ABB SACE The data and illustrations are not binding. We reserve
www.abb.com
SACE Tmax XT
New low voltage moulded-case
circuit-breakers up to 250 A
Construction Characteristics 1
Accessories 3
Overall dimensions 5
Wiring Diagrams 6
Ordering codes 7
Glossary 8
1SDC210033D0201
New SACE Tmax XT.
Simply XTraordinary.
2
Today a highly advanced range of circuit-breakers has been
brought out, with unparalleled versatility of use and able to
solve all installation problems brilliantly.
You can find the new SACE Tmax XT in the three-pole and
four-pole, fixed, plug-in and withdrawable versions, fitted with
the very latest generation thermomagnetic and electronic trip
units, with the possibility of interchangeability. The new SACE
Tmax XT set up a new technological standard and leave
you free to think up and build installations with extraordinary
performances. An extraordinary demonstration of ABB SACE’s
innovation capability.
Extraordinary latest generation electronics. Extraordinary
coverage of all plant requirements. Extraordinary
performances in compact dimensions.
Extraordinary simplicity of installation and putting into service.
Extraordinary range of accessories available.
3
New SACE Tmax XT.
XTraordinary completeness of range.
4
The new SACE Tmax XT go everywhere and fear no tests frames. To say nothing of the new and large number of
as they are made to respond successfully to all plant dedicated accessories available, even for special applications.
engineering requirements, from the standard ones to the most All that remains is for you to choose: XT1 and XT3 for
technologically advanced ones, thanks to the extraordinary building standard installations with ABB SACE’s unquestioned
fullness of their range. A complete offer up to 250A for reliability and safety, whereas XT2 and XT4 for building
distribution, for motor protection, for generator protection, for technologically advanced installations with top of market
oversized neutral, as switch-disconnectors and for any other performance. New SACE Tmax XT, for any choice, always and
needs. A new range of both thermomagnetic and electronic in any case simply extraordinary.
protection trip units, interchangeable right from the smallest New SACE Tmax XT. XTreme protection.
5
New SACE Tmax XT.
XTraordinary advanced electronics.
6
The trip units are interchangeable and guarantee absolute All the Ekip trip units can be fitted with a vast range of
tripping reliability and precision. Apart from the continuous dedicated accessories. The main ones are:
green LED, which indicates correct operation of the protection – the Ekip Display, to be applied onto the front of the
trip unit, all the Ekip trip units also have a LED to signal electronic trip unit for simpler setting and for better reading
intervention of all the protection functions. of information;
To allow the Ekip units to communicate and exchange – the Ekip LED Meter, a device to be installed on the front of
information with the other devices, simply insert the Ekip Com the trip unit to simplify current readings;
module inside the circuit-breaker, leaving the space inside the – the Ekip TT, the new trip test unit;
electric panel free. – the Ekip T&P, the extraordinary testing and programming
unit.
Finally, for the first time ground fault protection G is also
available on the 160A frame.
Ekip: isn’t all this simply XTraordinary?
New SACE Tmax XT. XTended technology.
7
Construction Characteristics
Index
Construction characteristics ...................................................................................................1/2
Nomenclature of the trip units and residual current protection devices .................................1/7
1/1
1SDC210033D0201
Construction characteristics
XT1
Size(G2.1) [A] 160
Poles [No.] 3, 4
Rated service voltage, Ue(G2.4) (AC) 50-60Hz [V] 690
(DC) [V] 500
Rated insulation voltage, Ui(G2.5) [V] 800
Rated impulse withstand voltage, Uimp(G2.6) [kV] 8
Versions Fixed, Plug-in (2)
Breaking capacities according to IEC 60947-2 B C N S H
Rated ultimate short-circuit breaking capacity, Icu (G2.7)
Icu @ 220-230V 50-60Hz (AC) [kA] 25 40 65 85 100
Icu @ 380V 50-60Hz (AC) [kA] 18 25 36 50 70
Icu @ 415V 50-60Hz (AC) [kA] 18 25 36 50 70
Icu @ 440V 50-60Hz (AC) [kA] 15 25 36 50 65
Icu @ 500V 50-60Hz (AC) [kA] 8 18 30 36 50
Icu @ 525V 50-60Hz (AC) [kA] 6 8 22 35 35
Icu @ 690V 50-60Hz (AC) [kA] 3 4 6 8 10
Icu @ 250V (DC) 2 poles in series [kA] 18 25 36 50 70
Icu @ 500V (DC) 3 poles in series [kA] 18 25 36 50 70
Rated service short-circuit breaking capacity, Ics (G2.8)
Ics @ 220-230V 50-60Hz (AC) [kA] 100% 100% 75% (50) 75% 75%
Ics @ 380V 50-60Hz (AC) [kA] 100% 100% 100% 100% 75%
Ics @ 415V 50-60Hz (AC) [kA] 100% 100% 100% 75% 50% (37.5)
Ics @ 440V 50-60Hz (AC) [kA] 75% 50% 50% 50% 50%
Ics @ 500V 50-60Hz (AC) [kA] 100% 50% 50% 50% 50%
Ics @ 525V 50-60Hz (AC) [kA] 100% 100% 50% 50% 50%
Ics @ 690V 50-60Hz (AC) [kA] 100% 100% 75% 50% 50%
Ics @ 250V (DC) 2 poles in series [kA] 100% 100% 100% 75% 75%
Ics @ 500V (DC) 3 poles in series [kA] 100% 100% 100% 75% 75%
Rated short-circuit making capacity, Icm (G2.10)
Icm @ 220-230V 50-60Hz (AC) [kA] 52.5 84 143 187 220
Icm @ 380V 50-60Hz (AC) [kA] 36 52.5 75.6 105 154
Icm @ 415V 50-60Hz (AC) [kA] 36 52.5 75.6 105 154
Icm @ 440V 50-60Hz (AC) [kA] 30 52.5 75.6 105 143
Icm @ 500V 50-60Hz (AC) [kA] 13.6 36 63 75,6 105
Icm @ 525V 50-60Hz (AC) [kA] 9 13.6 46.2 73.5 73.5
Icm @ 690V 50-60Hz (AC) [kA] 4.5 6 9 13.6 17
Breaking capacities according to NEMA-AB1
@ 240V 50-60Hz (AC) [kA] 25 40 65 85 100
@ 480V 50-60Hz (AC) [kA] 8 18 30 36 65
Utilisation Category (IEC 60947-2) A
Reference Standard IEC 60947-2
Isolation behaviour
Mounted on DIN rail DIN EN 50022
Mechanical life(G2.14) [No. Operations] 25000
[No. Hourly operations] 240
Electrical life @ 415 V (AC)(G2.13) [No. Operations] 8000
[No. Hourly operations] 120
Dimensions - Fixed 3 poles [mm] 76.2 x 70 x 130
(Width x Depth x Height) H
4 poles [mm] 101.6 x 70 x 130
D W
1/2
1SDC210033D0201
XT2 XT3 XT4
160 250 160/250
3, 4 3, 4 3, 4
690 690 690
500 500 500
1000 800 1000
8 8 8
Fixed, Withdrawable, Plug-in Fixed, Plug-in Fixed, Withdrawable, Plug-in
N S H L V N S N S H L V
100% 100% 100% 100% 100% 75% 50% 100% 100% 100% 100% 100%
100% 100% 100% 100% 100% 75% 50% (27) 100% 100% 100% 100% 100%
100% 100% 100% 100% 100% 75% 50% (27) 100% 100% 100% 100% 100%
100% 100% 100% 100% 100% 75% 50% 100% 100% 100% 100% 100%
100% 100% 100% 100% 100% 75% 50% 100% 100% 100% 100% 100%
100% 100% 100% 100% 100% 75% 50% 100% 100% 100% 100% 100%
100% 100% 100% 100% 75% 75% 50% 100% 100% 100% 100% 75% (20)
100% 100% 100% 100% 100% 100% 75% 100% 100% 100% 100% 100%
100% 100% 100% 100% 100% 100% 75% 100% 100% 100% 100% 100%
143 187 220 330 440 143 187 143 187 220 330 440
75.6 105 154 264 440 75.6 105 75.6 105 154 264 330
75.6 105 154 264 330 75.6 105 75.6 105 154 264 330
75.6 105 143 220 330 75.6 105 75.6 105 143 220 330
63 75.6 105 132 220 63 75.6 63 75.6 105 132 220
40 52.5 63 75.6 132 46.2 75.6 40 52.5 63 75.6 198
17 24 30 36 40 9 13.6 13.6 22.5 30 40 52.5
15 15 15
15 15 15
Q Q
Q
Q Q
Q Q
Q Q
Q Q
Q Q Q
Q
V V
V V
Q Q
V V
V V
1/3
1SDC210033D0201
Construction characteristics
(Gx.x)
The references in round brackets in the technical catalogue refer to the Glossary in the final charter of the
technical catalogue.
All the moulded-case circuit-breakers in the SACE Tmax XT family are realized in accordance with
the following construction characteristics:
Q double insulation(G1.5);
Q positive operation(G1.6);
Q isolation behaviour(G1.7);
Q electromagnetic compatibility(G1.8);
Positive operation
Q tropicalization(G1.9);
Q power supply from the top towards the bottom or vice versa;
Q no nominal performance derating for use up to an altitude of 2000m. Above 2000m, the proper-
ties of the atmosphere (composition of the air, dielectric strength, cooling power and pressure)
change, having an impact on the main parameters which define the circuit-breaker. The table
Installation positions below gives the changes to the main performance parameters;
Q the SACE Tmax XT circuit-breakers can be used in environments where the temperature is be-
tween -25°C and +70°C and stored in environments where the temperature is between -40°C
and +70°C. To use temperatures other than 40°C, see the “Temperature Performances” para-
graph of the Characteristic Curves and the technical information chapter;
Circuit-breaker
1SDC210A20F0001
With Without With Front With With transmitted With high With low
front front (1) for lever rotary rotary handle and terminal terminal
-FLD- Handles accessory IP54 covers HTC covers LTC
A IP40 IP20 IP40 IP40 IP54 IP40 IP40
B IP20 IP20 IP20 IP20 IP20 IP40 IP40
Protection degrees C NC NC NC NC NC IP40 IP30
(1)
During the installation of electrical accessories
NC Not classifiable
Accessories
Motor operator Residual Residual current Automatic Transfer
MOD, MOE current from switchboard Switch ATS021
or MOE-E devices RCQ020 and ATS022
On Front IP30 IP40 IP41 IP40
Q all the circuit-breakers in the XT family are fitted with a test pushbutton which allows the release
test to be done. This test must be carried out with the circuit-breaker closed.
Test pushbutton
1/4
1SDC210033D0201
Regulations and Reference Standards
Certification of conformity with the product Standards is carried out in the ABB SACE tests labora-
tory (accredited by SINAL) in respect of the EN 45011 European Standard, by the Italian certification
body ACAE (Association for Certification of Electrical Apparatus), member of the European LOVAG
organisation (Low Voltage Agreement Group) and by the Swedish certification body SEMKO be-
longing to the international IECEE organisation.
The SACE Tmax XT series has a hologram on the front, obtained using special anti-forgery tech-
niques, a guarantee of the quality and genuineness of the circuit-breaker as an ABB SACE product.
1/5
1SDC210033D0201
Identification of the SACE Tmax XT
circuit-breakers
The characteristics of the circuit-breaker are given on the rating nameplate on the front of the circuit-
breaker, and on the side rating plate.
Front label 1 7 4 3
7 10
6
5
15
11
1
9
16
12
14
8 13
2
Side label 1
7 9
7
3
6
5 4
15
16
6 14
12
10
1/6
1SDC210033D0201
Nomenclature of the trip units and
residual current protection devices
The tables below give details of the logic with which each thermomagnetic trip units, electronic trip
units and residual current devices has been named.
Example:
Q MA: magnetic only trip unit, with adjustable protection threshold;
Q TMD: thermomagnetic trip unit, with adjustable thermal and fixed magnetic protection threshold;
Q TMG: thermomagnetic trip unit, with adjustable thermal and fixed magnetic protection threshold, specifically
for protection of generators.
Example:
Q Ekip LS/I: electronic trip unit for distribution networks protection, with “L” against overload and as an alterna-
tive “S” protection function against delay short circuit or “I” protection function against instantaneous short
circuit;
Q Ekip M-LRIU: electronic trip unit for motors protection, with LRIU protection functions;
Q Ekip N-LS/I XT2: loose electronic trip unit for the neutral protection, with “L” against overload and as an alter-
native “S” protection function against delay short circuit or “I” protection function against instantaneous short
circuit.
Example:
Q RC Inst: residual current protection device with instantaneous timing;
Q RC Sel 200: residual current protection device with adjustable time trip, reduced to 200mm;
Q RC B type: residual current protection device “B” type.
1/7
1SDC210033D0201
The SACE Tmax XT Ranges
Index
The SACE Tmax XT family ranges .......................................................................................2/2
Switch-disconnectors
Special applications
Communication system.........................................................................................................2/26
2/1
1SDC210033D0201
The SACE Tmax XT family ranges
The SACE Tmax XT moulded-case circuit-breaker family complies with different installation require-
ments. Circuit-breakers are available with trip units dedicated to different applications, such as
power distribution, generator protection, motor protection and oversized neutral protection. Some
of these circuit-breakers can also be used in communication systems and plants that function at
400Hz. Switch-disconnectors are also available.
In = Rated uninterrupted current(G2.2) XT1 160 XT2 160 XT3 250 XT4 250
Power distribution
Thermomagnetic trip units
TMD 16…160 63…250
TMD/TMA 1.6…160 16…250
Electronic trip units
Ekip LS/I 10…160 40…250
Ekip I 10…160 40…250
Ekip LSI 10…160 40…250
Ekip LSIG 10…160 40…250
Motor protection
Magnetic trip units
MF/MA 1…100(1) 100…200 (1) 10…200 (1)
Electronic trip units
Ekip M-I 20…100(1)
Ekip M-LIU 25…100 (1) 40…160 (1)
(1)
Ekip M-LRIU 25…100 40…160 (1)
Generator Protection
Thermomagnetic trip units
TMG 16…160 63…250
Electronic trip units
Ekip G-LSI 10…160 40…250
Oversized Neutral Protection 160%
Electronic trip units
Ekip N-LS/I 10…100(2) 40…160 (2)
Switch-disconnectors Q Q Q
Special applications
400 Hz Q Q Q Q
Communication Q Q
(1)
Only 3 poles version
(2)
Only 4 poles version
2/2
1SDC210033D0201
Circuit-breakers for power distribution
Main characteristics
SACE Tmax XT moulded-case circuit-breakers are the ideal solution for all distribution levels, from
the main low voltage switchboard to the subswitchboards in the installation. They feature high
specific let-through current peak and energy limiting characteristics that allow the circuits and
equipment on the load side to be sized in an optimum way. SACE Tmax XT circuit-breakers with
thermomagnetic and electronic trip units protect against overloads, short-circuits, earth faults and
indirect contacts in low voltage distribution networks.
2/3
1SDC210033D0201
Circuit-breakers for power distribution
Main characteristics
2/4
1SDC210033D0201
Circuit-breakers for power distribution
Thermomagnetic trip units
TMD
Main characteristics:
Q available for XT1 and XT3 in the three-pole and four-pole versions;
Q protections:
– against overload (L): adjustable protection threshold from 0.7...1xIn, with inverse long-time
trip curve;
– against instantaneous short-circuits (I): fixed 10xIn protection threshold, with instantaneous
trip curve;
Q 100% neutral protection in four-pole circuit-breakers. 50% neutral protection is only available for
In≥125A;
Q the thermal protection setting is made by turning the relative cursor on the front of the release.
XT1
TMD
Breaking capacity B B B,C B,C,N B,C,N ALL ALL ALL ALL ALL ALL
In [A] 16 20 25 32 40 50 63 80 100 125 160
Neutral [A] - 100% 16 20 25 32 40 50 63 80 100 125 160
I 1 = 0.7…1xIn Neutral [A] - 50% – – – – – – – – – 80 100
I3 [A] 450 450 450 450 450 500 630 800 1000 1250 1600
Neutral [A] - 100% 450 450 450 450 450 500 630 800 1000 1250 1600
I 3 = 10xIn Neutral [A] - 50% – – – – – – – – – 800 1000
XT3
TMD
In [A] 63 80 100 125 160 200 250
Neutral [A] - 100% 63 80 100 125 160 200 250
I 1 = 0.7…1xIn Neutral [A] - 50% – – – 80 100 125 160
I3 [A] 630 800 1000 1250 1600 2000 2500
Neutral [A] - 100% 630 800 1000 1250 1600 2000 2500
I 3 = 10xIn Neutral [A] - 50% – – – 800 1000 1250 1600
2/5
1SDC210033D0201
Circuit-breakers for power distribution
Thermomagnetic trip units
TMD/TMA
Main characteristics:
Q available for XT2 and XT4 in the three-pole and four-pole versions;
Q protections:
– against overload (L): adjustable protection threshold from 0.7...1xIn, with inverse long time
trip curve;
– against instantaneous short-circuit (I):
- fixed protection threshold for In≤32A,
- adjustable threshold beteewn 8…10xIn for 40A,
- adjustable threshold beteewn 6…10xIn for 50A,
- adjustable threshold beteewn 5…10xIn for In≥63A;
Q 100% neutral protection in four-pole circuit-breakers. 50% neutral protection is only available for
In≥125A;
Q the thermal and magnetic protection settings are made by turning the relative cursors on the
front of the release.
XT2
TMD/TMA
In [A] 1.6(1) 2(1) 2.5(1) 3.2(1) 4(1) 5(1) 6.3(1) 8(1) 10(1) 12.5(1) 16 20 25 32 40 50 63 80 100 125 160
Neutral [A] - 100% 1.6 2 2.5 3.2 4 5 6.3 8 10 12.5 16 20 25 32 40 50 63 80 100 125 160
I1 = 0.7…1xIn Neutral [A] - 50% – – – – – – – – – – – – – – – – – – – 80 100
TMD 16 20 25 32 40 50 63 80 100 125 300 300 300 320
TMA 300… 300… 300… 400… 500… 625… 800…
400 500 630 800 1000 1250 1600
Neutral [A] - 100% 16 20 25 32 40 50 63 80 100 125 300 300 300 320 300… 300… 300… 400… 500… 625… 800…
400 500 630 800 1000 1250 1600
Neutral [A] - 50% – – – – – – – – – – – – – – – – – – – 400… 1000…
800 2000
(1)
Available only as complete circuit-breaker
XT4
TMD/TMA
In [A] 16 20 25 32 40 50 63 80 100 125 160 200 225 250
Neutral [A] - 100% 16 20 25 32 40 50 63 80 100 125 160 200 225 250
I1 = 0.7…1xIn Neutral [A] - 50% – – – – – – – – – 80 100 125 125 160
TMD 300 300 300 320
TMA 300… 300… 315… 400… 500… 625… 800… 1000… 1125… 1250…
400 500 630 800 1000 1250 1600 2000 2250 2500
Neutral [A] - 100% 300 300 300 320 300… 300… 315… 400… 500… 625… 800… 1000… 1125… 1250…
400 500 630 800 1000 1250 1600 2000 2250 2500
Neutral [A] - 50% – – – – – – – – – 315… 500… 625… 625… 500…
630 1000 1250 1250 1000
2/6
1SDC210033D0201
Circuit-breakers for power distribution
Electronic trip units
Ekip I
Main characteristics:
Q usable with the XT2 and XT4 circuit-breaker in the three-pole and four-pole versions;
Q protections:
– against instantaneous short-circuit (I): adjustable protection threshold from 1...10xIn, with
instantaneous trip curve;
– of the neutral in four-pole circuit-breakers:
- for In≥100A in the OFF or ON positions, 50% and 100% of the phases can be selected;
- for In<100A, neutral protection is fixed at 100% of the phases and disableded by user;
Q manual setting using the relative dip-switches, which allow the settings to be made even when
the trip unit is off;
Q LED:
– LED lit with a steady green light indicating that the trip unit is supplied correctly. The LED
comes on when the current exceeds 0.2xIn;
– LED with a steady red light, indicating that protection I has tripped; Red LED light on connect-
ing Ekip TT or Ekip T&P accessories after circuit-breaker opening for “I protection” interven-
tion;
– Ekip I is equipped with a trip coil disconnection protection device that detects whether the
opening solenoid has disconnected. Signalling is made by all the LEDs flashing simultane-
ously;
Q test connector on the front of the trip unit;
– to connect the Ekip TT trip test unit, which allows trip test, LED test and signalling about lat-
est trip happened;
– to connect the Ekip T&P unit, which allows the measurements to be read, the trip test to be
conducted and the I protection function test to be carried out;
Q self-supply from a minimum current of 0.2xIn up.
Ekip I
Protection function Trip threshold Trip curve (1) Excludability Relation
Manual setting:
I 3= 1, 1.5, 2, 2.5, 3, 3.5, 4.5,
Against short-circuits with 5.5, 6.5, 7, 7.5, 8, 8.5, 9,
adjustable treshold and 10xIn ≤40 ms Yes t=k
instantaneous trip time
Tolerance: ±20% I>4In
±10% I≤4In
(1)
Tollerances in case of:
– self-powered trip unit at full power;
– 2 or 3 phase power supply.
In conditions other than those considered, the trip time is ≤60 ms.
2/7
1SDC210033D0201
Circuit-breakers for power distribution
Electronic trip units
Ekip LS/I
Main characteristics: :
Q available for XT2 and XT4 in the three-pole and four-pole versions;
Q protections:
– against overload (L): 0.4...1xIn adjustable protection threshold, with adjustable time trip curve;
– against short-circuit with delay (S): 1...10xIn adjustable protection threshold, with adjustable
time trip curve (as an alternative to I protection);
– against instantaneous short-circuit (I): 1...10xIn adjustable protection threshold, with instan-
taneous trip curve (as an alternative to S protection);
– of the neutral in four-pole circuit-breakers:
- for In ≥100A can be selected in the OFF or ON positions, 50%, 100% of the phases;
- for In <100A, neutral protection is fixed at 100% of the phases and disableded by user;
Q manual setting using the relative dip-switches on the front of the trip unit, which allow the set-
tings to be made even when the trip unit is off;
Q LED:
– LED with steady green light indicating that the trip unit is supplied correctly. The LED comes
on when the current exceeds 0.2xIn;
– red LED for each protection:
- L: LED with steady red light, indicates pre-alarm for current exceeding 0.9xI1;
- L: LED with flashing red light, indicates alarm for current exceeding setted threshold;
- LS/I: LED with steady red light, shows that the protection has tripped. After the circuit-
breaker has opened, connect the Ekip TT or Ekip T&P accessory to find out which protec-
tion function tripped the trip unit;
– Ekip LS/I is equipped with a trip coil disconnection detection device that detects whether the
opening solenoid has disconnected. Signalling is made by all the LEDs flashing simultaneously;
Q test connector on the front of the release:
– to connect the Ekip TT trip test unit, which allows trip test, LED test and signalling about lat-
est trip happened;
– to connect the Ekip T&P unit, which allows the measurements to be read, the trip test to be
conducted and the protection functions test to be carried out;
Q thermal memory which can be activated by Ekip T&P;
Power-on LED
Ekip LS/I
Protection function Trip threshold Trip curve(1) Excludability Relation Thermal memory
Against overloads with Manual setting: Manual setting:
long inverse time delay trip I1= 0.4...1xIn step 0.04 t1= 12-36s at I=3xI1
– t = k/l2 Yes
according to IEC 60947-2 Tolerance: trip between Tolerance: ±10% up to 4xIn
Standard 1.05…1.3 I1 (IEC 60947-2) ±20% from 4xIn
Manual setting: t2= 0.1-0.2s
Against short-circuits with I2= 1-1.5-2-2.5-3-3.5-4.5-5.5- Tolerance: ±10% up to 4xIn
indipendend time delay 6.5-7-7.5-8-8.5-9-10xIn Yes t=k –
(t=k) ±20% from 4xIn
Tolerance: ±10%
Manual setting:
Against short-circuits with I3= 1-1.5-2-2.5-3-3.5-4.5-5.5-
adjustable treshold and 6.5-7-7.5-8-8.5-9-10xIn Instantaneous Yes t=k –
instantaneous trip time
Tolerance: ±10%
(1)
Tollerances in case of: Protection Trip threshold Trip time
– self-powered trip unit at full power;
L release between 1.05 and 1.25 x I1 ±20%
– 2 or 3 phase power supply.
In conditions other than those considered, the S ±10% ±20%
following tollerance hold: I ±15% ≤60 ms
2/8
1SDC210033D0201
Ekip LSI and Ekip LSIG
Main characteristics:
Q available for XT2 and XT4 in three-pole and four-pole versions;
Q protections:
– against overloads (L): 0.4...1xIn adjustable protection threshold, with adjustable time trip
curve;
– against short-circuits with delay (S): 1...10xIn adjustable protection threshold, with adjustable
time trip curve (short inverse time (t=k2) or indipendent time (t=k));
– against instantaneous short-circuits (I): 1...10xIn adjustable protection threshold, with instan-
taneous trip curve;
– against earth faults (G): 0.2...1xIn adjustable protection threshold, with indipendent time trip
curve;
– of the neutral in four-pole circuit-breakers:
- for In≥100A can be selected in OFF or ON, 50%, 100% of phases;
- for In<100A neutral protection is fixed on 100% of phases and disableded by user;
Q setting:
– manual setting using the relative dip-switches on the front of the trip unit, which allow the
settings to be made even when the trip unit is off;
– electronic setting, made both locally using the Ekip T&P or Ekip Display accessory and via
remote control, by means of the Ekip Com unit;
Q LED:
– LED on with steady green light indicating that the trip unit is supplied correctly. The LED
comes on when the current exceeds 0.2xIn;
– red LED for each protection:
- L: LED with steady red light, indicates pre-alarm for current exceeding 0.9xI1;
- L: LED with flashing red light, indicates alarm for current exceeding setted threshold;
- LSIG: LED with steady red light, shows that the protection has tripped. After the circuit-
breaker has opened, connect the Ekip TT or Ekip T&P accessory to find out which protec-
tion function tripped the trip unit;
– the trip unit is equipped with a device that detects the eventual opening solenoid disconnec-
tion thanks to the simultaneous blinking of all the LED;
Q test connector on the front of the release:
– to connect the Ekip TT trip test unit, which allows trip test, LED test and signalling about the
latest trip happened;
– to connect the Ekip T&P unit, which allows the measurements to be read, the trip test to be
conducted, the protection functions test to be carried out, electronic setting of the protection
functions of the trip unit and of the communication parameters;
Q thermal memory which can be activated by Ekip T&P or Ekip Display;
Q self-supply from a minimum current of 0.2xIn up;
Q the three-pole version can be accessorized with external neutral;
Q with the addition of the Ekip Com in the circuit-breaker, you can:
– acquire and transmit a wide range of information via remote control;
– accomplish the circuit-breaker opening and closing commands by means of the motor op-
erator in the electronic version (MOE-E);
– know the state of the circuit-breaker (open/closed/trip) via remote control;
– setting the configuration and programming the unit, such as the current thresholds and the
protection function curves.
2/9
1SDC210033D0201
Circuit-breakers for power distribution
Electronic trip units
Test connector
Dip switch for the S trip
curves selection
Selection for manual or
electronic setting
2/10
1SDC210033D0201
Circuit-breakers for motors protection
Main characteristics
The safety and reliability of the solution are important aspects that must be considered when choos-
ing and manufacturing the system for starting(G4.3 and G4.4) and monitoring motors.
Start-up is a particularly critical phase for the motor itself and for the installation powering it. Even
rated service needs to be adequately monitored and protected so as to deal with any faults that
might occur.
When it comes to direct starting, ABB SACE proposes two different solutions:
Q a conventional system with three poles a circuit-breaker equipped with a magnetic only trip
unit for protection against short-circuits, a thermal relay for protection against overloads and
phase failure or imbalance, and a contactor to operate the motor;
Q an advanced protection system which integrates all the protection and monitoring functions,
and a contactor for operating the motor, in the circuit-breaker itself.
Several different factors must be considered when choosing and coordinating the protection and
operating devices, e.g.:
Q the electrical specifications of the motor (type, power rating, efficiency, cosϕ);
Q the starting type and diagram;
Q the fault current and voltage in the part of the network where the motor is installed.
