GPSA Engineering Data Book 14th Edition: Revision Date Reason (S) For Revision
GPSA Engineering Data Book 14th Edition: Revision Date Reason (S) For Revision
GPSA Engineering Data Book 14th Edition: Revision Date Reason (S) For Revision
FIG. 11-1
Nomenclature
Acfm = actual volumetric flow rate of air-vapor mixture, lbw =
cu ft/min
ahp = air horsepower, hp L =
AWB = ambient wet bulb temperature, °F LG =
B = combined water loss through blowdown and MCDB =
windage, % of circulating water or cu ft/min
CWT = cold water temperature, °F MCWB =
DB = dry bulb temperature, °F Q =
E = water evaporated, % of circulating water or cu PF =
ft/min
gpm = gallons per minute R =
G = air rate, lb/(sq ft • hr) V =
ha = specific enthalpy of dry air, BTU/lb va =
has = hs - ha, BTU/lb vas =
hs = enthalpy of moist air at saturation per lb of dry vs =
air, BTU/lb
HWT = hot water temperature, °F Ws =
lba = pounds of dry air WB =
WSAC =
Air Horsepower = The power output developed by a fan in moving Fan Cylinder =
a given air rate against a given resistance.
Air Inlet = Opening in a cooling tower through which air Fan Deck =
enters. Sometimes referred to as the louvered
face on induced draft towers.
Air Rate = Mass flow of dry air per square foot of cross- Fan Pitch =
sectional area in the tower's heat transfer region
per hour.
Air Velocity = Velocity of air-vapor mixture through a specific Fill =
region of the tower (i.e. the fan).
Capacity (Wet = The total amount of heat rejected by the wet Louvers (Wet Surface =
Surface Air Cooler) surface air cooler to atmosphere Air Cooler)
Circulation Rate = Actual water flow rate through a given tower. Natural Draft =
Circulation Rate (Wet = Actual water flow over the top of the tube Net Effect Volume =
Surface Air Cooler) bundles
Cold Water = Temperature of the water leaving the collection Performance Factor =
Temperature basin, exclusive of any temperature effects
incurred by the addition of makeup and/or the
removal of blowdown.
Collection Basin = Chamber below and integral with the tower Psychrometer =
where water is transiently collected and directed
to the sump or pump suction line.
Double-Flow = A crossflow cooling tower where two opposed Water Basin (Wet =
fill banks are served by a common air plenum. Surface Air Cooler)
Drift = Circulating water loss from the tower as liquid Water Rate =
droplets entrained in the exhaust air stream.
Units percent of circulating water rate or gpm.
[For more precise work, an L/G parameter is
used, and drift becomes pounds of water per
million pounds of exhaust air (ppmw).]
KEY
= Example calculation from the book
= Application worksheet for user to fill out
= Numbers that must be filled in according to the user's data, specific situation, graphs, charts and figures
pounds of water
ooling Towers
Given Data:
Flow = 1000 gpm
Hot Water = 105 °F
Cold Water = 85 °F
Wet Bulb = 75 °F
This is commonly referred to as 105-85-75 or 20° Range (105-85) and 10° Approach (85-75).
The sample calculations, equations and spreadsheets presented herein were developed using examples published in the Engine
While every effort has been made to present accurate and reliable technical information and calculation spreadsheets based on
The Calculation Spreadsheets are provided without warranty of any kind including warranties of accuracy or reasonableness of
In no event will the GPA or GPSA and their members be liable for any damages whatsoever (including without limitation, thos
These calculation spreadsheets are provided to provide an “Operational level” of accuracy calculation based on rather broad as
Application 11-1 -- Effect of Varying WB Temperature on Cold Water Temperature (CWT)
Given Data:
Flow = 1000 gpm
Hot Water = 105 °F
Cold Water = 85 °F
Wet Bulb = 75 °F
This is commonly referred to as 105-85-75 or 20° Range (105-85) and 10° Approach (85-75).
