Study of Power Quality Issues
Study of Power Quality Issues
March 2014
A.D Thirumoorthy
Principal Investigator
Tamilnadu energy development Agency, Coimbatore
Dr. C. Chellamuthu
Co-Principal Investigator
RMK Engineering College, Kavaraipettai
ACKNOWLEDGEMENTS
CHAPTER 1
LITERATURE REVIEW
The wind energy sector has grown significantly in India despite ups and
downs. Today, after having surmounted many problems, wind energy development
in India is known to be a very mature industry. In India, wind farms are
concentrated in rural areas, where transmission and distribution grids tend to be
very weak and often lack the capacity to tie-in large amounts of wind power. The
insufficient capacity of the power system can cause large variations in steady state
voltage and power outages. Substations are not always equipped with automatic
voltage regulators, further adding to the complications and instability. Inadequate
grid capacity and equipment affect both the efficiency and operation of the wind
turbines. Thus with the increasing penetration of wind power, there is a need to
study the impact of their interconnection to grid.
In India FSIG (Fixed Speed Induction Generator) is the most commonly
used machine. A few turbines are equipped with DDSG (Direct Drive Synchronous
Generator). So, this project will focus on the modeling of FSIG and DDSG
systems. Analysis will be carried out with detailed and reduced order models.
Complexities of the various parts of a wind electric system model, such as
aerodynamic conversion, drive-train and generator representation will be analyzed.
Machines may be represented with active stall and pitch mechanisms. The inverter
modeling will be taken up for DDSG systems. Finally, a comparison of both the
models for WECS will be done. A conclusion on the option of generator and its
parameters to allow a higher penetration of wind power into the grid may be
provided.
In this work, the steady state behavior of WECS will be studied using load
flow analysis. It is important to study the dynamic performance because the
performance of wind turbines is affected by disturbances in the grid frequency
variations, voltage quality and fluctuations in steady state voltage. Wind power
output is reduced during disturbances simply because turbines go off-line in an
2
probability of a particular wind speed occurring can be estimated. This can be done
by assuming a Weibull or a Rayleigh probability distribution. Once the wind speed
is known, the power injected into the grid can be calculated by means of the wind
turbine power curve. Therefore, assessment of steady state performance of
electrical networks with WECS is not as simple as with conventional generation
and can be planned from a probabilistic point of view only. Several researchers in
India and abroad have developed steady state models for various types of WECS
and demonstrated the application of these models for both deterministic and
probabilistic load flow analysis.
The fast growth of wind power in India has led to the concern about the
impact of WECS on the dynamics of electric power systems. With the increase in
wind power penetration into the utility grid, the power quality and the dynamic
security of the power system might be affected because of the following reasons:
CHAPTER 2
DATA COLLECTION AND ANALYSIS OF WIND FARM
LOCATED AT PEEDAMPALLI SUBSTATION
2.1 Introduction
The wind farm of fixed speed induction generator is identified at the
Coimbatore district in Tamilnadu for measuring the power quality issues. Two
power quality analyzer Fluke and Dranetz are connected at the individual wind
turbines and at the Group control circuit breaker. The various power quality events
such as sag, swell, impulsive transient, oscillatory transient and interruption are
measured.
2.2 Fixed Speed Induction Generator (FSIG)
TEDA has selected peedampalli substation Coimbatore district for recording
the power quality events with the help of power analyzers according to EN50160
standard. The substation consists of six fixed speed wind turbine units connected
through 11kv line. The schematic diagram of peedampalli wind farms, its location
and distances from the substation are shown in Figure 2.1.
The each wind turbine generates 600KW at 690V. The total capacity of this
wind farm is 3.6MW.The fixed speed squirrel cage Induction generator directly
connected to LV side of transformer rated at 800KVA, 690V/11KV. The HV side
of the transformer is connected to 11KV common feeder .The 11KV peedampalli
substation is connected to 110KV substation through transformer rated at 16MVA,
11KV/110KV
Two data loggers were installed at different location in wind farm substation
to record the Voltage quality or disturbance according to EN50160 European
standard. The Power quality Analyzer manufactured by Dranetz was installed at
group control circuit breaker at 11KVsubstation .Another power quality analyzer
manufactured by Fluke435 was installed at wind station, No: SE859 on the LV side
of 690V/11KV transformer. The period of recording of the events in the system is
from 24.07.2011 to 21.08.2011, (29 days).
5
4. Interruption
Short duration temporary interruption
Long duration interruption
2.5 Conclusion
The power quality issues related to grid connected wind farm have been
recorded and the possible causes are identified. Two power quality analyzers of
different manufacturers are used at Peedampalli substation, Coimbatore district
from 24.7.11 to 21.8.11(29 days). The Fluke 435 series analyzer installed at wind
turbine on LV side of transformer and the Dranetz analyzer was installed at
substation. Totally 78 mutually exclusive events such as Transient, Sag, Swell and
Interruptions were recorded. 26 data recorded by the fluke 435 matches with 26
same data of Dranetz in spite of a microsecond delay. 34 Impulse transients of
time duration of nanosecond to microsecond were recorded. 10% to 20% voltage
spikes were due to Switching of capacitance, Switching of isolator and utility fault
clearing. It is observed that system stability was maintained even with these
disturbances. An oscillatory transient is a sudden change in the steady state
condition of the voltage, current or both, at both the positive and negative signal
limits, oscillating at the natural system frequency. Only 1 oscillatory transient has
been identified. Totally 27 events of Sag were recorded. The main reason for sag
was due to sudden increase in the load. It was seen from the recorded graph,
voltage drop varied from 40% to 60% of the nominal value. Totally 3 events of
Swell due to sudden removal of load and sudden change in wind speed were
recorded. Voltage rise was about 10% of nominal value. There were 2 events of
Interruption due to switching of wind turbine and sudden drop in wind speed for
the period ranging from second to minute.
