Model MBW15 MBW22
Model MBW15 MBW22
00
MODEL |MBW15-22
> PERKINS Diesel engine.
> Water cooling system.
> Internal residential muffler.
> Set easy to be transported with hand pallet.
TECHNICAL CHARACTERISTICS NOT IMPEGNATIVE RESERVATION OF MODIFICATIONS FOR INNOVATION OF THE PRODUCT
EMERGENCY POWER LTP kVA (kW) 13,8 (11,0) 20,1 (16,1)
Voltage Volt 400/231 400/231
Frequency Hz 50 50
Power factor Cos φ 0,8 0,8
Fuel capacity Litres 51 51
Autonomy ( 100% load PRP) h 14,0 10,0
Acoustic power LWA 94 93
Acoustic pressure at 7m dB(A) 69 68
TECHNICAL FEATURES
• Voltmeter.
Instrumentation
• Hours-counter.
(analogue) • Ammeter.
MANUAL CONTROL PANEL (MCP)
Protections with
• Engine protection: battery charger failure, low oil pressure, high engine temperature.
alarm
• Engine protection: battery charger failure, low oil pressure, high engine temperature.
Protections with shut
• Circuit breaker protection: IV poles.
down • Differential protection.
Manual control panel, mounted on 1 x 400V/32A 3P+N+T CE.
the genset and complete of:
instrumentation, control, protection 1 x 400V/16A 3P+N+T CE.
and sockets. Output sockets
2 x 230V/16A 2P+T CE.
1 x Schuko 230V/16A.
ON*: when selected this position, the system will take some seconds for air perheating by means of a glow plug. The preheating period is lighted by the proper
led on the engine protection unit.
PAGE 1.3
AUTOMATIC CONTROL PANEL (ACP) MBW15 MBW22
• Selector switch with six positions: Automatic test - Automatic starting - Engine locked - Mains contactor forced -
Manual starting - Genset contactor forced.
Commands and • Push-buttons: start/stop, up/down selection, reset.
others • Emergency stop button.
• Remote starting availability.
TECHNICAL CHARACTERISTICS NOT IMPEGNATIVE RESERVATION OF MODIFICATIONS FOR INNOVATION OF THE PRODUCT
* Manual Starting: the preheating period begins automatically when this position is selected. It is necessary to select again this position to enable one more time the preheating
period.
• Selector switch with six positions: Automatic test - Automatic starting - Engine locked - Mains contactor forced -
AUTOMATIC CONTROL PANEL (AMF)
• Plinth row for connection from pre-wired panel (mounted on the genset) to AMF panel.
Power output
• Power cables connected to terminals board (internal).
* Manual Starting: the preheating period begins automatically when this position is selected. It is necessary to select again this position to enable one more time the preheating
period.
> RSS: REMOTE CONTROL. Not available for MCP panel. Standard on automatic versions.
PAGE 2.3
ACCESSORIES
> LOAD TRANSFER SWITCH PANEL. MBW15 MBW22
Change over
IV poles - 20A. IV poles 32A.
contactors
PAGE 3.3