es published in the Engineering Data Book as published by the Gas Processors Suppliers Association as a service to the gas processing indu
ion spreadsheets based on the GPSA Engineering Data Book sample calculations, the use of such information is voluntary and the GPA and
uracy or reasonableness of factual or scientific assumptions, studies or conclusions, or merchantability, fitness for a particular purpose, or n
ng without limitation, those resulting from lost profits, lost data or business interruption) arising from the use, inability to, reference to or re
n based on rather broad assumptions (including but not limited to: temperatures, pressures, compositions, imperial curves, site conditions e
to the gas processing industry. All information and calculation formulae has been compiled and edited in cooperation with Gas Processors
voluntary and the GPA and GPSA do not guarantee the accuracy, completeness, efficacy, or timeliness of such information. Reference herei
r a particular purpose, or non-infringement of intellectual property.
ability to, reference to or reliance on the information in this Publication, whether based on warranty, contract, tort or any other legal theory a
al curves, site conditions etc) and do not replace detailed and accurate Design Engineering taking into account actual process conditions, flu
ation with Gas Processors Association (GPA).
rmation. Reference herein to any specific commercial product, calculation method, process, or service by trade-name, trademark, and serv
or any other legal theory and whether or not advised of the possibility of such damages.
ual process conditions, fluid properties, equipment condition or fowling and actual control set-point dead-band limitations.
ame, trademark, and service mark manufacturer or otherwise does not constitute or imply endorsement, recommendation or favoring by the
ndation or favoring by the GPA and/or GPSA.
GPSA Engineering Data Book 14th Edition
Example 11-2 -- Effect of Varying Cooling Range on Cold Water Temperature Application 11-2 -- Effect of V
What is the new CWT when cooling range is changed from What is the new CWT when co
20 ° to 30 °?
(50% increase in heat load) with gpm and WB held constant? (50% increase in heat load) wit
Enter Nomograph Fig. 11-5 at 85° CWT, go horizontally to 75° WB, vertically to
R = 20° F, horizontally to R = 30° F, vertically downward to 75° WB, read new Enter Nomograph Fig. 11-5 at 8
CWT of 20° F, horizontally to R = 30° F
87.5 °F.
The sample calculations, equations and spreadsheets presented herein were developed using examples published in the Engine
While every effort has been made to present accurate and reliable technical information and calculation spreadsheets based on
The Calculation Spreadsheets are provided without warranty of any kind including warranties of accuracy or reasonableness of
In no event will the GPA or GPSA and their members be liable for any damages whatsoever (including without limitation, thos
These calculation spreadsheets are provided to provide an “Operational level” of accuracy calculation based on rather broad as
pplication 11-2 -- Effect of Varying Cooling Range on Cold Water Temperature
= 1000 gpm
= 105 °F
= 85 °F
= 75 °F
mples published in the Engineering Data Book as published by the Gas Processors Suppliers Association as a service to the gas processing in
ulation spreadsheets based on the GPSA Engineering Data Book sample calculations, the use of such information is voluntary and the GPA
accuracy or reasonableness of factual or scientific assumptions, studies or conclusions, or merchantability, fitness for a particular purpose, o
uding without limitation, those resulting from lost profits, lost data or business interruption) arising from the use, inability to, reference to o
ation based on rather broad assumptions (including but not limited to: temperatures, pressures, compositions, imperial curves, site condition
ciation as a service to the gas processing industry. All information and calculation formulae has been compiled and edited in cooperation w
uch information is voluntary and the GPA and GPSA do not guarantee the accuracy, completeness, efficacy, or timeliness of such informatio
ntability, fitness for a particular purpose, or non-infringement of intellectual property.
ng from the use, inability to, reference to or reliance on the information in this Publication, whether based on warranty, contract, tort or any
mpositions, imperial curves, site conditions etc) and do not replace detailed and accurate Design Engineering taking into account actual pro
and edited in cooperation with Gas Processors Association (GPA).
meliness of such information. Reference herein to any specific commercial product, calculation method, process, or service by trade-name,
arranty, contract, tort or any other legal theory and whether or not advised of the possibility of such damages.
king into account actual process conditions, fluid properties, equipment condition or fowling and actual control set-point dead-band limitati
or service by trade-name, trademark, and service mark manufacturer or otherwise does not constitute or imply endorsement, recommendati
Example 11-3 -- Effect of Varying Water Circulating Rate and Heat Load on
Cold Water Temperature
Given Data:
Flow = 1000 gpm
Hot Water = 105 °F
Cold Water = 85 °F
Wet Bulb = 75 °F
What is the new CWT when water circulation is changed from 1000 gpm to 1500
gpm (50% change in heat load at constant Range).