It is observed from the various events, 35 events were transient in nature and
about 27 sag events, totaling to 78. Therefore, dynamic simulation of Peedampalli
substation in DIgSILENT was necessary to study the sag and transient events
14
CHAPTER 3
SIMULATION OF THE PEEDAMPALLI SUBSTATION
3.1 Introduction
The steady and dynamic state stabilities are analyzed for the grid connected
Peedampalli wind farm located at Coimbatore district .The power quality analyzers
Dranetz and Fluke were connected at this substation to record the various power
quality issues. The general structure of fixed speed wind electric system is shown
in Figure 3.1
software provide the ability to simulate load flow, RMS fluctuations and transient
events in the same environment. DIgSILENT provides a comprehensive library
models for electrical components in the power system e.g. generators, motors,
power plant controllers, dynamic loads and various passive network elements, such
as lines, transformers, static loads and shunts. In the present study , we used the
grid model with the electrical components of wind turbine and built in
standard component models available in the DIgSILENT library. The models of
the wind speed, aerodynamic model, shaft model, and pitch angle control model of
the wind turbines are implemented in the Dynamic Simulation Language
(DSL).Each individual model are built with individual block definition (blk). The
mathematical equations of the individual model are written in the block definition
in DSL form. The values of parameter variable are entered with help of common
model. A Frame is a type of block definition which includes a number of slots for
integrating the various blocks defined. All the individual blocks such as turbine
blk, shaft model blk, pitch angle controller blk and built in model of Induction
machine (ASM blk) are connected together through the slot with help of Frame
definition. The Figure 3.2 shows the frame definition block. In order to connect
the wind electric system to the grid, the composite model is used. In the composite
model, a frame is selected for linking the individual slots to the variables of the
common model. The Figure 3.3 shows the composite model of wind electric
system. In this software, the simulation of EMT (Electromagnetic Transient), RMS
(Electromechanical Transient), Fault, Optimal load, Reliability and Harmonic load
flow including Flickering can be carried out.
16
Figure 3.2: Frame definitions to form slots to integrate all the blocks
Table 3.1 Grid Bus bar Voltage Increased from 110kV to 121 kV
Table 3.2 Grid Bus bar Voltage decreased from 110kV to 100 kV
Si. Power system RMS simulation of steady state
No component analysis
1. Generator 1 0.60MW,0.63kV,-0.29MVAR,0.6kA
2. Generator 6 0.60MW,0.63kV,-0.29MVAR,0.6kA
3. Feeder 11kV 10kV
4. Feeder 110kV 100kV
5. Grid Frequency 50Hz
external grid supplies the power to compensate extra load. Therefore the bus bar
frequency is remaining constant as shown in Table 3.4. In this software, there is a
facility to increase or decrease the grid frequency. The grid frequency is increased
to 51Hz from 50Hz. It is observed that the generator real power and current is
increased but the generator bus bar voltage remain constant as shown in Table
3.5.As the grid frequency decreased, it is observed that generator real power and
current is decreased but voltage remain constant as shown in Table 3.5a.
Table 3.3 Frequency variation at each bus bar with light load
Si.No Element Name Frequency Value
1 Generator Bus 1 50
2 Generator Bus 2 50
3 Generator Bus 3 50
4 Generator Bus 4 50
5 Generator Bus 5 50
6 Generator Bus 6 50
7 Feeder 11 kV 50
8 Feeder 110 kV 50
Table 3.4 Frequency variation at each bus bar when the load is more than
generation
Si.no Element Name Frequency Value
1 Generator Bus 1 50
2 Generator Bus 2 50
3 Generator Bus 3 50
4 Generator Bus 4 50
5 Generator Bus 5 50
24
6 Generator Bus 6 50
7 Feeder 11kV 50
8 Feeder 110kV 50
comes nearer to the cut in speed of 3.5m/s, the induction generator behaves like
an induction motor and starts absorbing the reactive and real power from the grid
as shown in the Table 3.8 (negative sign in real and reactive powers indicate its
absorbs the power ).
Table 3.6 Wind velocity (V=12m/s)
Si. Power system RMS simulation of steady state
No Component analysis
1 Generator 1 0.6MW,-0.3MVAR, 0.526kA
2. Generator 6 0.6MW,-0.3MVAR, 0.526kA
3. Feeder 11kV 11kV
4. Feeder 110kV 110kV
Figure 3.11: Variation of active power, reactive power, voltage and current at
generator 6 during the short circuit
Figure 3.12: Voltage dip at generator bus bar and the active power of
generator 1 during the short circuit
29
Figure 3.14: Speed and torque oscillation during the short circuit interval
30
Figure 3.15: Voltage sag at the bus bars during sudden increase in the load
31
Figure 3.16: Line voltages of Generator bus bars during sudden increase in
load
3.6.3 Flickering
The IEC 61000-4-15 standard specifies the function and design of apparatus
for the measurement of flicker, termed the "Flicker meter‖. The Power
Factory provides a Flicker meter command for the calculation of the short-term and
long-term flicker according to IEC 61000-4-15.
The continuous and switching operations give different types of flickering.
With the help of harmonic load flow in the DIgSILENT software the long term and
the short term flickering due to continuous and switching operations can be
calculated with the constant wind speed of 12m/s and with SCC equal to 15MVA
for various grid impedance angles (30˚, 50˚, 70˚, 85). The Table 3.9 shows the
flickering data at the various generator bus bar for 30˚ impedance value at wind
speed Vw=12m/s and SSC=15MVA .The value of Pst, and Plt for continuous and
switching operations for 30˚ are plotted and shown in Figures 3.17.