Circuit-breaker with
electronic trip unit
Circuit-breaker
Ekip M-LRIU
with magnetic
only trip unit
PR212/CI
Contactor
Contactor
Thermal relay
Motor
Motor
PTC
Consult the QT7 Technical Application Paper: “The asynchronous three-phase motor: general infor-
mation and ABB’s offer for coordinating the protections” for further details.
The motor protection and operating devices must be chosen in accordance with the coordination
tables provided by ABB either through documentation “Coordination tables” or on the web site:
http://www.abbcontrol.fr/coordination_tables/.
2/11
1SDC210033D0201
Circuit-breakers for motors protection
Main characteristics
2/12
1SDC210033D0201
Circuit-breakers for motors protection
Magnetic trip units
MF/MA
Main characteristics:
Q available for XT2, XT3 and XT4 in the three-pole version only, these trip units are mainly used for
protecting motors, in conjunction with a thermal relay and a contactor;
Q protections:
– against instantaneous short-circuit (I) for XT2: for In≤12.5A the protection threshold I is fixed
at 14xIn, whereas for In>12.5A the protection threshold I is adjustable from 6..14xIn;
– against instantaneous short-circuit (I) for XT3: the protection threshold I is adjustable from
6..12xIn;
– against instantaneous short-circuit (I) for XT4: the protection threshold I is adjustable from
5..10xIn;
Q the magnetic protection setting is made by turning the relative cursor on the front of the release.
XT2
MF/MA
In [A] 1(1) 2(1) 4(1) 8.5(1) 12.5(1) 20 32 52 80 100
I3 = MF 14 28 56 120 175
I3 = 14xIn [A]
I3 = 6..14xIn [A] I3 = MA 120...280 192…448 314…728 480…1120 600...1400
(1)
Available only as complete circuit-breaker
XT3
MA
In [A] 100 125 160 200
I3 [A] 600…1200 750…1500 960…1920 1200…2400
I3 = 6..12xIn
XT4
MA
In [A] 10(1) 12.5(1) 20 32 52 80 100 125 160 200
I3 [A] 50…100 62.5…125 100…200 160…320 260…520 400…800 500…1000 625…1250 800…1600 1000…2000
I3 = 5..10xIn
(1)
Available only as complete circuit-breaker
2/13
1SDC210033D0201
Circuit-breakers for motors protection
Electronic trip units
Ekip M-I
Main characteristics:
Q only available for XT2 in three-pole version. It is normally used in combination with a thermal relay
and a contactor for motor protection;
Q protections:
– against instantaneous short-circuit (I): protection threshold adjustable from 6...14xIn, with
instantaneous trip curve;
Q manual setting by means of the special dip-switches positioned on the front of the trip unit,
which allow its adjustment even with the trip unit off;
Q LED:
– fixed green LED which indicates correct operation of the trip unit; the LED lights up for a cur-
rent over 0.2xIn;
Q Test connector positioned on the front of the trip unit:
– for connection of the Ekip TT test unit, which allows the trip test and the LED test;
– for connection of the Ekip T&P unit, which allows the measurements to be read, to carry out
the trip test and to carry out the protection function test;
– self-supply starting from a minimum current of 0.2 x In.
LED power-on
Ekip M-I
Thermal
Protection function Trip threshold Trip curve(1) Excludability Relation
memory
Manual setting:
Against short-circuits with I 3 = 6-6,5-7-7,5-8-8,5-9-9,5-10-
adjustable threshold and 10,5-11-11,5-12,5-13-13,5- Instantaneous – t=k –
instantaneous trip time 14xIn
Tolerance: ±10%
(1)
Tollerances in case of:
– self-powered trip unit at full power;
– 2 or 3 phase power supply.
In conditions other than those considered, the
following tollerance hold:
2/14
1SDC210033D0201
Ekip M-LIU
Main characteristics:
Q available for XT2 and XT4 in the three-pole version, this device protects motors. The L protection
function protects the motor against overloads, in accordance with the indications and classes
defined by standard IEC 60947-4-1;
Q protections:
– against overloads (L): 0.4...1xIn adjustable threshold. The operating time is established by
choosing the operating class defined by Standard IEC 60947-4-1: Class 3E, 5E, 10E, 20E;
– against short-circuits (I): 6...13xIn adjustable threshold with instantaneous operating time;
– against phase imbalance (U): the protection can be selected either in the ON or OFF position.
When the selector is in the ON position, the threshold is 50% I1, with fixed operating time;
Q manual setting using the relative dip-switches on the front of the release;
Q LED:
– LED on with steady green light indicating that the trip unit is supplied correctly. The LED
comes on when the current exceeds 0.2xIn;
– red LED for each protection:
- L: LED with steady red light, indicates pre-alarm for current exceeding 0.9xI1;
- L: LED with flashing red light, indicates alarm for current exceeding setted threshold;
- LIU: LED with steady red light, shows that the protection has tripped. After the circuit-
breaker has opened, connect the Ekip TT or Ekip T&P accessory to find out which protec-
tion function tripped the trip unit;
– release Ekip M-LIU is equipped with a trip coil disconnection detection device that detects
whether the opening solenoid has disconnected. Signalling is made by all the LEDs flashing
simultaneously;
Q test connector on the front of the release:
– to connect the Ekip TT trip test unit, which allows trip test, LED test and signalling about the
latest trip happened;
– to connect the Ekip T&P unit, which allows the measurements to be read, the trip test to be
conducted and the protection function test to be carried out;
Q thermal memory always active;
Ekip M-LIU
Thermal
Protection function Trip threshold Trip curve(1) Excludability Relation
memory
Manual setting: Manual setting:
Against overloads with long I 1= 0.4...1xIn step 0.04 Operating class: 3E, 5E,
inverse time delay according Tolerance: 10E, 20E – t = k/l 2 Yes
to IEC 60947-4-1 Standard trip between 1.05…1.3xI Tolerance: ±10% up to 4xIn
1
(IEC 60947-4-1) ±20% from 4xIn
Against short-circuits with Manual setting:
adjustable threshold and I 3 = 6...13xIn step 1 Instantaneous – t=k –
instantaneous trip time Tolerance: ±10%
Manual setting: Manual setting:
Aganist phase current I 6 = ON / OFF When ON, t 6= 2s
unbalanced or loss of phase When ON, I 6=50% I1 Yes t=k –
with indipendend time delay Tolerance: ±10%
Tolerance: ±15% (IEC 60947-4-1)
(1)
Tollerances in case of: Protection Trip threshold Trip time
– self-powered trip unit at full power;
L release between 1.05 and 1.25 x I1 ±20%
– 2 or 3 phase power supply.
In conditions other than those considered, I ±15% ≤60 ms
the following tollerance hold: U ±20% ±20%
2/15
1SDC210033D0201
Circuit-breakers for motors protection
Electronic trip units
Ekip M-LRIU
Main characteristics:
Q available for XT2 and XT4 in the three-pole version, this device is generally used for protecting
integrated motors;
Q protections:
– against overloads (L): 0.4...1xIn adjustable threshold. The operating time is established by
choosing the operating class defined by standard IEC 60947-4-1;
– rotor locking (R): with adjustable threshold in the OFF position or from 3...9xI1, with settable
operating time;
– against instantaneous short-circuits (I): with adjustable threshold from 6...13xIn and instanta-
neous operating time;
– against phase imbalance (U): with adjustable threshold in the ON or OFF positions;
Q setting:
– manual setting using the relative dip-switches on the front of the trip unit, which allow the
settings to be made even when the trip unit is off;
– electronic setting, made both locally using Ekip T&P or Ekip Display accessory and via remote
control, by means of the dialogue unit Ekip Com. Use of electronic setting allows other func-
tions to be activated:
- function for protection against earth faults (G): 0.2..1xIn adjustable protection threshold,
with a time constant trip curve;
- duty mode setting (Normal/Heavy):
- the Normal duty mode requires use of a circuit-breaker and a contactor. In the case of
tripping, the Ekip M-LRIU release commands the opening of the contactor via PR212/CI;
- the Heavy duty mode foresees circuit-breaker opening for all overcurrent conditions, and
just the function of motor operation is entrusted to the contactor;
- BACK UP function:
- this protection is designed to handle the situation whereby, in the Normal duty mode, the
opening command transmitted to the contactor via PR212/CI has not been implement-
ed, i.e. the contactor has not tripped. If this happens, the Ekip M-LRIU release transmits
a trip command directly to the circuit-breaker after having waited a time defined. A wait-
ing time between the command transmitted to the contactor and the back-up command
transmitted to the circuit-breaker is required so as to take the contactor opening time
into account;
- PTC protection setting:
- PTC: this protection, monitors the temperature inside the protected motor by means
of a PTC sensor. If the temperature is too high, the Ekip M-LRIU release will command
contactor opening (if the mode is “Normal”) or circuit-breaker opening (if the mode is
“Heavy”). To realize this protection is necessary to order the connector available for PTC;
Q LED:
– LED on with steady green light indicating that the trip unit is supplied correctly. The LED
comes on when the current exceeds 0.2xIn;
– red LED for each protection:
- L: LED with steady red light, indicates pre-alarm for current exceeding 0.9xI1;
- L: LED with flashing red light, indicates alarm for current exceeding setted threshold;
- fixed LED MAN/ELT show the kind of active parameters;
- LRIU: LED with steady red light, shows that the protection has tripped. After the circuit-
breaker has opened, connect the Ekip TT or Ekip T&P accessory to find out which protec-
tion function tripped the trip unit;
– Ekip M-LRIU is equipped with a trip coil disconnection detection device that detects whether
the opening solenoid has disconnected. Signalling is made by all the LEDs flashing simulta-
neously;
Q test connector on the front of the release:
– to connect the Ekip TT trip test unit, which allows trip test, LED test and signalling about the
latest trip happened;
– to connect the Ekip T&P unit, which allows the measurements to be read, the trip test to be
conducted, the protection function test to be carried out, and electronic setting of the protec-
tion function of the release and of the communication parameters;
Q thermal memory always active;
Q self-supply from a minimum current of 0.2xIn up;
2/16
1SDC210033D0201
Q with the addition of the Ekip Com in the circuit-breaker, you can:
– acquire and transmit a wide range of information via remote control;
– accomplish the circuit-breaker opening and closing commands by means of the motor op-
erator in the electronic version (MOE-E);
– know the state of the circuit-breaker (open/closed/trip) via remote control;
– setting the configuration and programming parameters of the unit, such as the current thresh-
olds and the protection function curves.
Power-on LED
Dip switch for the trip Slot for lead seal
classes setting according
to IEC 60947-4-1 Test connector
Dip switch for R protection function setting Dip switch for the trip curve selection
Ekip M-LRIU
Protection function Trip threshold Trip curve (1) Excludability Relation Thermal
memory
Manual setting: Manual setting:
I1 = 0.4...1xIn step 0.04 Trip class: 3E, 5E, 10E, 20E
– t = k/l2 Yes
Tolerance: in accordance Tolerance: ±10% up to 4xIn
Against overloads with long with IEC 60947-4-1 ±20% from 4xIn
inverse time delay trip according
to IEC 60947-4-1 Electronic setting: Electronic setting:
I1 = 0.4...1xIn step 0.01 Trip class: 1...10s step 0.5s
– t = k/l2 Yes
Tolerance: in accordance Tolerance: ±10% up to 4xIn
with IEC 60947-4-1 ±20% from 4xIn
Manual setting: Manual setting: t5 = 1, 4s
I5 = OFF, 3, 6, 9xI1 Tolerance: ±10% up to 4xIn Yes t=k –
Against rotor block with delayed Tolerance: ±10% (IEC 60947-4-1) ±20% from 4xIn
trip and with an indipendent time
R delay trip Electronic setting: Electronic setting:
I5 = OFF, 3...9xI1 step 0.1I1 t5 =1...4s step 0.5
Yes t=k –
Tolerance: ±10% (IEC 60947-4-1) Tolerance: ±10% up to 4xIn
±20% from 4xIn
Manual setting:
I3 = 6-8-11-13xIn Instantaneous – t=k –
Against short-circuits threshold Tolerance: ±10%
with adjustable threshold and
istantaneous trip time Electronic setting:
I3 = 1...13xIn Instantaneous – t=k –
Tolerance: ±10%
Manual setting: Manual setting:
I6 = On / Off t6 = 2s
When ON, I6 = 50% I1 Yes t=k –
Tolerance: ±20%
Aganist phase current Tolerance: ±15%
unbalanced or loss of phase Electrical setting: Electronic setting:
with tripping at indipendent time I6 = On / Off t6 = 0...5s step 0.5
When ON, I6 = 10%..50% I1 step Tolerance: ±20% Yes t=k –
10% I1
Tolerance: ±15%
Electronic setting: Electronic setting:
Against earth fault with I4 = 0.2...1xIn step 0.1In t4 = 0.1...0.8s step 0.01 Yes t=k –
indipendent time delay trip(2)
Tolerance: ±10% Tolerance: ±15%
(1) (2)
Tollerances in case of: Protection Trip threshold Trip time Protection G is inhibited for currents higher than 4
– self-powered trip unit at full power; In when In≥40A and for currents higher than 2 In
L release between 1.05 and 1.25 x I1 ±20%
– 2 or 3 phase power supply. for In<40A.
In conditions other than those considered, R ±20% ±20%
the following tollerance hold: I ±20% ≤50 ms
U ±20% ±20%
G ±15% ±20%
2/17
1SDC210033D0201
Circuit-breakers for generator protection
Main characteristics
SACE Tmax XT circuit-breakers can be equipped with thermomagnetic trip units with a low mag-
netic threshold.
This type of release can been designed and made so as to provide a solution for protecting small
generators and distribution networks with very long cables (slight end of line fault current owing to
the high cable impedance).
Generator protection requires a low magnetic threshold, typically about three times circuit-breaker’s
rated current, so as to “cut” the short-circuit current in the “transient” zone of the decrement curve
of the generator fault current. Consult the “Electrical installation handbook” ABB SACE guide vol. 2
for further details.
t [s]
10
synchronous
phase
transient
phase
10-1
10-2
sub transient
phase
1SDC21092EF0001
10-3
1 10 10 2
x I1
2/18
1SDC210033D0201
TMG
Main characteristics:
Q available for XT2 and XT3 in the three-pole and four-pole versions;
Q protections:
– against overloads (L): adjustable 0.7...1xIn protection threshold, with inverse long-time trip
curve;
– against instantaneous short-circuits (I): fixed 3xIn protection threshold, with instantaneous
trip curve;
– 100% neutral protection in four-pole circuit-breakers;
Q the thermal protection setting is made by turning the relative cursor on the front of the release.
XT2
TMG
In [A] 16 (1) 20(1) 25(1) 32 (1) 40(1) 50 (1) 63(1) 80 100 125 160
Neutral [A] - 100% 16 20 25 32 40 50 63 80 100 125 160
I 1 = 0.7…1xIn
I 3 [A] 160 160 160 160 200 200 200 240 300 375 480
Neutral [A] - 100% – – – – – – – – – 450 450
I 3 = 3xIn
(1)
Available only as complete circuit-breaker
XT3
TMG
In [A] 63 80 100 125 160 200 250
Neutral [A] - 100% 63 80 100 125 160 200 250
I 1 = 0.7…1xIn
I 3 [A] 400 400 400 400 480 600 750
Neutral [A] - 100% 400 400 400 400 480 600 750
I 3 = 3xIn
2/19
1SDC210033D0201
Circuit-breakers for generator protection
Main characteristics
Ekip G-LS/I
Main characteristics:
Q available for XT2 and XT4 in the three-pole and four-pole versions. Allows the protection against
overloads to be extensively adjusted;
Q protections:
– against overloads (L): I1=0.4...1xIn adjustable protection threshold, with inverse long-time trip
curve;
– against delayed short-circuits (S): 1...10xIn adjustable protection threshold, with adjustable
trip curve (as an alternative to I protection);
– against instantaneous short-circuits (I): 1...10xIn adjustable protection threshold, with instan-
taneous operating time (as an alternative to S protection);
– neutral, in four-pole circuit-breakers, can be set in the OFF, ON positions at 50% or 100% of
the phases;
Q manual setting using the relative dip-switches on the front of the trip unit, which allow the set-
tings to be made even when the trip unit is off;
Q LED:
– LED on with steady green light indicating that the trip unit is supplied correctly. The LED
comes on when the current exceeds 0.2xIn;
– red LED for each protection:
- L: LED with steady red light, indicates pre-alarm for current exceeding setted threshold;
- L: LED with flashing red light, indicates alarm for current exceeding setted threshold;
- LS/I: LED with steady red light, shows that the protection has tripped. After the circuit-
breaker has opened, connect the Ekip TT or Ekip T&P accessory to find out which protec-
tion function tripped the trip unit;
– Ekip G-LS/I is equipped with a trip coil disconnection detection device that detects whether
the opening solenoid has disconnected. Signalling is made by all the LEDs flashing simulta-
neously;
Q test connector on the front of the release:
– to connect the Ekip TT trip test unit, which allows trip test, LED test and signalling about the
latest trip happened;
– for connecting the Ekip T&P unit which allows the measurements to be read and the trip test
to be carried out;
Q thermal memory which can be activated by Ekip T&P;
Q self-supply from 0.2xIn up.
2/20
1SDC210033D0201
Dip switch for the selection between S protection
L, S, I protection LED function or I protection function
Power-on LED
Test connector
Ekip G-LS/I
Protection function Trip threshold Trip curve(1) Excludability Relation Thermal
memory
Manual setting: Manual setting:
Against overloads with I 1 = 0.4...1xIn step 0.04 t 1 = 3-6s at I = 3xI1
inverse long-time delayed
Tolerance: Tolerance: ±10% up to 4xIn – t = k/l 2 Yes
tripping according to
IEC 60947-2 standard trip between 1.05…1.3xI 1 ±15% from 4xIn
(IEC 60947-2)
Manual setting: t 2 = 0.05-0.075-0.1-0.2s
I 2 = 1-1.5-2-2.5-3-3.5-4.5-5.5- Tolerance: ±10% up to 4xIn
Against short-circuit with 6.5-7-7.5-8-8.5-9-10xIn ±15% from 4xIn Yes t=k –
indipendent time delay trip
Tolerance: ±10% up to 2xIn
±20% from 2xIn
Manual setting:
Against short-circuits with I 3 = 1-1.5-2-2.5-3-3.5-4.5-5.5-
adjustable threshold and 6.5-7-7.5-8-8.5-9-10xIn Instantaneous Yes t=k –
istantaneous trip time
Tolerance: ±10%
(1)
Tollerances in case of:
– self-powered trip unit at full power;
– 2 or 3 phase power supply.
In conditions other than those considered, the following tollerance hold:
2/21
1SDC210033D0201
Circuit-breakers for oversized neutral protection
Main characteristics
The SACE Tmax XT range of circuit-breakers with oversized neutral is used in certain applications
where harmonics or unbalance loads or single phase create an overload on the neutral conductor.
Under these conditions, a current of a considerable value could travel along the neutral conductor.
In particular, third-order harmonics and relative multiples add together on the neutral and give rise to
a current value that could be higher than the one which travels along the phase conductors.
For this reason, circuit-breakers with oversized neutral provide adequate protection in installations
where the neutral conductor is sized with a larger section than the phase conductors.
The main types of equipment that generate harmonics are given below by way of example:
Q personal computers;
Q fluorescent lamps;
Q static converters;
Q no-break power units;
Q variable speed drives;
Q welding machines.
By and large, the wave shape is distorted owing to the presence of semiconductor devices able to
conduct for a fraction of the entire cycle, creating discontinuous trends and consequently introduc-
ing numerous harmonics.
Consult the “Electrical installation handbook” ABB SACE guide vol. 2 for further details.
2/22
1SDC210033D0201
Ekip N-LS/I
Main characteristics:
Q available for XT2 and XT4 in the four-pole version;
Q protections:
– against overload (L): I1=0.4...1xIn adjustable protection threshold, with inverse long-time trip
curve;
– against delayed short-circuits (S): 1...10xIn adjustable protection threshold, with adjustable
trip curve (as an alternative to I protection);
– against instantaneous short-circuit (I): 1...10xIn adjustable protection threshold, with instan-
taneous operating time (as an alternative to S protection);
– neutral can be set in the OFF or ON positions, at 100% or at 160% of the phases;
Q manual setting using the relative dip-switches on the front of the trip unit, which allow the set-
tings to be made even when the trip unit is off;
Q LED:
– LED on with steady green light indicating that the trip unit is supplied correctly. The LED
comes on when the current exceeds 0.32xIn;
– red LED for each protection:
- L: LED with steady red light, indicates pre-alarm for current exceeding 0.9xI1;
- L: LED with flashing red light, indicates alarm for current exceeding setted threshold;
- LS/I: LED with steady red light, shows that the protection has tripped. After the circuit-
breaker has opened, connect the Ekip TT or Ekip T&P accessory to find out which protec-
tion function tripped the trip unit;
– Ekip N-LS/I is equipped with a device that detects whether the opening solenoid has discon-
nected. Signalling is made by all the LEDs flashing simultaneously;
Q test connector on the front of the release:
– to connect the Ekip TT trip test unit which allows trip test, LED test and signalling about the
latest trip happened;
– for connecting the Ekip T&P unit, which allows the measurements to be read and the trip test
to be carried out;
Q thermal memory which can be activated by Ekip T&P;
Q self-supply from 0.32xIn.
Power-on LED
Dip switch for Test connector
neutral selection
Slot for lead seal
Ekip N-LS/I
Protection function Trip threshold Time-current curve (1) Excludability Relation Thermal
memory
Against overloads with inverse Manual setting: Manual setting:
long-time delayed tripping. I1 = 0.4...1xIn step 0.04 t1 = 12-36s at I= 3xI1
– t = k/l2 Yes
According to IEC 60947-2 Tolerance: trip between Tolerance: ±10% up to 4xIn
Standard 1.05…1.3xI1 (IEC 60947-2) ±15% from 4xIn
Manual setting: t2 = 0.1-0.2s
Against short-circuits with I2 = 1-1.5-2-2.5-3-3.5-4.5-5.5- Tolerance: ±10% up to 4xIn
inverse short indipendent time 6.5-7-7.5-8-8.5-9-10xIn Yes t=k –
delay trip (t=k) ±20% from 4xIn
Tolerance: ±10%
Manual setting:
Against short-circuits with I3 = 1-1.5-2-2.5-3-3.5-4.5-5.5-
6.5-7-7.5-8-8.5-9-10xIn Instantaneous Yes t=k –
istantaneous trip time
Tolerance: ±10%
(1)
Tollerances in case of: Protection Trip threshold Trip time
– self-powered trip unit at full power;
L release between 1.05 and 1.25 x I1 ±20%
– 2 or 3 phase power supply.
In conditions other than those considered, the following tollerance hold: S ±10% ±20%
I ±15% ≤60 ms
2/23
1SDC210033D0201
Switch-disconnectors
Main characteristics
The switch-disconnector (or, in short, disconnector) is a device created from the corresponding
circuit-breakers (of which it features the same overall dimensions, versions, fastening mechanisms
and ability to be fitted with accessories).
The main function of these devices is to disconnect the circuit they are installed in. In the open
position, the disconnector disconnects and guarantees a sufficient insulation distance (between the
contacts) to assure safety and to prevent an electrical arc from striking.
Applications
Switch-disconnectors are generally used as:
XT1D Q general disconnectors of subswitchboards;
Q operating and disconnecting devices for lines, pan-assembliess or groups of equipment;
Q bus-ties;
Q general disconnecting devices for groups of machines;
Q general group disconnecting devices for motor operation and protection;
Q insulation of small tertiary distribution units.
Protection
A disconnector is unable to automatically break the short-circuit or overload current. For this rea-
son, each switch-disconnector must be protected on the supply side by a coordinated device that
safeguards it against short-circuits. The circuit-breaker able to act as a protection for each switch-
disconnector is indicated in the table below.
XT3D
Category of use (G2.11)
The CEI EN 60947-3 Standard defines the utilisation categories for disconnectors in accordance
with the table below. Tmax XT disconnectors comply with the AC21A, AC22A and AC23A utilisation
categories.
Class of use
Infrequent Frequent Typical applications
operation operation
AC-21A AC-21B Control of resistive loads with overloads of modest entity
AC-22A AC-22B Control of mixed resistive and inductive loads with overloads of modest entity
AC-23A AC-23B Control of motors or other highly inductive loads
XT4D
Characteristics of switch-disconnectors
XT1D XT3D XT4D
(G2.1)
Size [A] 160 250 250
Rated operating current in class AC21, Ie(G.2.12) [A] 160 250 250
Rated operating current in class AC22, Ie(G.2.12) [A] 160 250 250
Rated operating current in class AC23, Ie(G.2.12) [A] 125 200 200
Poles [Nr.] 3, 4 3, 4 3, 4
(AC) 50-60Hz [V] 690 690 690
Rated service voltage, Ue(G2.4)
(DC) [V] 500 500 500
Rated insulation voltage, Ui(G2.5) [V] 800 800 800
Rated impulse withstand voltage, Uimp(G2.6) [kV] 8 8 8
Test voltage at industrial frequency for 1 min [V] 3000 3000 3000
(Min) Disconnector only [kA] 2.8 5.3 5.3
Rated breaking capacity
in short-circuit, Icm(G2.10) (Max) With automatic
[kA] 187 105 105
circuit-breaker on supply side
(G2.9)
Rated short-time withstand current for 1s, Icw [kA] 2 3.6 3.6
Fixed, Fixed, Fixed, Withdrawable,
Versions
Plug-in Plug-in Plug-in
2/24
1SDC210033D0201
Special applications
400Hz installations
The circuit-breakers used for power distribution can operate in alternating current at different fre-
quencies from 50/60Hz (frequencies which the rated performance of the apparatus refers to) so
long as the appropriate derating coefficients are applied.
At 400Hz, the performance of the circuit-breakers is reclassified so as to take the following phe-
nomena into account:
Q an increase in the skin effect and increased inductive reactance in a way that is directly propor-
tional to the frequency, overheat the conductors or the copper components that normally carry
the current in the circuit-breaker;
Q lengthening of the hysteresis loop and reduction of the magnetic saturation value, which conse-
quently varies the forces associated with the magnetic field to a given current value.
By and large, these phenomena influence the behaviour of both the thermomagnetic trip units and
the current interrupting parts of the circuit-breaker.
Consult the “Electrical installation handbook” ABB SACE guide for further details.
All the circuit-breakers in the SACE Tmax XT family equipped with thermomagnetic or electronic
trip units (except for the Ekip M-I, Ekip M-LIU and Ekip M-LRIU trip units) can be used in 400Hz
installations. The 10A and 25A settings for operation at 400Hz are only available on request.
Contact ABB SACE for more details about performance derating.
2/25
1SDC210033D0201
Special applications
Communication system
The XT2 and XT4 moulded-case circuit-breakers, equipped with Ekip LSI, Ekip LSIG
or Ekip M-LRIU trip unit and Ekip Com dialogue module, can be integrated in supervision systems
for control and management of electrical and technological plants.
With XT2 and XT4, equipped with thermomagnetic trip units, Ekip Com dialogue module and Elec-
tronic Motor, it is possible to read the state of the circuit-breaker remotely and to operate it.
Protocols available, for communication on bus(G5.4) network with circuit-breakers XT2 and XT4, are:
Q Modbus RTU (standard protocol of ABB SACE);
Q ProfiBus-DP (usable with ABB SACE devices, jointly with EP010 accessory);
Q DeviceNet (usable with ABB SACE devices, jointly with EP010 accessory).
+
24 V –
Modbus
Positioned in the right-hand slot of the circuit-breaker, the Ekip Com accessory connects to the Ekip
LSI, Ekip LSIG or Ekip M-LRIU trip unit via connector supplied. Four cables come out of Ekip Com,
of which two are required for auxiliary supply and two for connection to the Modbus.
This configuration allows you to:
Q read the measurements and settings from the electronic trip unit in remote mode;
Q program the electronic trip unit in remote mode;
Q know the state of the circuit-breaker (Open/Closed/Tripped) in remote mode.
Consult the Electric Diagrams chapter for further details about wiring.