Varying water rate, particularly over wide ranges, may require modifications to the distribution
system. Enter Nomograph Fig. 11-5 at 85° CWT, go horizontally to 75° WB, vertically to R =
20° F, horizontally to Performance Factor of
3.1 .
Obtain new PF by multiplying (3.1)(1500/1000) = 4.65, then enter Nomograph at PF of 4.65, go
horizontally to R = 20° F, vertically down to 75° WB, read new CWT of
90.5 °F.
The sample calculations, equations and spreadsheets presented herein were developed using examples published in the Engine
While every effort has been made to present accurate and reliable technical information and calculation spreadsheets based on
The Calculation Spreadsheets are provided without warranty of any kind including warranties of accuracy or reasonableness of
In no event will the GPA or GPSA and their members be liable for any damages whatsoever (including without limitation, thos
These calculation spreadsheets are provided to provide an “Operational level” of accuracy calculation based on rather broad as
Application 11-3 -- Effect of Varying Water Circulating Rate and Heat Load on
Cold Water Temperature
Given Data:
Flow = 1000 gpm
Hot Water = 105 °F
Cold Water = 85 °F
Wet Bulb = 75 °F
What is the new CWT when water circulation is changed from 1000 gpm to 1500
gpm (50% change in heat load at constant Range).
Varying water rate, particularly over wide ranges, may require modifications to the distribution
system. Enter Nomograph Fig. 11-5 at 85° CWT, go horizontally to 75° WB, vertically to R =
20° F, horizontally to Performance Factor of
3.1 .
Obtain new PF by multiplying (3.1)(1500/1000) = 4.65, then enter Nomograph at PF of 4.65, go
horizontally to R = 20° F, vertically down to 75° WB, read new CWT of
90.5 °F.
es published in the Engineering Data Book as published by the Gas Processors Suppliers Association as a service to the gas processing indu
ion spreadsheets based on the GPSA Engineering Data Book sample calculations, the use of such information is voluntary and the GPA and
uracy or reasonableness of factual or scientific assumptions, studies or conclusions, or merchantability, fitness for a particular purpose, or n
ng without limitation, those resulting from lost profits, lost data or business interruption) arising from the use, inability to, reference to or re
n based on rather broad assumptions (including but not limited to: temperatures, pressures, compositions, imperial curves, site conditions et
vice to the gas processing industry. All information and calculation formulae has been compiled and edited in cooperation with Gas Proces
n is voluntary and the GPA and GPSA do not guarantee the accuracy, completeness, efficacy, or timeliness of such information. Reference h
ss for a particular purpose, or non-infringement of intellectual property.
e, inability to, reference to or reliance on the information in this Publication, whether based on warranty, contract, tort or any other legal the
perial curves, site conditions etc) and do not replace detailed and accurate Design Engineering taking into account actual process condition
ited in cooperation with Gas Processors Association (GPA).
ess of such information. Reference herein to any specific commercial product, calculation method, process, or service by trade-name, trade
, contract, tort or any other legal theory and whether or not advised of the possibility of such damages.
nto account actual process conditions, fluid properties, equipment condition or fowling and actual control set-point dead-band limitations.
vice by trade-name, trademark, and service mark manufacturer or otherwise does not constitute or imply endorsement, recommendation or
t dead-band limitations.
ment, recommendation or favoring by the GPA and/or GPSA.
GPSA Engineering Data Book 14th Edition
Example 11-4 -- Effect of Varying WB Temperature, Range, and Water Circulating Rate on
Cold Water Temperature
Given Data:
Flow = 1000 gpm
Hot Water = 105 °F
Cold Water = 85 °F
Wet Bulb = 75 °F
Enter Nomograph Fig. 11-5 at 85° CWT, go horizontally to 75° WB, vertically to R = 20° F, horizontally
read PF =
3.1
then multiply (3.1)(1250/1000) = 3.88 (new PF). Enter Nomograph at PF = 3.88, go horizontally to R = 25°
F, vertically down to 60° WB, read new CWT of
82 °F.