32
Table 3.9 Flickering data at the bus bar for 30˚ impedance value for
Vw=12m/s and SSC=15MVA
Short-Term Long-Term Short-Term Short-Term
Flicker Flicker Flicker Flicker
Disturbance Disturbance Disturbance Disturbance
Factor Factor Factor Factor
Si. Continuous Continuous Switching Switching
No Element Operation Operation Operation Operation
Generator 1
1. bus bar 0.085264 0.085264 0.223803 0.214897
Generator 2
2. bus bar 0.085264 0.085264 0.223803 0.214896
Generator 3
3. bus bar 0.085264 0.085264 0.223803 0.214896
Generator 4
4. bus bar 0.085264 0.085264 0.223803 0.214896
Generator 5
5. bus bar 0.085263 0.085264 0.223802 0.214896
Generator 6
6. busbar 0.08526 0.085263 0.223799 0.214893
Transformer
7. busbar 1 0.084779 0.08526 0.223793 0.214887
0.25 Variable
Pst continous operation
Plt continous operation
Pst switching operation
Plt switching operation
0.20
Flickering
0.15
0.10
0.05
Figure 3.17: Plot of Pst, and Plt for continuous and switching operations for
30˚
The RMS simulation is executed for minimum of 600sec.The values of Pst and
Plt measured with help flicker meter are 0.084563 and 0.225468 respectively.
Figure 3.19 Simulated voltage sag in 11kV bus bar at peedampalli substation
3.7.4 Swell
Voltage swell is an increase (between 10% and 90%) in RMS voltage at a
power frequency for duration from 0.5 cycles to 1 min. In the designed network,
the low voltage loads which are connected to the 11kV bus bar are disconnected.
The voltage thus rises from its nominal value of 1 p.u to1.01 p.u shown in Figures
3.26 to 3.27. The Figure 3.28 shows the measured waveform which is similar to the
simulated one.
40
Under the steady state analysis, the wind speed is considered as constant.
The performances of wind farm are observed under the variations in grid voltage
and wind speed. If the wind velocity is decreased below its rated value of 12m/s,
the generated power and current of the generator 1 and 6 are reduced. At 3m/s, the
induction generator acts as a motor absorbing the real power from the grid. The
110kV grid bus bar voltage is varied in steps. As the grid bus bar voltage is
42
increased, the generated power remains constant and the current decreases. The
generators absorb more reactive power from the grid. If the grid voltage is
decreased, the generated real power again remains constant, current increases and
reactive power absorption from the grid decreases. The system frequency remains
constant with increase or decrease in load demand since the system connected to
external grid which behaves like an infinite bus bar.
Under dynamic analysis, wind speed is assumed to vary from cut in speed to
cut out speed (3.5m/s to 20m/s). As the wind turbines are a few kilometers apart,
the wind speed at individual wind turbines are assumed different values in the
simulation. Various scenarios such as Transient stability analysis, three phases
Fault, sudden increase of load, load flow harmonics and wind variation were
simulated for 600 sec. The wind generator 1 is a few km away from grid bus bar
and the generator 6 which is nearer to the grid bus bar are taken for the analysis.
The wind generator is pitch controlled to generate constant real power for speeds
above the rated value. The three-phase symmetrical fault is applied at 11kV bus bar
t=5 sec for the duration of 500ms for the simulation time of 20 seconds. The
voltage at 11kV bus bar drops to zero and the other bus bar voltages near to the
fault are decreased. At the 11kV bus bar, industrial load was suddenly included for
a short span of time about 300 milliseconds. During this interval, there is a sudden
60% dip in the voltage level at 11kV feeder and generator bus bars. The harmonics
were injected at the generator bus and its effects were identified at different bus
bars with the help of harmonic load flow analysis. The values of P st and Plt for
continuous and switching operation are calculated using Flicker meter for various
impedance angle 30˚, 50˚, 70˚and 85˚ at the point of measurement.
The comparison between the results of the simulations and measurements
was carried out to validate the model developed for the peedampalli substation.
During this study, power quality issues such as voltage sag, interruption, oscillatory
transient and interruption were recorded. The sags are momentary in nature and
43
they occur due to sudden inclusion of motor at 11kV bus bar. The 30% voltage dip
is observed in the simulated and measured result for 5 cycle duration. The
capacitive switching is considered as one of the causes of the oscillatory transient
in the network. The capacitor is switched off after eight sec, the oscillations in the
line voltage of the generators 1 and 6 are observed. The measured and simulated
waveforms are well matched with each other. The interruption waveform occurs
due to tripping of the generator and the short circuit. The generator 1 is tripped for
a short span of time; the line-to-line voltage of generator 1 suddenly starts decaying
and becomes zero. It is restored back to the normal operation after the closure of
the circuit breaker. The measured voltage during interruption is very similar to the
simulated voltage.
44
CHAPTER 4
DATA COLLECTION AND ANALYSIS OF WIND FARM
LOCATED AT PETHAPPAMPATTY WIND FARM
4.1 Introduction
The Substation consists of four wind farm feeder namely Pukkulam, SV
Patty, Eluppanagaram and Ponneri connected to the 33kV feeder. The station was
constructed and commissioned by M/s Gamesa during the year of 2010-11. The
wind turbines installed in the wind farm are variable speed doubly fed induction
generators (DFIG). The wind farm layout is shown in Figure 4.1
The Pukkulam feeder, consisting of 12 units of variable speed wind turbine
connected to doubly fed induction generator with rating 600 kW at 11kV is shown
in Figure 4.2.The total capacity of this feeder is 7.2 MW. The DFIG injects the
power into the grid from the stator and the rotor with the help of inverter and
converter. The voltage generated by the DFIG is directly connected to LV side of
the transformer rated at 25MVA at 11/33kV. The HV side of the transformer is
connected to the common 33kV feeder.
SV Patty Feeder consists of 17 units of variable speed wind turbine
connected to DFIG which generates 600kW at 11kV as shown in Figure 4.3. The
total capacity of this wind feeder is 10.2MW. The DFIG is directly connected to
the LV side of the 11/33kV transformer. The HV side of the transformer is
connected to common 33kV feeder.
