FAN

FUNDAMENTALS
ABOUT SYSTEMAIRE
• Over 25 Years in WA’s HVAC market.
• Local sales team for Fantech fans and attenuation
products.
• Engineers with extensive hands-on HVAC project
experience.
• Part of the Elta Group, a family of businesses with
operations in six countries on four continents which,
together with a network of international distributors,
provides quality fans and related air movement
equipment to customers worldwide.
OVERVIEW
• Fundamentals – what’s important to you?
• Fan types & applications
• Fan selection
• The Fan Laws
• Speed Control
• System Effects
• Case studies
What is
important
to you?
Power?
Location?
$
The trade-off…
The fan.
PROPELLOR FANS
Cost: low
Volume: high
Pressure: low
Sound: loud
Efficiency: low

Common uses:
• Transformer rooms
• Switch rooms
• Bin Store, etc.
AXIAL FLOW FANS
Cost: medium
Volume: high
Pressure: medium
Sound: loud
Efficiency: medium

Common uses:
• Just about anything...
CENTRIFUGAL FANS
Cost: high
Volume: medium
Pressure: high
Sound: low
Efficiency: high

Common uses:
• AHU’s to Kitchen
• Just about Anything!
MIXED FLOW FANS
Cost: medium
Volume: medium
Pressure: medium
Sound: medium
Efficiency: medium

Common uses:
• Outside / Exhaust Air
• Classrooms
• Apartments, etc.
FAN SELECTIONS
Consider water
pouring from a tap
into a bucket…
TO CONSIDER...
• Power supply (eg. 415V, 240V, 50Hz)
• Motor enclosure type. (eg. IP55, IP20)
• Gas to be handled. (eg. Paint fumes,
Air)
• Where a roof ventilator is required. Is
discharge to be vertical or horizontal.
FINDING THE RIGHT FAN
• All = 4344 fans
• Duty (1000l/s @ 150Pa) = 727 fans
• Power (3 phase) = 665 fans
• Mounting (in line) = 71 fans
• Noise = 58 db(A) @3m max = 19 fans
• Compliant? (Yes) = 12 fans (6 safe)
• Cost vs. Safety vs. Size
FAN DUTY

• Require an AP adjustable pitch axial fan.


• Look at 500 diameter, 4 Pole, 10 Blades.
• Need 1800 L/s at 120 Pa Static Pressure.
• 1800 L/s = 1.8 m³/s.
Select a fan to do
1800 L/s @ 120 Pa
120 Pa

1800 L/s = 1.8m³/s


Fan needs to be set
to 25 degrees pitch
angle

Next largest motor


above 0.52 kW is 0.55
kW. Therefore need a
0.55kW motor
0.52 kW
SELECTION TIPS

• Keep away from extremities.


• Try to select in the centre of a fan curve when
looking at AP fans.
FAN STALL
• When fan stalls, it can’t produce as much lift.
• Therefore the airflow drops dramatically.
• Can create vibration in stall.
• Fan sounds “rough”, may pulse. Tonal sounds
can increase.
WE HAVE
THE
TECH-
NOLOGY
THE FAN LAWS
FAN (SCALING) LAWS
 Useful for noting the effect of changes in size
and speed

 Valid for fans ‘geometrically similar’

 Applies to fans Airflow, Pressure Generated,


Power Absorbed and Noise Output
FAN LAW: AIRFLOW
FAN LAW: PRESSURE
FAN LAW: ABS. POWER
FAN LAW: NOISE
FAN SCALING: 10% SPEED +

Airflow

Pressure

Power
SPEED
CONTROL
For every litre/second of air
that is unnecessarily moved
through a building, around
2 watts of power are wasted.
Single Phase
SPEED CONTROL

Electronic Speed Controller


100% down to approximately 30%
Power consumption is reduced by up to 70%
Three Phase
SPEED CONTROL

Variable Speed Drives


Sinusoidal Filter?
VSD Shielding?
EC

Variable Speed Fans


sensors & controls direct
BMS integration
FANS &
SYSTEM
EFFECTS
THINK
OUTSIDE
THE
FLANGES
FAN NOT PERFORMING?!
• Fan rotation / wiring?
• Receiving uniform air?
• System resistance under
estimated ?
• System design?
CASE STUDY 1
Tunnel fans
Fan 1 not performing to
specification.
• Fan not pulling full Amps
• Fan performance 80% of design
• Fan sounded like it was hunting eg in stall
• Initial diagnoses was uneven air on
conditions due to transition pieces
• Damper in front of fans disruption air flow on
to blades
CONCLUSION
• While there were installation issues the
real problem was the Type arrangement
being Type “D” not Type “A”
• Increased blade pitch angle will increase
load on motor and satisfy client of
performance.
• Air velocities in the tunnel are to spec
before pitch change.
CASE STUDY 2
Building the Education
Revolution (BER) program
FAN NOT PERFORMING
• Fan did not perform even when
new
• Service tech could not find any
problem
• Possible fan too small
• Very quiet operation
• Client adamant there was a fan
problem
CONCLUSION
• Install the fan!
THANK YOU