DN-60239:C3

RP-2001(E)
Deluge - Preaction Control Panel

Conventional Releasing Panels

General
The RP-2001 is a six-zone FACP for single and dual hazard
deluge and preaction applications. The RP-2001 provides reli-
able fire detection, signaling and protection for commercial,
industrial and institutional buildings requiring water-based
releasing. The RP-2001 is compatible with System Sensor’s i3
detectors which are conventional smoke detectors that can
transmit a maintenance trouble signal to the FACP indicating
the need for cleaning and a supervisory ‘freeze’ signal when
the ambient temperature falls below the detector rating of
approximately 45°F (7.22°C). In addition, the control panel is
compatible with conventional input devices such as two-wire
smoke detectors, four-wire smoke detectors, pull stations,
waterflow devices, tamper switches and other normally-open
contact devices. Refer to the Notifier Device Compatibility
Document for a complete listing of compatible devices.
Four outputs are programmable as NACs (Notification Appli-

RP2001.jpg
ance Circuits) or releasing circuits. Three programmable
Form-C relays (factory programmed for Alarm, Trouble and
Supervisory) and 24 VDC special application resettable and
non-resettable power outputs are also included on the main
circuit board. The RP-2001 supervises all wiring, AC voltage, • Built-in Programmer.
battery charger and battery level. • ANN-BUS for connection to optional devices (up to 8 total
Activation of a compatible smoke detector or any normally- of any of the following):
open fire alarm initiating device will activate audible and visual – N-ANN-80 Remote LCD Annunciator
signaling devices, illuminate an indicator, display alarm infor- – N-ANN-I/O LED Driver
mation on the panel’s LCD, sound the piezo sounder at the
– N-ANN-S/PG Printer Module
FACP, activate the FACP alarm relay and operate an optional
module used to notify a remote station or initiate an auxiliary – N-ANN-RLY Relay Module
control function. – N-ANN-LED Annunciator Module
The RP-2001E offers the same features as the RP-2001 but • 80-character LCD display (backlit).
allows connection to 240 VAC. Unless otherwise specified, the • Real-time clock/calendar with daylight savings time control.
information in this data sheet applies to both the 120 VAC and • History log with 256 event storage.
240 VAC versions of the panels.
• Piezo sounder for alarm, trouble and supervisory.
Features • 24 volt DC operation.
• Low AC voltage sense.
• Listed to UL Standard 864, 9th edition.
• Outputs Programmable for:
• FM Approved.
– Releasing circuits or NACS
• Designed for sprinkler standards NFPA 13, 15 and 16.
• NACs programmable for:
• Dual hazard operation.
– Silence Inhibit
• Adjustable waterflow discharge timer and two soak timers.
– Auto-Silence
• Cross-zone (double-interlock) capability.
– Strobe Synchronization
• Six programmable Style B (Class B) IDCs (Initiating Device
Circuit). – Selective Silence (horn-strobe mute)
• System Sensor i3 series detectors compatible. – Temporal or Steady Signal
• Four programmable Style Y (Class B) output circuits - (spe- – Silenceable or Non-silenceable
cial application power). – Release Stage Sounder
• Strobe Synchronization: • Disable/Enable control per input zone and output zone.
– System Sensor • Extensive transient protection.
– Wheelock • Automatic battery charger with charger supervision.
– Gentex • Optional Dress Panel DP-51050 (red).
– Faraday • Optional Trim Ring TR-CE (red) for semi-flush mounting the
– Amseco cabinet.
• Three programmable Form-C relays. • Optional N-CAC-5X Class A Converter Module for Outputs
and IDCs.
• 7.0 amps total 24 VDC output current.
• Optional 4XTM Municipal Box Transmitter Module.
• Resettable and non-resettable output power.