Eluppanagaram feeder has 18 units of variable speed wind turbine connected
to DFIG as shown in Figure 4.4. The total power capacity of this wind feeder is
10.8MW.The Ponneri feeder consists of 9 units of wind electric system having a
total power capacity of 5.4MW. All the DFIG are connected to the LV side of
11/33 kV transformer as shown in Figure 4.5.
45
All the four wind farm feeders are connected to a common 33kV feeder. The
power transformers, 33/110 kV and 110/230kV are used to step up the voltage
from 11kV to 230 kV for connecting the wind electric system to the 230kV grid.
The Power Quality analyzers were installed at various locations in the
Pethappampatty substations from 13/04/2012 to 24/05/2012 (43 days).Three
different Power Quality meter was installed: The Fluke 435 meter was installed at
wind station connected to Pukkulam feeder using the current transformers. The
other Power Quality analyzer manufactured by Dranetz was installed at feeder
breaker in Pukkulam substation. The third Power Quality analyzer, HIOKI was
installed at 110kV circuit breaker point.
transient is a sudden change in the steady state condition of the voltage, current or
both, at both the positive and negative signal limits, oscillating at the natural
system frequency. Only 25 oscillatory transient has been identified. Totally 2
events of Sag and Swell were recorded. The main reason for sag was the sudden
increase in the load. It is seen from the recorded graph, voltage drop varied from
40% to 60% of the nominal value. Totally 2 events of Swell due to sudden removal
of load and sudden change in wind speed were recorded. Voltage rise was about
10% of nominal value. Two events of Interruption occurred at wind generator
station due switching of wind turbine and sudden drop in wind speed for the period
ranging from second to minute.
60
CHAPTER 5
DATA COLLECTION AND ANALYSIS OF WIND FARM AT
CHINNAPUTHUR SUBSTATION
5.1 Introduction
The Chinnaputhur substation was constructed and commissioned by Enercon
Pvt Limited in the year 2008 and is located at Dharapuram district. The wind
turbines installed in this wind farm are variable speed Permanent Magnet
Synchronous Generators (PMSG).
5.2 Substation layout
The layout of the substation of Chinnaputhur is shown in Figure 5.1. It is
seen that the substation has fourteen wind farm feeders (E1- E14) of different
rating that are connected to a 22kV bus bar. Each turbine of the wind farm is
capable of generating 0.85MW at 0.44kV and is connected to a transformer of
rating 0.950MVA, 0.44kV/22kV. This connection is realized with a converter and
an inverter control system.
The HT side of the unit transformer of the wind generator is connected to the
22kV bus bar. This 22kV bus bar is connected to 110kV bus bar through the two
identical transformers capacity 50MVA, 22/110kV.The capacity of all the 14 wind
power feeders (E1- E14) is given in the Table 5.1. The total power generation of
the substation is 123.0MW (Table 5.1).
61
In order to analyze the power quality disturbances in the grid connected wind
farm, two power quality analyzers namely Fluke 435 and Dranetz meters were
installed in the substation from 16/07/13 to 24/08/13 (40 days).The Dranetz was
installed at the 22kV feeder E2 and fluke 435 meter was installed at the group
control breaker of the 110kV bus bar. The specification as well as the connection
details of the both the power quality analyzers were clearly explained in the
previous reports 2 and 3. The various power quality events such as sag, swell,
transient, interruption, flickering and harmonics were found to occur during the
measurement period.
5.3 Analysis of recorded events
Analysis is carried out for the data recorded by the Power Quality
measurement instruments. The events recorded are classified as transients, sag,
swell and interruption
63
5.3.1 Transients
The various transient events recorded are shown in Figures 5.3- 5.4.The 15%
of dip in the voltage occurs during the transient period for the duration of 0.01ms..
The transient occurs due to the switching operation of isolator switch and
generator.
5.3.4. Swell
The only swell event recorded is shown in Figure.5.8. The swell may occur
due sudden removal of load for the duration of 0.09 sec.
voltage specifies the upper voltage and lower voltage limits whose values are 67V
and 55V respectively.
During forty days of observation, the magnitude of voltage decreases below
the lower limit for six times and increases above the upper limit only once. The
drop in voltage below the lower voltage limit is called as Sag and the increase in
the voltage above the upper limit is called as Swell. As per the compliance report
EN50160 standard, the sags have sustained for the duration of 10 to 100
milliseconds and a swell have sustained for the duration of 10 milliseconds. The
occurrence of sag is due to the varying power demand and a fault in the substation
and swell may occur due to the removal of load at the distribution level.
There was no interruption during the period of study. Nineteen transient
events were observed which might have been caused due to the switching of
capacitor bank or isolator.
Volts
65
64
63
62
61
60
A Vrms
5% 95% 99%
C re a ted with Dr a nVie w 6 .8.1
5.5 Conclusion
The various power quality events of variable speed permanent magnet
synchronous generator are analyzed. The Chinnaputhur substation located at
Coimbatore district consist of variable speed wind turbines. It has fourteen (E1-
E14) wind farms feeders of different capacity which are connected at 22kV bus
bar. To analyze the power quality disturbances in grid connected wind farm, two
power quality analyzers namely Fluke 435 and Dranetz meters were installed from
16/07/13 to 24/08/13 (40 days).The meter Dranetz was installed at the feeder E2 of
wind farm and fluke 435 was installed at the group control breaker of the 110kV
bus bar. The various power quality events such as Sag, Swell, Transient and
interruption and Flickering were recorded according to EN51620 standard. Totally
22 events were recorded out of which 6 events were sag, 1 event was swell and
the remaining events were transient events. The flickering occurs due to
continuous and switching operation of the wind turbines. The recorded flickering
graph shows the Pst, Plt values are less than 1 for most of the time and it exceeded
the value unity almost six times during the measuring period. Therefore, variable
speed generator produces less flickering. From the recorded report, the variable
speed generator has less number of power quality events than the fixed speed
generator.