The sample calculations, equations and spreadsheets presented herein were developed using examples published in the Engine
While every effort has been made to present accurate and reliable technical information and calculation spreadsheets based on
The Calculation Spreadsheets are provided without warranty of any kind including warranties of accuracy or reasonableness of
In no event will the GPA or GPSA and their members be liable for any damages whatsoever (including without limitation, thos
These calculation spreadsheets are provided to provide an “Operational level” of accuracy calculation based on rather broad as
Application 11-4 -- Effect of Varying WB Temperature, Range, and Water Circulating Rate on
Cold Water Temperature
Given Data:
Flow = 1000 gpm
Hot Water = 105 °F
Cold Water = 85 °F
Wet Bulb = 75 °F
Enter Nomograph Fig. 11-5 at 85° CWT, go horizontally to 75° WB, vertically to R = 20° F, horizontally read
PF =
3.1
then multiply (3.1)(1250/1000) = 3.88 (new PF). Enter Nomograph at PF = 3.88, go horizontally to R = 25°
F, vertically down to 60° WB, read new CWT of
82 °F.
mples published in the Engineering Data Book as published by the Gas Processors Suppliers Association as a service to the gas processing i
ulation spreadsheets based on the GPSA Engineering Data Book sample calculations, the use of such information is voluntary and the GPA
accuracy or reasonableness of factual or scientific assumptions, studies or conclusions, or merchantability, fitness for a particular purpose,
luding without limitation, those resulting from lost profits, lost data or business interruption) arising from the use, inability to, reference to o
ation based on rather broad assumptions (including but not limited to: temperatures, pressures, compositions, imperial curves, site conditio
60
1000
o horizontally to R = 25°
a service to the gas processing industry. All information and calculation formulae has been compiled and edited in cooperation with Gas Pr
mation is voluntary and the GPA and GPSA do not guarantee the accuracy, completeness, efficacy, or timeliness of such information. Refere
fitness for a particular purpose, or non-infringement of intellectual property.
he use, inability to, reference to or reliance on the information in this Publication, whether based on warranty, contract, tort or any other lega
s, imperial curves, site conditions etc) and do not replace detailed and accurate Design Engineering taking into account actual process cond
edited in cooperation with Gas Processors Association (GPA).
iness of such information. Reference herein to any specific commercial product, calculation method, process, or service by trade-name, tra
nty, contract, tort or any other legal theory and whether or not advised of the possibility of such damages.
g into account actual process conditions, fluid properties, equipment condition or fowling and actual control set-point dead-band limitations
service by trade-name, trademark, and service mark manufacturer or otherwise does not constitute or imply endorsement, recommendation
Given Data:
Flow = 1000 gpm
Hot Water = 105 °F
Cold Water = 85 °F
Wet Bulb = 75 °F
The air flow rate varies as the cube root of the horsepower and performance varies
almost directly with the ratio of water rate to air rate, therefore the change in air flow
rate can be applied to the Performance Factor. Increasing the air flow rate (by installing
a larger motor) decreases the Performance Factor.
The sample calculations, equations and spreadsheets presented herein were developed using examples published in the Engine
While every effort has been made to present accurate and reliable technical information and calculation spreadsheets based on
The Calculation Spreadsheets are provided without warranty of any kind including warranties of accuracy or reasonableness of
In no event will the GPA or GPSA and their members be liable for any damages whatsoever (including without limitation, thos
These calculation spreadsheets are provided to provide an “Operational level” of accuracy calculation based on rather broad as
Application 11-5 -- Effect of Varying Fan HP Input on Cold Water Temperature
Given Data:
Flow = 1000 gpm
Hot Water = 105 °F
Cold Water = 85 °F
Wet Bulb = 75 °F
The air flow rate varies as the cube root of the horsepower and performance varies
almost directly with the ratio of water rate to air rate, therefore the change in air flow
rate can be applied to the Performance Factor. Increasing the air flow rate (by installing
a larger motor) decreases the Performance Factor.
