signal, alarm only and not stop the genset, besides,
the VFD displays the warning information.
Warnings as following,
No. Type Description
When controller detects the speed is higher than the set
1 Over Speed Warn
value, it will send warn signal.
When controller detects the speed is lower than the set
2 Under Speed Warn
value, it will send warn signal.
Loss of Speed When controller detects the speed is 0 and the action
3
Signal Warn select “Warn”, it will send warn signal.
Over Frequency When controller detects the frequency is higher than the
4 set value, it will send warn signal.
Warn
Under Frequency When controller detects the frequency is lower than the
5
Warn set value, it will send warn signal.
When controller detects the voltage is higher than the
6 Over Voltage Wan
set value, it will send warn signal.
When controller detects the voltage is lower than the set
7 Under Voltage Warn
value, it will send warn signal.
When controller detects the current is higher than the
8 Over Current Warn
set value, it will send warn signal.
9 Fail to Stop When generator not stops after the “stop delay” is over.
When controller detects the charger voltage is lower
10 Charge Alt Fail
than the set value, it will send warn signal.
Battery Over When controller detects the battery voltage is higher
11
Voltage than the set value, it will send warn signal.
Battery Under When controller detects the battery voltage is lower than
12
Voltage the set value, it will send warn signal.
When count down time is 0 and the action select “Warn”,
13 Maintenance Due
it will send warn signal.
When controller detects the reverse power value (power
14 Reverse Power is negative) is lower than the set value, it will send warn
signal.
When controller detects the reverse power value (power
15 Over Power
is positive) is higher than the set value, it will send warn

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 24 of 63


HGM8110A/8120A Genset Controller
No. Type Description
signal.
When controller detects the generator loss phase, it will
16 Gen Loss of Phase
send warn signal.
Gen Phase When controller detects the reverse phase, it will send
17
Sequence Wrong warn signal.
When controller detects the switch on and off fail, and
18 Switch Fail Warn
the action select enable, it will send warn signal.
When controller detects the sensor is open circuit, and
19 Temp. Sensor Open
the action select “warn”, it will send warn signal.
When controller detects the temperature is higher than
20 High Temp. Warn
the set value, it will send warn signal.
When controller detects the temperature is lower than
21 Low Temp. Warn
the set value, it will send warn signal.
Pressure Sensor When controller detects the sensor is open circuit, and
22
Open the action select “warn”, it will send warn signal.
When controller detects the oil pressure is lower than
23 Low OP Warn
the set value, it will send warn signal.
When controller detects the sensor is open circuit, and
24 Level Sensor Open
the action select “warn”, it will send warn signal.
When controller detects the oil lever is lower than the set
25 Low Level Warn
value, it will send warn signal.
Flexible Sensor 1 When controller detects the sensor is open circuit, and
26
Open the action select “warn”, it will send warn signal.
Flexible Sensor 1 When controller detects the sensor value is higher than
27
High the max. set value, it will send warn signal.
Flexible Sensor 1 When controller detects the sensor value is lower than
28
Low the min. set value, it will send warn signal.
Flexible Sensor 2 When controller detects the sensor is open circuit, and
29
Open the action select “warn”, it will send warn signal.
Flexible Sensor 2 When controller detects the sensor value is higher than
30
High the max. set value, it will send warn signal.
Flexible Sensor 2 When controller detects the sensor value is lower than
31
Low the min. set value, it will send warn signal.
When digit input port is set as warning and active,
32 Digital Input Warn
controller sends corresponding warning signal.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 25 of 63


HGM8110A/8120A Genset Controller
5.2 SHUTDOWN ALARM
When controller detects shutdown alarm, it will send signal to stop the generator.
Shutdown alarms as following,
No. Type Description
When controller detects emergency stop signal, it will
1 Emergency Stop
send stop signal.
When controller detects the speed value is higher than
2 Over Speed
the set value, it will send stop signal.
When controller detects the speed value is lower than
3 Under Speed
the set value, it will send stop signal.
Loss Of Speed When controller detects speed value equals to 0, and
4
Signal the action select “Shutdown”, it will send stop signal
When controller detects the frequency value is higher
5 Over Frequency
than the set value, it will send stop signal.
When controller detects the frequency value is lower
6 Under Frequency
than the set value, it will send stop signal.
When controller detects the voltage value is higher than
7 Over Voltage
the set value, it will send stop signal.
When controller detects the voltage value is lower than
8 Under Voltage
the set value, it will send stop signal.
If genset start failure within setting of start times,
9 Fail To Start
controller will send stop signal.
When controller detects the current value is higher than
10 Over Current
the set value, it will send stop signal.
When count down time is 0 and the action select
11 Maintenance Due
“Shutdown”, it will send stop signal.
When controller detects reverse power value (power is
Reverse Power
12 negative) is lower than the set value, and the reverse
Shutdown
power action select “shutdown”, it will send stop signal.
When controller detects reverse power value (power is
Over Power
13 positive) is higher than the set value, and the reverse
Shutdown
power action select “shutdown”, it will send stop signal.
When controller detects sensor is open circuit, and the
14 Temp. Sensor Open
action select “shutdown”, it will send stop signal.
High Temp. When controller detects temperature is higher than the
15
Shutdown set value, it will send stop signal.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 26 of 63


HGM8110A/8120A Genset Controller
No. Type Description
Pressure Sensor When controller detects sensor is open circuit, and the
16
Open action select “shutdown”, it will send stop signal.
When controller detects oil pressure is lower than the
17 Low OP Shutdown
set value, it will send stop signal.
Level Sensor When controller detects sensor is open circuit, and the
18
Open action select “shutdown”, it will send stop signal.
Flexible Sensor 1 When controller detects sensor is open circuit, and the
19
Open action select “shutdown”, it will send stop signal.
Flexible Sensor 1 When controller detects the sensor value is higher than
20
High the max. set value, it will send stop signal.
Flexible Sensor 1 When controller detects the sensor value is lower than
21
Low the min. set value, it will send stop signal.
Flexible Sensor 2 When controller detects sensor is open circuit, and the
22
Open action select “shutdown”, it will send stop signal.
Flexible Sensor 2 When controller detects the sensor value is higher than
23
High the max. set value, it will send stop signal.
Flexible Sensor 2 When controller detects the sensor value is lower than
24
Low the min. set value, it will send stop signal.
When digital input port is set as shutdown, and the
25 Digital Input Port
action is active, it will send stop signal.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 27 of 63