72
CHAPTER 6
MODELLING AND CONTROLING CONCEPT OF THE
VARIABLE SPEED WIND TURBINE WITH PMSG IN
DIgSILENT
6.1 General
A comprehensive dynamic simulation model of the PMSG wind turbine is
implemented in the power system simulation software DIgSILENT Power Factory
and a control strategy for the entire turbine system is developed. The general
structure of the variable speed wind turbine type with full-scale converter is shown
in Figure 6.1.
language (DSL) of the DIgSILENT. The DSL makes it possible for the users to
create their own blocks either as modifications to the existing models or as
completely new models. These new models can be collected into a library, which
can be easily used further in the modeling of other wind farms and wind turbines.
The DIgSILENT provides a comprehensive library of models of electrical
components in power systems. The library includes models of generators, motors,
power electronic controllers, dynamic loads and various passive network elements
such as lines, transformers, static loads and shunts. Therefore, in the modeling, the
grid model and the electrical components of the wind turbine model are taken from
the standard components in the existing library.
The Figure 6.2 shows the modeling scheme of the PMSG wind turbine and
its control concept. The whole model includes the models for both the aero
dynamical and mechanical system as well as for the electrical system and its
control structure. The built-in models for all the electrical components
(generator model, converter models, transformer model, grid model) are
provided in the DIgSILENT library and they are marked by the yellow blocks.
The models for all mechanical components (wind, aerodynamics, drive train
model) and for the total control system developed by the user are marked in
Figure 6.2 by the grey blocks.
The frequency converter control of the PMSG is divided into two types: a
control for the grid side converter and a control for the generator side converter.
The frequency converter control is coordinated with the pitch angle control of the
rotor blades.
74
Figure 6.2: Modelling scheme and control concept of the variable speed wind
turbine with PMSG
Vw- Wind Velocity Us- Stator voltage of the generator
Ωrot-Angular velocity of the Turbine rad/sec Trot-Wind Turbine Torque
Ωgen- Angular velocity of the Generator rad/sec Tgen-Generator Torque
Pgrid – Real power at the Grid side
Qgrid- Reactive power at the Grid side
The DIgSILENT has the ability to simulate load flow, RMS fluctuations
and transient events in the same software environment. It provides models on
different levels of the detailing. It combines the models of electromagnetic
transient simulations of the instantaneous values with the models of the
electromechanical simulations of RMS values. This makes the models useful for
the studies of grid fault, the power quality and control issues.
75
The developed model will be able to support the analysis of the interaction
between the mechanical structure of the wind turbine and the electrical grid both
during normal operation of the wind turbine and during the transient grid fault
events. The dynamic interaction between a wind turbine/wind farm and a power
system are simulated by using RMS simulation in the DIgSILENT. In the recent
years, the trend has been moved from the installations of a few wind turbines to the
large wind farms with several hundred MW of capacity. This situation means that
future wind farms must be able to replace conventional power stations, and thus be
active controllable elements in the power supply network. In other words, wind
farms must develop power plant characteristics. The TNEB utility which is
responsible for the transmission systems in Tamil Nadu has issued requirements
that focus on the influence of wind farms on the grid stability and the power quality
and on the control capabilities of the wind farms.. The E2 wind power feeder of
Chinnaputhur substation is simulated to study the various power quality issues and
their causes.
6.3 Simulation model of individual blk using dsl
In this simulation model, mechanical side control and converter side control
of variable speed PMSG are modeled independently. The mechanical side control
consists of wind speed blk, shaft blk, pitch angle control blk, speed measurement
blk and machine blk and are connected together to generate the electrical energy.
The generated electrical energy is controlled with help of generator side converter.
The converter side control consists of converter blk, inverter blk, maximum power
point tracking blk, grid side controller blk and generator side controller and they
are connected together. The converter system controllers generate a constant
stator voltage, real power and necessary reactive power at all the power system
condition such as load variation and fault. In this section, modeling of individual
blocks in the DSL and their interconnection together are explained.
76
Figure 6.6: Frame definition to form slots to integrate the Generator PMG
blocks
In load flow analysis, the PWM converter model supports several control
conditions.
The supported control conditions are as follows:
Vac-phi – Specifies magnitude and phase of the AC terminal voltage. It is
typical control mode is for the motor-side converters in variable speed
applications.
Vdc-phi – Specifies the DC-voltage and the AC-voltage phase. No specific
application.
PWM-phi – Load flow setup without control. The PWM index and phase are
directly set.
Vdc-Q – Specifies DC-voltage and reactive power. Typical applications:
STATCOM, UPFC, grid-side converter for doubly-fed induction machine.
Vac-P - Specifies AC-voltage magnitude and active power. This mode is
equivalent to a PV characteristic of synchronous generators. Typical
applications: Grid-side converter control driven synchronous machines and
VSC.
P-Q – Specifies P and Q at the AC-side. This control is equivalent to a PQ
characteristic of synchronous machines. Typical applications: Grid-side
control of converter driven synchronous machines, VSC.
Since the model is based on the fundamental frequency approach, the load
flow calculations will assume always a frequency as defined in the external grid.
Then, the voltage angle for each bus bar is calculated with respect to the global
reference. For all the control conditions in the load flow analysis the frequency is
not a controlled variable.
84
The control variables for the stability model are defined in 4 ways depending on
the applications (DIgSILENT, 2006):
A. Pmr, Pmi– Real and imaginary part of the PWM index. The reference system
in this case is the global reference frame, which is usually defined by a
reference-machine, external network, voltage source or a PWM converter.
This set of inputs must be always used in combination with phase
measurement devices e.g. Phase Locked Loop (PLL) and transformation
between reference frames.
