User Manual: HGM8100A Genset Controller (HGM8110A/HGM8120A)
User Manual: HGM8100A Genset Controller (HGM8110A/HGM8120A)
User Manual: HGM8100A Genset Controller (HGM8110A/HGM8120A)
(HGM8110A/HGM8120A)
(VFD DISPLAY)
USER MANUAL
English trademark
2013-12-23 1.4 Add function: Long pressing “ ” button can reset trip
alarm.
Change the “Working Conditions” and “Storage Condition”
2014-10-23 1.5
temperature as (-40~+70)℃
Modify the picture of mask and the graph of controller
2016-09-28 1.6
dimension.
CONTENT
1 OVERVIEW................................................................................................................ 6
3 SPECIFICATION ..................................................................................................... 10
4 OPERATION .............................................................................................................11
5 PROTECTION ......................................................................................................... 24
10 COMMISSIONING ................................................................................................... 58
12 INSTALLATION ....................................................................................................... 61
1 OVERVIEW
♦ For Mains, controller has over and under voltage, over and under frequency, loss of
phase and phase sequence wrong detection functions; For generator, controller has
over and under voltage, over and under frequency, loss of phase, phase sequence
3 SPECIFICATION
ITEM CONTENT
Operating voltage DC8. 0V to 35. 0V, Continuous Power Supply
Power consumption <6W(Standby mode: ≤3W)
Alternator Input Range
3-Phase 4 Wire AC20V - AC360V (ph-N)
3-Phase 3 Wire AC30V - AC600V (ph- ph)
Single-Phase 2 Wire AC20V - AC360V (ph-N)
2-Phase 3 Wire AC20V - AC360V (ph-N)
Alternator Frequency 50Hz / 60Hz
Speed sensor voltage 1.0V to 24.0V (RMS)
Speed sensor Frequency 10,000 Hz (max)
Start Relay Output 16 A DC28V at DC supply output.
Fuel Relay Output 16 A DC28V at supply output.
Aux. Output 1 16 A DC28V at supply output.
Aux. Output 2 16 A DC28V at supply output.
Aux. Output 3 16 A DC28V at supply output.
Aux. Output 4 16 A AC250V at DC supply output.
Gen Close Relay 16A AC250V passive
Aux. Output 5
Mains Close Relay 16A AC250V passive
Aux. Output 6
Overall Dimensions 243.7mm x 176.2mm x 51.2mm
Panel Cutout 214mm x 160mm
C. T. Secondary 5A (rated)
Temperature: (-40~+70)°C
Working Conditions
Humidity: (20~93)%RH
Storage Condition Temperature: (-40~+70)°C
Protective Level IP55 Gasket
Apply AC2.2kV voltage between high voltage terminal and
Insulation Intensity low voltage terminal;
The leakage current is not more than 3mA within 1min.
Weight 0.80kg
4 OPERATION
Pressing this key will set the module into manual mode.
Manual mode /
In setting parameter status, press this key will decrease
Config. ‘-’
setting value.
Pressing this key will set the module into test mode (only
Test mode/
for HGM8120A). In setting parameter status, press this
Config. ‘+’
key will increase setting value.
Pressing this key will set the module into auto mode. In
Auto mode/Confirm setting parameter status, press this key will right shift
cursor or confirm setting value.
Pressing this key will view shutdown history records.
Again pressing this key will exit.
Event log
When there is trip alarm occurs, pressing and holding
this button for more than 3 seconds can reset the alarm.
Screen scroll in parameters interface or event log
Page Down
interface;
NOTE: Pressing and holding for more than 3 seconds enters basic parameter
configuration menu;
WARNING: Default password is 00318, user can change it in case of others change
the advanced parameters setting. Please clearly remember the password after changing. If
you forget it, please contact Smartgen services.
Main screen is used to display real time data of all parameters, use to scroll the
screen.
★Status, including as below,
Status of genset, mains (HGM8120A), and ATS
★Mains, including as below
Phase voltage, Line voltage, frequency
Note: When mains close indicator lights, count active and inactive power, apparent
power, power factor, but accumulate electric energy. Counting the generator active and
reactive power, apparent power, power factor, and accumulate electric energy under other
conditions.
Remark:
P stands for active power
Q stands for inactive power
Note:
1. Input active power, generator or mains supply electricity to load.
2. Output active power, load supply electricity to generator or mains.
3. Input reactive power, generator or mains send reactive power to load.
4. Output reactive power, load send reactive power to generator or mains.
★Engine, including as below,
Speed, engine temperature, engine oil pressure, liquid (fuel) level, flexible sensor 1, flexible
sensor 2, battery voltage, charger voltage, accumulated run time, accumulated start times.