HGM8110A/8120A Genset Controller
5.3 TRIP AND STOP ALARM
When controller detects trip and stop alarm signal, it will shutdown generator quickly and
stop after high speed cooling.
Trip and stop alarm as following,
No. Type Description
When controller detects the value is higher than the set
1 Over Current value, and the action select “trip and stop”, it will send
trip and stop signal.
When count down time is 0 and the action select “trip
2 Maintenance Due
and stop”, it will send a trip and stop signal.
When controller detects reverse power value (power is
3 Reverse Power negative) is lower than the set value, and the action
select “trip and stop”, it will send a trip and stop signal.
When controller detects the over power value (power is
4 Over Power positive) is higher than the set value, and the action
select “trip and stop”, it will send a trip and stop signal.
When digital input port is set as “trip and stop”, and the
5 Digital Input Ports
action is active, it will send a trip and stop signal.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 28 of 63


HGM8110A/8120A Genset Controller
5.4 TRIP ALARM
When controller detects trip alarm, it will break close generator signal quickly, but genset
not stop.
Trip alarm as following,
No. Type Description
When controller detects the value is higher than the set
1 Over Current
value, and the action select “trip”, it will send trip signal.
When controller detects reverse power value (power is
2 Reverse Power negative) is lower than the set value, and the action
select “trip”, it will send a trip signal.
When controller detects the over power value (power is
3 Over Power positive) is higher than the set value, and the action
select “trip”, it will send a trip signal.
When digital input port is set as “trip”, and the action is
4 Digital Input Ports
active, it will send a trip signal.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 29 of 63


HGM8110A/8120A Genset Controller

6 CONNECTING

Compared with HGM8120A, HGM8110A has no 31~34 terminals. The back panel of
HGM8110A and HGM8120A controller is shown as follows:

Cable Size
No. Function Remarks
(mm2)
Connected with negative of starter
1 DC input B- 2.5
battery.
Connected with positive of starter
2 DC input B+ 2.5
battery. Max. 20A fuse is recommended.
Connected with DC power supply via
emergency stop button. Also supply
3 Emergency stop 2.5
power to fuel relay and start relay. Max.
30A fuse is recommended.
2.5 DC power is supplied by 3 terminal,
4 Fuel relay output
rated 16A
2.5 DC power is supplied by 3 terminal,
5 Start relay output
rated 16A
6 Aux. Output 1 2.5 B+ output,rated 16A
7 Aux. Output 2 2.5 B+ output,rated 16A Details
2.5 B+ output,rated 16A see form
8 Aux. Output 3
2
1.0 Connected with charger starter’s D+
9 Charger(D+) terminal. Ground connected is not
allowed.
10 Aux. Input 1 1.0 Ground connected

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 30 of 63


HGM8110A/8120A Genset Controller
Cable Size
No. Function Remarks
(mm2)
is active (B-)
1.0 Ground connected Details see form 3
11 Aux. Input 2
is active (B-)
1.0 Ground connected
12 Aux. Input 3
is active (B-)
1.0 Ground connected
13 Aux. Input 4
is active (B-)
1.0 Ground connected
14 Aux. Input 5
is active (B-)
1.0 Ground connected
15 Aux. Input 6
is active (B-)
1.0 Common grounded; Connected with
16 Magnetic Pickup
enclosure or negative of starter battery.
17 Magnetic Pickup + 1.0
Connected to speed sensor
18 Magnetic Pickup - 1.0
Oil pressure sensor input, can be
Oil Pressure sensor 2 connected to an external resistance
19 1.0
input sensor. (Also can be set as Temperature
sensor or Fuel level sensor).
20
Volts free contactors, rated 16A.
21 Aux. Output 4 2.5
Details see form 2
22
23 RS485 0.5 Opto-isolation; (Impedance-120Ω
24 RS485+ 0.5 shielding wire is recommended, its
0.5 single-end earthed. Hang up the 26
25 RS485- terminal.)
If needed, please make this terminal
26 Matched Resistance and 25 terminal short circuit. If not, hang
it in the air.
27 Aux. Output 6 Control mains to take load. Volts free
28 Mains Close Relay 2.5 contactor. Rated 16A. (Also can be set
48 Output as other function; Details see form 2).

29 Control generator to take load. Normally


Aux. Output 5
open volts free contactor. Rated 16A.
Gen Close Relay 2.5
30 (Also can be set as other function;
Output
Details see form 2)
Mains A-phase Connected to A-phase of mains (2A fuse
31 1.0
voltage sensing input is recommended) (HGM8110A without)
Mains B-phase Connected to B-phase of mains (2A fuse
32 1.0
voltage sensing input is recommended) (HGM8110A without)
Connected to C-phase of mains (2A
Mains C-phase
33 1.0 fuse is recommended) (HGM8110A
voltage sensing input
without)

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 31 of 63


HGM8110A/8120A Genset Controller
Cable Size
No. Function Remarks
(mm2)
Connected to N-wire of mains
34 Mains N-wire input 1.0
(HGM8110A without)
Genset A-phase Connected to A-phase of gen-set (2A
35 1.0
voltage sensing input fuse is recommended)
Genset B-phase Connected to B-phase of gen-set (2A
36 1.0
voltage sensing input fuse is recommended)
Genset C-phase Connected to C-phase of gen-set (2A
37 1.0
voltage sensing input fuse is recommended)
38 Genset N-wire input 1.0 Connected to N-wire of gen-set
CT A-phase sensing Outside connected to secondary coil of
39 2.5
input current transformer(rated 5A)
CT B-phase sensing Outside connected to secondary coil of
40 2.5
input current transformer(rated 5A)
CT C-phase sensing Outside connected to secondary coil of
41 2.5
input current transformer(rated 5A)
Common grounded; Connected with
42 CT COM 2.5
negative of starter battery.
Temperature sensor input, can be
connected to an external resistance
43 Temperature sensor 2 1.0
sensor. (Also can be set as Oil Pressure
sensor or Fuel level sensor).
Oil pressure sensor input, can be
44 Oil pressure sensor 1 1.0 connected to an external resistance
sensor.
Temperature sensor 1 input, can be
45 Temperature sensor 1 1.0 connected to an external resistance
sensor.
Fuel level sensor input, can be
46 Fuel level sensor 1.0 connected to an external resistance
sensor.
Public terminal of sensor, (B-) has
47 Sensor COM /
already connected.
Communication with the computer
RS232 connectors 0.5
(2-RXD、3-TXD、5-GND)
Note: Prohibit removing starting battery when the engine is running, or it will damage the
control system because of over DC input voltage.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 32 of 63


HGM8110A/8120A Genset Controller

7 SCOPES AND DEFINITIONS OF CONFIGURABLE

PARAMETERS

HGM8110A/8120A generator controllers can set the following parameters, (HGM8110 has
no mains items)