B. Pmd, Pmq, cosref, sinref– This set of input is used in grid connected
applications. The PWM Index-vector is specified with reference to a
reference system, which is defined by cosref and sinref. For example the
outputs from the current controllers are connected to Pmd and Pmq while the
voltage is measured using a PLL and its output gives the cosref and sinref
signals.
C. Pm_in, dphiu – magnitude and phase of the PWM Index. This representation
is equivalent to Pmr, Pmi. The phase of PWM Index dphiu is expressed with
reference to the global reference frame.
D. Pm_in, f0 (50Hz) – Pm _in is the magnitude of the PWM index and f0
permits varying the frequency of the output voltage. The control variable f 0
defines the frequency in p.u., the base value 50Hz. This input pair ―is
especially useful in variable speed-drive applications, in which a PWM
converter is used for driving an induction machine.
6.3.2.2 Generator side controller
The stator voltage of the generator and the voltage of the DC-link with
respect to real power are regulated. The controller is equipped with fast current
loop. The current reference values are derived from the voltage regulators as
indicated in Figure 6.11.
85
6.3.2.4 Frame
A PWM Frame , connecting all the individual blocks such as Rectifier blk,
grid side controller blk (Vdc-Q), Generator side controller blk (Vac-P) ,MPT blk,
Inverter in-built blk are connected together through the slot in the frame as shown
in Figure 6.17. When a slot in the frame definition is selected, the project block
gets opened where in the number of functional blocks already defined are
displayed. The connection of the individual blk at generator side controlling and
grid side controlling are visualized with the help of PWM frame.
Figure 6.17: PWM Frame definition to form slots to integrate all the blocks
the individual slots to the variables of the common model. The various slots and
their linking to the common block variables are shown in Figure 6.18.
ripple content. The generator power is synchronized to the grid through the step up
transformer and underground cable.
Figure 6.19: Simulation model of variable speed wind electric system with
PMSG
93
6.5 Conclusion
With a view to getting a better understanding of the variable speed wind
electric system, a generic model was introduced, where the various independent
elements of a wind turbine and their interaction are explained. The individual
blocks such as turbine BlkDef (block), shaft BlkDef, pitch angle control BlkDef,
Grid side controller BlkDef, Generator side controller BlkDef, MPT BlkDef were
designed using the mathematical model in DSL. All the individual blocks were
connected together with help of frame definition block including the built-in model
of SYM BlkDef and Converter BlkDef .The values of the parameter variable in
each block are entered using common model. The composite model (ElmComp)
connects the frame slot and common model. Finally, the simulation model of the
grid connected variable speed wind turbine was built with the help of power system
component such as bus bar, transformer, cable, feeder etc from the software. The
generator side converter controls the stator voltage and optimal power generation
with respect to the speed of the machine. The grid side controller controls the real
power and reactive power at the grid bus bar.
94
CHAPTER 7
ANALYSIS AND SIMULATION OF E2 WIND FARM FEEDER
IN CHINNAPUTHUR SUBSTATION
7.1 Introduction
The E2 wind farm feeder has eleven individual variable speeds PMSG of
same rating of 0.85MW. The total generated power capacity is 9.45MW. The
generators are located at 8.25KM to 12.25KM away from the substation. The
Figure 7.1 shows the layout of E2 wind farm feeder. The Table 7.1 shows the
distance of generators from the grid 110kV. The E2 feeder layout is modeled with
the help of DIgSILENT software to analyze the various power quality issues. The
generator in the left hand side of the layout is considered as G1 which is far away
from the grid and G11 near to the grid in this simulation. The power quality
analyzer, Dranetz 431 was installed at E2 wind farm feeder. The power quality
events as per EN50160 standard were recorded.
The electromechanical transient (RMS) simulation is performed for 600sec
under steady state and dynamic state conditions. The various power quality events
such as Sag, Swell and Transient are simulated.
Table 7.1 Distance of generators from grid for E2 feeder
Generator G1 G2 G3 G4 G5 G6 G7 G8 G9 G10 G11
Location 12.25 12.5 12.00 11.86 9.68 9.46 9.42 8.9 8.78 8.57 8.23
from the
grid in
KM
95
Table 7.4: Grid bus bar voltage increased from 110kV to 121 kV at wind
velocity of 12m/s
Si. Power system Real power Reactive Voltage Current
No component flow power flow kV kA
MW Mvar
1. Generator G11 0.85 0.08 0.44 1.122
2. Generator side 0.85 0.08 0.44 1.122
converter
3. Grid side converter 0.85 0.12 0.44 1.01
4. Generator bus bar 0.44
5. DC bus bar 0.702
6. LV bus bar 0.44
7. MV busbar22 24.5
8. HV bus bar 110kV 121
Figure 7.3: Bar chart for rise in bus bar voltage for the Generator G11 far
away from the grid
100
Table 7.5: Grid bus bar voltage decreased from 110kV to 99kV
at wind speed of 12m/s
remains constant for wind speeds above the rated value and decreases gradually
below the rated wind speed from 11m/s to cut-in speed of 5m/s. The grid side
converter controller controls the real and reactive power flow to the grid under the
variable load conditions. Therefore, the system frequency is almost maintained
constant under all the load conditions.
The Table 7.6 shows the constant frequency for the wind speed condition
above the rated value. The Table 7.7 shows the variation in the frequency for the
speeds below the rated wind speed. The generator and reactance bus bar
frequencies are varied but the grid side converter controller maintaining the
constant grid bus bar frequency. The Figure 7.5 shows the bar chart of generator
and grid frequency under change in wind speed.
Table 7.6: Constant frequency above the rated wind speed at 19m/s
102
Table 7.7: Variation of the frequency below the rated wind speed at 8m/s
The Table 7.9 shows the value of G1 in the E2 feeder for the wind speed of
8m/s. The generator real power gradually decreases with respect to change in the
wind speed but the generator stator voltage remains constant. The Figure 7.6 shows
the bar chart of generator real power and bus bar voltage for wind speed below and
rated speed.