sing examples published in the Engineering Data Book as published by the Gas Processors Suppliers Association as a service to the gas pro
and calculation spreadsheets based on the GPSA Engineering Data Book sample calculations, the use of such information is voluntary and
anties of accuracy or reasonableness of factual or scientific assumptions, studies or conclusions, or merchantability, fitness for a particular p
ever (including without limitation, those resulting from lost profits, lost data or business interruption) arising from the use, inability to, refe
cy calculation based on rather broad assumptions (including but not limited to: temperatures, pressures, compositions, imperial curves, site
n as a service to the gas processing industry. All information and calculation formulae has been compiled and edited in cooperation with Ga
formation is voluntary and the GPA and GPSA do not guarantee the accuracy, completeness, efficacy, or timeliness of such information. Re
lity, fitness for a particular purpose, or non-infringement of intellectual property.
m the use, inability to, reference to or reliance on the information in this Publication, whether based on warranty, contract, tort or any other
itions, imperial curves, site conditions etc) and do not replace detailed and accurate Design Engineering taking into account actual process c
ed in cooperation with Gas Processors Association (GPA).
s of such information. Reference herein to any specific commercial product, calculation method, process, or service by trade-name, tradem
contract, tort or any other legal theory and whether or not advised of the possibility of such damages.
o account actual process conditions, fluid properties, equipment condition or fowling and actual control set-point dead-band limitations.
ice by trade-name, trademark, and service mark manufacturer or otherwise does not constitute or imply endorsement, recommendation or fa
dead-band limitations.
ent, recommendation or favoring by the GPA and/or GPSA.
GPSA Engineering Data Book 14th Edition
Example 11-6 -- Effect of correction factor on gpm instead of Cold Water Temperature
Given Data:
Flow = 1000 gpm
Hot Water = 105 °F
Cold Water = 85 °F
Wet Bulb = 75 °F
Use the PF correction factor from Example 11-5 to increase gpm instead of decreasing CWT.
Example 11-5:
What is the new CWT if motor is changed from 20 HP to 25
HP in Example 11-4? Example 11-4 information given below:
WB change: 75 to 60
R change: 20 to 25
GPM change: 1000 to 1250
Original PF: 3.1 (see example 11-4 for how to get this value)
In Example 11-4, we developed a new CWT of 82 ° F when circulating 1250 gpm at R = 25°
F and 60° WB. If motor HP is increased from 20 to 25 under these conditions with PF
correction factor = 1.077 (as shown in Example 11-5), GPM could be increased from 1250 to
(1250)(1.077) =
1347 gpm.
The sample calculations, equations and spreadsheets presented herein were developed using examples published in the Enginee
While every effort has been made to present accurate and reliable technical information and calculation spreadsheets based on t
The Calculation Spreadsheets are provided without warranty of any kind including warranties of accuracy or reasonableness of
In no event will the GPA or GPSA and their members be liable for any damages whatsoever (including without limitation, those
These calculation spreadsheets are provided to provide an “Operational level” of accuracy calculation based on rather broad ass
Application 11-6 -- Effect of correction factor on gpm instead of Cold Water Temperature
Given Data:
Flow = 1000 gpm
Hot Water = 105 °F
Cold Water = 85 °F
Wet Bulb = 75 °F
Use the PF correction factor from Example 11-5 to increase gpm instead of decreasing CWT.
Application 11-5:
What is the new CWT if motor is changed from 20 HP to 25
HP in Example 11-4? Application 11-4 information given below:
WB change: 75 to 60
R change: 20 to 25
GPM change: 1000 to 1250
Original PF: 3.1 (see Application 11-4 for how to get this value)
In Application 11-4, we developed a new CWT of 82°F when circulating 1250 gpm at R =
25° F and 60° WB. If motor HP is increased from 20 to 25 under these conditions with PF
correction factor = 1.077 (as shown in Application 11-5), GPM could be increased from 1250
to (1250)(1.077) =
1347 gpm.
