Fmm-1, Fmm-101, Fzm-1 & Fdm-1: Monitor Modules With Flashscan®

Four different monitor modules are available for Notifier's intelligent control panels. FMM-1 is a standard-sized module that supervises either a Class A (Style D) or Class B (Style B) circuit of dry-contact input devices. FZM-1 monitors and supervises compatible two-wire, 24 volt, smoke detectors.

Uploaded by

koduvayur2001
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
300 views4 pages

Fmm-1, Fmm-101, Fzm-1 & Fdm-1: Monitor Modules With Flashscan®

Four different monitor modules are available for Notifier's intelligent control panels. FMM-1 is a standard-sized module that supervises either a Class A (Style D) or Class B (Style B) circuit of dry-contact input devices. FZM-1 monitors and supervises compatible two-wire, 24 volt, smoke detectors.

Uploaded by

koduvayur2001
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

dn-6720:B • H-220

FMM-1, FMM-101,
FZM-1 & FDM-1
Monitor Modules with FlashScan®
Intelligent/Addressable Devices

General
Four different monitor modules are available for Notifier’s intel-
ligent control panels for a variety of applications. Monitor mod-
ules supervise a circuit of dry-contact input devices, such as
conventional heat detectors and pull stations, or monitor and
power a circuit of two-wire smoke detectors (FZM-1).
FMM-1 is a standard-sized module (typically mounts to a 4"
[10.16 cm] square box) that supervises either a Class A (Style
D) or Class B (Style B) circuit of dry-contact input devices.
FMM-101 is a miniature monitor module (a mere 1.3" (3.302
cm) H x 2.75" (6.985 cm) W x 0.5" (1.270 cm) D) that super-
vises a Class B (Style B) circuit of dry-contact input devices.
Its compact design allows the FMM-101 to often be mounted
in a single-gang box behind the device it monitors.
FZM-1 is a standard-sized module that monitors and super-

6999cov.jpg
vises compatible two-wire, 24 volt, smoke detectors on a
Class A (Style D) or Class B (Style B) circuit.
FDM-1 is a standard-sized dual monitor module that monitors
and supervises two independent two-wire Style B (Class B)
dry-contact initiating device circuits (IDCs) at two separate, FMM-1 (Type H)
consecutive addresses in intelligent, two-wire systems.
A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor
FlashScan® (U.S. Patent 5,539,389) is a communication pro- (provided) terminates the Style B circuit. No resistor is
tocol developed by NOTIFIER that greatly increases the speed required for supervision of the Style D circuit.
of communication between analog intelligent devices. Intelli-
gent devices communicate in a grouped fashion. If one of the FMM-1 OPERATION
devices within the group has new information, the panel CPU Each FMM-1 uses one of the available module addresses on
stops the group poll and concentrates on single points. The an SLC loop. It responds to regular polls from the control panel
net effect is response speed greater than five times that of and reports its type and the status (open/normal/short) of its
other designs. protocols. Initiating Device Circuit (IDC). A flashing LED indicates that
the module is in communication with the control panel. The
FMM-1 Monitor Module LED latches steady on alarm (subject to current limitations on
the loop).
• Built-in type identification automatically identifies this device
as a monitor module to the control panel. FMM-1 SPECIFICATIONS
• Powered directly by two-wire SLC loop. No additional power Nominal operating voltage: 15 to 32 VDC.
required.
Maximum current draw: 5.0 mA (LED on).
• High noise (EMF/RFI) immunity.
Maximum operating current: 375 µA (LED flashing).
• SEMS screws with clamping plates for ease of wiring.
Maximum IDC wiring resistance: 1,500 ohms.
• Direct-dial entry of address: 01 – 159 on FlashScan sys-
tems; 01 – 99 on CLIP systems. , 01 – 99 on . EOL resistance: 47K ohms.
• LED flashes green during normal operation (this is a pro- Temperature range: 32°F to 120°F (0°C to 49°C).
grammable option) and latches on steady red to indicate
Humidity range: 10% to 93% noncondensing.
alarm.
The FMM-1 Monitor Module is intended for use in intelligent, Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
two-wire systems, where the individual address of each mod- 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
ule is selected using the built-in rotary switches. It provides 2.125" (5.398 cm) deep box.
either a two-wire or four-wire fault-tolerant Initiating Device Cir-
cuit (IDC) for normally-open-contact fire alarm and supervisory FMM-101 Mini Monitor Module
devices. The module has a panel-controlled LED indicator.
• Built-in type identification automatically identifies this device
The FMM-1 can be used to replace MMX-1 modules in
as a monitor module to the panel.
existing systems.
• Powered directly by two-wire SLC loop. No additional power
FMM-1 APPLICATIONS required.
Use to monitor a zone of four-wire smoke detectors, manual • High noise (EMF/RFI) immunity.
fire alarm pull stations, waterflow devices, or other normally- • Tinned, stripped leads for ease of wiring.
open dry-contact alarm activation devices. May also be used
• Direct-dial entry of address: 01 – 159 on FlashScan sys-
to monitor normally-open supervisory devices with special
tems; 01 – 99 on CLIP systems. , 01 – 99 on .
supervisory indication at the control panel. Monitored circuit
may be wired as an NFPA Style B (Class B) or Style D (Class