★Alarm:
Display all kinds of alarm information, such as Gen Overvolts, Gen Undervolts, Gen Over
Frequency, Gen Under Frequency and so on.
★Event log
Records all start/stop events (shutdown alarm, trip and stop alarm, manual /auto start or
stop) and the real time when alarm occurs.
Example:
Gen Load
UL-L 0 0 0V Current 0.0 0.0 0.0A
UL-N 0 0 0V Power 0.0kW 0.0 kVA
F = 0.0Hz 0rpm cosΦ = 0.00 0.0 kVar
Stop Mode Gen Overvolts Warn
Crank Disconnect
Form 2:Press to enter settings (form 3); press
2:Speed sensor + Gen freq.
or or to return to previous menu. (Form
1).
Crank Disconnect
Form 3: are used for changing the setting
2:Speed sensor + Gen freq.
contents. Confirm setting (form 2), exit
Engine Setting
Form 2: are used for changing the setting
>Return
>AC Systerm contents (form 3). Select “Return” and press to
>Poles
>Rated Voltage return to previous menu (form 1). Press also can
Generator Setting
Form 3: are used for changing the setting
>Gen Undervolt Shutdown
> Gen Overfreq. Shutdown contents. Confirm setting (form 4), exit
> Gen Underfreq. Shutdown
> Gen Overvolt Warn setting (form 1).
Overvolt Warn
Form 4: Press to enter settings (form 5); Press
Sel: Disable
Set Value: 00110% or or to return to previous menu. (Form
Return Value: 00108%
Delay: 00005 3).
Overvolt Warn
Form 6: are used for changing the setting
Sel: Disable
Set Value: 00110% contents ( form 5). Confirm setting (form 7),
Return Value: 00108%
return to previous menu (form 4)
Delay: 00005
Overvolt Warn
Form 7: are used for changing the setting
Sel: Enable
Set Value: 00000 contents (form 5). Confirm setting, return to
Return Value: 00108%
Delay: 00005 previous menu (form 4).
Overvolt Warn
Form 8: are used for changing the setting
Sel: Enable
Set Value: 0000 contents. Confirm setting (form 4), return
Return Value: 00108%
Delay: 00005 to previous menu (form 4).
NOTE: Pressing and holding for a long time can exit setting directly during setting.
NOTE: In case of “Remote Start (off Load)”, the procedure is the same, except for step
NO. 9: the closing relay will NOT be energised, generator will NOT accept load.
Stopping Sequence
1) HGM8120A:If mains turns normal during genset is running, enter into mains voltage
“normal delay” and its indicator illuminates after mains is confirmed normally, “Start
delay” is beginning.
2) HGM8110A:Genset enters into “stop delay” as soon as “Remote Start” input is
1) HGM8120A: “Manual Mode” is active when press key and its indicator illuminates.
Press key, then controller enters “Test Mode” and indicator illuminates. Under the
both modes, press key to start genset, and it automatically detects if it starts
successfully and accelerate high speed running. With high temperature, low oil
pressure, over speed and abnormal voltage during diesel genset running, controller
can protect genset to stop effectively and quickly (please refer to No.4~9 of Starting
Sequence for more details). Under “Manual Mode ”, genset on-load is decided by
whether mains are normal or not. If mains are normal, loading switch isn’t transferred;
while mains are abnormal, loading switch is transferred into generator’s side. Under
“Test Mode “, after genset runs well in high speed, no matter mains is normal or
not, loading switch must be transferred into Generator’s side.
2) HGM8110A: “Manual Mode” is active when press key, and its indicator is
illuminates. Then press key to start generator, it automatically detects if it is started
successfully and genset automatically accelerates high speed running. With high
temperature, low oil pressure, over speed and voltage abnormal during diesel genset
running, controller can protect genset to stop effectively and quickly (please refer to
No.4~9 of Starting Sequence for more details). After genset runs well in high speed,
controller will send signal of Generator close.
3) Manual stop: press key can shutdown the running genset (please refer to No.3~7
of Stopping Sequence for more details).