examples published in the Engineering Data Book as published by the Gas Processors Suppliers Association as a service to the gas processi
calculation spreadsheets based on the GPSA Engineering Data Book sample calculations, the use of such information is voluntary and the G
s of accuracy or reasonableness of factual or scientific assumptions, studies or conclusions, or merchantability, fitness for a particular purpo
(including without limitation, those resulting from lost profits, lost data or business interruption) arising from the use, inability to, reference
lculation based on rather broad assumptions (including but not limited to: temperatures, pressures, compositions, imperial curves, site cond
vice to the gas processing industry. All information and calculation formulae has been compiled and edited in cooperation with Gas Proces
n is voluntary and the GPA and GPSA do not guarantee the accuracy, completeness, efficacy, or timeliness of such information. Reference
ss for a particular purpose, or non-infringement of intellectual property.
e, inability to, reference to or reliance on the information in this Publication, whether based on warranty, contract, tort or any other legal the
mperial curves, site conditions etc) and do not replace detailed and accurate Design Engineering taking into account actual process condition
d in cooperation with Gas Processors Association (GPA).
of such information. Reference herein to any specific commercial product, calculation method, process, or service by trade-name, trademar
ntract, tort or any other legal theory and whether or not advised of the possibility of such damages.
account actual process conditions, fluid properties, equipment condition or fowling and actual control set-point dead-band limitations.
service by trade-name, trademark, and service mark manufacturer or otherwise does not constitute or imply endorsement, recommendation
Example 11-7 -- Cooling tower calculations on concentration and blowdown rate Application 11-7 -- Cooling tower calculations on concentration and blowdown rate
Calculate the concentrations and blowdown rate for the following cooling tower: Calculate the concentrations and blowdown rate for the following cooling tower:
Circulation Rate = 10000 gpm Circulation Rate = 10000 gpm
Water Temperature Drop Water Temperature Drop
Through Tower = 20 °F Through Tower = 20 °F
Type of Tower = Mechanical-draft towers Type of Tower = Mechanical-draft towers
Blowdown Rate = 20 gpm Blowdown Rate = 20 gpm
or 0.2% of circulation rate or 0.2% of circulation rate
Therefore: Therefore:
Evaporation Loss = 2% (1% for each 10° temperature drop) Evaporation Loss = 2% (1% for each 10° temperature drop)
Windage Loss = 0.3% Maximum for Mechanical-draft towers , p. 11-4 Windage Loss = 0.3% Maximum for Mechanical-draft towers, p. 11-4
The windage component of B is 0.003, therefore the blowdown rate required would be The windage component of B is 0.003, therefore the blowdown rate required would be 0.0067
0.0067 - 0.003 = 0.0037 or -0.003 = 0.0037 or
(10000 gpm) (0.0037) = (10000 gpm) (0.0037) =
37 gpm. 37 gpm.
The sample calculations, equations and spreadsheets presented herein were developed using examples published in the Engineering Data Book as published by the Gas Processors Suppliers Association as a service to the gas processing industry. All information and calculation formulae has been compiled and edited in cooperation with Gas Processors Association (GPA).
While every effort has been made to present accurate and reliable technical information and calculation spreadsheets based on the GPSA Engineering Data Book sample calculations, the use of such information is voluntary and the GPA and GPSA do not guarantee the accuracy, completeness, efficacy, or timeliness of such information. Reference herein to any specific commercial product, calculation method, process, or service by trade-name, trademark, and service mark manufacturer or otherwise does not constitute or imply endorsement, recommendation or favoring by the GPA and/or GPSA.
The Calculation Spreadsheets are provided without warranty of any kind including warranties of accuracy or reasonableness of factual or scientific assumptions, studies or conclusions, or merchantability, fitness for a particular purpose, or non-infringement of intellectual property.
In no event will the GPA or GPSA and their members be liable for any damages whatsoever (including without limitation, those resulting from lost profits, lost data or business interruption) arising from the use, inability to, reference to or reliance on the information in this Publication, whether based on warranty, contract, tort or any other legal theory and whether or not advised of the possibility of such damages.
These calculation spreadsheets are provided to provide an “Operational level” of accuracy calculation based on rather broad assumptions (including but not limited to: temperatures, pressures, compositions, imperial curves, site conditions etc) and do not replace detailed and accurate Design Engineering taking into account actual process conditions, fluid properties, equipment condition or fowling and actual control set-point dead-band limitations.