7.1 CONTENTS AND SCOPES OF PARAMETERS


FORM 1
No. Items Parameters Defaults Description
Mains Setting
0: 3P4W; 1: 3P3W;
1 AC System (0~3) 0
2: 2P3W; 3: 1P2W.
Standard for checking mains
Rated over/under voltage. (It is primary
2 (30~30000)V 230
Voltage voltage when using voltage
transformer.)
Rated Standard for checking mains
3 (10.0~75.0) Hz 50.0
Frequency over/under frequency.
The delay from mains abnormal to
4 Normal Time (0~3600)s 10
normal.
Abnormal The delay from mains normal to
5 (0~3600)s 5
Time abnormal.
Volt.
6 (0~1) 0 0: Disable ; 1: Enable
Trans.(PT)
Setting value is mains rated voltage’s
7 Over Voltage (0~1000)% 120% percentage, and return value and
delay value can be set.
Setting value is mains rated voltage’s
Under
8 (0~1000)% 80% percentage, and return value and
Voltage
delay value can be set.
Setting value is mains rated
Over
9 (0~1000)% Disable frequency’s percentage, return value
Frequency
and delay value can be set.
Setting value is mains rated
Under
10 (0~1000)% Disable frequency’s percentage. Return value
Frequency
and delay value can be set.
Loss of
11 (0~1) 1
Phase
0: Disable; 1: Enable
Reverse
12 (0~1) 1
Phase

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 33 of 63


HGM8110A/8120A Genset Controller

No. Items Parameters Defaults Description

Timer Setting
Time from mains abnormal or remote
1 Start Delay (0~3600)s 1
start signal is active to start genset.
Time from mains normal or remote
2 Stop Delay (0~3600)s 1 start signal is deactivated to genset
stop.
Preheat Time of pre-powering heat plug
3 (0~3600)s 0
Delay before starter is powered up.
Cranking
4 (3~60)s 8 Time of starter power up
Time
Crank Rest The waiting time before second
5 (3~60)s 10
Time power up when engine start fail.
Alarms for low oil pressure, high
Safety On temperature, under speed, under
6 (0~3600)s 10
Delay frequency/voltage, charge fail are
inactive.
Start Idle Idle running time of genset when
7 (0~3600)s 0
Time starting.
Warming Up Warming time between genset switch
8 (0~3600)s 10
Time on and high speed running.
Radiating time before genset stop,
9 Cooling Time (0~3600)s 10
after it unloads.
Stop Idle
10 (0~3600)s 0 Idle running time when genset stop.
Time
ETS Solenoid Stop electromagnet’s power on time
11 (0~3600)s 20
Hold when genset is stopping.
Time between ending of genset idle
delay and stopped when “ETS time”
Fail to Stop is set as 0;
12 (0~3600)s 0
Delay Time between ending of ETS hold
delay and stopped when “ETS Hold
output time” is not 0.
After Stop Time between genset stopped and
13 (0~3600)s 0
Time standby
Engine Setting
1 Engine Type Fixed value: 0 0 Default: Conventional genset
Tooth number of the engine, for
judging of starter separation
Flywheel
2 (10~300) 118 conditions and inspecting of engine
Teeth
speed. See the installation
instructions.
HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 34 of 63
HGM8110A/8120A Genset Controller

No. Items Parameters Defaults Description

Offer standard to judge


3 Rated Speed (0~6000)r/min 1500
over/under/loading speed.
Setting value is percentage of rated
Speed on speed. Controller detects when it is
4 (0~100)% 90%
Load ready to load. It won’t switch on when
speed is under loading speed.
Loss of Time from detecting speed is 0 to
5 (0~3600)s 5
Speed Signal confirm the action.
Loss of
6 (0~1) 0 0:Warn; 1:Shutdown
Speed Action
Setting value is percentage of rated
Over Speed
7 (0~200)% 114% speed and delay value also can be
Shutdown
set.
Setting value is percentage of rated
Under Speed
8 (0~200)% 80% speed and delay value also can be
Shutdown
set.
Setting value is percentage of rated
Over Speed
9 (0~200)% 110% speed. Delay value and return value
Warn
also can be set.
Setting value is percentage of rated
Under Speed
10 (0~200)% 86% speed. Delay value and return value
Warn
also can be set.
Battery Rated Standard for detecting over/under
11 (0~60.0)V 24.0
Voltage voltage of battery.
Setting value is percentage of rated
Battery Over
12 (0~200)% 120% voltage of battery. Delay value &
Volts
return value also can be set.
Setting value is percentage of rated
Battery Under
13 (0~200)% 85% voltage of battery. Delay value &
Volts
return value also can be set.
In normal running, when charger
Charge Alt
14 (0~60.0)V 8.0 D+(WL) voltage under this value,
Fail
charge failure alarms.
Max. Crank times of crank attempts.
15 Start Attempts (1~10) times 3 When reach this number, controller
will send start failure signal.
See form 5
There are 3 conditions of
Crank
16 (0~6) 2 disconnecting starter with engine.
Disconnect
Each condition can be used alone
and simultaneously to separating the

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 35 of 63


HGM8110A/8120A Genset Controller

No. Items Parameters Defaults Description


start motor and genset as soon as
possible.
When generator frequency higher
Disconnect
than the set value, starter will be
17 Generator (0~200)% 24%
disconnected. See the installation
Freq
instruction.
Setting value is percentage of rated
speed. When engine speed higher
Disconnect
18 (0~200)% 24% than the set value, starter will be
Engine Speed
disconnected. See the installation
instruction.
When generator oil pressure higher
Disconnect than the set value, starter will be
19 (0~1000)kPa 200
Oil Pressure disconnected. See the installation
instruction.
Generator Setting
0: 3P4W; 1: 3P3W;
1 AC System (0~3) 0
2: 2P3W; 3: 1P2W.
Numbers of generator pole, used for
2 Poles (2~32) 4 calculating starter rotate speed when
without speed sensor.
To offer standards for detecting of
Rated generator’ over/under voltage and
3 (30~30000)V 230
Voltage loading voltage. (It is primary voltage
when using voltage transformer).
Setting value is percentage of
generator rated voltage. Detect when
Loading
4 (0~200)% 85% controller ready to loading. If
Voltage
generator voltage under load voltage,
won’t enter into normally running.
Rated (10.0~600.0) To offer standards for detecting of
5 50.0
Frequency Hz over/under/load frequency.
Setting value is percentage of
generator rated frequency. When
Loading
6 (0~200)% 85% generator frequency under load
Frequency
frequency, it won’t enter into normal
running.
Volt.
7 (0~1) 0 0: Disable; 1:Enable
Trans.(PT)
Over Volt. Setting value is percentage of
8 (0~200)% 120%
Shutdown generator rated volt. Delay value can