2/26
1SDC210033D0201
Configuration 2: Supervision and Remote control (Thermomagnetic trip unit, Ekip Com and
MOE-E)
+
24 V –
+
Modbus
The Ekip Com accessory, positioned in the right-hand slot of the circuit-breaker, is connected with
the thermomagnetic trip unit by means of the connector supplied with the Ekip Com, and with the
MOE-E by means of the connector on the rear of the MOE-E.
4 cables come out of the Ekip Com, of which 2 are needed for the auxiliary power supply and 2 for
connection to the Modbus.
With this configuration it is possible to:
Q read the Open/Closed/Tripped state of the circuit-breaker remotely;
Q open/close the circuit-breaker remotely.
For further details regarding cabling of the various devices, please refer to the chapter on Electric
Diagrams.
Configuration 3: Supervision and Remote Control (Electronic trip unit, Ekip Com and MOE-E)
+
24 V –
+
Modbus
Positioned in the right-hand slot of the circuit-breaker, the Ekip Com accessory connects to the Ekip
LSI, Ekip LSIG or Ekip M-LRIU trip unit via connector supplied with Ekip Com and to the MOE-E
via connector be present on MOE-E behind. Four cables come out of Ekip Com of which two are
required for auxiliary supply, two for connection to the Modbus.
This configuration allows you to:
Q read the measurements and settings from the solid-state release in remote mode;
Q program the electronic trip unit in remote mode;
Q read the state of the circuit-breaker (Open/Closed/Tripped) in remote mode;
Q open/close the circuit-breaker in remote mode.
Consult the Electric Diagrams chapter for further details about wiring.
2/27
1SDC210033D0201
Special applications
Communication system
Configuration 4: EP010 - Fieldbus Plug (Electronic trip unit, Ekip Com and EP010)
+
24 V –
+ Modbus
EP010
Positioned in the right-hand slot of the circuit-breaker, the Ekip Com accessory connects to the Ekip
LSI, Ekip LSIG or Ekip M-LRIU trip unit via connector supplied and to the MOE-E via connector be
present on MOE-E behind (MOE-E connection is optional for this configuration). Four cables come
out of Ekip Com, of which two are required for auxiliary supply, two for connection to the EP010.
Connection of the EP010 to the network is to be made by the Customer and depends on the Field-
bus plug connector used.
With this configuration, it is possible to:
Q make the SACE Tmax XT circuit-breakers communicate in a network with Profibus or Devicenet
comunication protocol;
Q read the measurements and settings from the solid-state release in remote mode;
Q program the electronic trip unit in remote mode;
Q read the state of the circuit-breaker (Open/Closed/Tripped) in remote mode;
Q open/close the circuit-breaker in remote mode.
Configuration 5: Interface from front panel (Electronic trip unit, Ekip Com and HMI030 Unit)
With XT2 and XT4 circuit-breakers, equipped with electronical trip unit Ekip LSI, Ekip LSIG or Ekip M-
LRIU, in addiction with the interface unit HMI030, it’s possible to visualize directly on the panel door
the mainly electrical magnitude values and the intervention threshold for the imposed protection.
The necessary accessories, useful to permit the lecture directly from the front of the switchboard
are:
Q interface device HMI030;
Q communication module Ekip Com.
+
24 V –
HMI030
Modbus
The Ekip Com accessory, positioned in the right-hand slot of the circuit-breaker, is connected to the
Ekip LSI, Ekip LSIG or Ekip M-LRIU trip unit by means of supplied connector. Four cables come out
of the Ekip Com, two of which are needed for the auxiliary power supply and two for connection to
the HMI030.
This configuration makes it possible to read the measurements and settings from the electronic trip
unit by means of the HMI030 accessory positioned on the front of the panel.
For further details on cabling the various different devices, refer to the Electric Diagram Chapter.
2/28
1SDC210033D0201
Accessories
Index
Versions and types
Fixed part of plug-in and withdrawable versions ................................................................... 3/2
Conversion kits ....................................................................................................................... 3/3
Mechanical Accessories
Connection terminals ............................................................................................................. 3/5
Terminal covers, phase separators and sealable screws for terminal covers .......................3/12
Rotary handle operating mechanism ....................................................................................3/12
IP54 Protection ......................................................................................................................3/13
Front for operating lever mechanism ....................................................................................3/13
Locks .....................................................................................................................................3/14
Rear mechanical interlock .....................................................................................................3/16
Bracket for fixing on DIN rail .................................................................................................3/16
Flanges ..................................................................................................................................3/16
Electrical Accessories
Service releases ....................................................................................................................3/17
Auxiliary contacts ..................................................................................................................3/19
Motor operators ....................................................................................................................3/23
Connectors for electrical accessories ...................................................................................3/27
Residual current releases ......................................................................................................3/28
3/1
1SDC210033D0201
Accessories
Versions and types
Starting from the fixed version, SACE Tmax XT circuit-breakers can easily be converted into the
plug-in and withdrawable versions using the relative conversion kits.
The moving part can always be obtained in the required version, fully pre-engineered in the factory,
by ordering the fixed circuit-breaker and the conversion kit at the same time.
Version
Fixed Plug-in Withdrawable
XT1 Q Q
Plug-in circuit-breaker
XT2 Q Q Q
XT3 Q Q
XT4 Q Q Q
Fixing at 50mm
Fixing at 70mm
3/2
1SDC210033D0201
Conversion kits
The following conversion kits can be obtained in order to create the different versions:
Q Kit for converting the fixed circuit-breaker into the moving part of plug-in/withdrawable
versions. The conversion kit converts the fixed circuit-breaker into the moving part of plug-in/
withdrawable versions. Only when withdrawable versions are made is it essential to order an
accessory to apply to the front of the circuit-breaker so as to maintain the IP40 degree of protec-
Conversion kit for turning a fixed tion over the entire isolation run. This accessory can be chosen from:
circuit-breaker into the moving
– front for lever operating mechanism (FLD);
part of a plug-in circuit-breaker
– motor operator (MOE);
– direct or transmitted rotary handle operating mechanisms (RHD or RHE).
In the case where no accessory to be applied onto the front is indicated, the front for lever op-
erating mechanism (FLD) is automatically included in the order.
Q kit for converting the fixed part of plug-in versions into the fixed part of withdrawable ver-
sions. The kit comprises:
– a guide for turning the fixed part of the plug-in circuit-breaker into the fixed part of the with-
drawable circuit-breaker;
– a racking-out rotary handle that allows the moving part to be inserted and withdrawn. The
mechanism allows the circuit-breaker to be set to the isolated position (with the power and
Conversion kit for turning a fixed auxiliary circuits disconnected) with the compartment door closed, all to the advantage of
circuit-breaker into the moving part operator safety. The rotary handle can only be inserted when the circuit-breaker is open.
of a withdrawable circuit-breaker Once it has been removed or withdrawn, the circuit-breaker can be set to the open/closed
position;
– a flange for the compartment door, which replaces the one supplied with the fixed version of
the circuit-breaker.
Q Kit for converting fixed type into the plug-in version for RC Sel residual current devices
for XT2-XT4. RC Sel four-pole residual current devices for XT2 e XT4 can be converted from the
fixed version into the plug-in version using the special kit.
Q Kit for converting plug-in types into the withdrawable version for RC Sel residual cur-
rent devices for XT2-XT4. RC Sel four-pole residual current devices for XT2 and XT4 can
be converted from the plug-in version to the withdrawable version using the special kit, which
comprises a bellows to apply to the front of the residual current device so as to allow it and the
residual current part to be withdrawn when the panel door is closed. This kit can also be as-
sembled on fixed circuit-breakers fitted with the front part for locks or the direct rotary handle,
thus adding to the range of uses for residual current devices.
In the plug-in to withdrawable conversion kit, there is also a 6 pin connector to be applied onto
the right side of the circuit-breaker to facilitate disconnection of the auxiliary circuits connected
to the residual current device.
This kit contains also the shunt opening release of the residual current device dedicated to the
Conversion kit for turning a fixed part
of plug-in version into the fixed part
withdrawable version, which is fitted with a connector for the fixed part and the moving part.
of a withdrawable version
3/3
1SDC210033D0201
Accessories
Versions and types
Plug-in version
+ + =
Withdrawable version
1st solution
+ + + =
Fixed part of Fixed Conversion kit for turning Frontal accessory Withdrawable
withdrawable circuit-breaker a fixed circuit-breaker FLD(1) circuit-breaker
into the moving part of a
withdrawable circuit-breaker
2nd solution
+ + + + =
Fixed part Conversion kit for turning Fixed Conversion kit for turning Frontal accessory Withdrawable
of plug-in a fixed part of plug-in circuit-breaker a fixed circuit-breaker FLD(1) circuit-breaker
version into the fixed part into the moving part of a
of a withdrawable version withdrawable circuit-breaker
(1)
Frontal accessory mandatory. If not specified in the order, the FLD is supplied automatically
3/4
1SDC210033D0201
Accessories
Mechanical Accessories
Connection terminals
Connection terminals allow the circuit-breaker to be connected to the system in the way most suited
to the installation requirements. By and large they consist of:
Q front terminals: for connecting cables or busbars directly from the front of the circuit-breaker;
Q rear terminals: for installing circuit-breakers in segregated panels with rear access.
Where possible, the terminals have laser marking on the surface indicating the tightening torques for
the correct isolation of cables and bars.
Fixed version
The part of the standard equipment, fixed version SACE Tmax XT circuit-breakers are supplied with
front terminals (F). However, they can be fitted with the following types of terminals as accessories
thanks to the special kits:
Q extended front (EF);
Q extended spread front (ES);
Q front for copper/aluminium cables (FCCuAI). A pitch adapter must be applied to the terminal
zone of the circuit-breaker to ensure that copper and aluminium cables with sections of up to
240mm2 can be connected to all the circuit-breakers. The pitch adapter is automatically sup-
plied when it is necessary (see table page 3/9);
Q front for copper cables (FCCu);
Q for flexible busbars (FB);
Q multicable (MC);
Q rear oriented (R).
3/5
1SDC210033D0201
Accessories
Mechanical Accessories
The adapter reproduces the terminal zone of the fixed circuit-breaker. This means that fixed parts
can also be equipped with the same terminal covers and phase separators as those used for fixed
circuit-breakers.
H3 H1 H2
Fixing at 50mm
Fixing at 70mm
3/6
1SDC210033D0201
Front terminals - F
CB. Vers. Busbar dimensions Cable terminals Tightening H Terminal covers H Separators
[mm] [mm] [mm] [mm]
W min W max H Ø D min D max W Ø Cable or busbar 2 50 60 25 100 200
/Terminal
XT1 F 13 16 7.5 6.5 – 5 16 6.5 M6 6Nm R R – S R R
XT2 F 13 20 7.5 6.5 2.5 5 20 6.5 M6 6Nm R R – S R R
XT3 F 17 24 9.5 8.5 – 8 24 8.5 M8 8Nm R – R S R R
XT4 F 17 25 10 8.5 5 8 25 8.5 M8 8Nm R – R S R R
Front extended terminal - EF EF terminal with cable lug EF terminal with busbar
W Width F Fixed
H Hole Heigth P Plug-in
D Depth W Withdrawable
Ø Diameter
S Standard
D W
R On Request
3/7
1SDC210033D0201
Accessories
Mechanical Accessories
Front extended spread ES terminal with cable lug ES terminal with busbar
terminal - ES
FCCu terminal FCCu terminal with cable FCCu terminal with busbar
W Width F Fixed
H Hole Heigth P Plug-in
D Depth W Withdrawable
Ø Diameter
S Standard
D W
R On Request
3/8
1SDC210033D0201
Terminals for copper/aluminium cables - FC CuAl
CB Type of Vers. Cable Tightening L H Terminal covers H Separators
terminal [mm2] cable [mm] [mm]
Rigid Flexible Terminal Cable or busbar stripping 2 50 60 25 100 200
/CB /Terminal [mm]
Internal FCCuAl terminal for Internal FCCuAl terminal for External FCCuAl terminal for FCCuAl internal terminal FCCuAl external terminal
copper/aluminium cables copper and aluminium cable copper/aluminium cables with cable with cables
with take-up of auxiliary voltage
H Dimensions [mm]
Circuit-breaker Poles
[WxHxD]
3 105x50x68
D W XT1
4 140x50x68
Pitch adapter 3 105x50x68
XT2
4 140x50x68
3 105x50x68
XT3
4 140x50x68
3 105x50x68
XT4
4 140x50x68
Note: With XT1 and XT2 the adaptor increases the width of the circuit-breaker
W Width F Fixed
H Hole Heigth P Plug-in
D Depth W Withdrawable
Ø Diameter
S Standard
D W
R On Request
3/9
1SDC210033D0201
Accessories
Mechanical Accessories
Multi-cable terminals - MC
CB Vers. Cable Tightening L H Terminal covers H Separators
[mm2] cable [mm] [mm]
stripping
Rigid Flexible Terminal Cable or busbar 2 50 60 25 100 200
[mm]
/CB /terminal
XT1 F-P 6x2.5…35 6x2.5…25 M6 6Nm Ø8 7Nm 10, 20, 30 – S – – – –
XT2 F-P-W 6x2.5…35 6x2.5…25 M6 6Nm Ø8 7Nm 10, 20, 30 – S – – – –
XT3(1) F-P 6x2.5…35 6x2.5…25 M8 8Nm Ø8 7Nm 15, 30 – – S – – –
XT4(1) F-P-W 6x2.5…35 6x2.5…25 M8 8Nm Ø8 7Nm 15, 30 – – S – – –
(1)
Take up auxiliary voltage device included
Rear horizontal terminals (R) R terminal with horizontal busbar R terminal with vertical busbar
3/10
1SDC210033D0201
Extended front terminals for fixed part - EF
CB Vers. Busbar dimensions MAX Cable terminals Tightening Rear Separators
[mm] [mm] [mm]
W P Ø W Ø Terminal/ Cable or busbar 90
CB /Terminal
XT1 P 20 4 8.5 20 8.5 6Nm 9Nm R
XT2 P-W 20 4 8.5 20 8.5 6Nm 9Nm R
XT3 P 20 6 8.5 20 8.5 6Nm 9Nm R
XT4 P-W 20 10 8.5 20 8.5 6Nm 9Nm R
W Width F Fixed
H Hole Heigth P Plug-in
D Depth W Withdrawable
Ø Diameter
S Standard
D W
R On Request
3/11
1SDC210033D0201
Accessories
Mechanical Accessories
Direct rotary handle (RHD) Transmitted rotary handle (RHE) (LH) Handle grip (RHS) Lateral handle
3/12
1SDC210033D0201
All rotary handles are available in two versions:
Q standard: grey colour;
Q emergency: red on a yellow background. Suitable for operating machine tools.
Use of the rotary handle is an alternative to the motor operator and to all accessories of the front
type.
The rotary handles can be locked by means of a vast range of key locks and padlocks (consult the
“locks” section of the Accessories chapter).
The direct and transmitted rotary operating mechanisms allow early contacts to be used on closing
so as to supply the undervoltage release in advance of circuit-breaker closing (consult the “early
auxiliary contacts” section of the Accessories chapter).
IP54 Protection
Device which can be applied onto the transmitted rotary and lateral handle allowing IP54 degree of
protection(G.1.11) to be achieved.
IP54 protection
3/13
1SDC210033D0201
Accessories
Mechanical Accessories
Locks
Padlocks or key locks that prevent the circuit-breaker from being closed and/or opened. They can
be fitted:
Q directly on the front of the circuit-breaker;
Key lock Q on the rotary handle operating mechanism;
Q on the front for lever operating mechanism;
Q on the motor;
Q to the fixed and withdrawable part, to prevent the moving part from being inserted;
Q on the front of the thermomagnetic trip unit, to prevent the adjuster of the thermal part from be-
ing tampered with.
All locks that hold the circuit-breaker in the open position ensure circuit isolation in accordance with
the IEC 60947-2 Standard. In the closed position, the locks do not prevent the mechanism from
releasing after a fault or remote control.
Removable padlock
in open position
RHD with key lock RHE with key lock FLD with key lock
MOD with key lock MOE with key lock Withdrawable fixed part
with key lock/padlock
3/14
1SDC210033D0201
Optional/
Circuit- Position of Type Removability
Type of lock Standard
breaker circuit-breaker lock of lock of key
supply
padlocks max 3 padlocks
XT1…XT4 Optional OPEN / CLOSED
Ø 7mm stem (not supplied)
–
PLL
Fixed padlock device padlocks max 3 padlocks
XT1…XT4 Optional OPEN
Ø 7mm stem (not supplied)
–
PLL
padlocks max 3 padlocks
Removable XT1, XT3 Optional OPEN
Ø 7mm stem (not supplied)
–
Circuit- padlock device
breaker
Ronis Same key
XT1…XT4 Optional OPEN OPEN
(A, B, C, D type)
KLC Ronis
XT1…XT4 Optional OPEN OPEN
Key lock (5) Different key
Ronis
XT1…XT4 Optional OPEN OPEN / CLOSED
Same key
Ronis
XT1…XT4 Optional OPEN OPEN
Same key
RHL Ronis
Rotary XT1…XT4 Optional OPEN OPEN
Key lock(1) Different key
handle
Ronis
(RHD/RHE/ XT1…XT4 Optional OPEN / CLOSED OPEN / CLOSED
Different key
RHE-LH/
RHS) padlocks max 3 padlocks
Padlock device XT1…XT4 Standard OPEN
Ø 6mm stem (not supplied)
–
DOOR LOCKED WHEN
Door lock(4) XT1…XT4 Standard
CIRCUIT-BREAKER CLOSED
– –
padlocks max 3 padlocks
Padlock device XT2, XT4 Standard OPEN
Ø 6mm stem (not supplied)
–
DOOR LOCKED WHEN
Door lock XT2, XT4 Standard
CIRCUIT-BREAKER CLOSED
– –
Frontal for Ronis
XT2, XT4 Optional OPEN OPEN
operating Same key
lever RHL Ronis
(FLD) XT2, XT4 Optional OPEN OPEN
Key lock(1) Different key
Ronis
XT2, XT4 Optional OPEN / CLOSED OPEN / CLOSED
Different key
padlocks max 3 padlocks
Padlock device XT1…XT4 Standard OPEN
Ø 8mm stem (not supplied)
–
Ronis
Key lock on motor XT1…XT4 Optional OPEN OPEN
Different keys
MOL-D
Motor MOL-S Ronis
XT1…XT4 Optional OPEN OPEN
(MOD, MOE, Same keys
MOE-E) Key lock against
Ronis WITH LOCK
manual operation XT1…XT4 Optional MANUAL
key INSERTED
MOL-M (2)
Ronis key Different +
Key WITHDRAWN / INSERTED
XT2, XT4 Optional
Padlock WITHDRAWN
padlocks max 3 padlocks –
Ø 6mm stem (not supplied)
Ronis key Same +
Key WITHDRAWN / INSERTED
KLF-FP XT2, XT4 Optional
Padlock WITHDRAWN
padlocks max 3 padlocks –
Fixed part of Key lock / padlock Ø 6mm stem (not supplied)
withdrawable for fixed part of Giussani key Different +
withdrawable device Key WITHDRAWN / INSERTED
XT2, XT4 Optional
Padlock WITHDRAWN
padlocks max 3 padlocks –
Ø 6mm stem (not supplied)
Giussani key Same +
Key WITHDRAWN / INSERTED
XT2, XT4 Optional
Padlock WITHDRAWN
padlocks max 3 padlocks –
Ø 6mm stem (not supplied)
3/15
1SDC210033D0201
Accessories
Mechanical Accessories
+ =
Flanges
Plastic plate that acts as an interface between the circuit-breaker and the hole in the panel door. All
the Tmax XT series flanges are newly designed and do not require screws for installation. Flanges
are applied:
Q around the front part of the fixed/plug-in circuit-breaker (standard supply with the circuit-breaker);
Q around the operating lever for all fixed/plug-in/withdrawable version circuit-breakers (optional);
Q around the MOD or MOE motor operator (standard supply with MOD and MOE);
Q around the front for FLD locks (standard supply with FLD);
Q around the direct rotary handle operating mechanism (standard supply with RHD);
Q around the transmitted rotary handle operating mechanism (standard supply with RHE);
XT1-XT3 circuit-breaker Q around the RC Inst, RC Sel for XT1 and XT3, RC Sel for XT2 and XT4 residual current release
with standard flange
(standard supply with residual current devices).
3/16
1SDC210033D0201
Accessories
Electrical Accessories
Service releases
Shunt opening release (SOR). Allows the circuit-breaker to be opened by means of a non-per-
manent electrical control. Release operation is guaranteed for voltage between 70% and 110% of
the rated power supply voltage Un, in both alternating and direct current. SOR is equipped with a
Cabled SOR - PS SOR - UVR built-in limit contact to shut-off the power supply in the open position with the relay tripped.
A remote controlled emergency opening command can be created by connecting an opening but-
ton to the SOR.
Shunt opening release with permanent service (PS-SOR), unlike SOR, this version can be
continuously powered. The power input of PS SOR is much lower than the power input of SOR.
Undervoltage release (UVR). Allows the circuit-breaker to open when the release is subjected to
either a power failure or voltage drop. Opening, as prescribed in the Standard, is guaranteed when
the voltage is between 70% to 35% of Un. After tripping, the circuit-breaker can be closed again
if the voltage exceeds the 85% of Un. When the undervoltage release is nor energized, neither the
Cabled SOR - PS SOR - UVR circuit-breaker nor the main contacts can be closed. A remote controlled emergency opening com-
for withdrawable circuit-breaker
mand can be created by connecting an opening button to the UVR.
None of the service releases in the Tmax XT series require screws for installation. They are extremely
easy to fit. Just use slight pressure in the appropriate place. All service releases are available in two
versions:
Q cabled (AWG20 cable section -0.5mm2 up to 300V, AWG17 - 1mm2 up to 525V)):
– for fixed/plug-in circuit-breakers with 1m long cables;
– for withdrawable circuit-breakers with fixed part and moving part connector;
Uncabled Q not cabled:
SOR - PS SOR - UVR – for fixed/plug-in circuit-breakers with cables from 1.5 mm2 in section.
3/17
1SDC210033D0201
Accessories
Electrical Accessories
In circuit-breakers:
Q three-pole: as an alternative, SOR, PS-SOR or UVR can be installed in the slot on the left of the
operating lever;
Q four-pole: SOR, PS-SOR or UVR can be housed at the same time in the slot of the third and
fourth pole. If the circuit-breaker is the withdrawable type, the connector for the fourth pole must
be ordered to be able to install SOR, PS SOR and UVR in the fourth pole. If there is a residual
current release, the opening solenoid (SA) of the residual current device must be installed in the
slot of the third pole on the left of the operating lever.
SOR
SOR SOR PS-SOR
PS-SOR PS-SOR UVR
UVR UVR SA
3/18
1SDC210033D0201
Time delay device for undervoltage release (UVD)
The undervoltage release (UVD) can be combined with an external electronic power supply time
delay which allows circuit-breaker opening to be delayed with preset and adjustable timing if the
power supply voltage of the release either drops or fails, thus preventing untimely tripping caused
by temporary faults. The time delay must be used with the undervoltage release (UVR) of the cor-
responding voltage.
A remote control positive safety opening command can be created by connecting an opening push-
button to the UVR combined with the UVD.
Auxiliary contacts
Contacts which allow information about the operating state of the circuit-breaker to be routed out-
side the circuit-breaker. The following information is available:
Q open/closed: indication of the position of the circuit-breaker power contacts (Q);
Q trip: signalling circuit-breaker opening due to the current release tripping (owing to overload or
short-circuit), the residual current device, the opening or undervoltage releases, the emergency
opening pushbutton of the motor operator, or owing to use of the test button (SY);
Q trip unit tripping: indicates that one of the protection functions of the electronic or thermomag-
netic trip unit has tripped (S51).
Changeover of auxiliary contacts Q (open/closed), SY (Relay tripped) and S51 (trip unit tripping)
CB Open Q=12 SY=96 S51=06
Normal sequence
CB Closed Q=14 SY=96 S51=06
Trip Sequence CB Open Q=12 SY=96 S51=06
(trip caused by: CB Closed Q=14 SY=96 S51=06
- SOR,
- UVR, CB Trips Q=12 SY=98 S51=06
- Trip Test) CB Resets Q=12 SY=96 S51=06
CB Open Q=12 SY=96 S51=06
Trip Sequence CB Closed Q=14 SY=96 S51=06
(trip caused by trip unit) CB Trips Q=12 SY=98 S51=08
CB Resets Q=12 SY=96 S51=06
3/19
1SDC210033D0201
Accessories
Electrical Accessories
2Q 2Q
1SY 1SY
XT1
3Q left 3Q left
3Q 3Q
1SY 1SY
XT3
3Q left 3Q left
2SY 2SY
2Q 2Q
3Q left 3Q left
XT2
XT4 1S51 1S51
or 1Q or 1Q
3/20
1SDC210033D0201
AUX 250V AC/DC - Electrical specifications
Power supply Voltage Operating current [A]
Class of use
[V] AC DC
DC-12 – 0.5
110 AC/DC
DC-14 – 0.05
AC-12, AC-13, AC-14 6 –
125 AC/DC
AC-15 5 –
AC-12 and DC-12 6 0.3
AC-13 6 –
250 AC/DC
AC-14 and DC-14 5 0.03
AC-15 4 –
AUX AUX
400V 400V
XT2
XT4
3/21
1SDC210033D0201
Accessories
Electrical Accessories
3/22
1SDC210033D0201
Early auxiliary contacts - AUE
Early contacts in relation to closing: allow the undervoltage release to be supplied before the main
contacts close, in accordance with the IEC 60204-1, VDE 0113 Standards.
Early contacts in relation to opening: allow any electronic devices connected to the system that
could be damaged owing to overvoltages generated by the circuit-breaker opening operation to be
disconnected in advance.
The early opening/closing auxiliary contacts can be:
Q installed inside the direct and transmitted rotary handle operating mechanisms for all the SACE
Early auxiliary contacts Tmax XT family circuit-breakers (max two contacts @ 400V):
in the handle – in the cabled version with 1m long cables (AWG20 cable sections);
– a dedicated code is available in the withdrawable version which includes the connector for
the moving part and fixed part;
Q installed in the three-pole and four-pole fixed version SACE Tmax XT2 and XT4 circuit-breakers
(max two 250V auxiliary contacts). In the four-pole version the early opening/closing contacts
are inserted in the slot of the third pole. This type of early contact is supplied with a back clamp-
ing to be installed on the left-hand side of the circuit-breaker to facilitate wiring operations
(AWG20 cable diameters). Opening/closing contacts in the circuit-breaker excludes use of the
four-pole RC Sel release.
For further details about the electrical specifications of the contacts, consult the “400V DC and
Early auxiliary contacts inside the 250V AC contacts” section of the Accessories chapter.
circuit-breaker and connector
Motor operators
Devices that allow circuit-breaker opening and closing to be controlled:
Q in the remote mode, by means of electric controls;
Q locally directly from the front, by means of a special mechanisms.
Test pushbutton
The direct action motor control available for XT1 and XT3, is supplied:
Q complete with 1m long cables;
Q with flange, to replace the standard one supplied with the circuit-breaker;
Q with padlock device, only removable when the motor is in the open position. The padlock device
accepts up to three 8 mm padlocks;
Q auxiliary contacts (AU-MO) which allow the motor control mode (manual or auto) signal to be
routed outside;
Q (on request) the motor operator can be fitted with a key lock (consult the “locks” section in the
Accessories chapter).
3/23
1SDC210033D0201
Accessories
Electrical Accessories
Operating principles:
Q a selector on the front of the MOD, is used for selecting the operating mode:
– AUTO: when the selector is in this position, circuit-breaker closing can only take place re-
motely by means of an electric impulse, whereas opening is allowed both remotely and from
the front of the motor;
– MANUAL: when the selector is in this position, the circuit-breaker can only be opened/closed
from the front of the motor by means of the relative lever housed in a slot made in the motor
itself;
Q operation of the motor operator via remote control is also guaranteed by permanent electrical
opening/closing impulses;
Q the resetting modes shown in the diagrams below depend on the reset wiring diagram chosen
by the customer (consult the reset wiring diagrams in the “Electric Diagrams”) chapter.