In the control panel, press key to view previous running records of the controller,
including all start/stop records (shutdown, trip and stop, manual/auto start/stop) and
corresponding time. Press key to view records backward. Again press key to
return real time display status of the controller. HGM8100A controller can save recent 99
5 PROTECTION
5.1 WARNINGS
When controllers detects the warning signal, alarm only and not stop the genset, besides,
the VFD displays the warning information.
Warnings as following,
No. Type Description
When controller detects the speed is higher than the set
1 Over Speed Warn
value, it will send warn signal.
When controller detects the speed is lower than the set
2 Under Speed Warn
value, it will send warn signal.
Loss of Speed When controller detects the speed is 0 and the action
3
Signal Warn select “Warn”, it will send warn signal.
Over Frequency When controller detects the frequency is higher than the
4 set value, it will send warn signal.
Warn
Under Frequency When controller detects the frequency is lower than the
5
Warn set value, it will send warn signal.
When controller detects the voltage is higher than the
6 Over Voltage Wan
set value, it will send warn signal.
When controller detects the voltage is lower than the set
7 Under Voltage Warn
value, it will send warn signal.
When controller detects the current is higher than the
8 Over Current Warn
set value, it will send warn signal.
9 Fail to Stop When generator not stops after the “stop delay” is over.
When controller detects the charger voltage is lower
10 Charge Alt Fail
than the set value, it will send warn signal.
Battery Over When controller detects the battery voltage is higher
11
Voltage than the set value, it will send warn signal.
Battery Under When controller detects the battery voltage is lower than
12
Voltage the set value, it will send warn signal.
When count down time is 0 and the action select “Warn”,
13 Maintenance Due
it will send warn signal.
When controller detects the reverse power value (power
14 Reverse Power is negative) is lower than the set value, it will send warn
signal.
When controller detects the reverse power value (power
15 Over Power
is positive) is higher than the set value, it will send warn
6 CONNECTING
Compared with HGM8120A, HGM8110A has no 31~34 terminals. The back panel of
HGM8110A and HGM8120A controller is shown as follows:
Cable Size
No. Function Remarks
(mm2)
Connected with negative of starter
1 DC input B- 2.5
battery.
Connected with positive of starter
2 DC input B+ 2.5
battery. Max. 20A fuse is recommended.
Connected with DC power supply via
emergency stop button. Also supply
3 Emergency stop 2.5
power to fuel relay and start relay. Max.
30A fuse is recommended.
2.5 DC power is supplied by 3 terminal,
4 Fuel relay output
rated 16A
2.5 DC power is supplied by 3 terminal,
5 Start relay output
rated 16A
6 Aux. Output 1 2.5 B+ output,rated 16A
7 Aux. Output 2 2.5 B+ output,rated 16A Details
2.5 B+ output,rated 16A see form
8 Aux. Output 3
2
1.0 Connected with charger starter’s D+
9 Charger(D+) terminal. Ground connected is not
allowed.
10 Aux. Input 1 1.0 Ground connected
PARAMETERS
HGM8110A/8120A generator controllers can set the following parameters, (HGM8110 has
no mains items)
Timer Setting
Time from mains abnormal or remote
1 Start Delay (0~3600)s 1
start signal is active to start genset.
Time from mains normal or remote
2 Stop Delay (0~3600)s 1 start signal is deactivated to genset
stop.
Preheat Time of pre-powering heat plug
3 (0~3600)s 0
Delay before starter is powered up.
Cranking
4 (3~60)s 8 Time of starter power up
Time
Crank Rest The waiting time before second
5 (3~60)s 10
Time power up when engine start fail.
Alarms for low oil pressure, high
Safety On temperature, under speed, under
6 (0~3600)s 10
Delay frequency/voltage, charge fail are
inactive.
Start Idle Idle running time of genset when
7 (0~3600)s 0
Time starting.
Warming Up Warming time between genset switch
8 (0~3600)s 10
Time on and high speed running.
Radiating time before genset stop,
9 Cooling Time (0~3600)s 10
after it unloads.
Stop Idle
10 (0~3600)s 0 Idle running time when genset stop.
Time
ETS Solenoid Stop electromagnet’s power on time
11 (0~3600)s 20
Hold when genset is stopping.
Time between ending of genset idle
delay and stopped when “ETS time”
Fail to Stop is set as 0;
12 (0~3600)s 0
Delay Time between ending of ETS hold
delay and stopped when “ETS Hold
output time” is not 0.