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 36 of 63


HGM8110A/8120A Genset Controller

No. Items Parameters Defaults Description


Under Volt. be set.
9 (0~200)% 80%
Shutdown
Setting value is percentage of
Over Freq.
10 (0~200)% 114% generator rated freq. Delay value
Shutdown
also can be set.
Setting value is percentage of
Under Freq.
11 (0~200)% 80% generator rated frequency. Delay
Shutdown
value can be set.
Setting value is percentage of
Over Volt.
12 (0~1000)% 110% generator rated voltage. Delay value
Warn
and return value also can be set.
Setting value is percentage of
Under Volt.
13 (0~1000)% 84% generator rated volt. Delay value and
Warn
return value also can be set.
Setting value is percentage of
Over Freq.
14 (0~1000)% 110% generator rated freq. Delay value and
Warn
return value also can be set.
Setting value is percentage of
Under Freq.
15 (0~1000)% 84% generator rated freq. Delay value and
Warn
return value also can be set.
Loss of
16 (0~1) 1
Phase
Phase 0: Disable 1: Enable
17 Sequence (0~1) 1
Wrong
Load Setting
Current
1 (5~6000)/5 500 The ratio of external CT
Trans.
Full Current Generator’s rated current, standard
2 (5~6000)A 500
Rating of load current.
Generator’s rated power, standard of
3 Full kW rating (0~6000)kW 276
load power.
Setting value is percentage of
4 Over Current (0~200)% 120% generator full load current. Delay
value also can be set.

5 Over Power (0~1) 0 0: Disable 1: Enable

Reverse
6 (0~1) 0 0: Disable 1: Enable
Power
Switch Setting
1 Transfer Time (0~7200)s 5 Interval time from mains switch off to

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 37 of 63


HGM8110A/8120A Genset Controller

No. Items Parameters Defaults Description


generator switch on; or from
generator switch off to mains switch
on.
Pulse width of mains/generator
2 Close Time (0~20.0)s 5.0 switch on. When it is 0, means output
constantly.
Pulse width of mains/generator
3 Open Time (0~20.0)s 3.0
switch off.
Time of detecting switch auxiliary
4 Check Time (0~20.0)s 5.0
contacts after transferred.
5 Warn Enable (0~1) 0 0: Disable 1: Enable
6 Check Enable (0~1) 0 0: Disable 1: Enable
Enable
Immediate
7 (0~1) 1 0: Disable 1: Enable
Mains
Dropout
Module Setting
Power on 0: Stop mode 1: Manual mode
1 (0~2) 0
Mode 2: Auto mode
Module Controller’s address during remote
2 (1~254) 1
Address sensing.
3 Stop Bits (0~1) 0 0: 2 stop bits; 1: 1 stop bit
0: Simplified Chinese 1: English
4 Language (0~2) 0
2: Others
For entering advanced parameters
5 Password (0~65535) 00318
setting.
Scheduling And Maintenance Setting
Scheduled
1 (0~1) 0 0: Disable; 1: Enable
Run
Scheduled
2 (0~1) 0 0: Disable; 1: Enable
Not Run
3 Maintenance (0~1) 0 0: Disable; 1: Enable
Analog Sensors Setting
Temperature Sensor
1 Curve Type (0~15) 7 SGX See form 4.
Open Circuit 0: Warn; 1: Shutdown;
2 (0~2) 0
Action 2: No action
Shutdown when sensor temperature
High Temp. higher than this value. Detecting only
3 (0~300)ºC 98
Shutdown after safety delay is over. The delay
value also can be set.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 38 of 63


HGM8110A/8120A Genset Controller

No. Items Parameters Defaults Description


Warn when sensor temperature
higher than this value. Detecting
High Temp.
4 (0~300) ºC 95 only after safety delay is over. The
Warn
delay value and return value also can
be set.
Low Temp.
5 (0~1) 0 0: Disable; 1: Enable
Warn
Oil Pressure Sensor
1 Curve Type (0~15) 7 SGX See form 4.
Open Circuit 0: Warn 1: Shutdown
2 (0~2) 0
Action 2: No action
Shutdown when oil pressure lower
Low OP than this value. Detecting only after
3 (0~1000)kPa 103
Shutdown safety delay is over. The delay value
also can be set.
Warn when oil pressure higher than
this value. Detecting only after safety
4 Low OP Warn (0~1000)kPa 124
delay is over. The delay value and
return value also can be set.
Liquid Level Sensor
1 Curve Type (0~15) 4 SGH See form 4
Open Circuit
2 (0~2) 0 0:Warn; 1:Shutdown; 2:No action
Action
Warn when level lower than this
Low Level value. It is detecting all the time. The
3 (0~300)% 10
Warn delay value and return value also can
be set.
Flexible Sensor 1
Flexible 0: Disable 1: Enable; (can be set as
1 Sensor 1 (0~1) 0 temperature/pressure/liquid lever
Setting sensor).
Flexible Sensor 2
Flexible 0: Disable; 1: Enable; (can be set as
1 Sensor 2 (0~1) 0 temperature/pressure/liquid lever
Setting sensor).
Flexible Input Ports
Flexible Input Port 1
Contents
1 (0~50) 28 Remote start (on load). See form 3
Setting
0: Closed to active
2 Active Type (0~1) 0
1: Open to active

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 39 of 63


HGM8110A/8120A Genset Controller

No. Items Parameters Defaults Description


Flexible Input Port 2
Contents High temperature shutdown
1 (0~50) 26
Setting See form 3
0: Closed to active
2 Active Type (0~1) 0
1: Open to active
Flexible Input Port 3
Contents Low oil pressure shutdown
1 (0~50) 27
Setting See form 3
0: Closed to active
2 Active Type (0~1) 0
1: Open to active
Flexible Input Port 4
Contents
1 (0~50) 0 User defined. See form 3
Setting
0: Closed to active
2 Active Type (0~1) 0
1: Open to active
0: From safety on 1: From starting
3 Arming (0~3) 2
2: Always 3:Never
Active 0: Warn; 1: Shutdown; 2:Trip and
4 (0~4) 0
Actions stop 3:Trip 4: Indication
5 Active Delay (0~20.0)s 2.0 Time from detecting active to confirm
6 Description User defined.
Flexible Input Port 5
Contents
1 (0~50) 0 User defined. See form 3
Setting
0: Closed to active
2 Active Type (0~1) 0
1: Open to active
0: From safety on 1: From starting
3 Arming (0~3) 2
2: Always 3:Never
Active 0: Warn; 1: Shutdown; 2:Trip and
4 (0~4) 1
Actions stop 3:Trip 4: Indication
5 Active Delay (0~20.0)s 2.0 Time from detecting active to confirm
6 Description User defined.
Flexible Input Port 6
Contents
1 (0~50) 0 User defined .See form 3
Setting
0: Closed to active
2 Active Type (0~1) 0
1: Open to active
0: From safety on 1: From starting
3 Arming (0~3) 2
2: Always 3:Never
Active 0: Warn; 1: Shutdown; 2:Trip and
4 (0~4) 2
Actions stop 3:Trip 4: Indication