dn-6720:B • 01/21/09 — Page 1 of 4


• LED flashes during normal operation; this is a programma-

6720m101.wmf
ble option.
• LED latches steady to indicate alarm on command from
control panel.
The FZM-1 Interface Module is intended for use in intelligent,
addressable systems, where the individual address of each
module is selected using built-in rotary switches. This module
allows intelligent panels to interface and monitor two-wire con-
ventional smoke detectors. It transmits the status (normal,
open, or alarm) of one full zone of conventional detectors back
to the control panel. All two-wire detectors being monitored
must be UL compatible with the module. The FZM-1 can be
used to replace MMX-2 modules in existing systems.
FZM-1 APPLICATIONS
Use the FZM-1 to monitor a zone of two-wire smoke detectors.
The monitored circuit may be wired as an NFPA Style B (Class
B) or Style D (Class A) Initiating Device Circuit. A 3.9 K ohm
End-of-Line Resistor (provided) terminates the end of the Style
The FMM-101 Mini Monitor Module can be installed in a sin- B or D (class B or A) circuit (maximum IDC loop resistance is
gle-gang junction directly behind the monitored unit. Its small 25 ohms). Install ELR across terminals 8 and 9 for Style D
size and light weight allow it to be installed without rigid mount- application.
ing. The FMM-101 is intended for use in intelligent, two-wire FZM-1 OPERATION
systems where the individual address of each module is
selected using rotary switches. It provides a two-wire initiating Each FZM-1 uses one of the available module addresses on
device circuit for normally-open-contact fire alarm and security an SLC loop. It responds to regular polls from the control panel
devices. The FMM-101 can be used to replace MMX-101 and reports its type and the status (open/normal/short) of its
modules in existing systems. Initiating Device Circuit (IDC). A flashing LED indicates that
the module is in communication with the control panel. The
FMM-101 APPLICATIONS LED latches steady on alarm (subject to current limitations on
Use to monitor a single device or a zone of four-wire smoke the loop).
detectors, manual fire alarm pull stations, waterflow devices, or FZM-1 SPECIFICATIONS
other normally-open dry-contact devices. May also be used to
monitor normally-open supervisory devices with special super- Nominal operating voltage: 15 to 32 VDC.
visory indication at the control panel. Monitored circuit/device Maximum current draw: 5.1 mA (LED on).
is wired as an NFPA Style B (Class B) Initiating Device Circuit.
Maximum IDC wiring resistance: 25 ohms.
A 47K ohm End-of-Line Resistor (provided) terminates the cir-
cuit. Maximum operating current: 270 µA (LED flashing).
EOL resistance: 3.9K ohms.
FMM-101 OPERATION
Each FMM-101 uses one of the available module addresses External supply voltage (between Terminals T3 and T4):
on an SLC loop. It responds to regular polls from the control DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms
panel and reports its type and the status (open/normal/short) maximum. Current: 90 mA per module maximum.
of its Initiating Device Circuit (IDC). Temperature range: 32°F to 120°F (0°C to 49°C).
FMM-101 SPECIFICATIONS Humidity range: 10% to 93% noncondensing.
Nominal operating voltage: 15 to 32 VDC. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
Maximum operating current: 375 µA.
2.125" (5.398 cm) deep box.
Maximum IDC wiring resistance: 1,500 ohms.
EOL resistance: 47K ohms. FDM-1 Dual Monitor Module
Temperature range: 32°F to 120°F (0°C to 49°C). The FDM-1 Dual Monitor Module is intended for use in intelli-
Humidity range: 10% to 93% noncondensing. gent, two-wire systems. It provides two independent two-wire
initiating device circuits (IDCs) at two separate, consecutive
Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x addresses. It is capable of monitoring normally open contact
0.65" (1.651 cm) deep. fire alarm and supervisory devices; or either normally open or
Wire length: 6" (15.24 cm) minimum. normally closed security devices. The module has a single
panel-controlled LED.
FZM-1 Interface Module NOTE: The FDM-1 provides two Class B (Style B) IDC circuits
ONLY. Class A (Style D) IDC circuits are NOT supported in any
• Supports compatible two-wire smoke detectors. application.
• Supervises IDC wiring and connection of external power
source. FDM-1 SPECIFICATIONS
• High noise (EMF/RFI) immunity. Normal operating voltage range: 15 to 32 VDC.
• SEMS screws with clamping plates for ease of wiring. Maximum current draw: 6.4 mA (LED on).
• Direct-dial entry of address: 01 – 159 on FlashScan sys- Maximum operating current: 750 µA (LED flashing).
tems, 01 – 99 on CLIP systems. Maximum IDC wiring resistance: 1,500 ohms.