I: ON I: ON
trip unit trip unit
intervention intervention
opening closing
move the move the signal in signal in
Trip lever in OFF lever in ON Trip remote remote
move the lever opening operator mode mode
in OFF in remote mode
O: OFF O: OFF
The MOE or MOE-E stored energy motor operator available for XT2 and XT4 is supplied:
Q complete with 1m long cables;
Q complete with connector for the fixed part and moving part of withdrawable devices. If the motor
operator is used with fixed or plug-in circuit-breakers, the connector can be easily removed;
Q with flange, to use instead of the standard one supplied with the circuit-breaker;
Q with padlock device, only removable when the motor is in the open position. The padlock device
accepts up to three 8mm padlocks;
Q with lock of the AUTO-MANUAL selector;
Q with auxiliary contacts (AUX-MO) that allow the motor’s control mode (manual or remote) signal
to be routed outside;
3/24
1SDC210033D0201
Q (on request) the motor operator can be equipped with key lock (consult the “locks” section in the
Accessories chapter);
Q (on request) the motor operator can be equipped with lock to safeguard against manual opera-
tion MOL-M (consult the “locks” section in the Accessories chapter).
Operating principles:
Q a selector on the front of the MOE, is used for selecting the operating mode:
– AUTO: when the selector is in this position, the pushbuttons on the front of the motor are
locked. Circuit-breaker closing can only take place remotely by means of an electric impulse,
whereas opening is allowed both remotely and from the front of the motor;
– MANUAL: the circuit-breaker can only be opened/closed from the front of the motor using
the relative pushbuttons;
– LOCKED: when the selector is in this position, the circuit-breaker is in the open position. The
padlock device can be withdrawn and the motor locked in the open position;
Q operation of the motor operator via remote control is also guaranteed by permanent electrical
opening/closing impulses. Once an opening command has been given, the next closing com-
mand (permanent) is taken over by the motor operator once opening has been completed. In
the same way, an opening command is taken over once the previous closing operation has been
completed;
Q the resetting modes shown in the diagrams below depend on the reset wiring diagram chosen
by the customer (consult the reset wiring diagrams in the “Electric Diagrams”) chapter.
If the electronic trip unit Ekip LSI, Ekip LSIG or Ekip M-LRIU with Ekip Com module is used, motor
operator MOE-E can be used instead of motor operator MOE.
MOE-E allows the digital signals from the supervision and monitoring system to be used by means
of the release and Ekip Com contacts and to be converted into power signals for operating the
motor operator. All the features described above for the MOE motor operator are also valid for the
MOE-E version.
3/25
1SDC210033D0201
Accessories
Electrical Accessories
Changeover of auxiliary contacts Q (open/closed), SY (Relay tripped) and S51 (trip unit tripping)
Circuit-breaker with MOE (MANUAL Mode)
CB Closed Q=14 SY=96 S51=06
By pressing the Red pushbutton, the CB trips Q=12 SY=98 S51=06
Normal sequence
Charging the springs, CB opens Q=12 SY=96 S51=06
By pressing the Green pushbutton, the CB Closes Q=14 SY=96 S51=06
Trip Sequence CB Closed Q=14 SY=96 S51=06
(trip caused by: CB trips Q=12 SY=98 S51=06
- SOR,
- UVR, Charging the springs, CB opens Q=12 SY=96 S51=06
- Trip Test) By pressing the Green pushbutton, the CB Closes Q=14 SY=96 S51=06
CB Closed Q=14 SY=96 S51=06
Trip Sequence CB trips Q=12 SY=98 S51=08
(trip caused by
trip unit) Charging the springs, CB opens Q=12 SY=96 S51=06
By pressing the Green pushbutton, the CB Closes Q=14 SY=96 S51=06
Circuit-breaker with MOE (AUTO Mode)
CB Closed Q=14 SY=96 S51=06
By pressing the Opening pushbutton remotely,
Q=12 SY=98 S51=06
Normal sequence the CB opens
By pressing the Closing pushbutton remotely, the
Q=14 SY=96 S51=06
CB Closes
CB Closed Q=14 SY=96 S51=06
Trip Sequence CB trips Q=12 SY=98 S51=06
(trip caused by:
- SOR, By pressing the Opening pushbutton remotely,
Q=12 SY=96 S51=06
- UVR, the CB opens
- Trip Test) By pressing the Closing pushbutton remotely, the
Q=14 SY=96 S51=06
CB Closes
CB Closed Q=14 SY=96 S51=06
CB trips Q=12 SY=98 S51=08
Trip Sequence
(trip caused by By pressing the Opening pushbutton remotely,
Q=12 SY=96 S51=06
trip unit) the CB opens
By pressing the Closing pushbutton remotely, the
Q=14 SY=96 S51=06
CB Closes
3/26
1SDC210033D0201
Connectors for electrical accessories
Plug-in circuit-breaker
In the plug-in version of SACE Tmax XT circuit-breakers, the auxiliary circuits can be disconnected
by means of two different types of adapter:
Q plug and socket adapter to be fixed on the bottom of the panel: for XT1, XT2, XT3, XT4;
Q plug and socket adapter installed on the rear of the circuit-breaker and in the fixed part of plug-in
devices: for XT2, XT4.
Plug and socket adapters installed on the rear of the circuit-breaker and in the fixed part
Only for the plug-in versions of Tmax XT2 and XT4 circuit-breakers, the auxiliary circuits can be
automatically disconnected by means of an adapter installed on the rear of the circuit-breaker and
in the fixed part of plug-in versions.
The 12 PIN connector can only be used with accessories that function at a voltage of not more than
250V AC/DC. The cables are connected to /disconnected from the connector in a fast and simple
way without the aid of any dedicated tools. Wiring is to be carried out by the Customer.
Withdrawable circuit-breaker
When withdrawable circuit-breakers are used, the codes of the electrical accessories specifically
designed for this version must be ordered. These dedicated codes contain the wired electrical ac-
cessory with connector for the moving part and for the fixed part to be inserted in the side of the
fixed part. If the MOE motor operator is ordered, connectors for the fixed part and moving part are
always supplied since there is no dedicated code for the withdrawable version.
The connectors of electrical accessories for withdrawable circuit-breakers must all be installed on
the right side of the circuit-breaker in housings made in the side of the fixed part.
This type of connection allows the auxiliary circuits to be disconnected automatically when the
circuit-breaker is withdrawn from the fixed part.
Cabling of withdrawable version
If the Customer wants to wire the fixed part in advance of the moving part, the fixed part mounting
connectors can be ordered as spare parts.
3/27
1SDC210033D0201
Accessories
Electrical Accessories
The table gives all the residual current devices which can be used with the Tmax XT family of circuit-
breakers:
3/28
1SDC210033D0201
RC Sel 200 residual current releases (type A) XT1
Thanks to its low height, the RC Sel 200 residual current release can be installed in 200mm mod-
ules. Moreover, its special shape reduces the overall size of the installation if two or more units are
to be installed side by side.
Power-on LED
Current setting
Alarm and prealarm
signal LED
Time of non trip setting
Magnetic indicator of
residual current trip Test pushbotton
Power-on LED
Current setting
Test pushbutton
Disconnection device
for the insulation test
3/29
1SDC210033D0201
Accessories
Electrical Accessories
RC Inst, RC Sel residual current releases (type A) for XT1 and XT3
Power-on LED
Disconnection device
for insulation test
Current setting
Power-on LED
3/30
1SDC210033D0201
The fixed version of the RC Sel residual current release can easily be converted:
Q into the plug-in type:
– by ordering the kit for converting the residual current release from the fixed to the plug-in version;
Q into the withdrawable type:
– by ordering the kit for converting the residual current release from the plug-in to the withdraw-
able version. This kit contains the shunt opening release of the withdrawable residual cur-
rent device to replace the shunt opening release supplied with the fixed version. The shunt
opening release of the withdrawable residual current device contains both the connector for
the moving part and the connector for the fixed part. The 160A frame with residual current
withdrawable breaker can be used up to a maximum current of 135A, whereas the 250A
frame can be used up to 210A.
With the RC Sel residual current release for XT2-XT4, it is possible to use the same terminals us-
able for the fixed circuit-breaker and for the fixed parts of plug-in and withdrawable circuit-breakers.
Current setting
Power-on LED
The RC B Type residual current release, to be used in conjunction with the XT3 circuit-breaker, has
the following features:
Q it complies with type B operation, which guarantees sensitivity to residual fault currents with
alternating, pulsating alternating and direct current components (IEC 60947-1, IEC 60947-2
Annex B, IEC 60755);
Q the maximum frequency band of the residual fault current can be selected (3 steps: 400 -
700 - 1000Hz). The residual current device can therefore be adapted to suit various industrial
installation requirements according to the prospective fault frequencies generated on the load
side of the release. Typical installations that may require different frequency thresholds from the
standard ones (50 - 60Hz) are welding systems for the automobile industry (1000Hz), the textile
industry (700Hz), airports and three-phase drives (400Hz).
3/31
1SDC210033D0201
Accessories
Electrical Accessories
3/32
1SDC210033D0201
Signals available:
Q LED to indicate the status of the residual current device (supplied or not supplied). RCQ02 is
equipped with the positive safety function thanks to which the RCQ020 commands automatic
circuit-breaker opening in the absence of auxiliary voltage;
Q LED for signalling faults;
Q LED for signalling tripping of the residual current device;
Q pre-alarm/alarm/trip electrical signals.
3/33
1SDC210033D0201
Accessories
Accessories for electronic trip units
Ekip Display
The Ekip Display is a unit which can be applied on the front of the solid-state trip unit and shows the
current values, alarms and protection and communication parameter programming.
Display
Power-on LED
Fixing Device
Main features:
Q installation: Ekip Display can easily be installed on the front of the Ekip LSI, Ekip LISIG and
Ekip M-LRIU electronic trip units. It is connected by means of the test connector on the front
of the trip unit, and fixing is simple and reliable thanks to a specially designed mechanism. This
mechanism also provides a practical way of fastening the accessories to the circuit-breaker in
order to prevent undesired access to the dip-switches. Installation can be carried out under any
conditions, even with the door closed and the electronic trip unit already on and functioning;
Q functions: Ekip Display has four buttons for browsing through the menus. It functions in the
self-supply mode starting from a current of I>0.2xIn circulating through at least one phase.
Backlighting is activated in the presence of higher loads, thereby allowing a better leggibility of
visualized informations. The rear lighting comes on in self-supply for a current I>0.4xIn and is
always on when there is electronic trip unit auxiliary power supply.
Ekip Display:
– shows the current values;
– shows the settings of the protection functions in Amperes or in In;
– shows the protection that caused the release to trip and the fault current (only when there is
24V external voltage or the Ekip TT unit);
– allows the trip thresholds of the trip unit to be programmed and the communication param-
eters to be set on bus system;
Q compatibility: Ekip Display can be fitted even when front accessories, such as the motor, direct
and transmitted rotary handles etc. are already installed. It's possible to use Ekip TT or Ekip T&P
without removing Ekip Display.
3/34
1SDC210033D0201
Ekip LED Meter
The Ekip LED Meter can be applied to the front of the electronic trip unit and displays the current
values and alarms.
L, S, I, G protection LED
Power-on LED
Main features:
Q installation: Ekip LED Meter can be easily installed on the front of Ekip LSI, Ekip LSIG and
Ekip M-LRIU electronic trip units. It is connected by means of the test connector on the front
of the release and fixing is simple and reliable thanks to a specially designed mechanism. This
mechanism also provides a practical way of fastening the accessories to the circuit-breaker in
order to prevent undesired access to the dip-switches. Installation can be carried out under any
conditions, even with the door closed and the electronic trip unit already on and functioning;
Q functions: Ekip LED Meter provides an accurate indication about the value of the current cir-
culating in the trip unit. It does this by means of a scale of LED. Their different colours allow the
normal operation, prealarm and alarm states of the circuit-breaker to be recognized at a glance.
It functions in self-supply mode from a current of I>0.2xIn circulating through at least one phase
or when electronic trip unit’s auxiliary power is available;
Q compatibility: the Ekip LED Meter can also be fitted when front accessories, such as the
motor, direct and transmitted rotary handles. It's possible to use Ekip TT or Ekip T&P without
removing Ekip LED Meter.
3/35
1SDC210033D0201
Accessories
Accessories for electronic trip units
Connection accessories
Devices which allow the electronic trip unit to be connected to external plant units or components.
The connectors are available for the circuit-breakers in fixed, plug-in and withdrawable version.
The connector for the auxiliary power supply is inserted inside the right-hand slot of the circuit-
breaker, and occupies the space of two due auxiliary contacts. To check compatibility with the
auxiliary contacts, consult the compatibility tables in the Accessories chapter.
3/36
1SDC210033D0201
Accessories
Communication devices and systems
Alarm LED
Display
Display push-botton
Main features:
Q installation: HMI030 can be fitted into the hole in the door using the automatic click-in method.
In situations where mechanical stress is particularly intense, it can also be installed by using the
special clips supplied. It must be connected directly to the Ekip LSI, Ekip LSIG or Ekip M-LRIU
protection trip unit with Ekip Com via the serial communication line. HMI030 requires a 24V DC
power supply;
Q functions: HMI030 consists of a graphic display and 4 buttons for browsing through the men-
us. This accessory allows you to view:
– the measurements taken by the release to which it is connected;
– the alarms/events of the release.
Thanks to its high level of accuracy, the same as that of the trip unit protection, the device is a
valid substitute for conventional instruments without any additional current transformers.
3/37
1SDC210033D0201
Accessories
Accessories for electronic trip units
Ekip Com
Ekip Com allows the MOE-E motor operator to be controlled, to determine the ON/OFF/TRIP state
of the circuit-breaker and to connect the electronic trip unit to a Modbus communication line.
Ekip Com is available in two versions: one version for the circuit-breakers in the fixed/plug-in version
and a version complete with connector for the fixed part and the moving part for circuit-breakers in
the withdrawable version.
Main characteristics:
Q installation: the Ekip Com module is inserted in the special seat made in the right-hand pole of
the circuit-breaker and fixing is carried out automatically without any need for screws or tools.
Connection to the trip unit is made using the special small cable which, for greater practicality
and safety, is fitted with a cable guide. The connection towards the Modbus line is made by
means of the terminal box to which a 24V DC auxiliary power supply must also be connected,
which activates both the module and the protection trip unit;
Q functions: the Ekip Com module offers the possibility of acquiring the state of the circuit-
breaker remotely and, in combination with the MOE-E motor operator, allows it to be opened
and closed. If combined with a trip unit fitted with communication (Ekip LSI, Ekip LSIG or Ekip
M-LRIU), the Ekip Com module allows the trip unit to be connected to a Modbus network,
offering the possibility of programming the protections and acquiring the measurements and
alarms when it is connected to a control and/or supervision system. When it is connected to the
HMI030 unit, it is possible to have these data locally on the front of the switchboard.
For further details on the comunication systems which can be made by means of the Ekip Com
module, refer to the “Communication Systems” paragraph in the “Ranges” chapter.
Ekip Com
Circuit-breaker 3p Circuit-breaker 4p
Ekip Ekip
Com Com
XT2
XT4
EP010 - FBP
The EP010 Fieldbus interface allows SACE Tmax XT circuit-breakers to be integrated into commu-
nication systems to control and supervise using the most diffused communication protocols, such
as Profibus, DeviceNet and CANopen (besides ModBus RTU, supported by Ekip Com).
To realize this, EP010 is interfaced on one side by an intelligent connector from ABB Field Bus Plug
family’s, to allow the choosing of desired protocol.
This is achieved by using ABB FBP FieldBusPlug smart connectors, which allow communication to
be activated with various different protocols.
Main features:
Q installation: the EP010 interface allows XT2 and XT4 circuit-breakers fitted with the Ekip LSI,
Ekip LSIG or Ekip M-LRIU electronic trip unit to be connected to the Fieldbus Plug system.
Connections between EP010 and the electronic trip unit are made by means of the Ekip Com
accessory, whereas connections between EP010 and the network are to be carried out by the
Customer and depend on the Field bus plug system used. The PDP22 connector is advisable if
the Profibus protocol is used, or the DNP21 connector in the case of the Device Net protocol.
3/38
1SDC210033D0201
Accessories
Communication devices and systems
Ekip Connect
Installation and diagnosis software for ABB SACE products with Modbus RTU communication. The
software can be used during the commissioning stage, or for troubleshooting in an up and running
communication network.
Ekip Connect automatically scans the RS-485 bus, detects all the devices connected and checks
their configuration, checking all the possible address, parity and baud rate combinations. A simple
click over SCAN will highlight:
Q devices that fail to respond;
Q configuration errors;
Q incorrect addresses and parity;
Q any wiring errors (with the SACE electronic trip unit);
thus achieving a complete diagnosis of the communication network.
Thanks to this friendly program, the Modbus communication network installation is very easy. Ekip
T&P SW is distributed free of charge and can be downloaded from the BOL web site (http://bol.
it.abb.com).
3/39
1SDC210033D0201
Accessories
Test and configuration accessories
Ekip T&P
Ekip T&P is a kit purpose studied to supervise, configure and testing electronic protection trip units.
Ekip T&P
The Ekip T&P unit is connected on one side to the USB port of its own PC and on the other, by
means of a cable provided, to the protection trip unit of the SACE Tmax XT series.
The Ekip T&P unit allows automatic, manual test and the trip test of the device it is connected to.
These functions are managed by means of the Ekip T&P Interface which can only be activated di-
rectly by the Ekip Connect when the Ekip T&P is present and connected to the PC.
3/40
1SDC210033D0201
Ekip TT
LED
- green: in operation
- flashing green: trip test
- red: battery flat
The Ekip TT accessory is supplied with a special connector which makes connection between the
electronic trip unit and the Ekip TT unit easier. The kit also include san adaptor which allows use of
the Ekip TT unit with the current Tmax breakers.
Ekip TT is a device which allows:
Q verify the correct functioning of the electronic trip unit’s opening solenoid and the trip mecha-
nism of circuit-breaker (trip test);
Q testing of the LEDs on the electronic trip unit it is connected to;
Q (in case of intervention by electronic trip unit) to supply the trip unit powered by auxiliary power
to show the latest intervened protection. Simply linking Ekip TT to the electronic trip unit (or to
the Ekip display or to the Ekip LED Meter), the LED light on the latest protection intervened.
Its reduced dimension make it pocket size.
3/41
1SDC210033D0201
Accessories
Automatic network-generator transfer unit ATS021-ATS022
The ATS (Automatic Transfer Switch) is the network-generator transfer unit used in installations
where switching the main power line to an emergency one is required, to ensure power supply to
the loads in the case of anomalies in the main line.
The unit is able to manage the entire transfer procedure automatically, and prepares the commands
for carrying out the procedure manually as well.
In the case of an anomaly in the main line voltage, in accordance with the parameters set by the
user, the opening of the circuit-breaker of the main line, the starting of the generator set (when pro-
vided) and the closing of the emergency line are performed. In the same way, in the case of the main
ATS021 line returning, the procedure of reverse transfer is controlled automatically.
The new generation of ATS (ATS021 and ATS022) offers the most advanced and complete solu-
tions to guarantee service continuity. The ATS021 and ATS022 can be used both with all the circuit-
breakers in the SACE Tmax XT family and with the switch-disconnectors.
The ATS021 and ATS022 devices have been designed to operate with self-supply. The ATS022
unit also prepares the connection for auxiliary power supply, which allows additional functions to
be used.
The ATS021 and ATS022 devices carry out control of both the power supply lines and analyse:
Q phase unbalance;
Q frequency unbalance;
Q phase loss.
Apart from the standard control functions, with the ATS022 unit, the following is possible:
Q selecting the priority line;
Q controlling a third circuit-breaker;
ATS022 Q incorporating the device in a supervision system with Modbus communication (auxiliary power
supply is needed);
Q reading and setting the parameters, and displaying the measurements and alarms, by means of
a graphic display.
Typical applications for use are: power supply to UPS (Uninterrupted Power Supply) units, operating
rooms and primary hospital services, emergency power supply for civil buildings, airports, hotels,
data banks and telecommunication systems, power supply of industrial lines for continuous proc-
esses.
For correct configuration, each circuit-breaker connected to the ATS021 or ATS022 must be fitted
with the following accessories:
Q mechanical interlock;
Q motorised control of opening and closing;
Q key lock against just manual operation for the motor operator;
Q contact for signalling the state (open/closed) and contact for tripped;
Q contact for racked-in (in the case of a withdrawable version circuit-breaker).
3/42
1SDC210033D0201
ATS021 ATS022
General
Not Required
Auxiliary Power Supply Not Required (24-110 Vdc is required only for Modbus
dialogue and 16 2/3 Hz system)
Rated Voltage, Un [VAC] Max 480 Max 480
Frequency [Hz] 50, 60 16 2/3, 50, 60, 400
Dimensions (HxLxD) [mm] 96x144x170 96x144x170
Door mounting Door mounting
Type of installation
DIN-rail mounting DIN-rail mounting
Operating Mode Auto/Manual Auto/Manual
Features
Monitoring of the Normal and Emergency lines Q Q
Controlling CBs of the Normal and Emergency lines Q Q
Generator set startup Q Q
Generator set shutdown with adjustable delay Q Q
Bus-tie – Q
No-priority Line – Q
Modbus RS485 – Q
Display – Q
Ambient conditions
Operating temperature -20…+60 °C -20…+60 °C
Humidity 5% - 90% without condensation 5% - 90% without condensation
Operating thresholds
Minimum voltage -30%…-5%Un -30%…-5%Un
Maximum voltage +5%…+30%Un +5%…+30%Un
Fixed frequency thresholds -10%…+10%fn -10%…+10%fn
Test
Test Mode Q Q
Compliance with standards
Electronic equipment for use in power installations EN-IEC 50178 EN-IEC 50178
EN 50081-2 EN 50081-2
Electromagnetic compatibility
EN 50082-2 EN 50082-2
IEC 68-2-1 IEC 68-2-1
Environmental conditions IEC 68-2-2 IEC 68-2-2
IEC 68-2-3 IEC 68-2-3
3/43
1SDC210033D0201
Accessories
Compatibility of accessories
Check whether the different devices are compatible/incompatible with each other when ordering
accessories. The following table allow provides a simple check of the compatibility between:
Q mechanical accessories, accessories for electronic trip units, motors and residual current devices;
Q internal electrical accessories.
3p
To understand the abbreviations used to identify the accessories more easily, refer to the “Symbols”
paragraph in chapter 8, “Glossary”.
3p PS-SOR 3p
4p
3Q sx 3p
SA 3p
SOR 4p
UVR 4p
.....
3/44
1SDC210033D0201
Compatibility of electrical accessories
Fixed/plug-in circuit-breaker compatibility XT1-XT3
SOR UVR PS-SOR 3Q sx SA SOR UVR PS-SOR 3Q sx 1Q 2Q 3Q KLC on
3p 3p 3p 3p 3p 4p 4p 4p 4p 1SY 1SY 1SY CB
SOR 3p
UVR 3p
PS-SOR 3p
3Q sx 3p
SA 3p
SOR 4p
UVR 4p
PS-SOR 4p
3Q sx 4p
1Q 1SY
2Q 1SY
3Q 1SY
KLC on CB
Compatibility
3/45
1SDC210033D0201
Accessories
Compatibility of accessories
3/46
1SDC210033D0201
Characteristic Curves and
Technical Information*
Index
Characteristic Curves
Examples of Curve reading .....................................................................................................4/2
240V ......................................................................................................................................4/15
415-440V ...............................................................................................................................4/16
500V ......................................................................................................................................4/17
690V ......................................................................................................................................4/18
Limiting curves
240V ......................................................................................................................................4/19
415-440V ...............................................................................................................................4/20
500V ......................................................................................................................................4/21
690V ......................................................................................................................................4/22
Technical Information
* All the curves contained in this chapter are Temperature performances ...............................................................................................4/23
preliminary; for more information contact
ABB SACE Dissipated powers ..............................................................................................................4/27
4/1
1SDC210033D0201
Examples of Curve reading
t [s]
Example 1 – XT3N 250 104
10-2
10-1 1 10 102
x I1
10-2
1 10 10 2 10 3
x Irms [kA]
Ip [kA]
Example 3 – XT2N 160 10 3
Limitation curves
The figure below gives the trend of the Limitation curves of the
XT2N 160 In=160 A circuit-breaker. A curve
The effective value of the prospective symmetrical short-circuit cur- 10 2
rent is given on the abscissas of the diagram, whereas the peak value 50 kA
of the short-circuit current is indicated on the ordinates.
The limiting effect can be evaluated by comparing the peak value 36.5 kA 160 A
corresponding to the prospective short-circuit current (curve A) with
the peak limited value (curve B), at the same value of symmetrical B curve
10
13.5 kA
short-circuit current.