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 40 of 63


HGM8110A/8120A Genset Controller

No. Items Parameters Defaults Description


5 Active Delay (0~20.0)s 2.0 Time from detecting active to confirm
6 Description User defined.
Flexible Output Ports
Flexible Output Port 1
Contents User defined period output (default
1 (0~239) 1
Setting output is in preheating) See Form 2
2 Active Type (0~1) 0 0:Normally open; 1:Normally close
Flexible Output Port 2
Contents
1 (0~239) 48 Common alarm. See form 2
Setting
2 Active Type (0~1) 0 0:Normally open; 1:Normally close
Flexible Output Port 3
Contents
1 (0~239) 38 ETS solenoid hold. See form 2
Setting
2 Active Type (0~1) 0 0:Normally open; 1:Normally close
Flexible Output Port 4
Contents
1 (0~239) 35 Idle speed control. See form 2
Setting
2 Active Type (0~1) 0 0:Normally open; 1:Normally close
Flexible Output Port 5
Contents
1 (0~239) 29 Generator closed output. See form 2
Setting
2 Active Type (0~1) 0 0:Normally open; 1:Normally close
Flexible Output Port 6
Contents
1 (0~239) 31 Mains closed output. See form 2
Setting
2 Active Type (0~1) 0 0:Normally open; 1:Normally close

Note:Overcurrent setting details about definite time delay and inverse definite
minimum time are as follows:
Definite Time:Overcurrent delay is definite time delay. Different overcurrent value has
corresponding delay.
Inverse Definite Minimum Time(IDMT):Overcurrent delay decrease with the increase of
overcurrent. Different overcurrent value has corresponding delay.
IDMT formula:
T = t / ((IA/IT)-1)2
T:Overcurrent delay (second)

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 41 of 63


HGM8110A/8120A Genset Controller
t:Timing multiplier ratio
IA:Current max. load current(L1/L2/L3)
IT:Overcurrent setting value
Example:
t = 36
IA = 550A
IT =500A
Conclusion: T = 3600s(1hour)

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 42 of 63


HGM8110A/8120A Genset Controller
7.2 ENABLE DEFINITION OF PROGRAMMABLE OUTPUT
PORTS
(Form 2)
No. Type Description
0 Not Used
1 Custom Period 1
2 Custom Period 2
3 Custom Period 3
4 Custom Period 4
5 Custom Period 5
6 Custom Period 6 Details of function description please see the
7 Custom Combined 1 following.
8 Custom Combined 2
9 Custom Combined 3
10 Custom Combined 4
11 Custom Combined 5
12 Custom Combined 6
13 Reserved
14 Reserved
15 Reserved
16 Reserved
Action when over speed shutdown and
17 Air Flap emergence stop. It also can close the air
inflow to stop the engine as soon as possible.
Action when warning, shutdown, trips. Can be
connected annunciator externally. When
18 Audible Alarm
“alarm mute” configurable input port is active,
it can remove the alarm.
Action in genset starting and disconnect when
19 Louver Control
genset stopped completely.
It is controlled by fuel pump of level sensor’s
20 Fuel Pump Control
limited threshold.
21 Heater Control It is controlled by heating of temperature

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 43 of 63


HGM8110A/8120A Genset Controller

sensor’s setting bound.


It is controlled by cooler of temperature
22 Cooler Control
sensor’s setting bound.
23 Oil Pre-supply Actions in period of cranking to safety run.
Output in start period. If there is no generator
24 Excite Generator frequency during hi-speed running, output for
2 seconds again.
25 Pre-Lubricate Actions in period of pre-heating to safety run.
26 Remote PC Output This port is controlled by communication (PC).
27 Reserved
28 Reserved
29 Close Generator Control generator to take load.
30 Open Breaker Control generator to off load.
31 Close Mains Control mains to take load.
32 Reserved
33 Crank Relay
Action when genset is starting and disconnect
34 Fuel Relay
when stop is completed.
Used for engine which has idles. Close before
starting and open in warming up delay; Close
35 Idle Control
during stopping idle mode and open when
stop is completed.
36 Raise Speed Action in warming up delay.
Action between the period from “stop idle” to
37 Drop Speed
“failed to stop”.
Used for engines with ETS electromagnet.
38 ETS Control Close when stop idle is over and open when
pre-set “ETS delay” is over.
Active 0.1s when controller enter into stop
39 Pulse Drop speed idle, used for control part of ECU dropping to
idle speed (temporary reserved).
40 Reserved

41 Reserved

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 44 of 63


HGM8110A/8120A Genset Controller

Active 0.1s when controller enter into warming


42 Pulse raise speed up delay; used for control part of ECU raising
to normal speed (temporary reserved).
43 Crank Success Close when detects a successful start signal.
44 Generator OK Action when generator are normal.
Action in period of generator ok to hi-speed
45 Generator Available
cooling.
46 Mains OK Action when mains normal.
47 Reserved
Action when genset common warning,
48 Common Alarm
common shutdown, common trips alarm.
49 Common Trip and Stop Action when common trip and stop alarm.
50 Common Shutdown Action when common shutdown alarm.
51 Common Trip Alarm Action when common trips alarm.
52 Common Warn Alarm Action when common warning alarm.
53 Reserved
Action when battery’s over voltage warning
54 Battery High Volts
alarm.
Action when battery’s low voltage warning
55 Battery Low Volts
alarm.
56 Charge Alt Fail Action when charge failure warning alarms.
57 Reserved
58 Reserved
59 Reserved
60 Reserved

61 Reserved

62 Reserved

63 Reserved
64 Reserved
65 Reserved
66 Reserved
67 Reserved
68 Reserved

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 45 of 63


HGM8110A/8120A Genset Controller

69 Aux Input 1 Active Action when input port 1 is active


70 Aux Input 2 Active Action when input port 2 is active
71 Aux Input 3 Active Action when input port 3 is active
72 Aux Input 4 Active Action when input port 4 is active
73 Aux Input 5 Active Action when input port 5 is active
74 Aux Input 6 Active Action when input port 6 is active
75~98 Reserved
99 Emergency Stop Action when emergency stop alarm.
100 Failed To Start Action when failed start alarm.
101 Failed To Stop Action when failed stop alarm.
102 Under Speed Warn Action when under speed alarm.
103 Under Speed Shutdown Action when under speed shuts down.
104 Over Speed Warn Action when over speed warn.
105 Over Speed Shutdown Action when over speed shutdown alarm.
Loss of Speed Signal Action when loss of speed signal shutdown
106
Shutdown alarm.
107 Reserved
108 Reserved
Gen over frequency Action when generator over frequency
109
Warn warning.
Action when generator over frequency
110 Gen over frequency Shut
shutdown alarm.
111 Gen Over Volt Warn Action when generator over voltage warning.
112 Gen Over Volt Shut Action when generator over voltage shutdown.
113 Gen Under Freq. Warn Action when generator low frequency warning.
Action when generator low frequency
114
Gen Under Freq. Shut shutdown.
115 Gen Under Volt. Warn Action when generator low voltage warning.
116 Gen Under Volt. Shut Action when generator low voltage shutdown.
117 Gen Loss of Phase Action when generator loss phase.
118 Gen Reverse Phase Action when generator reverse phase.
119 Reserved
120 Over Power Action when controller detects generator have