Page 2 of 4 — dn-6720:B • 01/21/09


EOL resistance: 47K ohms.
Temperature range: 32° to 120°F (0° to 49°C).
Humidity range: 10% to 93% (non-condensing).
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
2.125" (5.398 cm) deep.
FDM-1 AUTOMATIC ADDRESSING
The FDM-1 automatically assigns itself to two addressable
points, starting with the original address. For example, if the
FDM-1 is set to address “26”, then it will automatically assign
itself to addresses “26” and “27”.
NOTE: “Ones” addresses on the FDM-1 are 0, 2, 4, 6, or 8 only.
Terminals 6 and 7 use the first address, and terminals 8 and 9 use
the second address.

CAUTION:
! Avoid duplicating addresses on the system.

Installation
FMM-1, FZM-1, and FDM-1 modules mount directly to a stan-
dard 4" (10.16 cm) square, 2.125" (5.398 cm) deep, electrical
box. They may also be mounted to the SMB500 surface-mount
box. Mounting hardware and installation instructions are pro-
vided with each module. All wiring must conform to applicable
local codes, ordinances, and regulations. These modules are
intended for power-limited wiring only.
The FMM-101 module is intended to be wired and mounted
without rigid connections inside a standard electrical box. All
wiring must conform to applicable local codes, ordinances, and
regulations.

Agency Listings and Approvals


In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult fac-
tory for latest listing status.
• UL: S635
• ULC: S3705
• FM Approved
• CSFM: 7300-0028:202
• MEA: 457-99-E, 457-99-E Vol. 3, 143-01-E
• U.S. Coast Guard:
– 161.002/23/3 (AFP-200: FMM-1/-101, FZM-1)
– 161.002/42/1 (NFS-640: FMM-1/-101)
• Lloyd’s Register:
– 03/60011/E1 (FMM-1/-101, FZM-1)
– 94/60004/E2 (AFP-200: except FDM-1)
– 02/60007 (NFS-640: FDM-1)

Product Line Information


NOTE: “A” suffix indicates ULC-listed model.
FMM-1(A): Monitor module.
FMM-101(A): Monitor module, miniature.
FZM-1(A): Monitor module, two-wire detectors.
FDM-1(A): Monitor module, dual, two independent Class B
circuits.
SMB500: Optional surface-mount backbox.
NOTE: See installation instructions and refer to the SLC Wiring
Manual, PN 51253.

dn-6720:B • 01/21/09 — Page 3 of 4


Notifier® and FlashScan® are registered trademarks of Honeywell
International Inc.
©2009 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com

Page 4 of 4 — dn-6720:B • 01/21/09

You might also like