For a fault current of 20 kA, the XT2N 160 circuit-breaker with a
thermomagnetic trip unit In =160 A limits the peak prospective
short-circuit current to 13.5 kA at a voltage of 500 V, with a reduc-
tion in relation to the peak value of the prospective short-circuit
current of 36.5 kA. 1
1 10 10 2 10 3
x Irms [kA]
4/2
1SDC210033D0201
Trip curves with thermomagnetic trip unit
Trip curves for distribution
t [s] t [s]
1SDC21017EF0001
1SDC21018EF0001
104 104
103 103
102 102
10 10
1 1
10-2 10-2
10-1 1 10 102 10-1 1 10 102
x I1 x I1
t [s] t [s]
1SDC21019EF0001
103 103
102 102
10 10
In=1.6...12.5 A
In=16...25 A
1 1
In=63...160 A
I3=40 A I3=10xIn
10-1 10-1
In=50 A
10-2 10-2
10-1 1 10 102 10-1 1 10 102
x I1 x I1
4/3
1SDC210033D0201
Trip curves with thermomagnetic trip unit
Trip curves for distribution
t [s]
1SDC21021EF0001
104
103
102
10
I3=5...10xIn
10-1
10-2
10-1 1 10 102
x I1
4/4
1SDC210033D0201
Trip curves with thermomagnetic trip unit
Trip curves for motor protection
t [s] t [s]
1SDC21022EF0001
1SDC21023EF0001
104 104
103 103
Overload limit
10 10
1 I3=14xIn 1
(In=1...12.5A)
I3=6...14xIn
I3=6...12xIn
(In=20...100A)
10-1 10-1
10-2 10-2
10-1 1 10 102 10-1 1 10 102
x I1 x I1
t [s]
1SDC21024EF0001
104
103
102
Overload limit
10
I3=5...10xIn
10-1
10-2
10-1 1 10 102
x I1
4/5
1SDC210033D0201
Trip curves with thermomagnetic trip unit
Trip curves for generator protection
t [s] t [s]
1SDC210125EF0001
1SDC21026EF0001
104 104
103 103
102 102
10 10
1 1
In=63...160A In=125...250A
In=50A In=100A
In=32-40A In=80A
In=25A In=63A
10-1 In=20A 10-1
In=16A
10-2 10-2
10-1 1 10 102 10-1 1 10 102
x I1 x I1
4/6
1SDC210033D0201
Trip curves with electronic trip unit
Trip curves for distribution
t [s] t [s]
1SDC21027EF0001
1SDC21028EF0001
104 104
0.4...1 0.4...1
0.4 1 0.4 1
1 10
103 103
1...10 1...10
102 102
10
10 10
1
102 102
1 1
10-1 10-1
10-2 10-2
10-3 10-3
10-1 1 10 10-1 1 10 10-1 1 10 10-1 1 10
x In I [kA] x In I [kA]
t [s] t [s]
1SDC21029EF0001
1SDC21030EF0001
104 104
0.4...1
0.4 1
1 10
103 103
1...10
102 102
10
1 10
10 10
I2t ON
102 102
1 1
10-1 10-1
I2t OFF
10-2 10-2
10-3 10-3
10-1 1 10 10-1 1 10 10-1 1 10 10-1 1 10
x In I [kA] x In I [kA]
4/7
1SDC210033D0201
Trip curves with electronic trip unit
Trip curves for distribution
t [s] t [s]
104 104
1SDC21031EF0001
1SDC21032EF0001
0.4...1
0.4 1 0.2...1
0.2 1
103 103
102 102
10
1 10
10 10
I2t ON
102 102
1 1
I4=0.2...0.49 in inibition at 4 In
I4=0.5...0.79 in inibition at 6 In
I4=0.79...1 in inibition at 8 In
10-1 10-1
I2t OFF
10-2 10-2
10-3 10-3
10-1 1 10 10-1 1 10 10-1 1 10 10-1 1 10
x In I [kA] x In I [kA]
t [s] t [s]
104 104
1SDC21033EF0001
1SDC21034EF0001
0.4...1 0.4...1
0.4 1 0.4 1
103 103
1...10
102 102
10
10 10
1
102 102
1 1
10-1 10-1
10-2 10-2
10-3 10-3
10-1 1 10 10-1 1 10 10-1 1 10 10-1 1 10
x In I [kA] x In I [kA]
4/8
1SDC210033D0201
XT4 Ekip I XT4 Ekip LSI
I function LSI functions
t [s] t [s]
104 104
1SDC21035EF0001
1SDC21036EF0001
0.4...1
0.4 1
1 10
103 103
Overload limit
1
102 102
10
1 10
10 10
I2t ON
102 102
1 1
I2t OFF
10-1 10-1
10-2 10-2
10-3 10-3
10-1 1 10 10-1 1 10 10-1 1 10 10-1 1 10
x In I [kA] x In I [kA]
t [s] t [s]
1SDC21086EF0001
1SDC21037EF0001
104 104
0.4...1
0.4 1 0.2...1
0.2 1
103 103
1...10
102 102
10
1 10
10 10
I2t ON
102 102
1 1
10-1 10-1
10-2 10-2
10-3 10-3
10-1 1 10 10-1 1 10 10-1 1 10 10-1 1 10
x In I [kA] x In I [kA]
4/9
1SDC210033D0201
Trip curves with electronic trip unit
Trip curves for motor protection
t [s]
t [s]
1SDC21015FF0001
104
1SDC210E33F0001
105
KRW
104 FROG
103
6 13
103
102
102
10
10A
10
30
1
20
10
30
10A
1 20
10-1 10
10A
10-1
10-2
10-1 1 10 10 2 1,05
10-1 1 10 102
x In x In
t [s]
t [s]
105
1SDC21039EF0001
104
1SDC210E34F0001
KRW
104
103
6 13
103
102
102
10
10A
10
1
30
1 20
10
10-1
10A
10-1
1,05 10-2
10-1 1 10 102 10-1 1 10 10 2
x In x In
4/10
1SDC210033D0201
XT2-XT4 Ekip M-LIU XT2-XT4 Ekip M-LRIU
U function L function
(hot and cold trip)
t [s]
1SDC21040EF0001
t [s]
104 105
1SDC210E33F0001
KRW
104
FROG
103
103
102
102
10
10A
10
30
1
20
10
30
10A
1 20
10-1 10
10A
10-1
10-2
10-1 1 10 10 2 1,05
10-1 1 10 102
x In x In
t [s]
t [s]
1SDC210E34F0001
KRW
104 103
6 13
103
102
102
10
10A
10
1
30
1 20
10 10-1
10A
10-1
1,05
10-2
10-1 1 10 102 10-1 1 10 10 2
x In x In
4/11
1SDC210033D0201
Trip curves with electronic trip unit
Trip curves for motor protection
t [s] t [s]
1SDC21043EF0001
104
1SDC21042EF0001
104
103 103
3...9 R
3 9
102 102
10 10
4...1
1 1 1
10-1 10-1
10-2 10-2
10-1 1 10 10 2 10-1 1 10 10 2
x In x In
4/12
1SDC210033D0201
Trip curves with electronic trip unit
Trip curves for generator protection
t [s] t [s]
1SDC21049EF0001
1SDC21050EF0001
104 104
0.4...1 0.4...1
0.4 1 0.4 1
1 10
103 103
1...10 1...10
102 102
10
10 10
1
102 102
1 1
10-1 10-1
10-2 10-2
10-3 10-3
10-1 1 10 10-1 1 10 10-1 1 10 10-1 1 10
x In I [kA] x In I [kA]
t [s] t [s]
1SDC21051EF0001
1SDC21052EF0001
104 104
0.4...1 0.4...1
0.4 1 0.4 1
1 10
103 103
1...10 1...10
102 102
10
10 10
1
102 102
1 1
10-1 10-1
10-2 10-2
10-3 10-3
10-1 1 10 10-1 1 10 10-1 1 10 10-1 1 10
x In I [kA] x In I [kA]
4/13
1SDC210033D0201
Trip curves with electronic trip unit
Trip curves for oversized neutral protection
t [s] t [s]
104 104
1SDC21053EF0001
1SDC21054EF0001
0.4...1 0.4...1
0.4 1 0.4 1
103 103
1...10 1...10
102 102
10
10 10
1
102 102
1 1
10-1 10-1
10-2 10-2
10-3 10-3
10-1 1 10 10-1 1 10 10-1 1 10 10-1 1 10
x In I [kA] x In I [kA]
t [s] t [s]
104 104
1SDC21055EF0001
1SDC21056EF0001
0.4...1 0.4...1
0.4 1 0.4 1
103 103
1...10 1...10
102 102
10
10 10
1
102 102
1 1
10-1 10-1
10-2 10-2
10-3 10-3
10-1 1 10 10-1 1 10 10-1 1 10 10-1 1 10
x In I [kA] x In I [kA]
4/14
1SDC210033D0201
Specific let-through energy curves
240V
XT1 XT2
240V 240V
1SDC21057EF0001
1SDC21058EF0001
1 1
160 A
160 A
10-1 10-1
10-2 10-2
1 10 10 2 10 3 1 10 10 2 10 3
x Irms [kA] x Irms [kA]
XT3
240V
250 A
10-1
10-2
1 10 10 2 10 3
x Irms [kA]
4/15
1SDC210033D0201
Specific let-through energy curves
415-440V
XT1 XT2
415-440V 415-440V
1SDC21060EF0001
1SDC21061EF0001
1 1
160 A
160 A
10-1 10-1
10-2 10-2
1 10 10 2 10 3 1 10 10 2 10 3
x Irms [kA] x Irms [kA]
XT3
415-440V
250 A
10-1
10-2
1 10 10 2 10 3
x Irms [kA]
4/16
1SDC210033D0201
Specific let-through energy curves
500V
XT1 XT2
500V 500V
1SDC21063EF0001
1SDC21064EF0001
1 1
160 A
160 A
10-1 10-1
10-2 10-2
1 10 10 2 10 3 1 10 10 2 10 3
x Irms [kA] x Irms [kA]
XT3
500V
250 A
10-1
10-2
1 10 10 2 10 3
x Irms [kA]
4/17
1SDC210033D0201
Specific let-through energy curves
690V
XT1 XT2
690V 690V
1SDC21066EF0001
1SDC21067EF0001
1 1
160 A
160 A
10-1 10-1
10-2 10-2
1 10 10 2 1 10 10 2
x Irms [kA] x Irms [kA]
XT3
690V
1
250 A
10-1
10-2
1 10 10 2
x Irms [kA]
4/18
1SDC210033D0201
Limiting curves
240V
XT1 XT2
240V 240V
Ip [kA] Ip [kA]
10 3 10 3
1SDC21069EF0001
1SDC21070EF0001
10 2 10 2
160 A 160 A
10 10
1 1
1 10 10 2 10 3 1 10 10 2 10 3
x Irms [kA] x Irms [kA]
XT3
240V
Ip [kA]
10 3
1SDC21071EF0001
10 2
250 A
10
1
1 10 10 2 10 3
x Irms [kA]
4/19
1SDC210033D0201
Limiting curves
415-440V
XT1 XT2
415-440V 415-440V
Ip [kA] Ip [kA]
10 3 10 3
1SDC21072EF0001
1SDC21073EF0001
10 2 10 2
160 A 160 A
10 10
1 1
1 10 10 2 10 3 1 10 10 2 10 3
x Irms [kA] x Irms [kA]
XT3
415-440V
Ip [kA]
10 3
1SDC21074EF0001
10 2
250 A
10
1
1 10 10 2 10 3
x Irms [kA]
4/20
1SDC210033D0201
Limiting curves
500V
XT1 XT2
500V 500V
Ip [kA] Ip [kA]
10 3 10 3
1SDC21075EF0001
1SDC21076EF0001
10 2 10 2
160 A
160 A
10 10
1 1
1 10 10 2 10 3 1 10 10 2 10 3
x Irms [kA] x Irms [kA]
XT3
500V
Ip [kA]
10 3
1SDC21077EF0001
10 2
250 A
10
1
1 10 10 2 10 3
x Irms [kA]
4/21
1SDC210033D0201
Limiting curves
690V
XT1 XT2
690V 690V
Ip [kA] Ip [kA]
10 2 10 2
1SDC21078EF0001
1SDC21079EF0001
160 A
160 A
10 10
1 1
1 10 10 2 1 10 10 2
x Irms [kA] x Irms [kA]
XT3
690V
Ip [kA]
10 2
1SDC21080EF0001
250 A
10
1
1 10 10 2
x Irms [kA]
4/22
1SDC210033D0201
Temperature performances
All the Tmax XT circuit-breakers can be used under the following environmental conditions:
Q -25°C +70°C: range of atmospheric temperature where the circuit-breaker is installed;
Q -40°C +70°C: range of atmospheric temperature where the circuit-breaker is stored.
The circuit-breakers fitted with thermomagnetic trip unit have the thermal element set for a reference
temperature of +40°C. With the same setting, for temperatures other than +40°C there is a variation
in the thermal trip threshold as indicated in the tables below.
4/23
1SDC210033D0201
Temperature performances
The electronic overcurrent trip units do not undergo any variations in performance as the temperature
varies.
However, even if heating does not affect the trip thresholds of the electronic trip units, in the case of
temperatures exceeding +40°C it is advisable to reduce the maximum setting for protection against
overloads (L) to preserve the copper parts of the circuit-breaker against high temperatures.
The same considerations can be done about the switch-disconnectors and magnetic only circuit-
breakers.
The table and graph below show the maximum adjustment at which the threshold I1 of the overcurrent
protection (L) must be set according to the ambient temperature and to the type of terminals used.
In [A]
180
1SDC21081EF0001
175
170
165
160
155
150
145
140
135
130
125
120
40 45 50 55 60 65 70
T [°C]
4/24
1SDC210033D0201
XT2 - Fixed circuit-breakers with only magnetic and electronic trip unit
40°C 50°C 60°C 70°C
Imax [A] Imax [A] Imax [A] Imax [A]
F 160 160 146 131
F = Front flat terminals
In [A]
180
1SDC21087EF0001
175
170
165
160
155
150
145
140
135
130
125
120
40 45 50 55 60 65 70
T [°C]
In [A]
260
1SDC21082EF0001
255
250
245
240
235
230
225
220
215
210
205
200
40 45 50 55 60 65 70
T [°C]
4/25
1SDC210033D0201
Temperature performances
XT4 - Fixed circuit-breakers with only magnetic, electronic trip unit and switch-disconnector
40°C 50°C 60°C 70°C
Imax [A] Imax [A] Imax [A] Imax [A]
F 250 250 238 213
F = Front flat terminals
In [A]
260
1SDC21088EF0001
255
250
245
240
235
230
225
220
215
210
205
200
40 45 50 55 60 65 70
T [°C]
4/26
1SDC210033D0201
Dissipated powers
To ensure service continuity of the plants, how to keep the temperature within acceptable levels for
operation of the various devices and not only for the circuit-breakers must be carefully assessed,
for example with recourse to forced ventilation in the switchboards and in the rooms where they
are installed.
The table gives the dissipated power values per single pole at the rated current In for each circuit-
breaker used. The total maximum dissipated power for a circuit-breaker used at 50/60Hz is equal
to the power per single pole multiplied by the number of poles.
4/27
1SDC210033D0201
Overall dimensions
Index
Tmax XT1 - Installation for fixed circuit-breaker .....................................................................5/2
Tmax XT1 - Terminals for fixed circuit-breaker .......................................................................5/5
Tmax XT1 - Accessories for fixed circuit-breaker ...................................................................5/8
Tmax XT1 - Installation for plug-in circuit-breaker ................................................................5/14
Tmax XT1 - Terminals for plug-in circuit-breaker ..................................................................5/17
Tmax XT1 - Accessories for plug-in circuit-breaker ..............................................................5/20
5/1
1SDC210033D0201
Overall dimensions
Tmax XT1 - Installation for fixed circuit-breaker
Caption
1SDC21077CF0001
A
With standard flange III - IV 74
III - IV 71
Without flange
III - IV 79
Caption
5/2
1SDC210033D0201
Drilling template for circuit-breaker fixing
1SDC21003DF0001
3 POLES 4 POLES
Flanges
Caption
7 Optional flange
1SDC21007DF0001
5/3
1SDC210033D0201
Overall dimensions
Tmax XT1 - Installation for fixed circuit-breaker
1SDC21002DF0001
3 POLES 4 POLES
Without flange
1SDC21006DF0001
3 POLES 4 POLES 3-4 POLES
1SDC21000DF0001
3-4 POLES
5/4
1SDC210033D0201
Overall dimensions
Tmax XT1 - Terminals for fixed circuit-breaker
Terminals F
Caption
1SDC21079CF0001
Terminals EF
Caption
1SDC21080CF0001
Terminals ES
Caption
5/5
1SDC210033D0201
Overall dimensions
Tmax XT1 - Terminals for fixed circuit-breaker
Caption
1SDC21082CF0001
1x35...95mm2 terminals FCCuAl
Caption
1SDC21017FF0001
Terminals FCCu
Caption
Terminals MC
Caption
5/6
1SDC210033D0201
Terminals R
Caption
1SDC21085CF0001
3 POLES 4 POLES
5/7
1SDC210033D0201
Overall dimensions
Tmax XT1 - Accessories for fixed circuit-breaker
1SDC21093CF0001
MINIMUM ROTATION RADIUS FOR
DOOR FULCRUM
Caption
5/8
1SDC210033D0201
Rotary handle operating mechanism on the compartment door (RHE)
1SDC21094CF0001
MINIMUM ROTATION RADIUS FOR
DOOR FULCRUM
Caption
5 Transmission unit
5/9
1SDC210033D0201
Overall dimensions
Tmax XT1 - Accessories for fixed circuit-breaker
Caption
7 Cables connection
1SDC21098CF0001
1SDC21099CF0001
5/10
1SDC210033D0201
RC Inst and RC Sel residual current release for 3 poles circuit-breaker
Caption
1SDC21095CF0001
A
With standard flange III 74
Without flange III 71
5/11
1SDC210033D0201
Overall dimensions
Tmax XT1 - Accessories for fixed circuit-breaker
Caption
1SDC21096CF0001
A
With standard flange IV 74
Without flange IV 71
5/12
1SDC210033D0201
RC Sel 200 4 poles residual current release
Caption
1SDC21097CF0001
5/13
1SDC210033D0201
Overall dimensions
Tmax XT1 - Installation for plug-in circuit-breaker
Caption
1 Fixed part
2 Moving part
Fixing at 50mm A
With standard flange III - IV 124
III - IV 121
Without flange
III - IV 129
1SDC21086CF0001
III - IV 141
Without flange
III - IV 149
1SDC21004DF0001
3 POLES 4 POLES
1SDC21005DF0001
4 POLES
3 POLES
5/14
1SDC210033D0201
Flanges
Caption
7 Optional flange
1SDC21008DF0001
5/15
1SDC210033D0201
Overall dimensions
Tmax XT1 - Installation for plug-in circuit-breaker
1SDC21009DF0001
3 POLES 4 POLES
Without flange
1SDC21011DF0001
3 POLES 4 POLES 3-4 POLES
1SDC21012DF0001
3-4 POLES
5/16
1SDC210033D0201
Overall dimensions
Tmax XT1 - Terminals for plug-in circuit-breaker
Terminals EF
20.5
40.5
1SDC21087CF0001
FIXING AT 50mm FIXING AT 70mm
Caption
Terminals ES
1SDC21088CF0001
FIXING AT 50mm
Caption
5/17
1SDC210033D0201
Overall dimensions
Tmax XT1 - Terminals for plug-in circuit-breaker
Caption
1SDC21089CF0001
FIXING AT 50mm
Caption
1SDC21018FF0001
Terminals FCCu
24.5
Caption
4 Terminals FCCu
FIXING AT 50mm
5/18
1SDC210033D0201
Terminals MC
Caption
1SDC21091CF0001
FIXING AT 50mm
Terminals HR/VR
Caption
5/19
1SDC210033D0201
Overall dimensions
Tmax XT1 - Accessories for plug-in circuit-breaker
Caption
1 Fixed part
2 Moving part
7 Cables connection
1SDC21098CF0001
FIXING AT 50mm
1SDC21099CF0001
5/20
1SDC210033D0201
Overall dimensions
Tmax XT2 - Installation for fixed circuit-breaker
Caption
1SDC21000CF0001
A
With standard flange III - IV 86
III - IV 83.5
Without flange
III - IV 91.5
Caption
1SDC21001CF0001
3 POLES 4 POLES
5/21
1SDC210033D0201
Overall dimensions
Tmax XT2 - Installation for fixed circuit-breaker
Flanges
Caption
9 Optional flange
1SDC21044CF0001
1SDC21045CF0001
5/22
1SDC210033D0201
Drilling templates compartment door
1SDC21042CF0001
1SDC21014DF0001
3 POLES 4 POLES
Without flange
1SDC21018DF0001
3-4 POLES
3 POLES 4 POLES
1SDC21037CF0001
3-4 POLES
5/23
1SDC210033D0201
Overall dimensions
Tmax XT2 - Terminals for fixed circuit-breaker
Terminals F
Caption
1SDC21003CF0001
Terminals EF
Caption
5/24
1SDC210033D0201
Terminals ES
1SDC21005CF0001
Caption
Caption
5/25
1SDC210033D0201
Overall dimensions
Tmax XT2 - Terminals for fixed circuit-breaker
1SDC21020FF0001
Caption
2 2x35...95mm2 terminals
FCCuAl
Terminals FCCu
Caption
7 Terminals FCCu
1SDC21098EF0001
5/26
1SDC210033D0201
Terminals MC
Caption
6 Multicable terminals
1SDC21099EF0001
Terminals R
Caption
1SDC21006CF0001
4 Drilling template for circuit-
breaker IV fixing on sheet
1SDC21002CF0001
1SDC21007CF0001
3 POLES 4 POLES
5/27
1SDC210033D0201
Overall dimensions
Tmax XT2 - Accessories for fixed circuit-breaker
1SDC21021CF0001
Caption MINIMUM ROTATION RADIUS
FOR DOOR FULCRUM
5/28
1SDC210033D0201
Rotary handle operating mechanism on the compartment door (RHE)
1SDC21020CF0001
MINIMUM ROTATION RADIUS
FOR DOOR FULCRUM
Caption
5 Transmission unit
5/29
1SDC210033D0201
Overall dimensions
Tmax XT2 - Accessories for fixed circuit-breaker
3 POLES
1SDC21018CF0001
4 POLES
Caption
5/30
1SDC210033D0201
Front for lever operating mechanism (FLD)
1SDC21019CF0001
Caption
5/31
1SDC210033D0201
Overall dimensions
Tmax XT2 - Accessories for fixed circuit-breaker
1SDC21022CF0001
1SDC21023CF0001
4 POLES
1SDC21000FF0001
Caption
1 Residual current
2 Front terminals
5/32
1SDC210033D0201
Overall dimensions
Tmax XT2 - Installation for plug-in circuit-breaker
Caption
1 Fixed part
2 Moving part
Fixing at 50mm A
With standard flange III - IV 136
III - IV 133.5
Without flange
III - IV 141.5
1SDC21008CF0001
III - IV 153.5
Without flange
III - IV 161.5
1SDC21005DF0001
3 POLES 4 POLES
1SDC21004DF0001
3-4 POLES
5/33
1SDC210033D0201
Overall dimensions
Tmax XT2 - Installation for plug-in circuit-breaker
Flanges
Caption
9 Optional flange
1SDC21044CF0001
1SDC21045CF0001
5/34
1SDC210033D0201
Overall dimensions
Tmax XT2 - Terminals for plug-in circuit-breaker
1SDC21042CF0001
3 POLES 4 POLES
Without flange
1SDC21043CF0001
3-4 POLES
3 POLES 4 POLES
1SDC21037CF0001
3-4 POLES
5/35
1SDC210033D0201
Overall dimensions
Tmax XT2 - Terminals for plug-in circuit-breaker
Terminals EF
1SDC21009CF0001
1SDC21009CF0001
FIXING AT 50mm FIXING AT 70mm
Caption
Terminals ES
1SDC21010CF0001
FIXING AT 50mm
Caption
5/36
1SDC210033D0201
1x1...95mm2 terminals FCCuAl
Caption
1SDC21011CF0001
provided
FIXING AT 50mm
Caption
1SDC21021FF0001
2x35...95mm2 terminals FCCuAl
Caption
5/37
1SDC210033D0201
Overall dimensions
Tmax XT2 - Terminals for plug-in circuit-breaker
Terminals FCCu
Caption
5 Terminals FCCu
1SDC21001FF0001
Note: 25mm insulating barriers between
phases (compulsory) provided as
standard with the circuit-breaker
Terminals MC
Caption
4 Multicable terminals
1SDC21002FCF0001
FIXING AT 50mm
5/38
1SDC210033D0201
Terminals HR/VR
1SDC21012CF0001
Caption
5/39
1SDC210033D0201
Overall dimensions
Tmax XT2 - Accessories for plug-in circuit-breaker
1SDC21030CF0001
1SDC21031CF0001
Caption
1 Fixed part
2 Moving part
3 MOE
5/40
1SDC210033D0201
Front for lever operating mechanism (FLD)
1SDC21028CF0001
1SDC21029CF0001
Caption
1 Fixed part
2 Moving part
5/41
1SDC210033D0201
Overall dimensions
Tmax XT2 - Accessories for plug-in circuit-breaker
1SDC21024CF0001
1SDC21023CF0001
4 POLES
Caption
1SDC21025CF0001
1SDC21026CF0001
1 Residual current
3 Fixed part
4 Moving part
6 Extended terminals
5/42
1SDC210033D0201
Overall dimensions
Tmax XT2 - Installation for withdrawable circuit-breaker
Fixing on sheet
ISOLATING DISTANCE
1SDC21013CF0001
Caption
1 Fixed part
2 Moving part
5/43
1SDC210033D0201
Overall dimensions
Tmax XT2 - Installation for withdrawable circuit-breaker
1SDC21005DF0001
3 POLES 4 POLES
1SDC21004DF0001
3-4 POLES
Flanges
Caption
C D
1SDC21046CF0001
5/44
1SDC210033D0201
Drilling templates compartment door
1SDC21042CF0001
3 POLES 4 POLES
Without flange
1SDC21043CF0001
3-4 POLES
3 POLES 4 POLES
1SDC21037CF0001
3-4 POLES
5/45
1SDC210033D0201
Overall dimensions
Tmax XT2 - Terminals for withdrawable circuit-breaker
Terminals EF
ISOLATING DISTANCE
1SDC21014CF0001
FIXING AT 50mm FIXING AT 70mm
Caption
2 Moving part
Terminals ES
1SDC21015CF0001
Caption
FIXING AT 50mm
5/46
1SDC210033D0201
1x1...95mm2 terminals FCCuAl
Caption
1SDC21016CF0001
FIXING AT 50mm
Caption
1SDC21023FF0001
Caption
5/47
1SDC210033D0201
Overall dimensions
Tmax XT2 - Terminals for withdrawable circuit-breaker
Terminals FCCu
Caption
2 Terminals FCCu
Terminals MC
Caption
1 Multicable terminals
1SDC21003FF0001
FIXING AT 50mm
5/48
1SDC210033D0201
Terminals HR/VR
1SDC21017CF0001
Caption
5/49
1SDC210033D0201
Overall dimensions
Tmax XT2 - Accessories for withdrawable circuit-breaker
1SDC21035CF0001
1SDC21036CF0001
Caption
1 Fixed part
2 Moving part
5 Extended terminals
5/50
1SDC210033D0201
Rotary handle operating mechanism on the compartment door (RHE)
2 Moving part
5 Extended terminals
1SDC21034CF0001
7 Transmission unit
5/51
1SDC210033D0201
Overall dimensions
Tmax XT2 - Accessories for withdrawable circuit-breaker
1SDC21020DF0001
Caption
1SDC21019DF0001
1 Fixed part
2 Moving part
5 Extended terminals
5/52
1SDC210033D0201
Front for lever operating (FLD)
1SDC21032CF0001
1SDC21033CF0001
Caption
1 Fixed part
2 Moving part
5 Extended terminals
A
6 Key lock optional
Front for lever operating FLD III - IV 170
5/53
1SDC210033D0201
Overall dimensions
Tmax XT2 - Accessories for withdrawable circuit-breaker
Caption
1 Fixed part
2 Moving part
6 Residual current
7 Extended terminals
5/54
1SDC210033D0201
Overall dimensions
Tmax XT3 - Installation for fixed circuit-breaker
Fixing on sheet
Caption
1SDC21047CF0001
With standard flange III - IV 74
III - IV 71
Without flange
III - IV 79
Caption
5/55
1SDC210033D0201
Overall dimensions
Tmax XT3 - Installation for fixed circuit-breaker
1SDC21069CF0001
3 POLES 4 POLES
Flanges
Caption
7 Optional flange
1SDC21074CF0001
5/56
1SDC210033D0201
Drilling templates compartment door
1SDC21071CF0001
1SDC21072CF0001
3 POLES 4 POLES
Without flange
1SDC21073CF0001
3 POLES 4 POLES 3-4 POLES
3-4 POLES
5/57
1SDC210033D0201
Overall dimensions
Tmax XT3 - Terminals for fixed circuit-breaker
Terminals F
Caption
1SDC21049CF0001
Terminals EF
Caption
1SDC21050CF0001
Terminals ES
Caption
5/58
1SDC210033D0201
1x70...185mm2 terminals FCCuAl
Caption
1 1x70...185mm 2 terminals
FCCuAl
1SDC21004FF0001
standard with the circuit-breaker
1SDC21005FF0001
Caption
2 2x35...150mm 2 terminals
FCCuAl
4 P ro v i d e d re a r i n s u l a t e d
plate (mandatory for CuAl
2x150mm2 cables)
5/59
1SDC210033D0201
Overall dimensions
Tmax XT3 - Terminals for fixed circuit-breaker
Terminals FCCu
Caption
1SDC21006FF0001
Terminals MC
Caption
5/60
1SDC210033D0201
Terminals R
Caption
1SDC21053CF0001
3 POLES 4 POLES
5/61
1SDC210033D0201
Overall dimensions
Tmax XT3 - Accessories for fixed circuit-breaker
1SDC21059CF0001
Caption
5/62
1SDC210033D0201
Rotary handle operating mechanism on the compartment door (RHE)
1SDC21058CF0001
heights for door with minimum distance
Caption
5 Transmission unit
5/63
1SDC210033D0201
Overall dimensions
Tmax XT3 - Accessories for fixed circuit-breaker
1SDC21064CF0001
1SDC21066CF0001
Caption
5/64
1SDC210033D0201
RC Inst and RC Sel residual current release for 3 poles circuit-breaker
Caption
1SDC21061CF0001
A
With standard flange III 74
Without flange III 71
5/65
1SDC210033D0201
Overall dimensions
Tmax XT3 - Accessories for fixed circuit-breaker
Caption
1SDC21062CF0001
A
With standard flange IV 74
Without flange IV 71
5/66
1SDC210033D0201
Overall dimensions
Tmax XT3 - Installation for plug-in circuit-breaker
Caption
1 Fixed part
2 Moving part
1SDC21054CF0001
Fixing at 50mm A
With standard flange III - IV 124
III - IV 121
Without flange
III - IV 129
5/67
1SDC210033D0201
Overall dimensions
Tmax XT3 - Installation for plug-in circuit-breaker
3 POLES 4 POLES
1SDC21070CF0001
3 POLES 4 POLES
Flanges
Caption
7 Optional flange
1SDC21024DF0001
5/68
1SDC210033D0201
Drilling templates compartment door
3 POLES 4 POLES
1SDC21076CF0001
Without flange
1SDC21075CF0001
3 POLES 4 POLES 3-4 POLES
1SDC21067CF0001
3-4 POLES
5/69
1SDC210033D0201
Overall dimensions
Tmax XT3 - Terminals for plug-in circuit-breaker
Terminals EF
1SDC21055CF0001
FIXING AT 50mm FIXING AT 70mm
Caption
Terminals ES
1SDC21056CF0001
FIXING AT 50mm
Caption
5/70
1SDC210033D0201
1x70...185mm2 terminals FCCuAl
Caption
1SDC21025DF0001
2x35...150mm2 terminals FCCuAl
Caption
5/71
1SDC210033D0201
Overall dimensions
Tmax XT3 - Terminals for plug-in circuit-breaker
Terminals FCCu
Caption
1SDC21008FF0001
Terminals MC
Caption
1SDC21008FF0001
5/72
1SDC210033D0201
Terminals HR/VR
1SDC21057CF0001
5/73
1SDC210033D0201
Overall dimensions
Tmax XT3 - Accessories for plug-in circuit-breaker
FIXING AT 50mm
1SDC21065CF0001
Caption
1 Fixed part
2 Moving part
5/74
1SDC210033D0201
Overall dimensions
Tmax XT4 - Installation for fixed circuit-breaker
Fixing on sheet
Caption
A
With standard flange III - IV 86
1SDC21033DF0001
III - IV 83.5
Without flange
III - IV 91.5
Caption
1SDC21034DF0001
3 POLES 4 POLES
5/75
1SDC210033D0201
Overall dimensions
Tmax XT4 - Installation for fixed circuit-breaker
Flanges
Caption
8 Optional flange
1SDC21036DF0001
5/76
1SDC210033D0201
Drilling templates compartment door
1SDC21037DF0001
3 POLES 4 POLES
Without flange
1SDC21038DF0001
3-4 POLES
3 POLES 4 POLES
3-4 POLES
5/77
1SDC210033D0201
Overall dimensions
Tmax XT4 - Terminals for fixed circuit-breaker
Terminals F
Caption
1SDC21040DF0001
Terminals EF
Caption
5/78
1SDC210033D0201
Terminals ES
1SDC21042DF0001
Caption
Caption
1 1x1...185mm2 terminals
FCCuAl
5/79
1SDC210033D0201
Overall dimensions
Tmax XT4 - Terminals for fixed circuit-breaker
1SDC21044DF0001
Caption
2 2x35...150mm 2 terminals
FCCuAl
5 P ro v i d e d re a r i n s u l a t e d