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 46 of 63


HGM8110A/8120A Genset Controller

over power.
121 Reserved
Action when controller detects generator have
122 Reverse Power
reverse power.
123 Over Current Action when over current.
124 Reserved
125 Mains Inactive
126 Mains Over Freq
127 Mains Over Volt
128 Mains Under Freq
129 Mains Under Volt
130 Mains Reverse Phase
131 Mains Loss of Phase
132~138 Reserved
139 High Temp Warn Action when hi-temperature warning.
140 Low Temp Warn Action when low temperature warning.
141 High Temp Shutdown Action when hi-temperature Shutdown alarm.
142 Reserved
143 Low OP Warn Action when low oil pressure warning.
144 Low OP Shutdown Action when low oil pressure shutdown.
Action when oil pressure sensor is open
145 OP Sensor Open
circuit.
146 Reserved
147 Low Level Warn Action when controller has low oil level alarm.
148 Reserved
149 Reserved
150 Config1 High Warn
151 Config1 Low Warn
152 Config1 High Shut
153 Config1 Low Shut
154 Config2 High Warn
155 Config2 Low Warn
156 Config2 High Shut

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 47 of 63


HGM8110A/8120A Genset Controller

157 Config2 Low Shut


158~229 Reserved
230 Stop Mode Action in stop mode.
231 Manual Mode Action in Manual mode.
232 Test Mode Action in Test mode. (HGM8110A without)
233 Auto Mode Action in Auto mode.
234 Generator On Load
235 Mains On Load
236 Reserved
237 Reserved
238 Reserved
239 Reserved

7.2.1 Custom Period Output

Defined Period output is composed by 2 parts, period output S1 and condition output S2.

While S1 and S2 are TRUE synchronously, OUTPUT;


While S1 or S2 is FALSE, NOT OUTPUT.
Period output S1, can set generator’s one or more period output freely, can set the delayed
time and output time after enter into period.
Condition output S2; can set as any conditions in output ports.

NOTE: when delay time and output time both are 0 in period output S1, it is TRUE in
this period.
Example,
Output period: start
Delay output time: 2s
Output time: 3s
Condition output contents: output port 1 is active
Close when condition output active/inactive: close when active (disconnect when inactive);
Output port 1 active, after enter “starts time” and delay 2s, this defined period output is
outputting, after 3s, stop outputting;
Output port 1 inactive, defined output period is not outputting.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 48 of 63


HGM8110A/8120A Genset Controller

7.2.2 Custom Combined Output

Defined combination output is composed by 3 parts, condition output S1 or S2 and


condition output S3.

S1 or S2 is TRUE, while S3 is TRUE, Defined combination output is outputting;


S1 and S2 are FALSE, or S3 is FALSE, Defined combination output is not outputting.

NOTE: S1, S2, S3 can be set as any contents except for “defined combination output”
in the output setting.

NOTE: 3 parts of defined combination output (S1, S2, S3) couldn’t include or
recursively include themselves.
Example,
Contents of probably condition output S1: output port 1 is active;
Close when probably condition output S1 is active /inactive: close when active (disconnect
when inactive);
Contents of probably condition output S2, output port 2 is active;
Close when probably condition output S2 is active /inactive: close when active (disconnect
when inactive);
Contents of probably condition output S3: output port 3 is active;
Close when probably condition output S3 is active /inactive: close when active (disconnect
when inactive);
When input port 1 active or input port 2 active, if input port 3 is active, Defined combination
output is outputting; If input port 3 inactive, Defined combination output is not outputting;
When input port 1 inactive and input port 2 inactive, whatever input port 3 is active or not,
Defined combination output is not outputting.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 49 of 63


HGM8110A/8120A Genset Controller
7.3 DEFINED CONTENTS OF CONFIGURABLE INPUT PORTS
(All active when connect to grand (B-))
Form 3
No. Type Description

Including following functions,


Indication: indicate only, not warning or
shutdown.
Warning: warn only, not shutdown.
Shutdown: alarm and shutdown immediately
Trip and stop: alarm, generator unloads and
0 Users Configured shutdown after hi-speed cooling
Trip: alarm, generator unloads but not shutdown.
Never: input inactive.
Always: input is active all the time.
From crank: detecting as soon as start.
From safety on: detecting after safety on run
delay.
1 Reserved
Can prohibit “Audible Alarm” output when input is
2 Alarm Mute
active.
Can reset shutdown alarm and trip alarm when
3 Reset Alarm
input is active.
Use for CANBUS engine and it is 60Hz when
4 60Hz Active
input is active.
All LED indicators are illuminating when input is
5 Lamp Test
active.

All buttons in panel is inactive except and


6 Panel Lock
there is in the left of first row in LCD when
input is active.
7 Reserved
Under voltage/frequency/speed protection is
8 Idle Control Mode
inactive.
In Auto mode, during generator normal running,
9 Inhibit Auto Stop when input is active, inhibit generator shutdown
automatically.
In Auto mode, inhibit generator start
10 Inhibit Auto Start
automatically when input is active.
In Auto mode, inhibit scheduled run genset
11 Inhibit Scheduled
when input is active.
12 Reserved

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 50 of 63


HGM8110A/8120A Genset Controller
13 Aux Gen Closed Connect generator loading switch’s Aux. Point.
14 Inhibit Gen Load Prohibit genset switch on when input is active.
15 Aux Mains Closed Connect mains loading switch’s Aux. Point.
16 Inhibit Mains Load Prohibit mains switch on when input is active.
When input is active, controller enters into Auto

17 Auto Mode Lock mode; all the keys except are inactive, and
will show in the first line of LCD display.
When input is active, controller won’t work under

18 Auto Mode Invalid Auto mode. key and simulate auto key input
does not work.
19 Reserved
20 Reserved
All shutdown alarms are prohibited except
21 Inhibit Alarm Stop emergence stop.(Means battle mode or override
mode)
22 Aux Instrument Mode All outputs are prohibited in this mode.
23 Reserved
Controller will set maintenance time and date as
24 Reset Maintenance
default when input is active.
25 Reserved