104
Figure 7.6: Variation in Generator real power and bus voltage for wind speeds
below and above the rated speed
105
Figure 7.7: Variation of Pitch angle, Generator speed and Active power of the
G1 and G11 for wind speed varying from 12 m/s down to 5 m/s
107
Figure 7.8: DC-link voltage and stator voltage for the variation of wind speed
from 12 m/s down to 5 m/s
Another case study has been carried out in which the wind speed is increased
in steps from 12 m/s to 20 m/s. The response of pitch angle, speed and power is
depicted in Figure 6.9. The step variation in the wind speed changes both the pitch
angle and the generator speed. The pitch mechanism reacts slowly compared to the
power controller. It is noticed that the variations in the generator speed occur at
each step change in the wind speed. The response of the pitch angle and the
generator speed has oscillations and the generator power is kept at its rated value of
0.85 MW. The speed responses of generator 1(green line) and generator 11 (red
line) are similar with a small deviation of 0.01p.u as shown Figure 7.9.
The Figure 7.10 shows the response of DC bus voltage with respect to simulation
time. The DC-link voltage is maintained constant at the set value with the help of
generator side controller.
108
Figure 7.9: Variation in Pitch angle, Generator speed and Active power for
change in wind speed
109
Figure 7.10: Variation of DC-link voltage for wind speed from 12 m/s to 20
m/s
7.4.2 Dynamic behavior of the wind turbine driven PMSG under grid faults
In order to evaluate the dynamic behavior of the wind turbines driven PMSG
under grid faults, a three-phase grid fault is created at the high voltage grid
terminal. The turbine system and its grid connection are illustrated in Figure 7.11.
110
settles down the DC voltage to its reference value with in 4 milliseconds during the
fault period. After clearing the fault, the DC-link voltage was found to be
oscillating and settles down to the reference value with in millisecond.
Figure 7.12 Variation in voltage, Active Power and Reactive power of G1and
G11 generators
112
7.4.3 Flickering
With the help of harmonic load flow in the DIgSILENT software the long
term and the short term flickering due to continuous and switching operations can
calculated for the constant wind speed and for the various grid impedance angles
.The Table 7.10 shows the flicker value appearing at various bus bars for 50˚
impedance angle.
113
Table 7.10: Flickering value at the bus bars for 50˚ impedance angle
The simulated flicker values for Pst and Plt are very less when compared to
the threshold value of unity. The RMS simulation is executed for minimum of
600sec and the values of Pst =0.004563 and Plt= 0.025468 are measured with the
help of flicker meter.
7.5.1 Introduction
The comparison between the results of the simulations and measurements
was performed to validate the model used. The power quality instrument
manufactured by Dranetz was connected at the common breaker of the wind farm.
During this study, power quality issues such as voltage sag, Interruption, swell and
oscillatory transient were recorded.
7.5.2 Simulation of voltage sag
Voltage sag is defined as the decrease (between 10% and 90%) in RMS
voltage at the power frequency for the duration of 0.5 cycles to 1 minute. In the
network design considered, the three phase fault is simulated at 110kV bus bar for
10 ms duration. The sags are momentary in nature as shown in the Figure 7.14. The
voltage sag measured at the wind feeder is depicted in Figure 7.15. The dip in the
114
voltage has occurred due to the fault alone at the grid bus bar but the generator bus
bar voltage and DC bus bar voltage are not affected because of the DC link.
then restoring it back. The simulation results of such a scenario show that there is a
variation in phase voltage as given Figures 7.16.
The noteworthy observations are: The line-to-line voltage of generator 11
suddenly starts decaying and becomes zero at some point in time. It is restored
back to the normal operation after the clearance of fault. The Figure 7.17 shows
that the measured voltage interruption wave is very similar to the simulated wave
form in the DIgSILENT.
can participate to re-establish the voltage properly during and after grid fault. The
conclusion is that a variable speed wind generator equipped with converter
control can help the grid to maintain the voltage stability. It also provides a good
dynamic performance for change in wind speed and grid voltage.
119
CHAPTER 8
REMEDIAL MEASURES AND SUGGESTIONS FOR
IMPROVING POWER QUALITY
8.3 Re-Conductoring
Re-Conductoring of distribution feeder is another effective method of
voltage improvement and voltage drop reduction. However, this method is costly as
it involves the replacement of high impedance small capacity conductor by low
impedance high capacity conductor. This technique is recommended only when the
benefit cost ratio of re-conductoring is equal or greater than unity. Cost is reduced
on the installation of new and dismantling of existing conductor. The benefits
include reduction of voltage drop and saving in energy losses for a period of about
five years and return value of the dismantled conductor.
8.4 Bifurcation
Bifurcation is applied to distribution feeder when it is highly overloaded and
simple capacitor application and other techniques do not provide the desired
results. The existing feeder is replaced by two or more feeders as per requirement
of the locality to supply a portion of the existing area. In this method the re-
allocation of loads is carried out. Additional feeder(s) are constructed either from
the same grid or from another nearby grid station depending on the economic
justification and achievement of maximum benefits. This method is costly as it
involves the construction of new feeder(s).
121
the major driver is the financial incentive arising out of the power conditioning. To
ensure the optimality of the solution, it is essential to capture all the performance
requirements, cost and benefit elements and arrive at an optimal solution.
8.12 Suggestions
1. All new wind generation plants must meet WECC LVRT requirements.
2. All new wind plants should be Type 3 or Type 4 generators that are capable
of providing dynamic reactive support to help the transmission grid to meet
applicable WECC transient stability performance standards and to prevent
the potential tripping due to low voltages.
