Elevator Pressurization

The document provides technical specifications for pressurizing an elevator shaft in a 40-story building. It includes details on building dimensions, temperature differences inside and out, leakage rates for the building walls and elevator walls, required pressure differences and flow rates for the basement floors and the remaining stories. The total volume flow rate required to properly pressurize the elevator shaft is calculated to be 6.52 cubic meters per second.

Uploaded by

neng oudom
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
184 views1 page

Elevator Pressurization

The document provides technical specifications for pressurizing an elevator shaft in a 40-story building. It includes details on building dimensions, temperature differences inside and out, leakage rates for the building walls and elevator walls, required pressure differences and flow rates for the basement floors and the remaining stories. The total volume flow rate required to properly pressurize the elevator shaft is calculated to be 6.52 cubic meters per second.

Uploaded by

neng oudom
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 1

Elevator Pressurization

General Data
NO. of Stories 40
Height Per Story 3.5 m
NO. of Cars 1
OUTSIDE DESIGN TEMPRATURE (46 c) 319 K
BUILDING DESIGN TEMPRATURE (22 c) 295 K
Minimum Design Pressure Diffrence (dPebt) 13 Pa
2
Total Area of Building Wall Per Story 400 m
Leakage Area of Building with Tight Wall 0.00007 area ratio
Area Between Building & Outside (Abo) 0.028 m2
2
Total area for Elevator Wall Per Floor 35 m
Leakage Area of Elevator With Average Wall 0.00084 area ratio
Area Between Elevator & Building (Aeb) 0.0294
Temprature Factor (B) -0.88 Pa/m

Basement Floor
Total area for Building Wall Per Floor (Basement) 580 m2
2
Area Between Building & Outside (Abo) 0.0406 m
2
Total area for Elevator Wall Per Floor 35 m
2
Area Between Elevator & Building (Aeb) 0.0294 m

Effective Area (Asbo) 0.024 m2


Pressure Diffrence Between Elevator & Outside at the top (dPe ot) 27.33 Pa
Pressure Diffrence Between Elevator & Outside at the Bottom (dPe ob) 150.87 Pa
3
Volume Flow Rate Required for Basement per Story 0.25 m /s
3
Volume Flow Rate Required for Basement for 3 Stories 0.74 m /s

the Rest of the Building


Height 129.5 m
Pressure Diffrence Between Elevator & Outside at the Bottom (dP eob) 141.61 Pa
Average Pressure Diffrence 84.47 Pa
Effective Area (Asbo) 0.0203 m2
3
Volume Flow Rate Required for Each Story 0.156 m /s
3
Volume Flow Rate Required for 37 story 5.78 m /s

Total Flow Required 6.52


3
m /s