26 Aux. High Temp Connected sensor digital input.

27 Aux. Low OP Connected sensor digital input.


In Auto mode, when input active, genset can be
Remote Start started automatically and take load after genset
28
(On Load) normal running; when input inactive, genset will
stop automatically.
In Auto mode, when input is active, genset can
Remote Start be started automatically and NOT take load after
29
(Off Load) genset normal running; when input is inactive,
genset will stop automatically.
In Manual mode, when input active, genset will
30 Aux. Manual Start start automatically; when input inactive, genset
will stop automatically
31 Reserved
32 Reserved
33 Simulate Stop key
34 Simulate Manual key An external button can be connected and
35 Simulate Manual Test key pressed as simulate panel.
36 Simulate Auto key
HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 51 of 63
HGM8110A/8120A Genset Controller
37 Simulate Start key
38 Reserved
39 Reserved
40 Reserved
41 Reserved
42 Reserved
43 Reserved
44 Reserved
In Auto mode, mains are normal when input is
45 Aux Mains OK
active (HGM8120A).
In Auto mode, mains are abnormal when input is
46 Aux Mains Fail
active (HGM8120A).
47 Alternative Config1 Users can set different parameters to make it
48 Alternative Config2 easy to select current configuration via input
49 Alternative Config3 port.
50 Reserved

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 52 of 63


HGM8110A/8120A Genset Controller
7.4 SELECTION OF SENSORS
Form4
No. Description Remark
0 Not used
1 Custom Res Curve
2 Custom 4-20mA curve
3 VDO
4 CURTIS
Defined resistance’s
Temperature 5 VOLVO-EC
1 range is 0~6KΩ,
Sensor 6 DATCON
default is SGX sensor.
7 SGX
8 SGD
9 SGH
10 PT100
11~15 Reserved
0 Not used
1 Custom Res Curve
2 Custom 4-20mA curve
3 VDO 10Bar
4 CURTIS Defined resistance’s
5 VOLVO-EC range is 0~6KΩ,
2 Pressure Sensor
6 DATCON 10Bar default is SGX
7 SGX sensor.
8 SGD
9 SGH
10 VDO 5bar
11~15 Reserved
0 Not used
1 Custom Res Curve Defined resistance’s
2 Custom 4-20mA curve range is 0~6KΩ,
3 Oil Level Sensor
3 SGD default is SGH
4 SGH sensor.
5~15 Reserved

NOTE: User should make special declare when order controller if your genset equip
with sensor of 4~20mA.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 53 of 63


HGM8110A/8120A Genset Controller
7.5 CONDITIONS OF CRANK DINSCONNECT SELECTION
No. Setting description
0 Gen frequency
1 Speed sensor
2 Speed sensor + Gen frequency
3 Oil pressure
4 Oil pressure + Gen frequency
5 Oil pressure + Speed sensor
6 Oil pressure + Speed sensor + Gen frequency
NOTE:
1. There are 3 conditions to make starter disconnected with engine, that is, speed sensor,
generator frequency and engine oil pressure. They all can be used separately. We
recommend that engine oil pressure should be using with speed sensor and generator
frequency together, in order to make the starter motor is separated with engine
immediately and can check crank disconnect exactly.
2. Speed sensor is the magnetic equipment which be installed in starter for detecting
flywheel teeth.
3. When set as speed sensor, must ensure that the number of flywheel teeth is as same
as setting, otherwise, “over speed shutdown” or “under speed shutdown” may be
caused.
4. If genset without speed sensor, please don’t select corresponding items, otherwise,
“start fail” or “loss speed signal” maybe caused.
5. If genset without oil pressure sensor, please don’t select corresponding items.
6. If not select generator in crank disconnect setting, controller will not collect and display
the relative power quantity (can be used in water pump set); if not select speed sensor
in crank disconnect setting, the rotating speed displayed in controller is calculated by
generator frequency and number of poles.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 54 of 63


HGM8110A/8120A Genset Controller

8 PARAMETER EDITING

1) Advanced Parameters Setting:After controller start,


Input Password
press and to advanced parameter password
confirmation interface (picture on the right). Press “+” 0****

and “-” to increase or decrease values and input the


corresponding password; press “√” key to right move the bit, in fourth bit press “√”
key to check password. If password is correct, enter into advanced parameter setting
interface, otherwise, exit directly. (Factory default password is 00318 and users can
modify it.)

Press “+” key and “-” key to scroll screen; select parameter you want to configure and
press “√” key (the parameter will highlight with black), press“+” key or “-” key to
change parameter value, press “√ ” key to move the bit, in fourth bit press“√” key to
confirm setting.
2) Basic Parameter Setting:After controller start, press Basic Parameter Setting
for more than 3s to enter into Basic Parameter >Return
Setting interface; The frequently-used parameters can >Mains Rated Voltage
> Mains Rated Frequency
be set via both Basic Parameter Setting and Advanced >Crank Disconnect
Parameter Setting, however, set the frequently-used
parameters via Basic Parameter Setting is recommended as there are lots of
parameters in Advanced Parameter Setting and inconvenience. The picture on the
right is “Basic Parameter Setting” interface, the parameter which highlight with black
is the current setting one.
3) Date and Time Setting: After controller start,
Date and Time
press and to the Date and Time Setting interface 2013.01.26 (6) 15:19:22
(picture on the right). The digital which highlight with
black is currently adaptable for user by pressing “+”
key and “-” key to increase and decrease the value.
Press “√” key to confirm setting and the bit will right move automatically. Number “6”
in the parenthesis is the day of the week. It is set by the microprocessor based on
current date, so the user does not need to modify it.

CAUTION: Please change the controller parameters when generator is in standby


HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 55 of 63
HGM8110A/8120A Genset Controller
mode only (e. g. Crank disconnect conditions selection, configurable input, configurable
output, various delay), otherwise, shutdown and other abnormal conditions may happen.

NOTE: Maximum set value must over minimum set value in case that the condition of
too high as well as too low will happen.

NOTE: When setting the warning alarm, please set the correct return value; otherwise,
maybe there is abnormal alarm. When setting the maximum value, the return value must
less than set value; When setting the minimum value, the return value must over set value.

NOTE: Please set the generator frequency value as low as possible when cranking, in
order to make the starter be separated quickly as soon as crank disconnect.

NOTE: Configurable input could not be set as same items; otherwise, there are
abnormal functions. However, the configurable output can be set as same items.