DN-60239:C3 • 3/6/2017 — Page 1 of 4


• Optional Digital Alarm Communicators (411, 411UD, • Standby Current: 4 mA.
411UDAC). Refer to the Notifier Device Compatibility Document for listed
• Optional ANN-SEC card for a secondary ANN-BUS. compatible devices.
PROGRAMMING AND SOFTWARE: Notification Appliance and Releasing Circuit(s) - TB5 and
TB7
• Custom English labels (per point) may be manually entered
or selected from an internal library file. • Four Output Circuits.
• Three programmable Form-C relay outputs. • Style Y (Class B) or Style Z (Class A) with optional con-
verter module.
• Pre-programmed and custom application templates.
• Special Application power.
• Continuous fire protection during online programming at the
front panel. • Supervised and power-limited circuitry.
• Program Check automatically catches common errors not • Normal Operating Voltage: Nominal 24 VDC.
linked to any zone or input point. • Maximum Signaling Current: 7.0 amps (3.0 amps special
application, 300 mA regulated maximum per NAC).
USER INTERFACE:
• End-of-Line Resistor: 4.7K Ohms, 1/2 watt (PN 71252).
• Integral 80-character LCD display with backlighting.
• Max. Wiring Voltage Drop: 2 VDC.
• Real-time clock/calendar with automatic daylight savings
Refer to the Notifier Device Compatibility Document for com-
adjustments.
patible listed devices.
• ANN-Bus for connection to remote annunciators.
Form-C Relays - Programmable - TB8
• Audible or silent walk test capabilities.
• Piezo sounder for alarm, trouble, and supervisory. • Relay 1 (factory default programmed as Alarm Relay).
• Relay 2 (factory default programmed as fail-safe Trouble
Relay).
Controls and Indicators
• Relay 3 (factory default programmed as Supervisory
LED INDICATORS Relay).
• FIRE ALARM (red) • Relay Contact Ratings:
• SUPERVISORY (yellow) – 2 amps @ 30 VDC (resistive)
• TROUBLE (yellow) – 0.5 amps @ 30 VAC (resistive)
• AC POWER (green) Auxiliary Trouble Input – J6
• ALARM SILENCED (yellow) The Auxiliary Trouble Input is an open collector circuit which
• DISCHARGE (red) can be used to monitor external devices for trouble conditions.
It can be connected to the trouble bus of a peripheral, such as
CONTROL BUTTONS a power supply, which is compatible with open collector cir-
• ACKNOWLEDGE cuits.
• ALARM SILENCE Special Application Resettable Power - TB9
• SYSTEM RESET (lamp test) • Operating Voltage: Nominal 24 VDC.
• DRILL • Maximum Available Current: 500 mA - appropriate for
AC Power – TB1 powering 4-wire smoke detectors (see note 1).
• RP-2001: 120 VAC, 60 Hz, 3.66 amps. • Power-limited Circuitry.
• RP-2001E: 240 VAC, 50/60 Hz, 2.085 amps. Refer to the Notifier Device Compatibility Document for com-
patible listed devices.
• Wire size: minimum #14 AWG (2.0 mm2) with 600V insula-
tion. NOTE: Total current for resettable power, nonresettable power
and Output Circuits must not exceed 7.0 amps.
• Supervised, nonpower-limited.
Battery (sealed lead acid only) – J12: Special Application Resettable or Nonresettable Power -
TB9
• Maximum Charging Circuit - Normal Flat Charge: 27.6
VDC @ 1.4 amp. Supervised, nonpower-limited. • Operating Voltage: Nominal 24 VDC.
• Maximum Charger Capacity: 26 Amp Hour battery (two • Maximum Available Current: 500 mA (see note 1).
18 Amp Hour batteries can be housed in the FACP cabinet. • Power-limited Circuitry.
Larger batteries require separate battery box such as the • Jumper selectable by JP31 for resettable or nonresettable
BB-26 or NFS-LBBR). power.
• Minimum Battery Size: 7 Amp Hour. Refer to the Notifier Device Compatibility Document for com-
Initiating Device Circuits - TB4 and TB6 patible listed devices.
• Alarm Zones 1 - 5 on TB4.
• Alarm Zone 6 on TB6.
• Supervised and power-limited circuitry.
• Style B (Class B) wiring with Style D (Class A) option.
• Normal Operating Voltage: Nominal 20 VDC.
• Alarm Current: 15 mA minimum.
• Short Circuit Current: 40 mA max.
• Maximum Loop Resistance: 100 Ohms.
• End-of-Line Resistor: 4.7K Ohms, 1/2 watt (PN 71252).