After Stop Time between genset stopped and
13 (0~3600)s 0
Time standby
Engine Setting
1 Engine Type Fixed value: 0 0 Default: Conventional genset
Tooth number of the engine, for
judging of starter separation
Flywheel
2 (10~300) 118 conditions and inspecting of engine
Teeth
speed. See the installation
instructions.
HGM8110A/8120A Genset Controller ISSUE2016-9-28 Version1.6 Page 34 of 63
HGM8110A/8120A Genset Controller
Reverse
6 (0~1) 0 0: Disable 1: Enable
Power
Switch Setting
1 Transfer Time (0~7200)s 5 Interval time from mains switch off to
Note:Overcurrent setting details about definite time delay and inverse definite
minimum time are as follows:
Definite Time:Overcurrent delay is definite time delay. Different overcurrent value has
corresponding delay.
Inverse Definite Minimum Time(IDMT):Overcurrent delay decrease with the increase of
overcurrent. Different overcurrent value has corresponding delay.
IDMT formula:
T = t / ((IA/IT)-1)2
T:Overcurrent delay (second)
41 Reserved
61 Reserved
62 Reserved
63 Reserved
64 Reserved
65 Reserved
66 Reserved
67 Reserved
68 Reserved
over power.
121 Reserved
Action when controller detects generator have
122 Reverse Power
reverse power.
123 Over Current Action when over current.
124 Reserved
125 Mains Inactive
126 Mains Over Freq
127 Mains Over Volt
128 Mains Under Freq
129 Mains Under Volt
130 Mains Reverse Phase
131 Mains Loss of Phase
132~138 Reserved
139 High Temp Warn Action when hi-temperature warning.
140 Low Temp Warn Action when low temperature warning.
141 High Temp Shutdown Action when hi-temperature Shutdown alarm.
142 Reserved
143 Low OP Warn Action when low oil pressure warning.
144 Low OP Shutdown Action when low oil pressure shutdown.
Action when oil pressure sensor is open
145 OP Sensor Open
circuit.
146 Reserved
147 Low Level Warn Action when controller has low oil level alarm.
148 Reserved
149 Reserved
150 Config1 High Warn
151 Config1 Low Warn
152 Config1 High Shut
153 Config1 Low Shut
154 Config2 High Warn
155 Config2 Low Warn
156 Config2 High Shut
Defined Period output is composed by 2 parts, period output S1 and condition output S2.
NOTE: when delay time and output time both are 0 in period output S1, it is TRUE in
this period.
Example,
Output period: start
Delay output time: 2s
Output time: 3s
Condition output contents: output port 1 is active
Close when condition output active/inactive: close when active (disconnect when inactive);
Output port 1 active, after enter “starts time” and delay 2s, this defined period output is
outputting, after 3s, stop outputting;
Output port 1 inactive, defined output period is not outputting.
NOTE: S1, S2, S3 can be set as any contents except for “defined combination output”
in the output setting.
NOTE: 3 parts of defined combination output (S1, S2, S3) couldn’t include or
recursively include themselves.
Example,
Contents of probably condition output S1: output port 1 is active;
Close when probably condition output S1 is active /inactive: close when active (disconnect
when inactive);
Contents of probably condition output S2, output port 2 is active;
Close when probably condition output S2 is active /inactive: close when active (disconnect
when inactive);
Contents of probably condition output S3: output port 3 is active;
Close when probably condition output S3 is active /inactive: close when active (disconnect
when inactive);
When input port 1 active or input port 2 active, if input port 3 is active, Defined combination
output is outputting; If input port 3 inactive, Defined combination output is not outputting;
When input port 1 inactive and input port 2 inactive, whatever input port 3 is active or not,
Defined combination output is not outputting.
17 Auto Mode Lock mode; all the keys except are inactive, and
will show in the first line of LCD display.
When input is active, controller won’t work under
18 Auto Mode Invalid Auto mode. key and simulate auto key input
does not work.
19 Reserved
20 Reserved
All shutdown alarms are prohibited except
21 Inhibit Alarm Stop emergence stop.(Means battle mode or override
mode)
22 Aux Instrument Mode All outputs are prohibited in this mode.
23 Reserved
Controller will set maintenance time and date as
24 Reset Maintenance
default when input is active.
25 Reserved
NOTE: User should make special declare when order controller if your genset equip
with sensor of 4~20mA.
8 PARAMETER EDITING
Press “+” key and “-” key to scroll screen; select parameter you want to configure and
press “√” key (the parameter will highlight with black), press“+” key or “-” key to
change parameter value, press “√ ” key to move the bit, in fourth bit press“√” key to
confirm setting.