NOTE: HGM8110A controller has no items about mains. Pressing and holding
for a long time can exit parameter setting menu directly and set the controller into
standby mode.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 56 of 63


HGM8110A/8120A Genset Controller

9 SENSORS SETTING

1. When reselect sensors, the sensor curve will be transferred into the standard value. For
example, if temperature sensor is SGX (120°C resistor type), its sensor curve is SGX
(120°C resistor type); if select the SGD (120°C resistor type), the temperature sensor
curve is SGD curve.
2. When there is difference between standard sensor curves and using sensor, user can
adjust it in “curve type”.
3. When input the sensor curve, X value (resistor) must be input from small to large,
otherwise, mistake occurs.
4. If select sensor type as “None”, sensor curve is not working.
5. If corresponding sensor has alarm switch only, user must set this sensor as “None”,
otherwise, maybe there is shutdown or warning.
6. The headmost or backmost values in the vertical coordinates can be set as same as
below,

Normal Pressure Unit Conversion Form

pa kgf/cm2 bar psi


1Pa 1 1.02x10-5 1x10-5 1.45x10-4
1kgf/cm2 9.8x104 1 0.98 14.2
1bar 1x105 1.02 1 14.5
1psi 6.89x103 7.03x10-2 6.89x10-2 1

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 57 of 63


HGM8110A/8120A Genset Controller

10 COMMISSIONING

Please make the under procedures checking before commissioning,


1. Ensure all the connections are correct and wires diameter is suitable.
2. Ensure that the controller DC power has fuse, controller’s positive and negative
connected to start battery are correct.
3. Emergence stop must be connected with positive of start battery via scram button’s
normal close point and fuse.
4. Take proper action to prevent engine to crank disconnect (e. g. Remove the connection
wire of fuel valve). If checking is OK, make the start battery power on; choose manual
mode and controller will executive routine.
5. Set controller under manual mode, press “start” button, genset will start. After the
cranking times as setting, controller will send signal of Start Fail; then press “stop” to
reset controller.
6. Recover the action of stop engine start (e. g. Connect wire of fuel valve), press start
button again, genset will start. If everything goes well, genset will normal run after idle
running (if idle run be set). During this time, please watch for engine’s running
situations and AC generator’s voltage and frequency. If abnormal, stop genset running
and check all wires connection according to this manual.
7. Select the AUTO mode from controller’s panel, connect mains signal. After the mains
normal delay, controller will transfer ATS (if fitted) into mains load. After cooling time,
controller will stop genset and make it into “at rest” mode until there is abnormal of
mains.
8. When mains is abnormal again, genset will be started automatically and into normal
running, then controller send signal to making generator switch on, and control the ATS
as generator load. If not like this, please check ATS’ wires connection of control part
according to this manual.
9. If there is any other question, please contact Smartgen’s service.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 58 of 63


HGM8110A/8120A Genset Controller

11 TYPICAL WIRING DIAGRAMS

HGM8110A Typical wiring diagram

HGM8120A Typical wiring diagram

Note: If the engine starting battery voltage is 24V, starting output, fuel output and stop
output (according to user’s configuration) should not be less than 2 ohms for battery
cathode resistance, if less than 2 ohms, please expand relays with more than 30A current
in corresponding output. if the engine starting battery voltage is12V, starting output, fuel
output and stop output (according to user’s configuration) should not be less than 1 ohms

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 59 of 63


HGM8110A/8120A Genset Controller
for battery cathode resistance; if less than 1 ohm,please expand relays with more than 30A
current in corresponding output.
3 Phase 3 Wire (take HGM8120A for example)

Single Phase 2 Wire (take HGM8120A for example)

2 Phase 3 Wire (take HGM8120A for example)

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 60 of 63


HGM8110A/8120A Genset Controller

12 INSTALLATION

The installation dimension of HGM8110A is just the same with HGM8120A.


Controller is panel built-in design; it is fixed by clips when installed. The controller’s
overall dimensions and cutout dimensions for panel, please refers to as following,

12.1 BATTERY VOLTAGE INPUT


NOTE: HGM8110A/8120A controller can suit for widely range of battery voltage
DC(8~35)V. Negative of battery must be connected with the engine shell. The diameter of
wire which from power supply to battery must be over 2.5mm2. If floating charge configured,
please firstly connect output wires of charger to battery’s positive and negative directly,
then, connect wires from battery’s positive and negative to controller’s positive and
negative input ports in order to prevent charge disturbing the controller’s normal working.
12.2 SPEED SENSOR INPUT
NOTE: Speed sensor is the magnetic equipment which be installed in starter and for
detecting flywheel teeth. Its connection wires to controller should apply for 2 cores shielding
line. The shielding layer should connect to No. 16 terminal in controller while another side is
hanging in air. The else two signal wires are connected to No.17 and No.18 terminals in
controller. The output voltage of speed sensor should be within AC(1~24)V (effective value)
during the full speed. AC12V is recommended (in rated speed). When install the speed
sensor, let the sensor is spun to contacting flywheel first, then, port out 1/3 lap, and lock the
nuts of sensor at last.

12.3 OUTPUT AND EXPAND RELAYS


CAUTION: All outputs of controller are relay contact output type. If need to expand the
relays, please add freewheel diode to both ends of expand relay’s coils (when coils of relay
has DC current) or, add resistance-capacitance return circuit (when coils of relay has AC
current), in order to prevent disturbance to controller or others equipment.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 61 of 63


HGM8110A/8120A Genset Controller
12.4 AC INPUT
Current input of HGM8110A/8120A controller must be connected to outside current
transformer. And the current transformer’s secondary side current must be 5A. At the same
time, the phases of current transformer and input voltage must correct. Otherwise, the
current of collecting and active power maybe not correct.

NOTE: ICOM port must be connected to negative pole of battery.

WARNING! When there is load current, transformer’s secondary side prohibit open
circuit.

12.5 WITHSTAND VOLTAGE TEST

CAUTION! When controller had been installed in control panel, if need the high voltage
test, please disconnect controller’s all terminal connections, in order to prevent high voltage
into controller and damage it.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 62 of 63


HGM8110A/8120A Genset Controller

13 FACTORY DEFAULT VALUES

Here are the common faults and troubleshooting. If there is any other problem, please
feel free to contact Smartgen’s service.
Symptoms Possible Solutions
Check starting batteries;
Controller no response with
Check controller connection wirings;
power.
Check DC fuse.
Check the water/cylinder temperature is too high or not;
Genset shutdown Check the genset AC voltage;
Check DC fuse.
Check emergence stop button is correct or not;
Check whether the starting battery positive be
Controller emergency stop
connected with the emergency stop input;
Check whether the circuit is open.
Low oil pressure alarm after Check the oil pressure sensor and its connections.
crank disconnect
High water temp. alarm after Check the temperature sensor and its connections.
crank disconnect
Check related switch and its connections according to
Shutdown Alarm in running the information on VFD;
Check programmable inputs.
Check fuel oil circuit and its connections;
Check starting batteries;
Crank not disconnect
Check speed sensor and its connections;
Refer to engine manual.
Check starter connections;
Starter no response
Check starting batteries.
Genset running while ATS not Check ATS;
transfer Check the connections between ATS and controllers.
Check connections;
Check setting of COM port is correct or not;
RS485 communication is Check RS485’s connections of A and B is reverse
abnormal connect or not;
Check RS485 transfer model whether damage or not;
Check communication port of PC whether damage.

HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 63 of 63

You might also like