Page 2 of 4 — DN-60239:C3 • 3/6/2017


Product Line Information
RP-2001: Six-zone, 24 volt Deluge-Preaction Control Panel
(includes backbox, power supply, technical manual, and a
frame & post operating instruction sheet) for single and dual
hazard deluge and preaction applications.
RP-2001E: Same as above but allows connection to 240 VAC.
NOTE: For ULC-listed model, see DN-60442.
N-CAC-5X: Class A Converter Module can be used to convert
the Style B (Class B) Initiating Device Circuits to Style D (Class
A) and Style Y (Class B) Output Circuits to Style Z (Class A).
NOTE: Two Class A Converter modules are required to convert all
four Output Circuits and six Initiating Device Circuits.
4XTM: Transmitter Module provides a supervised output for
local energy municipal box transmitter and alarm and trouble
reverse polarity. It includes a disable switch and disable trou-
ble LED.
N-ANN-80(-W): LCD Annunciator is a remote LCD annuncia-
tor that mimics the information displayed on the FACP LCD
display. Recommended wire type is unshielded. (Basic model
is black; order -W version for white; see DN-7114.)
N-ANN-LED: Annunciator Module provides three LEDs for
each zone: Alarm, Trouble and Supervisory. Ships with red or
black enclosure (see DN-60242).
N-ANN-RLED: Provides alarm (red) indicators for up to 30
input zones or addressable points. (See DN-60242).
N-ANN-RLY: Relay Module, which can be mounted inside or
outside the cabinet, provides 10 programmable Form-C relays.
(See DN-7107.)
N-ANN-S/PG: Serial/Parallel Printer Gateway module pro-
vides a connection for a serial or parallel printer. (See DN-
7103.)
N-ANN-I/O: LED Driver Module provides connections to a
user supplied graphic annunciator. (See DN-7105.)
ANN-SEC: The ANN-SEC module provides a secondary
ANN-BUS port for more wiring flexibility. (See #53944.)
DP-51050: Dress panel (red) is available as an option. The
dress panel restricts access to the system wiring while allow-
ing access to the membrane switch panel.
TR-CE: Trim-ring (red) is available as an option. The trim-ring
allows semi-flushing mounting of the cabinet.
BB-26: Battery box, holds up to two 26 Amp Hour batteries
and CHG-75.
NFS-LBBR: Battery box, houses two 55 Amp Hour batteries,
red.
BAT Series Batteries: Refer to DN-6933.
PRN-6: UL-listed compatible event printer. Dot-matrix, tractor-
fed paper, 120 VAC.
PRN-7: UL-listed compatible event printer. Dot-matrix, tractor-
fed paper, 120 VAC.
PRT-PK CABLE: Programming cable. Used to update the
FACPs Flash firmware. (Also requires an RS485 to RS232
converter).

DN-60239:C3 • 3/6/2017 — Page 3 of 4


SYSTEM SPECIFICATIONS

System Capacity useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme tempera-
• Annunciators ...................................................................... 8 ture ranges and humidity. Therefore, it is recommended that
this system and its peripherals be installed in an environment
Electrical Specifications with a normal room temperature of 15 – 27°C/60 – 80°F.
• RP-2001 (FLPS-7 Power Supply): 120 VAC, 60 Hz, 3.66
amps. NFPA Standards
• RP-2001E (FLPS-7 Power Supply): 240 VAC, 50/60 Hz, The RP-2001(E) complies with the following NFPA 72 Fire
2.085 amps. Alarm Systems requirements:
• Wire size: minimum 14 AWG (2.0 mm²) with 600 V insula- – NFPA 13 Installation of Sprinkler Systems
tion, supervised, nonpower-limited.
– NFPA 15 Water Spray Fixed Systems
– NFPA 16 Deluge Foam-Water Sprinkler and Foam-Water
Cabinet Specifications Spray Systems
Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x – NFPA 72 National Fire Alarm Code for Local Fire Alarm
0.72" (1.82 cm.) deep. Backbox: 19.00" (48.26 cm.) high x Systems and Remote Station Fire Alarm Systems
16.65" (42.29 cm.) wide x 5.25" (13.34 cm.) deep. Trim Ring (requires an optional Remote Station Output Module)
(TR- CE): 22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide.
Agency Listings and Approvals
Shipping Specifications
The listings and approvals below apply to the basic RP-
Weight: 20.7 lbs. (9.4 kg) 2001(E) and RP-2001(E)E fire alarm control panels. In some
Dimensions: cases, certain modules may not be listed by certain approval
agencies, or listing may be in process. Consult factory for lat-
– Height 20.00" (50.80cm) est listing status.
– Width 22.50" (57.15cm)
• UL: S635
– Depth 8.50" (21.59cm)
• FM approved
• CSFM: 7165-0028:0245
Temperature and Humidity Ranges
• MEA: 333-07-E
This system meets NFPA requirements for operation at 0 –
NOTE: For ULC-listed model, see DN-60442.
49°C/32 – 120°F and at a relative humidity 93% ± 2% RH
(noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the

NOTIFIER® and System Sensor® are registered trademarks of Honeywell


International Inc.
©2017 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Assembled in the USA
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com

Page 4 of 4 — DN-60239:C3 • 3/6/2017