3. In the event that some of the new wind plants are of Type 1 or 2 with no
dynamic reactive capability, the generator owner must provide sufficient
reactive resources to meet the Low Voltage Ride Through standards and
voltage control standard. Additional studies may be required to verify that
the generator has been provided appropriate additional external dynamic
reactive support to meet the interconnection standards.
4. Re-evaluate the optimal location and size of the dynamic reactive support.
5. Analyze the best solution for improving the nose point of the Q-V analysis
for critical 250 kV buses under critical contingency conditions. Potential
solutions include the use of series compensation and reduction of proposed
shunt compensation.
Type 1 machines operate in a very narrow speed range, and always consume
reactive power during operation. The reactive power consumption is a function of
active power production and grid conditions, and it cannot be controlled.
Consequently, both the reactive power consumption of the generator and the
126
Summary
Electric power quality is an electric power problem manifested in voltage,
current or the frequency deviations and results in failure of load side electric
equipments. From electric utility point of view, the power quality is the supply of
electrical power as per specified standards, whereas from the end user sight, it is
the smooth functioning of electrical equipments without any disruption. In the
deregulated and competitive environment, both the electric utilities as well as the
customers are becoming increasingly concerned about the quality of electric power.
The major reason for increased concerns is the availability of sophisticated
technology that has developed extremely sensitive electrical/electronic equipment.
Any sort of variation in electrical parameters greatly changes the characteristics of
such delicate equipments. Widespread use of electronics in the system from home
127
electronics to the control of massive and costly industrial processes has increased
the awareness of power quality. The study of power quality and way to control it is
a concern for electric utilities and electricity consumers. Equipments have become
more sensitive to even minute changes in the power supply. Different indices are
used by distribution engineers for the quantification of electric power quality.
These indices have general properties that they are relatively easy to calculate and
are calculated using standardized procedures. Majority of these indices are
interpreted and applied by distribution engineers. The proliferation of micro-
electronic processors in a wide range of equipment, from domestic appliances to
automated industrial and hospital diagnostic systems, has increased the
vulnerability of such equipment to power quality problems. These problems
include a variety of electrical disturbances, which may originate in several ways
and have very different effects on various kinds of sensitive loads.
Distributed Generation (DG) is said to be power generation paradigm of the
new era because of its ability to resolve many customer problems, especially from
power quality point of view. DG is used to provide electricity service at a high
level of reliability and power quality than conventional grid power system. DG is
capable of protecting sensitive loads from momentary voltage variations. It can
provide uninterruptible power supply to ride through any sort of outage until
primary or secondary power is restored. It is environmental friendly, promotes
renewable energy resources, improves system power factor, and power quality in
terms of node voltage drop and power loss reduction. A DG system provides
protection from long term outages. Power quality system needs to include
important design criteria that relates to system hardening. It is necessary to
understand the business mission and the tolerance for outage. To eliminate the
power quality and reliability disruptions, a facility may seek to minimize its energy
prices by introducing DG.
128
REFERENCES
1. Akhmatov V., Knudsen H., Nielsen A.H., Pedersen J.K. and Poulsen N.K.,
‗Modelling and Transient Stability of Large Wind Farms‘, Electric Power
and Energy Systems, Vol. 25, 2003, pp. 123-144.
2. Ana I. Estanqueiro ‗A Dynamic Wind Generation Model for Power Systems
Studies‘, IEEE Transactions on Power Systems, Vol. 22, No. 3, August
2007, pp. 920-928.
3. Boulaxis N.G., Papathanassiou S.A. and Papadopoulos M.P., ‗Wind Turbine
Effect on the Voltage Profile of Distribution Networks‘, Renewable Energy,
Vol. 25, 2002, pp. 401-415.
4. Chan T.F. and Lai L.L, ‗An Axial-Flux Permanent-Magnet Synchronous
Generator for a Direct-Coupled Wind-Turbine System‘, IEEE Transactions
on Energy Conversion, Vol. 22, No. 1, March 2007, pp. 86-94.
5. Chompoo-inwai C., Wei-Jen Lee, Pradit Fuangfoo, Mitch Williams and
James R. Liao, ‗System Impact Study for the Interconnection of Wind
Generation and Utility System‖, IEEE Trans. on Industry Applications, Vol.
41, No. 1, Jan./Feb 2005, pp. 163-168.
6. Chompoo-inwai C., Yingvivatanapong C., Methaprayoon K. and Wei-Jen
Lee, ‗Reactive Compensation Techniques to Improve the Ride-Through of
Induction Generators during Disturbance‘, IEEE Trans. on Industry
Applications, Vol. 41, No. 3, May-June 2005, pp. 666-672.
7. Divya K.C. and Nagendra Rao P.S., ‗Models for Wind Turbine Generating
Systems and their Application in Load Flow Studies‘, Electric Power
Systems Research, Vol. 76, 2005, pp. 844-856.
8. Eisenhut C., Krug F., Schram C. and Klockl B., ‗Wind-Turbine Model for
System Simulations Near Cut-In Wind Speed‘, IEEE Transactions on Energy
Conversion, Vol. 22, No. 2, June 2007, pp. 414-420.
9. Julio Usaola, Pablo Ledesma, Juan M. Rodriguez, Jose L. Fernandez,
Domingo Beato, Ramon Iturbe and Jose R. Wilhelmi, ‗Transient Stability
129
Studies in Grids with Great Wind Power Penetration - Modelling Issues and
Operation Requirements‘, IEEE Power Engineering Society General
Meeting, Vol. 3, 2003, pp. 1534-1541.
10.Muljadi E., Wan Y., Butterfield C.P. and Parsons B., ‗Study of a Wind Farm
Power System‘, NREL Report, 2002.
11.Oscar Alexis M.A., ‗Issues Regarding the Integration of Induction Wind
Turbines in Weak Electrical Networks‘, Nordic Wind Power Conference,
Chalmers University of Technology, March 2004, .-23.