plate (mandatory for CuAl
2x150mm2 cables)
5/80
1SDC210033D0201
Terminals FCCu
Caption
1 Terminals FCCu
1SDC21045DF0001
Terminals MC
Caption
2 Multicable terminals
1SDC21046DF0001
5/81
1SDC210033D0201
Overall dimensions
Tmax XT4 - Terminals for fixed circuit-breaker
Terminals R
Caption
1SDC21047DF0001
3 POLES 4 POLES
5/82
1SDC210033D0201
Overall dimensions
Tmax XT4 - Accessories for fixed circuit-breaker
Caption
1SDC21048DF0001
5/83
1SDC210033D0201
Overall dimensions
Tmax XT4 - Accessories for fixed circuit-breaker
Caption
5 Transmission unit
5/84
1SDC210033D0201
Stored energy motor operator (MOE)
Caption
5/85
1SDC210033D0201
Overall dimensions
Tmax XT4 - Accessories for fixed circuit-breaker
Caption
5/86
1SDC210033D0201
Residual current RC Sel
1SDC21052DF0001
Caption
1 Residual current
2 Front terminals
5/87
1SDC210033D0201
Overall dimensions
Tmax XT4 - Installation for plug-in circuit-breaker
Fixing on sheet
Caption
1 Fixed part
2 Moving part
1SDC21053DF0001
Fixing at 50mm A
With standard flange III - IV 136
III - IV 133.5
Without flange
III - IV 141.5
5/88
1SDC210033D0201
Drilling templates for support sheet
3 POLES 4 POLES
1SDC21054DF0001
3-4 POLES
5/89
1SDC210033D0201
Overall dimensions
Tmax XT4 - Installation for plug-in circuit-breaker
Flanges
Caption
8 Optional flange
1SDC21055DF0001
5/90
1SDC210033D0201
Drilling templates compartment door
1SDC21056DF0001
3 POLES 4 POLES
Without flange
1SDC21057DF0001
3-4 POLES
3 POLES 4 POLES
B=142 C=162
3 - POLES
3-4 4 POLI
5/91
1SDC210033D0201
Overall dimensions
Tmax XT4 - Terminals for plug-in circuit-breaker
Terminals EF
1SDC21059DF0001
FIXING AT 50mm FIXING AT 70mm
Caption
Terminals ES
1SDC21060DF0001
FIXING AT 50mm
Caption
5/92
1SDC210033D0201
1x1...185mm2 terminals FCCuAl
Caption
1SDC21061DF0001
FIXING AT 50mm
Caption
1SDC21026FF0001
Terminals FCCu
Caption
5 Terminals FCCu
FIXING AT 50mm
5/93
1SDC210033D0201
Overall dimensions
Tmax XT4 - Terminals for plug-in circuit-breaker
Terminals MC
Caption
4 Multicable terminals
1SDC21063DF0001
FIXING AT 50mm
Terminals HR/VR
Caption
5/94
1SDC210033D0201
Overall dimensions
Tmax XT4 - Accessories for plug-in circuit-breaker
1SDC21065DF0001
Caption
1 Fixed part
2 Moving part
8 Extended terminals
5/95
1SDC210033D0201
Overall dimensions
Tmax XT4 - Accessories for plug-in circuit-breaker
1SDC21066DF0001
Caption
1 Fixed part
2 Moving part
5/96
1SDC210033D0201
Residual current RC Sel
1SDC21067DF0001
Caption
1 Residual current
3 Fixed part
4 Moving part
6 Extended terminals
5/97
1SDC210033D0201
Overall dimensions
Tmax XT4 - Installation for withdrawable circuit-breaker
Fixing on sheet
ISOLATING DISTANCE
1SDC21068DF0001
Caption
1 Fixed part
2 Moving part
5/98
1SDC210033D0201
Drilling templates for support sheet
3 POLES 4 POLES
1SDC21069DF0001
3-4 POLES
Flanges
Caption
C D
1SDC21070DF0001
5/99
1SDC210033D0201
Overall dimensions
Tmax XT4 - Installation for withdrawable circuit-breaker
1SDC21071DF0001
3 POLES 4 POLES
Without flange
3-4 POLES
1SDC21072DF0001
3 POLES 4 POLES
B=142 C=162
3 - POLES
3-4 4 POLI
5/100
1SDC210033D0201
Overall dimensions
Tmax XT4 - Terminals for withdrawable circuit-breaker
Terminals EF
1SDC21074DF0001
FIXING AT 70mm FIXING AT 50mm
Caption
5/101
1SDC210033D0201
Overall dimensions
Tmax XT4 - Terminals for withdrawable circuit-breaker
Terminals ES
1SDC21075DF0001
FIXING AT 50 mm
Caption
FIXING AT 50 mm
5/102
1SDC210033D0201
2x35...150mm2 terminals FCCuAl
Caption
1SDC21077DF0001
1 2x35...150mm 2 terminals
FCCuAl 3 POLES 4 POLES
2 Terminal covers with degree
of protection IP40 (optional)
provided
3 P ro v i d e d re a r i n s u l a t e d
plate (mandatory for CuAl
2x150mm2 cables)
5/103
1SDC210033D0201
Overall dimensions
Tmax XT4 - Terminals for withdrawable circuit-breaker
Terminals FCCu
Caption
2 Terminale FCCu
1SDC21078DF0001
standard with the circuit-breaker
FIXING AT 50 mm
Terminals MC
Caption
1 Multicable terminals
FIXING AT 50 mm
5/104
1SDC210033D0201
Terminals HR/VR
FIXING AT 50 mm FIXING AT 50 mm
1SDC21080DF0001
Caption
5/105
1SDC210033D0201
Overall dimensions
Tmax XT4 - Accessories for withdrawable circuit-breaker
Caption
1SDC21081DF0001
1 Fixed part
2 Moving part
6 Extended terminals
5/106
1SDC210033D0201
Stored energy motor operator (MOE)
1SDC21082DF0001
Caption
1 Fixed part
2 Moving part
6 Extended terminals
5/107
1SDC210033D0201
Overall dimensions
Tmax XT4 - Accessories for withdrawable circuit-breaker
Caption
1 Fixed part
2 Moving part
6 Residual current
7 Extended terminals
5/108
1SDC210033D0201
Overall dimensions
Distances to be respected
A B C
Un≤440V
(mm) (mm) (mm)
XT1 25 20 20
XT2 30 20 25
XT3 50 20 20
XT4 30 20 25
A B C
Un>440V
(mm) (mm) (mm)
XT1 25 20 20
XT2 50 20 45
XT3 50 20 20
XT4 50 20 45
H
(mm)
XT1 80
XT2 120
XT3 140
XT4 160
Caption
5/109
1SDC210033D0201
Wiring Diagrams
Index
Information on how to read the diagrams ...............................................................................6/2
Resetting instructions............................................................................................................6/19
6/1
1SDC210033D0201
Wiring Diagrams
Information on how to read the diagrams
6/2
1SDC210033D0201
Wiring Diagrams
Graphic symbols (IEC 60617 and CEI 3-14 …3-26 Standards)
Electromagnetic effect Connection of conductors Changeover contact with Overcurrent release with
momentary break short inverse adjustable
time delay characteristic
Mechanical connection Socket and plug Opening position contact Overcurrent release for
(female and male) (limit switch) earth fault with short
inverse time characteristic
Manual mechanical Resistor (general symbol) Changeover contact Current relay for
operating mechanism with momentary break unbalance between
(general case) (limit switch) phases
Pushbutton operating Motor (general symbol) Power cut-off of switch- Relay for detecting lack
mechanism disconnector power with of phase in a three-phase
automatic opening system
Ground Current transformer with pri- Thermal trip unit Motor with excitation
mary consisting of 4 passing
(general symbol) conductors and with wound in series
secondary, with socket M
Conductors in shielded
cable (example two
conductors)
6/3
1SDC210033D0201
Wiring Diagrams of the circuit-breakers
State of operation
1SDC21084DF0001
1SDC21085DF0001
1SDC21086DF0001
Four-pole circuit-breaker with Four-pole circuit-breaker with Four-pole circuit-breaker with
thermomagnetic trip unit and RC Sel 200 thermomagnetic trip unit and electronic trip unit and RC Sel
or RC B type residual current release RC Sel residual current release residual current release
1SDC21087DF0001
1SDC21088DF0001
6/4
1SDC210033D0201
Description of Figures
Fig. 47 = Current transformer circuit on the neutral conductor outside the circuit-breaker (for plug-in or with-
drawable version circuit-breaker).
Notes
G) In the case of a three-pole fixed version circuit-breaker with a current transformer on the neutral
conductor outside the circuit-breaker, when you want to remove the circuit-breaker it is necessary
to short-circuit the terminals of the TI/N transformer.
Caption
= Diagram figure number
* = See the note indicated by the letter
J.. = Connectors for the auxiliary contacts of the withdrawable version circuit-breaker; extraction of the
connectors takes place at the same time as that of the circuit-breaker.
K51 = Electronic trip unit:
– of overcurrent type Ekip LS/I, Ekip N-LS/I, Ekip LSI, Ekip LSIG
– of motor protection type Ekip I, Ekip M-LIU, Ekip M-LRIU
– of generator protection Ekip G-LSI
K87 = Residual current release type RC Inst, RC Sel, RC Sel 200, RC B Type
Q = Main circuit-breaker
S75I/1..4 = Contacts for electrical signalling of circuit-breaker in the connected position (only provided with plug-
in or withdrawable version circuit-breakers)
S75S/1-2 = Contacts for electrical signalling of circuit-breaker in the racked-out position (only provided with
withdrawable version circuit-breakers)
SD = Power supply switch-disconnector of the residual current release type RC Inst, RC Sel, RC Sel 200
or RC B Type
TI = Toroidal current transformer
TI/L1 = Current transformer placed on phase L1
TI/L2 = Current transformer placed on phase L2
TI/L3 = Current transformer placed on phase L3
TI/N = Current transformer placed on the neutral
V1 = Circuit-breaker applications
X41 = Circuit connector for external neutral
XG-XH = Electronic trip unit connectors
XV = Terminal boxes of the circuit-breaker applications
YO1 = Opening solenoid of the overcurrent release
YO2 = Opening solenoid of the residual current release
6/5
1SDC210033D0201
Wiring Diagrams of the circuit-breakers
State of operation
1SDC21090DF0001
1SDC21089DF0001
1SDC21091DF0001
Three-pole or four-pole circuit- Three-pole circuit-breaker Three-pole or four-pole XT1D,
breaker with TMD, TMA or TMG with MA magnetic trip unit XT3D or XT4D
thermomagnetic trip unit switch-disconnector
1SDC21092DF0001
1SDC21093DF0001
1SDC21094DF0001
Three-pole or four-pole circuit-breaker Three-pole or four-pole circuit-breaker Four-pole circuit-breaker with
with Ekip LS/I or Ekip G-LSI with Ekip I, Ekip LSI or Ekip LSIG Ekip N-LS/I electronic trip unit
electronic trip unit electronic trip unit
1SDC21095DF0001
1SDC21096DF0001
6/6
1SDC210033D0201
Caption
= Diagram figure number
* = See the note indicated by the letter
K51 = Electronic trip unit:
– of overcurrent type Ekip LS/I, Ekip N-LS/I, Ekip LSI, Ekip LSIG
– of motor protection type Ekip I, Ekip M-LIU, Ekip M-LRIU
– of generator protection type Ekip G-LSI
K87 = Residual current release type RC Inst, RC Sel, RC Sel 200, RC B Type
Q = Main circuit-breaker
SD = Power supply switch-disconnector of the residual current release type RC Inst, RC Sel, RC Sel 200
or RC B Type
TI = Toroidal current transformer
TI/L1 = Current transformer placed on phase L1
TI/L2 = Current transformer placed on phase L2
TI/L3 = Current transformer placed on phase L3
TI/N = Current transformer placed on the neutral
YO1 = Opening solenoid of the overcurrent release
YO2 = Opening solenoid of the residual current release
6/7
1SDC210033D0201
Wiring Diagrams of the accessories
Service releases
1SDC21097DF0001
Description of Figures
Fig. 1 = Shunt opening release.
Fig. 2 = Supplementary shunt opening release (only for four-pole circuit-breakers).
Fig. 3 = Permanent shunt opening release.
Fig. 4 = Supplementary permanent shunt opening release (only for four-pole circuit-breakers).
Fig. 5 = Instantaneous undervoltage release (see Notes B and F).
Fig. 6 = Undervoltage release with electronic time delay device outside the circuit-breaker, see note B).
Notes
B) The undervoltage release is supplied for power supply branched on the supply side of the circuit-
breaker or from an independent source: closing is only possible with the release energised (the lock
on closing is made mechanically).
F) Additional external resistor for undervoltage supplied at 380/440V AC and 480/525V AC.
Caption
= Diagram figure number
* = See the note indicated by the letter
D = Undervoltage release electronic time delay device (outside the circuit-breaker) (only for voltages up
to 250V)
J.. = Connectors for the auxiliary contacts of the withdrawable version circuit-breaker; extraction of the
connectors takes place at the same time as that of the circuit-breaker
Q/0..7 = Circuit-breaker auxiliary contacts
R = Resistor (see note F)
SO = Pushbutton or contact for opening the circuit-breaker
V1 = Circuit-breaker applications
V4 = Indicative apparatus and connections for control and signalling, outside the circuit-breaker
XB.. = Three-way connector for the plug-in version circuit-breaker auxiliary circuits
XV = Terminal boxes of the circuit-breaker applications
YO = Shunt opening release
YU = Undervoltage release (see note B)
6/8
1SDC210033D0201
Service releases
1SDC21098DF0001
Description of Figures
Fig. 7 = Instantaneous undervoltage release in the version for machine tools with one contact in series (see
notes B, C and F).
Fig. 8 = Instantaneous undervoltage release in the version for machine tools with two contacts in series (see
Notes B, C and F).
Fig. 11 = One changeover contact for electrical signalling of circuit-breaker open due to tripping of the residual
current release type RC Inst, RC Sel, RC B Type or RC Sel 200.
Fig. 12 = Residual current release circuits type RC Sel, RC B or RC Sel 200.
Fig. 13 = Two contacts for electrical signalling of residual current release pre-alarm and alarm type RC Sel,
RC B or RC Sel 200.
Notes
B) The undervoltage release is supplied for power supply branched on the supply side of the circuit-
breaker or from an independent source: closing is only possible with the release energised (the lock
on closing is made mechanically).
C) Contacts S4/1 and S4/2 shown in figures 7-8 open the circuit with the circuit-breaker open and
reclose it when a manual closing command is given by means of the rotary handle, in accordance
with the Standards regarding machine tools (in any case closing does not take place if the undervolt-
age release is not supplied).
F) Additional external resistor for undervoltage supplied at 380/440V AC and 480/525V AC.
Caption
= Diagram figure number
* = See the note indicated by the letter
J.. = Connectors for the auxiliary contacts of the withdrawable version circuit-breaker; extraction of the
connectors takes place at the same time as that of the circuit-breaker
K87 = Residual current release type RC Inst, RC Sel, RC Sel 200, RC B Type
R = Resistor (see note F)
S4/1-2 = Early auxiliary contacts activated by the rotary handle of the circuit-breaker (see note C)
S87/1 = Contact for electrical signalling of pre-alarm of the residual current release type RC Sel, RC B or RC
Sel 200
S87/2 = Contact for electrical signalling of alarm of the residual current release type RC Sel, RC B or RC Sel 200
S87/3 = Contact for electrical signalling of circuit-breaker open due to tripping of the residual current release
type RC Sel, RC B or RC Sel 200
SO = Pushbutton or contact for opening the circuit-breaker
V1 = Circuit-breaker applications
V4 = Indicative apparatus and connections for control and signalling, outside the circuit-breaker
XB.. = Three-way connector for the plug-in version circuit-breaker auxiliary circuits
XC.. = Six-way connector for the plug-in version circuit-breaker auxiliary contacts
XV = Terminal boxes of the circuit-breaker applications
YU = Undervoltage release (see note B)
6/9
1SDC210033D0201
Wiring Diagrams of the accessories
Motor operator
1SDC21099DF0001
Description of Figures
Fig. 21 = Motor operator with direct action (MOD) (only for fixed or plug-in version circuit-breakers XT1 and
XT3).
Fig. 22 = Motor operator with stored energy (MOE) (only for circuit-breakers XT2 and XT4).
Fig. 23 = A contact for electrical signalling of stored energy motor operator that can be operated remotely.
Caption
= Diagram figure number
* = See the note indicated by the letter
A17 = Actuator unit type MOE for the stored energy motor operator
H2 = Signalling lamp for stored energy motor operator blocked
J.. = Connectors for the auxiliary contacts of the withdrawable version circuit-breaker; extraction of the
connectors takes place at the same time as that of the circuit-breaker
M = Motor with excitation in series for opening and closing the circuit-breaker (fig. 21)
M = Motor for opening the circuit-breaker and spring charging for closing the circuit-breaker (fig. 22)
M1 = Three-phase asynchronous motor
R1 = Motor thermistor
S1 = Contact controlled by the cam of the motor operator
S2 = Contact controlled by the key lock of the motor operator with direct action
S3/1-2 = Contacts controlled by the Auto/Manual selector and key lock of the stored energy motor operator
S4 = Contact controlled by the cam of the motor operator with direct action
S6/1-2 = Contacts controlled by the Auto/Manual selector of the motor operator with direct action
SC = Pushbutton or contact for closing the circuit-breaker
SO = Pushbutton or contact for opening the circuit-breaker
V2 = Motor operator applications
V4 = Indicative apparatus and connections for control and signalling, outside the circuit-breaker
XD.. = Nine-way connector for the auxiliary circuits of the plug-in version circuit-breaker
XV = Terminal boxes of the circuit-breaker applications
YC = Shunt closing release of the stored energy motor operator
6/10
1SDC210033D0201
Signalling contacts
1SDC21000EF0001
Description of Figures
Fig. 31 = One changeover contact for electrical signalling of circuit-breaker open or closed and one changeover
contact for electrical signalling of circuit-breaker open due to tripping of the magnetic, thermomagnetic
or electronic trip units, YO, YO1, YO2, YU (tripped position) (only for voltages up to 250V) (see note E).
Fig. 32 = Two changeover contacts for electrical signalling of circuit-breaker open or closed, two changeover
contacts for electrical signalling of circuit-breaker open due to tripping of the magnetic, thermomag-
netic or electronic trip units, YO, YO1, YO2, YU (tripped position) and one changeover contact for
electrical signalling of circuit-breaker open due to tripping of the thermomagnetic or electronic trip
unit (only for voltages up to 250V).
Fig. 33 = Three changeover contacts for electrical signalling of circuit-breaker open or closed and two
changeover contacts for electrical signalling of circuit-breaker open due to tripping of the magnetic,
thermomagnetic or electronic trip units, YO, YO1, YO2, YU (tripped position) (only for voltages up to
250V).
Notes
E) The 24V auxiliary power supply unit of fig. 48 must necessarily be installed in the circuit-breaker seats
marked SY/1 and Q/2. Therefore, should you want to install the unit in fig. 48 and the contacts in fig.
31 at the same time, the contacts of fig. 31 must be installed in the adjacent slots; that is, contact
SY/1 in the slot marked SY/2 and contact Q/2 in the slot marked Q/1.
Caption
= Diagram figure number
* = See the note indicated by the letter
J.. = Connectors for the auxiliary contacts of the withdrawable version circuit-breaker; extraction of the
connectors takes place at the same time as that of the circuit-breaker
Q/0..3 = Circuit-breaker auxiliary contacts
S51 = Contact for electrical signalling of circuit-breaker open due to tripping of the thermomagnetic or
electronic trip unit
SY/1..2 = Contacts for electrical signalling of circuit-breaker open due to tripping of the thermomagnetic trip
units, YO, YO1, YO2, YU (tripped position)
V1 = Circuit-breaker applications
V4 = Indicative apparatus and connections for control and signalling, outside the circuit-breaker
XC.. = Six-way connector for the plug-in version circuit-breaker auxiliary contacts
XD.. = Nine-way connector for the auxiliary circuits of the plug-in version circuit-breaker
XE.. = Fifteen-way connector for the auxiliary circuits of the plug-in version circuit-breaker
XV = Terminal boxes of the circuit-breaker applications
6/11
1SDC210033D0201
Wiring Diagrams of the accessories
Signalling contacts
1SDC21001EF0001
Description of Figures
Fig. 34 = Three changeover contacts for electrical signalling of circuit-breaker open and one changeover contact
for electrical signalling of circuit-breaker open due to tripping of the magnetic, thermomagnetic or
electronic trip units, YO, YO1, YO2, YU (tripped position) (only for voltages up to 250V).
Fig. 35 = One changeover contact for electrical signalling of circuit-breaker open due to tripping of the ther-
momagnetic electronic trip unit (only for voltages up to 250V).
Fig. 36 = Two changeover contacts for electrical signalling of circuit-breaker open or closed and one changeover
contact for electrical signalling of circuit-breaker open due to tripping of the magnetic, thermomagnetic
or electronic trip units, YO, YO1, YO2, YU (tripped position) (only for voltages up to 250V).
Fig. 37 = One changeover contact for electrical signalling of circuit-breaker open or closed and one changeover
contact for electrical signalling of circuit-breaker open due to tripping of the magnetic, thermomagnetic
or electronic trip units, YO, YO1, YO2, YU (tripped position) (only for voltage up to 400V).
Fig. 38 = Two changeover contacts for electrical signalling of circuit-breaker open or closed (only for voltage
up to 400V).
Caption
= Diagram figure number
* = See the note indicated by the letter
J.. = Connectors for the auxiliary contacts of the withdrawable version circuit-breaker; extraction of the
connectors takes place at the same time as that of the circuit-breaker
Q/0..3 = Circuit-breaker auxiliary contacts
S51 = Contact for electrical signalling of circuit-breaker open due to tripping of the thermomagnetic or
electronic trip unit
SY/1 = Contacts for electrical signalling of circuit-breaker open due to tripping of the thermomagnetic trip
units, YO, YO1, YO2, YU (tripped position)
V1 = Circuit-breaker applications
V4 = Indicative apparatus and connections for control and signalling, outside the circuit-breaker
XB.. = Three-way connector for the plug-in version circuit-breaker auxiliary circuits
XC.. = Six-way connector for the plug-in version circuit-breaker auxiliary contacts
XD.. = Nine-way connector for the auxiliary circuits of the plug-in version circuit-breaker
XE.. = Fifteen-way connector for the auxiliary circuits of the plug-in version circuit-breaker
XV = Terminal boxes of the circuit-breaker applications
6/12
1SDC210033D0201
Signalling contacts
104 102 114 112 124 122 134 132 142 144 152 154
104
102
114
112
124
122
134
132
142
144
152
154
101
111
121
131
141
151
101 111 121 131 141 151
1SDC21002EF0001
Description of Figures
Fig. 39 = Three supplementary changeover contacts for electrical signalling of circuit-breaker open or closed
(only for fixed or plug-in version circuit-breakers).
Fig. 41 = First changeover position contact of the circuit-breaker, for electrical signalling of connected (only
for plug-in or withdrawable version circuit-breakers).
Fig. 42 = Second changeover position contact of the circuit-breaker, for electrical signalling of connected (only
for plug-in or withdrawable version circuit-breakers).
Fig. 43 = Third changeover position contact of the circuit-breaker, for electrical signalling of connected(only
for plug-in or withdrawable version circuit-breakers).
Fig. 44 = Fourth changeover position contact of the circuit-breaker, for electrical signalling of connected (only
for plug-in or withdrawable version circuit-breakers).
Fig. 45 = First changeover position contact of the circuit-breaker, for electrical signalling of isolated (only for
withdrawable version circuit-breakers).
Fig. 46 = Second changeover position contact of the circuit-breaker, for electrical signalling of isolated (only
for withdrawable version circuit-breakers).
Fig. 48 = Auxiliary circuits of the 24V auxiliary power supply unit (see note E).
Notes
E) The 24V auxiliary power supply unit of fig. 48 must necessarily be installed in the circuit-breaker seats
marked SY/1 and Q/2. Therefore, should you want to install the unit in fig. 48 and the contacts in fig. 31
at the same time, the contacts of fig. 31 must be installed in the adjacent slots; that is, contact SY/1 in
the slot marked SY/2 and contact Q/2 in the slot marked Q/1.
Caption
= Diagram figure number
* = See the note indicated by the letter
J.. = Connectors for the auxiliary contacts of the withdrawable version circuit-breaker; extraction of the
connectors takes place at the same time as that of the circuit-breaker
K51 = Electronic trip unit:
– of overcurrent type Ekip LS/I, Ekip N-LS/I, Ekip LSI, Ekip LSIG
– of motor protection type Ekip I, Ekip M-I, Ekip M-LIU, Ekip M-LRIU
– of generator protection type Ekip G-LSI
Q/0..7 = Circuit-breaker auxiliary contacts
S75I/1..4 = Contacts for electrical signalling of circuit-breaker in connected position (only provided with plug-in
or withdrawable version circuit-breakers)
S75E/1-2 = Contacts for electrical signalling of circuit-breaker in racked-out position (only provided with with-
drawable version circuit-breakers)
V1 = Circuit-breaker applications
V4 = Indicative apparatus and connections for control and signalling, outside the circuit-breaker
WI = Serial interface with the trip unit accessories
X3 = Connector of the circuit for the 24V auxiliary power supply unit
XD.. = Nine-way connector for the auxiliary circuits of the plug-in version circuit-breaker
XV = Terminal boxes of the circuit-breaker applications
A18 = 24V auxiliary power supply unit (See note E)
XH1 = Electronic trip unit contacts
6/13
1SDC210033D0201
Wiring Diagrams of the accessories
1SDC21003EF0001
Description of Figures
Fig. 51 = Auxiliary circuits of the electronic trip unit type Ekip LSI, Ekip LSIG or Ekip MLRIU connected to display
unit type Ekip Display (display) or Ekip LED Meter (current display).