2) Basic Parameter Setting:After controller start, press Basic Parameter Setting
for more than 3s to enter into Basic Parameter >Return
Setting interface; The frequently-used parameters can >Mains Rated Voltage
> Mains Rated Frequency
be set via both Basic Parameter Setting and Advanced >Crank Disconnect
Parameter Setting, however, set the frequently-used
parameters via Basic Parameter Setting is recommended as there are lots of
parameters in Advanced Parameter Setting and inconvenience. The picture on the
right is “Basic Parameter Setting” interface, the parameter which highlight with black
is the current setting one.
3) Date and Time Setting: After controller start,
Date and Time
press and to the Date and Time Setting interface 2013.01.26 (6) 15:19:22
(picture on the right). The digital which highlight with
black is currently adaptable for user by pressing “+”
key and “-” key to increase and decrease the value.
Press “√” key to confirm setting and the bit will right move automatically. Number “6”
in the parenthesis is the day of the week. It is set by the microprocessor based on
current date, so the user does not need to modify it.
NOTE: Maximum set value must over minimum set value in case that the condition of
too high as well as too low will happen.
NOTE: When setting the warning alarm, please set the correct return value; otherwise,
maybe there is abnormal alarm. When setting the maximum value, the return value must
less than set value; When setting the minimum value, the return value must over set value.
NOTE: Please set the generator frequency value as low as possible when cranking, in
order to make the starter be separated quickly as soon as crank disconnect.
NOTE: Configurable input could not be set as same items; otherwise, there are
abnormal functions. However, the configurable output can be set as same items.
NOTE: HGM8110A controller has no items about mains. Pressing and holding
for a long time can exit parameter setting menu directly and set the controller into
standby mode.
9 SENSORS SETTING
1. When reselect sensors, the sensor curve will be transferred into the standard value. For
example, if temperature sensor is SGX (120°C resistor type), its sensor curve is SGX
(120°C resistor type); if select the SGD (120°C resistor type), the temperature sensor
curve is SGD curve.
2. When there is difference between standard sensor curves and using sensor, user can
adjust it in “curve type”.
3. When input the sensor curve, X value (resistor) must be input from small to large,
otherwise, mistake occurs.
4. If select sensor type as “None”, sensor curve is not working.
5. If corresponding sensor has alarm switch only, user must set this sensor as “None”,
otherwise, maybe there is shutdown or warning.
6. The headmost or backmost values in the vertical coordinates can be set as same as
below,
10 COMMISSIONING
Note: If the engine starting battery voltage is 24V, starting output, fuel output and stop
output (according to user’s configuration) should not be less than 2 ohms for battery
cathode resistance, if less than 2 ohms, please expand relays with more than 30A current
in corresponding output. if the engine starting battery voltage is12V, starting output, fuel
output and stop output (according to user’s configuration) should not be less than 1 ohms
12 INSTALLATION
WARNING! When there is load current, transformer’s secondary side prohibit open
circuit.
CAUTION! When controller had been installed in control panel, if need the high voltage
test, please disconnect controller’s all terminal connections, in order to prevent high voltage
into controller and damage it.
Here are the common faults and troubleshooting. If there is any other problem, please
feel free to contact Smartgen’s service.
Symptoms Possible Solutions
Check starting batteries;
Controller no response with
Check controller connection wirings;
power.
Check DC fuse.
Check the water/cylinder temperature is too high or not;
Genset shutdown Check the genset AC voltage;
Check DC fuse.
Check emergence stop button is correct or not;
Check whether the starting battery positive be
Controller emergency stop
connected with the emergency stop input;
Check whether the circuit is open.
Low oil pressure alarm after Check the oil pressure sensor and its connections.
crank disconnect
High water temp. alarm after Check the temperature sensor and its connections.
crank disconnect
Check related switch and its connections according to
Shutdown Alarm in running the information on VFD;
Check programmable inputs.
Check fuel oil circuit and its connections;
Check starting batteries;
Crank not disconnect
Check speed sensor and its connections;
Refer to engine manual.
Check starter connections;
Starter no response
Check starting batteries.
Genset running while ATS not Check ATS;
transfer Check the connections between ATS and controllers.
Check connections;
Check setting of COM port is correct or not;
RS485 communication is Check RS485’s connections of A and B is reverse
abnormal connect or not;
Check RS485 transfer model whether damage or not;
Check communication port of PC whether damage.