Caption
= Diagram figure number
A11 = Display unit type Ekip Display (display) or Ekip LED Meter (current display)
K51 = Electronic trip unit:
– of overcurrent type Ekip LSI, Ekip LSIG
– of motor protection type Ekip M-LRIU
Q = Main circuit-breaker
TI/L1 = Current transformer placed on phase L1
TI/L2 = Current transformer placed on phase L2
TI/L3 = Current transformer placed on phase L3
TI/N = Current transformer placed on the neutral
YO1 = Opening solenoid of the overcurrent release
6/14
1SDC210033D0201
Electronic trip unit Ekip LSI, Ekip LSIG or Ekip M-LRIU connected
to interface unit Ekip Com and with signalling unit LD030 DO
1SDC21004EF0001
Description of Figures
Fig. 52 = Auxiliary circuits of the electronic trip unit type Ekip LSI, Ekip LSIG or Ekip M-LRIU connected to
interface unit type Ekip Com and with signalling unit type LD030 DO.
Caption
= Diagram figure number
A12 = Interface unit type Ekip Com (with MODBUS serial communication)
A13 = Signalling unit type LD030 DO
K51 = Electronic trip unit:
– of overcurrent type Ekip LSI, Ekip LSIG
– of motor protection type Ekip M-LRIU
Q = Main circuit-breaker
Q/0..7 = Circuit-breaker auxiliary contacts
SY/1..3 = Contacts for electrical signalling of circuit-breaker open due to tripping of the thermomagnetic trip
units, YO, YO1, YO2, YU (tripped position)
TI/L1 = Current transformer placed on phase L1
TI/L2 = Current transformer placed on phase L2
TI/L3 = Current transformer placed on phase L3
TI/N = Current transformer placed on the neutral
WI = Serial interface with the trip unit accessories
WS = Serial interface with the control system (MODBUS EIA RS485 interface)
XF = Connector of the Interface unit type Ekip Com
XG-XH = Electronic trip unit connectors
XV = Terminal boxes of the circuit-breaker applications
YO1 = Opening solenoid of the overcurrent release
6/15
1SDC210033D0201
Wiring Diagrams of the accessories
Electronic trip unit Ekip LSI, Ekip LSIG or Ekip M-LRIU connected
to interface unit Ekip Com and with actuator unit type MOE-E for
the stored energy motor operator
1SDC21005EF0001
Description of Figures
Fig. 23 = One Contact for electrical signalling of stored energy motor operator that can be operated remotely.
Fig. 53 = Auxiliary circuits of the electronic trip unit type Ekip LSI, Ekip LSIG or Ekip M-LRIU connected to
interface unit type Ekip Com and with actuator unit type MOE-E for the stored energy motor operator.
Caption
= Diagram figure number
A12 = Interface unit type Ekip Com (with MODBUS serial communication)
A14 = Actuator unit type MOE-E for the stored energy motor operator
H2 = Signalling lamp for blocked stored energy motor operator
J.. = Connectors for the auxiliary contacts of the withdrawable version circuit-breaker; extraction of the
connectors takes place at the same time as that of the circuit-breaker
K51 = Electronic trip unit:
– of overcurrent type Ekip LSI, Ekip LSIG
– of motor protection type Ekip M-LRIU
M = Motor with excitation in series for opening and closing the circuit-breaker (fig. 21)
Q = Main circuit-breaker
Q/0..7 = Circuit-breaker auxiliary contacts
S1 = Contact controlled by the cam of the motor operator
S3/1-2 = Contacts controlled by the Auto/Manual selector and key lock of the stored energy motor operator
SC = Pushbutton or contact for closing the circuit-breaker
SO = Pushbutton or contact for opening the circuit-breaker
SY/1..3 = Contacts for electrical signalling of circuit-breaker open due to tripping of the thermomagnetic trip
units, YO, YO1, YO2, YU (tripped position)
TI = Toroidal current transformer
TI/L1 = Current transformer placed on phase L1
TI/L2 = Current transformer placed on phase L2
TI/L3 = Current transformer placed on phase L3
TI/N = Current transformer placed on the neutral
WI = Serial interface with the trip unit accessories
WS = Serial interface with the control system (MODBUS EIA RS485 interface)
XC.. = Six-way connector for the plug-in version circuit-breaker auxiliary contacts
XD.. = Nine-way connector for the auxiliary circuits of the plug-in version circuit-breaker
XF = Connector of the Interface unit type Ekip Com
XG-XH = Electronic trip unit connectors
XV = Terminal boxes of the circuit-breaker applications
YC = Shunt closing release of the stored energy motor operator
YO1 = Opening solenoid of the overcurrent release
6/16
1SDC210033D0201
Auxiliary circuits of the electronic trip unit Ekip M-LRIU
connected to the contactor control unit for starting the motor
PR212/CI (the circuit to the motor thermistor is optional)
X5 W5 JL3 W5 2
X5 W6 JH1 W6 7
X5 W7 JH1 W7 9
X5 W8 JL3 W8 12
1SDC21006EF0001
Description of Figures
Fig. 54 = Auxiliary circuits of the electronic trip unit type Ekip M-LRIU connected to the contactor control unit
for starting the motor type PR212/CI (the circuit to the motor thermistor is optional).
Fig. 62 = Motor thermistor circuit.
Caption
= Diagram figure number
A15 = Contactor control unit for starting the motor type PR212/CI
H1 = Signalling lamp
J.. = Connectors for the auxiliary contacts of the withdrawable version circuit-breaker; extraction of the
connectors takes place at the same time as that of the circuit-breaker
K = Contactor for starting the motor
K51 = Electronic trip unit Ekip M-LRIU
M1 = Three-phase asynchronous motor
Q = Main circuit-breaker
R1 = Motor thermistor
SC3 = Pushbutton for starting the motor
SO3 = Pushbutton for stopping the motor
TI/L1 = Current transformer placed on phase L1
TI/L2 = Current transformer placed on phase L2
TI/L3 = Current transformer placed on phase L3
X42 = Circuit connector for the motor thermistor
X5 = Circuit connector towards PR212/CI unit
XG-XH = Electronic trip unit connectors
YO1 = Opening solenoid of the overcurrent release
6/17
1SDC210033D0201
Wiring Diagrams of the accessories
X5 W5 JL3 W5 2
X5 W6 JH1 W6 7
X5 W7 JH1 W7 9
X5 W8 JL3 W8 12
1SDC21007EF0001
Description of Figures
Fig. 55 = Auxiliary circuits of the electronic trip unit type Ekip M-LRIU connected to the contactor control unit
for starting the motor type PR212/CI and with ABB AF series contactor (the circuit to the motor
thermistor is optional).
Fig. 62 = Motor thermistor circuit.
Caption
= Diagram figure number
A15 = Contactor control unit for starting the motor type PR212/CI
H1 = Signalling lamp
J.. = Connectors for the auxiliary contacts of the withdrawable version circuit-breaker; extraction of the
connectors takes place at the same time as that of the circuit-breaker
K = Contactor for starting the motor
K51 = Electronic trip unit Ekip M-LRIU
M1 = Three-phase asynchronous motor
Q = Main circuit-breaker
R1 = Motor thermistor
SC3 = Pushbutton for starting the motor
SO3 = Pushbutton for stopping the motor
TI/L1 = Current transformer placed on phase L1
TI/L2 = Current transformer placed on phase L2
TI/L3 = Current transformer placed on phase L3
X42 = Circuit connector for the motor thermistor
X5 = Circuit connector towards PR212/CI unit
XG-XH = Electronic trip unit connectors
YO1 = Opening solenoid of the overcurrent release
6/18
1SDC210033D0201
Resetting instructions
NB: If the magnetic, thermomagnetic or electronic trip unit is present, it is necessary to find the
causes which led to the circuit-breaker being in the tripped position so as to prevent reclosing under
short-circuit conditions. In all cases, manual resetting is always allowed.
6/19
1SDC210033D0201
Resetting instructions
1SDC21016EF0001
Caption
A17 = Actuator unit type MOE for the stored energy motor operator H2 = Signalling lamp for blocked stored
energy motor operator
J.. = Connectors for the auxiliary contacts of the withdrawable version circuit-breaker; extraction of the
connectors takes place at the same time as that of the circuit-breaker
KO = Auxiliary opening relay
M = Motor with excitation in series for opening and closing the circuit-breaker (fig. 21)
M = Motor for opening the circuit-breaker and spring charging for closing the circuit-breaker (fig. 22)
R1 = Motor thermistor
S1 = Contact controlled by the cam of the motor operator
S2 = Contact controlled by the key lock of the motor operator with direct action
S3/1-2 = Contacts controlled by the Auto/Manual selector and key lock of the stored energy motor operator
S6/1-2 = Contacts controlled by the Auto/Manual selector of the motor operator with direct action
SC = Pushbutton or contact for closing the circuit-breaker
SO1,S02 = Pushbuttons or contacts for opening the circuit-breaker (see “Instructions for resetting the
circuit-breaker following release tripping”)
SY/1..3 = Contacts for electrical signalling of circuit-breaker open due to tripping of the thermomagnetic trip
units, YO, YO1, YO2, YU (tripped position)
V1 = Circuit-breaker applications
V2 = Motor operator applications
V4 = Indicative apparatus and connections for control and signalling, outside the circuit-breaker
XB.. = Three-way connector for the plug-in version circuit-breaker auxiliary circuits
XC.. = Six-way connector for the plug-in version circuit-breaker auxiliary contacts
XD.. = Nine-way connector for the auxiliary circuits of the plug-in version circuit-breaker
XV = Terminal boxes of the circuit-breaker applications
YC = Shunt closing release of the stored energy motor operator
6/20
1SDC210033D0201
Ordering codes
Index
Examples of ordering ............................................................................................................7/2
Circuit-breakers .......................................................................................................................7/4
Accessories .............................................................................................................................7/5
Circuit-breakers .....................................................................................................................7/12
Accessories ...........................................................................................................................7/19
Circuit-breakers .....................................................................................................................7/29
Accessories ...........................................................................................................................7/31
Circuit-breakers .....................................................................................................................7/38
Accessories ...........................................................................................................................7/45
7/1
1SDC210033D0201
Ordering codes
Examples of ordering
XT1B 160A 3p fixed with EF top and FCCuAl bottom terminals for 240mm2 cables
1SDA…R1
XT1B 160 TMD 160-1600 3p F F 066809
EF Extended front terminals 3 pieces 066865
FCCuAl Terminals for Copper/Aluminium cables 1x95...240mm2 3 pieces 067159
XT2N in plug-in version with SOR, AUX 1Q+1SY, connector on rear of panel
1SDA…R1
XT2N 160 TMA 160-1600 3p F F 067560
KIT P MP 066278
KIT P PF EF (Fixed part of plug-in with EF terminals) 068187
SOR-C 220-240V AC / 220-250V DC 066325
AUX-C 1Q+1SY 250V AC 066431
Socket plug connector for panel with 9PINS 066411
XT2N in plug-in version with SOR, AUX 1Q+1SY, connector on rear of circuit-breaker
1SDA…R1
XT2N 160 TMA 160-1600 3p F F 067560
KIT P MP 066278
KIT P PF EF (Fixed part of plug-in with EF terminals) 068187
SOR-C 220-240V AC / 220-250V DC 066325
AUX-C 1Q+1SY 250V 066431
SOCKET-PLUG CONNECTOR MP 12PINS XT2-XT4 066413
SOCKET-PLUG CONNECTOR FP 12PINS XT2-XT4 066414
7/2
1SDC210033D0201
EXAMPLE 3: Electrical accessories for withdrawable version
With the circuit-breakers in the withdrawable version it is necessary to only and exclusively order
the accessories dedicated to this version. The electrical accessories specified for the withdrawable
version are fitted both with the connector for fixed part to be installed in the side of the fixed part,
and with the connector for the moving part.
7/3
1SDC210033D0201
Ordering codes for XT1
Circuit-breakers
XT1D - Switch-disconnector
1SDA…R1
3 poles 4 poles
XT1D 068208 068209
XT1D switch-disconnector
7/4
1SDC210033D0201
Ordering codes for XT1
Accessories
Conversion kit of the circuit-breaker from fixed into moving part of plug-in
Type 1SDA…R1
3 poles 4 poles
P MP KIT 066276 066277
Adapter for mounting the terminals of the fixed circuit-breaker on the fixed part
Type 1SDA…R1
3 poles 4 poles
ADP adapter for fixed part (2 pieces) 066305 066306
Fixed part adapter
Service releases
Uncabled Version
SOR 12V DC 066313
SOR 24-30V AC/DC 066314
SOR uncabled SOR 48-60V AC/DC 066315
SOR 110...127V AC / 110...125V DC 066316
SOR 220...240V AC / 220...250V DC 066317
SOR 380-440V AC 066318
SOR 480-525V AC 066319
Cabled Version
SOR-C 12V DC 066321
SOR-C 24-30V AC/DC 066322
SOR-C 48-60V AC/DC 066323
SOR-C 110-127V AC / 110-125V DC 066324
SOR-C 220-240V AC / 220-250V DC 066325
SOR-C 380-440V AC 066326
SOR cabled
SOR-C 480-525V AC 066327
7/5
1SDC210033D0201
Ordering codes for XT1
Accessories
Uncabled Version
PS-SOR 24-30V AC/DC 066336
PS-SOR 48-60V AC/DC 066337
PS-SOR 110...127V AC / 110...125V DC 066338
PS-SOR uncabled
PS-SOR 220...240V AC / 220...250V DC 066339
PS-SOR 380-440V AC 066340
PS-SOR 480-525V AC 066341
Cabled Version
PS-SOR-C 24-30V AC/DC 066343
PS-SOR-C 48-60V AC/DC 066344
PS-SOR-C 110-127V AC / 110-125V DC 066345
PS-SOR-C 220-240V AC / 220-250V DC 066346
PS-SOR-C 380-440V AC 066347
PS-SOR-C 480-525V AC 066348
PS-SOR cabled
Uncabled Version
UVR 24-30V AC/DC 066389
UVR 48V AC/DC 060964
UVR 60V AC/DC 066390
UVR uncabled
UVR 110...127V AC / 110...125V DC 066391
UVR 220...240V AC / 220...250V DC 066392
UVR 380-440V AC 066393
UVR 480-525V AC 066394
Cabled Version
UVR-C 24-30V AC/DC 066396
UVR-C 48V AC/DC 060965
UVR-C 60V AC/DC 066397
UVR-C 110-127V AC / 110-125V DC 066398
UVR-C 220-240V AC / 220-250V DC 066399
UVR cabled UVR-C 380-440V AC 066400
UVR-C 480-525V AC 066401
7/6
1SDC210033D0201
Connectors
Electrical signals
Uncabled Version
AUX 250V AC 066422
AUX 24V DC 066423
AUX uncabled Cabled Version
AUX-C 3Q 250V Left 066426
AUX-C 1Q+1SY 250V 066431
AUX-C 2Q+1SY 250V 066433
AUX-C 1Q+1SY 24V DC 066446
AUX cabled
Cabled Version
AUP-I – Four Racked-in contacts 250V AC for plug-in circuit-breaker 066450
AUP-I – Four Racked-in contacts 24V DC for plug-in circuit-breaker 066451
7/7
1SDC210033D0201
Ordering codes for XT1
Accessories
Motor Operators
IP54
7/8
1SDC210033D0201
Locks
Fixed padlock
KLC Ronis key lock open, different keys, removable in open position 066593
KLC Ronis key lock open, same Type A keys, removable in open position 066594
KLC Ronis key lock open, same Type B keys, removable in open position 066595
Key lock on the circuit-breaker
KLC Ronis key lock open, same Type C keys, removable in open position 066596
KLC Ronis key lock open, same Type D keys, removable in open position 066597
KLC Ronis key lock open, same keys, removable in both position 066598
Key lock on the handle RHL Ronis key lock open, same Type B keys 066619
RHL Ronis key lock open, same Type C keys 066620
RHL Ronis key lock open, same Type D keys 066621
RHL Ronis key lock open/closed, different keys 066622
Mechanical interlock
Type 1SDA…R1
MIR-H 066637
MIR-V 066638
Plate XT1 F 066639
Plate XT1 P 066640
Interlock
Plate XT3 F 066643
Plate XT3 P 066644
7/9
1SDC210033D0201
Ordering codes for XT1
Accessories
RC Inst / RC Sel
Installation
DIN Guide
Terminal covers
Sealable screw
7/10
1SDC210033D0201
Phase separators
Type 1SDA…R1
4 pcs 6 pcs
PB Height 25mm 066674 066679
PS Height 100mm 066676 066681
PS Height 200mm 066678 066683
Phase separators
Terminals
Type 1SDA…R1
3 pcs 4 pcs 6 pcs 8 pcs
F Front Terminals 066849 066850 066851 066852
EF Extended front terminals 066865 066866 066867 066868
EF Terminal
ES Extended spread front terminals 066889 066890 066891 066892
FC CuAl Terminals for CuAl cables 1x1.5...50mm2 067151 067152 067153 067154
FC CuAl Terminals for CuAl cables 1x35...95mm2 067155 067156 067157 067158
FC CuAl Terminals for CuAl cables 1x150...240mm2 067159 067160 067161 067162
+ ADP
FC Cu Terminals for Cu cables 066905 066906 066907 066908
FCCuAl Terminal
MC Multi-cable Terminals 6x2.5...35mm2 066921 066922 066923 066924
R Rear Adjustable Terminals 066937 066938 066939 066940
R-RC Rear terminals for Residual current 066953 066954
FB Flexibar Terminals 066957 066958 066959 066960
ATS021 065523
ATS022 065524
ATS021
Spare parts
Type 1SDA…R1
7/11
1SDC210033D0201
Ordering codes for XT2
Circuit-breakers
7/12
1SDC210033D0201
XT2 160 TMG - Fixed (F) - 3 poles - Front terminals (F)
Thermomagnetic trip unit - 1SDA…R1
TMG Icu
(415V)
N S
In I3 36kA 50kA
TMG 16 160 067716 067738
TMG 20 160 067717 067739
TMG 25 160 067718 067740
TMG 32 160 067719 067741
TMG 40 160 067720 067742
TMG 50 200 067721 067743
XT2 circuit-breaker TMG 63 200 067722 067744
TMG 80 240 067723 067745
TMG 100 300 067724 067746
TMG 125 375 067725 067747
TMG 160 480 067726 067748
7/13
1SDC210033D0201
Ordering codes for XT2
Circuit-breakers
XT2 160 Ekip LS/I - Fixed (F) - 3 poles - Front terminals (F)
Electronic trip unit - 1SDA…R1
Ekip LS/I Icu
(415V)
N S H L V
In 36kA 50kA 70kA 120kA 150kA
Ekip LS/I 10 067054 067800 067857 067914 067971
Ekip LS/I 25 067055 067801 067858 067915 067972
Ekip LS/I 63 067056 067802 067859 067916 067973
Ekip LS/I 100 067057 067803 067860 067917 067974
Ekip LS/I 160 067058 067804 067861 067918 067975
XT2 circuit-breaker
XT2 160 Ekip LSI - Fixed (F) - 3 poles - Front terminals (F)
Electronic trip unit - 1SDA…R1
Ekip LSI Icu
(415V)
N S H L V
In 36kA 50kA 70kA 120kA 150kA
Ekip LSI 10 067067 067810 067867 067924 067981
Ekip LSI 25 067068 067811 067868 067925 067982
Ekip LSI 63 067069 067812 067869 067926 067983
Ekip LSI 100 067070 067813 067870 067927 067984
Ekip LSI 160 067071 067814 067871 067928 067985
XT2 160 Ekip LSIG - Fixed (F) - 3 poles - Front terminals (F)
Electronic trip unit - 1SDA…R1
Ekip LSIG Icu
(415V)
N S H L V
In 36kA 50kA 70kA 120kA 150kA
Ekip LSIG 10 067072 067815 067872 067929 067986
Ekip LSIG 25 067073 067816 067873 067930 067987
Ekip LSIG 63 067074 067817 067874 067931 067988
Ekip LSIG 100 067075 067818 067875 067932 067989
Ekip LSIG 160 067076 067819 067876 067933 067990
XT2 160 Ekip M-I - Fixed (F) - 3 poles - Front terminals (F)
Electronic trip unit - 1SDA…R1
Ekip M-I Icu
(415V)
N S H L V
In 36kA 50kA 70kA 120kA 150kA
Ekip M-I 20 067086 067829 067886 067943 068000
Ekip M-I 32 067087 067830 067887 067944 068001
Ekip M-I 52 067088 067831 067888 067945 068002
Ekip M-I 100 067089 067832 067889 067946 068003
7/14
1SDC210033D0201
XT2 160 Ekip LS/I - Fixed (F) - 4 poles - Front terminals (F)
Electronic trip unit - 1SDA…R1
Ekip LS/I Icu
(415V)
N S H L V
In 36kA 50kA 70kA 120kA 150kA
Ekip LS/I 10 067090 067833 067890 067947 068004
Ekip LS/I 25 067091 067834 067891 067948 068005
Ekip LS/I 63 067092 067835 067892 067949 068006
Ekip LS/I 100 067093 067836 067893 067950 068007
Ekip LS/I 160 067095 067838 067895 067952 068009
XT2 circuit-breaker
XT2 160 Ekip LSI - Fixed (F) - 4 poles - Front terminals (F)
Electronic trip unit - 1SDA…R1
Ekip LSI Icu
(415V)
N S H L V
In 36kA 50kA 70kA 120kA 150kA
Ekip LSI 10 067102 067845 067902 067959 068016
Ekip LSI 25 067103 067846 067903 067960 068017
Ekip LSI 63 067104 067847 067904 067961 068018
Ekip LSI 100 067105 067848 067905 067962 068019
Ekip LSI 160 067107 067850 067907 067964 068021
XT2 160 Ekip LS/I - Fixed (F) - 4 poles - Front terminals (F)
Electronic trip unit - 1SDA…R1
Ekip LSIG Icu
(415V)
N S H L V
In 36kA 50kA 70kA 120kA 150kA
Ekip LSIG 10 067108 067851 067908 067965 068022
Ekip LSIG 25 067109 067852 067909 067966 068023
Ekip LSIG 63 067110 067853 067910 067967 068024
Ekip LSIG 100 067111 067854 067911 067968 068025
Ekip LSIG 160 067113 067856 067913 067970 068027
7/15
1SDC210033D0201
Ordering codes for XT2
Circuit-breakers
7/16
1SDC210033D0201
Loose trip units XT2
Electronic - Ekip LS/I 1SDA…R1
3 poles 4 poles
In
Ekip LS/I 25 067296 067329
Loose trip unit Ekip LS/I 63 067297 067330
Ekip LS/I 100 067298 067331
Ekip LS/I 160 067299 067333
7/17
1SDC210033D0201
Ordering codes for XT2
Circuit-breakers
7/18
1SDC210033D0201
Ordering codes for XT2
Accessories
Conversion Kit of the circuit-breaker from fixed to the moving part of plug-in
Type 1SDA…R1
3 pcs 4 pcs
P MP KIT 066278 066279
Conversion Kit of the circuit-breaker from fixed to the moving part of withdrawable
Type 1SDA…R1
3 pcs 4 pcs
W MP KIT 066284 066285
7/19
1SDC210033D0201
Ordering codes for XT2
Accessories
Adapter for mounting the terminals of the fixed circuit-breaker on the fixed part
Type 1SDA…R1
3 poles 4 poles
ADP Adapter fixed part (2 pieces) 066307 066308
Fixed part adapter
Service releases
7/20
1SDC210033D0201
Shunt Opening release with permanent operation -PS -SOR-
Type 1SDA…R1
Fixed/Plug-in Withdrawable
Uncabled Version
PS-SOR 24-30V AC/DC 066336
PS-SOR 48-60V AC/DC 066337
PS-SOR uncabled PS-SOR 110...127V AC / 110...125V DC 066338
PS-SOR 220...240V AC / 220...250V DC 066339
PS-SOR 380-440V AC 066340
PS-SOR 480-525V AC 066341
Cabled Version
PS-SOR-C 24-30V AC/DC 066343 066350
PS-SOR-C 48-60V AC/DC 066344 066351
PS-SOR-C 110-127V AC / 110-125V DC 066345 066352
PS-SOR-C 220-240V AC / 220-250V DC 066346 066354
PS-SOR cabled
PS-SOR-C 380-440V AC 066347 066355
PS-SOR-C 480-525V AC 066348 066356
7/21
1SDC210033D0201
Ordering codes for XT2
Accessories
Connectors
Electrical signals
7/22
1SDC210033D0201
Auxiliary Position Contacts -AUP-
Type 1SDA…R1
Cabled Version
AUP-I – Four Racked-in contacts 250V AC for plug-in/withdrawable circuit-breaker 066450
AUP-I – Four Racked-in contacts 24V DC for plug-in/withdrawable circuit-breaker 066451
AUP-R – Two Racked-out contacts 250V AC for withdrawable circuit-breaker 066452
AUP-R – Two Racked-out contacts 24V DC for withdrawable circuit-breaker 066453
Motor Operators
7/23
1SDC210033D0201
Ordering codes for XT2
Accessories
Rotary Handles
Type 1SDA…R1
Fixed/Plug-in Withdrawable
RHD Normal Direct Handle 069053 066476
RHD Direct Emergency Handle 069054 066478
RHE Normal Transmitted Handle 069055 066480
IP54
Locks
Lateral handle
PLL Fixed lock with padlocks in open position 066590
PLL Fixed lock with padlocks in open/closed position 066592
Fixed padlock
7/24
1SDC210033D0201
Key lock on the circuit-breaker
Type 1SDA…R1
KLC Ronis key lock open, different keys, removable in open position 066599
KLC Ronis key lock open, same Type A keys, removable in open position 066600
KLC Ronis key lock open, same Type B keys, removable in open position 066601
Key lock on the circuit-breaker
KLC Ronis key lock open, same Type C keys, removable in open position 066602
KLC Ronis key lock open, same Type D keys, removable in open position 066603
KLC Ronis key lock open, same keys, removable in both position 066604
Mechanical interlock
Type 1SDA…R1
MIR-H 066637
MIR-V 066638
Plate XT2 F 066641
Plate XT2 P/W 066642
Interlock
Plate XT4 F 066645
Plate XT4 P/W 066646
7/25
1SDC210033D0201
Ordering codes for XT2
Accessories
RC Sel
Installation
DIN guide
Terminal cover
Sealable screw
Phase separators
Type 1SDA…R1
4 pcs 6 pcs
PB Height 25mm 069062 069063
PB Height 100mm 066675 066680
PB Height 200mm 066677 066682
Phase separators
7/26
1SDC210033D0201
Terminals
Type 1SDA…R1
3 pcs 4 pcs 6 pcs 8 pcs
F Front Terminals 066853 066854 066855 066856
EF Extetnded front terminals 066869 066870 066871 066872
EF Terminal
ES Extended spread front terminals 066893 066894 066895 066896
FC CuAl Terminals for CuAl cables 1x1...95mm2 067163 067164 067165 067166
FC CuAl Terminals for CuAl cables 1x70...185mm2 067167 067168 067169 067170
FC CuAl Terminals for CuAl cables 1x150…240mm2 067171 067172 067173 067174
+ ADP
FC CuAl Terminals for CuAl cables 2x35...95mm2 067175 067176 067177 067178
FCCuAl Terminal
FC Cu Terminali for Cu cables 066909 066910 066911 066912
MC Multi-cable Terminals 6x2.5...35mm2 066925 066926 066927 066928
R Rear adjustable Terminals 066941 066942 066943 066944
FB Flexibar Terminals 066961 066962 066963 066964
Type 1SDA…R1
Fixed/Plug-in Withdrawable
Ekip Display 068659 068659
Ekip LED Meter 068660 068660
Ekip Com 068661 068662
Ekip Display PR212/CI Contactor control unit 050708 050708
EP010 Interface module 059469 059469
HMI030 Interface on front of panel 063143 063143
Connection Kit
Type 1SDA…R1
Fixed/Plug-in Withdrawable
Kit of 24V DC auxiliary voltage for electronic trip units 066980 066981
Kit for PTC Connection 066982 066983
Kit for external neutral Connection 066984 066985
Kit for PR212/CI Connection 066986 066987
7/27
1SDC210033D0201
Ordering codes for XT2
Accessories
ATS021 065523
ATS022 065524
ATS021
Spare parts
Type 1SDA…R1
Fixed/Plug-in Withdrawable
SA RC Sel - Opening solenoid of the residual current 066991 066993
device
AUX-C -Loose cabled Auxiliary Contact 250V AC(1) 066994 066995
AUX-C -Loose cabled Auxiliary Contact 24V DC(1) 066996 066997
(1)
un-numbered cables
1 connector for fixed part/moving part of withdrawable with 2 PINS for SOR/UVR up to 400V 067213
1 connector for fixed part/moving part of withdrawable with 3 PINS for AUX up to 400V 067214
7/28
1SDC210033D0201
Ordering codes for XT3
Circuit-breakers
7/29
1SDC210033D0201
Ordering codes for XT3
Circuit-breakers
XT3 circuit-breaker
XT3D - Switch-disconnector
1SDA…R1
3 poles 4 poles
XT3D 068210 068211
XT3D switch-disconnector
7/30
1SDC210033D0201
Ordering codes for XT3
Accessories
Conversion Kit of the circuit-breaker from fixed into moving part of plug-in
Type 1SDA…R1
3 poles 4 poles
P MP KIT 066280 066281
Adapter for mounting the terminals of the fixed circuit-breaker on the fixed part
Type 1SDA…R1
3 poles 4 poles
ADP adapter fixed part (2 pieces) 066309 066310
Fixed part adapter
Service releases
Uncabled Version
SOR 12V DC 066313
SOR 24-30V AC/DC 066314
SOR 48-60V AC/DC 066315
7/31
1SDC210033D0201
Ordering codes for XT3
Accessories
Uncabled Version
PS-SOR 24-30V AC/DC 066336
PS-SOR 48-60V AC/DC 066337
PS-SOR 110...127V AC / 110...125V DC 066338
PS-SOR uncabled
PS-SOR 220...240V AC / 220...250V DC 066339
PS-SOR 380-440V AC 066340
PS-SOR 480-525V AC 066341
Cabled Version
PS-SOR-C 24-30V AC/DC 066343
PS-SOR-C 48-60V AC/DC 066344
PS-SOR-C 110-127V AC / 110-125V DC 066345
PS-SOR-C 220-240V AC / 220-250V DC 066346
PS-SOR-C 380-440V AC 066347
PS-SOR-C 480-525V AC 066348
PS-SOR cabled
Uncabled Version
UVR 24-30V AC/DC 066389
UVR 48V AC/DC 069064
UVR 60V AC/DC 066390
UVR uncabled
UVR 110...127V AC - 110...125V DC 066391
UVR 220...240V AC - 220...250V DC 066392
UVR 380-440V AC 066393
UVR 480-525V AC 066394
Cabled Version
UVR-C 24-30V AC/DC 066396
UVR-C 48V AC/DC 069065
UVR-C 60V AC/DC 066397
UVR-C 110-127V AC - 110-125V DC 066398
UVR-C 220-240V AC - 220-250V DC 066399
UVR cabled
UVR-C 380-440V AC 066400
UVR-C 480-525V AC 066401
7/32
1SDC210033D0201
Connectors
Electrical signals
Uncabled Version
AUX 24V DC 066423
AUX 250V AC 066422
AUX uncabled Cabled Version
AUX-C 1Q+1SY 24V DC 066446
AUX-C 3Q+1SY 24V AC 066448
AUX-C 1Q+1SY 250V AC 066431
AUX-C 2Q+1SY 250V AC 066433
AUX-C 3Q 250V AC Left 066428
AUX-C 3Q+1SY 250V AC 066434
AUX cabled
Cabled Version
AUP-I – Four Racked-in contacts 250V AC for plug-in circuit-breaker 066450
AUP-I – Four Racked-in contacts 24V DC for plug-in circuit-breaker 066451
7/33
1SDC210033D0201
Ordering codes for XT3
Accessories
Motor Operators
Rotary Handles
Type 1SDA…R1
IP54
7/34
1SDC210033D0201
Locks
Fixed padlock
KLC Ronis key lock open, different keys, removable in open position 066605
KLC Ronis key lock open, same Type A keys, removable in open position 066606
KLC Ronis key lock open, same Type B keys, removable in open position 066607
Key lock on the circuit-breaker
KLC Ronis key lock open, same Type C keys, removable in open position 066608
KLC Ronis key lock open, same Type D keys, removable in open position 066609
KLC Ronis key lock open, same keys, removable in both position 066610
Mechanical interlock
Type 1SDA…R1
MIR-H 066637
MIR-V 066638
Plate XT1 F 066639
Plate XT1 P 066640
Interlock
Plate XT3 F 066643
Plate XT3 P 066644
7/35
1SDC210033D0201
Ordering codes for XT3
Accessories
Installation
DIN Guide
Terminal covers
Sealable screw
Phase separators
Type 1SDA…R1
4 pcs 6 pcs
PB Height 25mm
PB Height100mm 066676 066681
PB Height 200mm 066678 066683
Phase separators
7/36
1SDC210033D0201
Terminals
Type 1SDA…R1
3 pcs 4 pcs 6 pcs 8 pcs
F Front Terminals 066857 066858 066859 066860
EF Extetnded front terminals 066873 066874 066875 066876
EF Terminal
ES Extended spread front terminals 066897 066898 066899 066900
FC CuAl terminals for CuAl cables 1x70...185mm2 067179 067180 067181 067182
FC CuAl terminals for CuAl cables 1x150...240mm2 067183 067184 067185 067186
+ ADP
FC CuAl terminals for CuAl cables 2x35...150mm2 067187 067188 067189 067190
FC Cu terminali for Cu cables 066913 066914 066915 066916
FCCuAl Terminal
MC Multi-cable Terminals 6x2.5...35mm2 066929 066930 066931 066932
R Rear adjustable terminals 066945 066946 066947 066948
FB Flexibar Terminals 066965 066966 066967 066968
ATS021 065523
ATS022 065524
ATS021
Spare parts
Type 1SDA…R1
SA RC Sel/RC Inst/RC B Type - Opening solenoid of the residual current device 066992
SA RC B Type - Opening solenoid of the residual current device 067208
AUX-C - Loose uncabled Auxiliary Contact 250V(1) 066994
AUX-C - Loose cabled auxiliary contact 24V(1) 066996
(1)
un-numbered cables
7/37
1SDC210033D0201
Ordering codes for XT4
Circuit-breakers
7/38
1SDC210033D0201
XT4 160 MA - Fixed (F) - 3 poles - Front terminals (F)
Thermomagnetic trip unit - 1SDA…R1
MA Icu
(415V)
N S H L V
In I3 36kA 50kA 70kA 120kA 150kA
MA 10(1) 50...100 068112 068431 068441 068451 068461
MA 12.5(1) 62.5...125 068113 068432 068442 068452 068462
MA 20 100...200 068114 068433 068443 068453 068463
MA 32 160...320 068115 068434 068444 068454 068464
MA 52 260...520 068116 068435 068445 068455 068465
MA 80 400...800 068117 068436 068446 068456 068466
MA 100 500...1000 068118 068437 068447 068457 068467
XT4 circuit-breaker
MA 125 625...1250 068119 068438 068448 068458 068468
MA 160 800...1600 068120 068439 068449 068459 068469
(1)
Available stortly, please ask ABB SACE
XT4 160 Ekip LS/I - Fixed (F) - 3 poles - Front terminals (F)
Electronic trip unit - 1SDA…R1
Ekip LS/I Icu
(415V)
N S H L V
In 36kA 50kA 70kA 120kA 150kA
Ekip LS/I 40 068122 068471 068511 068551 068591
Ekip LS/I 63 068123 068472 068512 068552 068592
Ekip LS/I 100 068124 068473 068513 068553 068593
Ekip LS/I 160 068125 068474 068514 068554 068594
XT4 250 Ekip LS/I - Fixed (F) - 3 poles - Front terminals (F)
Electronic trip unit - 1SDA…R1
Ekip LS/I Icu
(415V)
N S H L V
In 36kA 50kA 70kA 120kA 150kA
Ekip LS/I 250 068126 068475 068515 068555 068595
7/39
1SDC210033D0201
Ordering codes for XT4
Circuit-breakers
XT4 160 Ekip LSI - Fixed (F) - 3 poles - Front terminals (F)
Electronic trip unit - 1SDA…R1
Ekip LSI Icu
(415V)
N S H L V
In 36kA 50kA 70kA 120kA 150kA
Ekip LSI 40 068132 068481 068521 068561 068601
Ekip LSI 63 068133 068482 068522 068562 068602
Ekip LSI 100 068134 068483 068523 068563 068603
Ekip LSI 160 068135 068484 068524 068564 068604
XT4 250 Ekip LSI - Fixed (F) - 3 poles - Front terminals (F)
Electronic trip unit - 1SDA…R1
XT4 circuit-breaker Icu
Ekip LSI N S H L V
(415V)
In 36kA 50kA 70kA 120kA 150kA
Ekip LSI 250 068136 068485 068525 068565 068605
XT4 160 Ekip LSIG - Fixed (F) - 3 poles - Front terminals (F)
Electronic trip unit - 1SDA…R1
Ekip LSIG Icu
(415V)
N S H L V
In 36kA 50kA 70kA 120kA 150kA
Ekip LSIG 40 068137 068486 068526 068566 068606
Ekip LSIG 63 068138 068487 068527 068567 068607
Ekip LSIG 100 068139 068488 068528 068568 068608
Ekip LSIG 160 068140 068489 068529 068569 068609
XT4 250 Ekip LSIG - Fixed (F) - 3 poles - Front terminals (F)
Electronic trip unit - 1SDA…R1
Ekip LSIG Icu
(415V)
N S H L V
In 36kA 50kA 70kA 120kA 150kA
Ekip LSIG 250 068141 068490 068530 068570 068610
XT4 160 Ekip LS/I - Fixed (F) - 4 poles - Front terminals (F)
Electronic trip unit - 1SDA…R1
Ekip LS/I Icu
(415V)
N S H L V
In 36kA 50kA 70kA 120kA 150kA
Ekip LS/I 40 068142 068491 068531 068571 068611
Ekip LS/I 63 068144 068492 068532 068572 068612
Ekip LS/I 100 068145 068493 068533 068573 068613
Ekip LS/I 160 068146 068494 068534 068574 068614
XT4 250 Ekip LS/I - Fixed (F) - 4 poles - Front terminals (F)
Electronic trip unit - 1SDA…R1
Ekip LS/I Icu
(415V)
N S H L V
In 36kA 50kA 70kA 120kA 150kA
Ekip LS/I 250 068147 068495 068535 068575 068615
7/40
1SDC210033D0201
XT4 160 Ekip I - Fixed (F) - 4 poles - Front terminals (F)
Electronic trip unit - 1SDA…R1
Ekip I Icu
(415V)
N S H L V
In 36kA 50kA 70kA 120kA 150kA
Ekip I 40 068148 068496 068536 068576 068616
Ekip I 63 068149 068497 068537 068577 068617
Ekip I 100 068150 068498 068538 068578 068618
Ekip I 160 068151 068499 068539 068579 068619
XT4 160 Ekip LSI - Fixed (F) - 4 poles - Front terminals (F)
Electronic trip unit - 1SDA…R1
Ekip LSI Icu
(415V)
N S H L V
In 36kA 50kA 70kA 120kA 150kA
Ekip LSI 40 068153 068501 068541 068581 068621
Ekip LSI 63 068154 068502 068542 068582 068622
Ekip LSI 100 068155 068503 068543 068583 068623
Ekip LSI 160 068156 068504 068544 068584 068624
XT4 250 Ekip LSI - Fixed (F) - 4 poles - Front terminals (F)
Electronic trip unit - 1SDA…R1
Ekip LSI Icu
(415V)
N S H L V
In 36kA 50kA 70kA 120kA 150kA
Ekip LSI 250 068157 068505 068545 068585 068625
XT4 160 Ekip LSIG - Fixed (F) - 4 poles - Front terminals (F)
Electronic trip unit - 1SDA…R1
Ekip LSIG Icu
(415V)
N S H L V
In 36kA 50kA 70kA 120kA 150kA
Ekip LSIG 40 068158 068506 068546 068586 068626
Ekip LSIG 63 068159 068507 068547 068587 068627
Ekip LSIG 100 068160 068508 068548 068588 068628
Ekip LSIG 160 068161 068509 068549 068589 068629
XT4 250 Ekip LSIG - Fixed (F) - 4 poles - Front terminals (F)
Electronic trip unit - 1SDA…R1
Ekip LSIG Icu
(415V)
N S H L V
In 36kA 50kA 70kA 120kA 150kA
Ekip LSIG 250 068162 068510 068550 068590 068630
XT4 D - Switch-disconnector
1SDA…R1
3 poles 4 poles
20kA 20kA
XT4 D 068212 068213
XT4D switch-disconnector
7/41
1SDC210033D0201
Ordering codes for XT4
Circuit-breakers
7/42
1SDC210033D0201
Loose trip units XT4
Electronic - Ekip LS/I 1SDA…R1
3 poles 4 poles
In
Ekip LS/I 40 067498 067518
Loose trip units Ekip LS/I 63 067499 067519
Ekip LS/I 100 067500 067520
Ekip LS/I 160 067501 067521
Ekip LS/I 250 067502 067522
7/43
1SDC210033D0201
Ordering codes for XT4
Circuit-breakers
7/44
1SDC210033D0201
Ordering codes for XT4
Accessories
Conversion Kit of the circuit-breaker from fixed into moving part of plug-in
Type 1SDA…R1
3 pcs 4 pcs
P MP KIT 066282 066283
Conversion Kit of the circuit-breaker from fixed into moving part of withdrawable
Type 1SDA…R1
3 pcs 4 pcs
W MP KIT 066286 066287
7/45
1SDC210033D0201
Ordering codes for XT4
Accessories
Adapter for mounting the terminals of the fixed circuit-breaker on the fixed part
Type 1SDA…R1
3 poles 4 poles
ADP adapter fixed part (2 pieces) 066311 066312
Fixed part adapter
Service releases
7/46
1SDC210033D0201
Shunt Opening release with permanent operation -PS -SOR-
Type 1SDA…R1
Fixed/Plug-in Withdrawable
Uncabled Version
PS-SOR 24-30V AC/DC 066336
PS-SOR 48-60V AC/DC 066337
PS-SOR uncabled PS-SOR 110...127V AC / 110...125V DC 066338
PS-SOR 220...240V AC / 220...250V DC 066339
PS-SOR 380-440V AC 066340
PS-SOR 480-525V AC 066341
Cabled Version
PS-SOR-C 24-30V AC/DC 066343 066350
PS-SOR-C 48-60V AC/DC 066344 066351
PS-SOR-C 110-127V AC / 110-125V DC 066345 066352
PS-SOR-C 220-240V AC / 220-250V DC 066346 066354
PS-SOR cabled
PS-SOR-C 380-440V AC 066347 066355
PS-SOR-C 480-525V AC 066348 066356
7/47
1SDC210033D0201
Ordering codes for XT4
Accessories
Connectors
Socket-plug connector
of fixed part
Electrical signals
7/48
1SDC210033D0201
Auxiliary position contacts -AUP-
Type 1SDA…R1
Cabled Version
AUP-I – Four Racked-in contacts 250V AC for plug-in/withdrawable circuit-breaker 066450
AUP-I – Four Racked-in contacts 24V DC for plug-in/withdrawable circuit-breaker 066451
AUP-R – Two Racked-out contacts 250V AC for withdrawable circuit-breaker 066452
AUP-R – Two Racked-out contacts 24V DC for withdrawable circuit-breaker 066453
Motor Operators
7/49
1SDC210033D0201
Ordering codes for XT4
Accessories
Rotary Handles
Rotary Handles
Type 1SDA…R1
Fixed/Plug-in Withdrawable
RHD Normal Direct Handle 069053 066476
RHD Direct Emergency Handle 069054 066478
RHE Normal Transmitted Handle 069055 066480
RHE Emergency Transmitted Handle 069056 066482
Direct handle
RHS L Normal Left Lateral Handle 069058
RHS L Emergency Left Lateral Handle 069059
RHS R Normal Right Lateral Handle 069060
RHS R Emergency Right Lateral Handle 069061
Transmitted Handle Spare Parts
RHE_B Base for Transmitted Handle 069057 066484
RHE_S Rod of 500mm 066576
RHE_H Normal Transmitted Handle 066577
RHE_H Emergency Transmitted Handle 066578
Transmitted handle LH Wide Normal Handle 066583
LH Wide Emergency Handle 066585
IP54
Locks
Fixed padlock
7/50
1SDC210033D0201
Key lock on the circuit-breaker
Type 1SDA…R1
KLC Ronis key lock open, different keys, removable in open position 066599
KLC Ronis key lock open, same Type A keys, removable in open position 066600
KLC Ronis key lock open, same Type B keys, removable in open position 066601
Key lock on the circuit-breaker
KLC Ronis key lock open, same Type C keys, removable in open position 066602
KLC Ronis key lock open, same Type D keys, removable in open position 066603
KLC Ronis key lock open, same keys, removable in both position 066604
Mechanical interlock
Type 1SDA…R1
MIR-H 066637
MIR-V 066638
Plate XT2 F 066641
Plate XT2 P/W 066642
Interlock
Plate XT4 F 066645
Plate XT4 P/W 066646
7/51
1SDC210033D0201
Ordering codes for XT4
Accessories
RC Sel
Panel type residual current relay
Type 1SDA...R1
Installation
DIN Guide
Terminals
Terminal cover
Sealable screw
Phase Separators
Type 1SDA…R1
4 pcs 6 pcs
PB Height 25mm 069062 069063
PB Height 100mm 066675 066680
PB Height 200mm 066677 066682
Phase separators
7/52
1SDC210033D0201
Terminals
Type 1SDA…R1
3 pcs 4 pcs 6 pcs 8 pcs
F Front Terminals 066861 066862 066863 066864
EF Extended front terminals 066877 066878 066879 066880
EF Terminal
ES Extended spread front terminals 066901 066902 066903 066904
FC CuAl Terminals for CuAl cables 1x1...150mm2 067191 067192 067193 067194
FC CuAl Terminals for CuAl cables 1x150...240mm2 067195 067196 067197 067198
+ ADP
FC CuAl Terminals for CuAl cables 2x35...150mm2 067199 067200 067201 067202
FC Cu Terminals for Cu cables 066917 066918 066919 066920
FCCuAl Terminal
MC Multi-cable Terminals 6x2.5...35mm2 066933 066934 066935 066936
R Rear adjustable Terminals 066949 066950 066951 066952
FB Flexibar Terminals 066969 066970 066971 066972
Type 1SDA…R1
Fixed/Plug-in Withdrawable
Ekip Display 068659 068659
Ekip LED Meter 068660 068660
Ekip Com 068661 068662
Ekip Display PR212/CI Contactor control unit 050708 050708
EP010 Interface module 059469 059469
HMI030 Interface on front of panel 063143 063143
7/53
1SDC210033D0201
Ordering codes for XT4
Accessories
ATS021 065523
ATS022 065524
ATS021
Spare parts
Type 1SDA…R1
Fixed/Plug-in Withdrawable
SA RC Sel - Opening solenoid of the residual current 067209 067210
device
AUX-C -Loose cabled Auxiliary Contact 250V AC(1) 066994 066995
AUX-C -Loose cabled Auxiliary Contact 24V DC(1) 066996 066997
(1)
un-numbered cables
1 connector for fixed part/moving part of withdrawable with 2 PINS for SOR/UVR up to 400V 067213
1 connector for fixed part/moving part of withdrawable with 3 PINS for AUX up to 400V 067214
7/54
1SDC210033D0201
Glossary
Index
Circuit-breaker.........................................................................................................................8/2
Motor protection......................................................................................................................8/9
Communication .....................................................................................................................8/10
Symbols.................................................................................................................................8/12
8/1
1SDC210033D0201
Glossary
Circuit-breaker
G1.1 Circuit-breaker
Mechanical switching apparatus, able to close, carry and break currents in normal short-
circuit condition and also close, carry for a specified time and break currents in specific
abnormal circuit conditions such as that verified in case of short-circuit.
8/2
1SDC210033D0201
G1.9 Tropicalization
All the Tmax XT series circuit-breakers can be used in the most critical environmental condi-
tions defined by the following standards:
Q IEC 60721-2-1 (climatogram 8);
Q IEC 60068-2-30;
Q IEC 60068-2-2;
Q IEC 60068-2-52.
Tropicalization is guaranteed by:
Q moulded-case made of synthetic resins reinforced with glass fiber;
Q rust-preventive treatment on the main metal parts;
Q Fe/Zn galvanisation (UNI ISO 2081), protected by a conversion layer free of hexavalent
chrome (in compliance with ROHS) with the corrosion resistance guaranteed by ISO 4520
class 2c;
Q application of anti-condensation protection for electronic trip units and relative accessori-
es.
8/3
1SDC210033D0201
Glossary
Performance Parameters
G2.1 Size
Term that indicates a group of circuit-breakers with phisical dimension common to a nominal
current size (same poles number).
8/4
1SDC210033D0201
Class B - Circuit-breakers specifically designed for selectivity under short-circuit conditions
in relation to other protection devices installed in series on the load side, i.e. with an inten-
tional delay (which can be adjusted), applicable under short-circuit conditions. The short-
time withstand current is specified for these circuit-breakers (Icw).
A circuit-breaker belongs to category B if its Icw value exceeds:
Q between 12In and 5kA, whichever is higher, for In≤2500A;
Q 30kA for In>2500A.
8/5
1SDC210033D0201
Glossary
Releases and Protections
G3.1 Release
Device, mechanically connected to a mechanical operating device, which frees the latching
components and allows the operating device to be opened or closed.
8/6
1SDC210033D0201
G3.13 Protection of the neutral
Detection of overcurrents in the neutral conductor so as to break the phase conductors
(neutral protected but not isolated) or to break the neutral conductor itself (neutral protected
and isolated).
G3.15 TT system
In the TT system, the neutral and conductive parts are connected to two electrically inde-
pendent earthing systems.
G3.16 TN system
In the TN system, the neutral is connected directly to the earth, while the conductive parts
are connected to the same earthing system as the neutral.
The TN system is divided into three different types, depending on whether the neutral and
protection conductors are separate or not:
1. TN-S: the neutral conductor N and the protection conductor PE are separate
8/7
1SDC210033D0201
Glossary
Releases and Protections
2. TN-C: the neutral and protection functions are combined in a single conductor called
PEN
3. TN-C-S: the neutral and protection functions are partly combined in a single conductor
called PEN and partly separate PE+N
Consult QT3: “Distribution systems and protection against indirect contacts and earth faults” for further details.
G3.17 IT system
IT system have no active parts directly earthed, but may have live parts connected to earth
through high value impedance. All the exposed-conductive-parts, separately or in group, are
connected to an independent earth electrode.
8/8
1SDC210033D0201
Glossary
Motor protection
Trip time
Trip time
Operating class Ti [s] for 7.2xIr
Ti [s] for 7.2xIr
(banda “E”)
2 – Ti ≤ 2
3 – 2 < Ti ≤ 3
5 0,5 < Ti ≤ 5 3 < Ti ≤ 5
10A 2 < Ti ≤ 10 –
10 4 < Ti ≤ 10 5 < Ti ≤ 10
20 6 < Ti ≤ 20 10 < Ti ≤ 20
30 9 < Ti ≤ 30 20 < Ti ≤ 30
40 – 30 < Ti ≤ 40
Time Ti is the cold trip time of the thermal relay at 7.2 times the set current value. It is com-
mon practice to associate class 10 with the normal starting type and class 30 with the
heavy-duty starting type.
The other trip classes and trip time indicated under band “E”, have recently been introduced
in a variant to the CEI EN 60947-4-1 Standard, and are characterised by a more restricted
trip range due to raising the minimum non-trip time.
(*)
The load characteristics which the motor must carry, the type of motor and the starting methods, are factors which affect the
starting time and therefore selection of the thermal trip unit.
G4.6 Contactor
Mechanical operating device with a single stand-by position and non-manual operation able
to make, carry and break currents under normal circuit conditions, including overload oper-
ating conditions.
G4.8 PTC
Thermostatic probe able to measure the internal temperature of an electric motor.
Consult QT7: The asynchronous three-phase motor, general information and ABB offer for coordinating the protections” for further details.
8/9
1SDC210033D0201
Glossary
Communication
G5.3 Network
A network generically consists of nodes interconnected with communication lines:
Q the node (an “intelligent” device able to dialogue with other devices) is the data transmis-
sion and/or reception point;
Q the communication line is the element that connects two nodes and represents the direct
path the information takes in order to be transferred between two nodes. In practice, it
is the physical means (coaxial cable, twisted telephone cable, optic fibre, infrared rays)
along which the information and data travel.
Consult QT9: “Communication with ABB circuit-breakers via Bus” for further details.
8/10
1SDC210033D0201
Glossary
Standards and Regulations
G6.1 Standards
Technical specification approved by a recognised organisation with the task of defining the
state-of-the-art characteristics (dimensional, environmental, safety, etc.) of a product or
service.
G6.2 Directive
Ensemble of rules which define the essential requirements regarding safety which the prod-
ucts must comply with in order to guarantee user safety.
G6.5 CE marking
This is a mark that must be affixed to certain types of product by the manufacturer in order to
self-certify correspondence (or conformity) with the essential requirements for marketing and
use of that product in the European Union. The law requires this mark to be affixed on the
product so that it can be marketed in the European Economic Area (EEA) member states.
8/11
1SDC210033D0201
Symbols
SYMBOL DESCRIPTION
CB Circuit-breaker
PF Fixed part
PM Mobile part
F Version Circuit-breaker in fixed version
P Version Circuit-breaker in plug-in version
W Version Circuit-breaker in withdrawable version
F Front terminals
EF Front extended terminals
ES Front extended spread terminals
FCCuAl Terminal for copper/aluminium cables
FCCu Terminal for copper cables
R Rear terminals
HR/VR Rear flat vertical/horizontal terminals
FB Terminals for flexible busbars
MC Multi-cable terminal
HTC High terminal covers
LTC Low terminal covers
PS Phase separators
RHD Direct rotary handle
RHE Transmitted rotary handle
RHE-LH Transmitted rotary handle with wide handgrip
RHS Lateral rotary handle
FLD Front for locks
PLL Padlock device
KLC Key lock
SOR or YO Shunt opening release
PS-SOR or YO Permanent shunt opening release
UVR or YU Undervoltage release
UVD Time-delay device for undervoltage release
AUX Q Auxiliary contact in open/closed position
AUX SY Auxiliary contact tripped
AUX S51 Release tripped auxiliary contact
SA Opening solenoid of residual current device
AUP-I Plugged-in auxiliary position contacts
AUP-E Withdrawn auxiliary position contacts
AUE Early auxiliary contacts on the handle
MOD Direct action motor operator
MOE Stored energy motor operator
MOE-E Electronic motor operator
CB Circuit-breaker
NE External neutral
RHx All the handles (RHD, RHE, RHE-UI, RHS)
3Q Left open/closed auxiliary contacts
24V 24V auxiliary voltage
AUE inside Early auxiliary contacts inside the circuit-breaker
8/12
1SDC210033D0201
ABB SACE documentation
The technical documentation is available on-line on BOL web site http://bol.it.abb.com in “Work
tools - Technical guides” section:
– Technical Application Paper, volume 1 “Low voltage selectivity with ABB circuit-breakers”
– Technical Application Paper, volume 2 “MV/LV transformer substations: theory and example
of short-circuit calculation”
– Technical Application Paper, volume 3 “Distribution system and protection against indirect
contact and earth fault”
– Technical Application Paper, volume 4 “ABB circuit-breakers inside LV switchboards”
– Technical Application Paper, volume 5 “ABB circuit-breakers for direct current applications”
– Technical Application Paper, volume 6 “Arc-proof low voltage switchgear and controlgear
assemblies”
– Technical Application Paper, volume 7 “Three-phase asynchronous motors. Generalities and
ABB proposals for the coordination of protective de-
vices”
– Technical Application Paper, volume 8 “ Power factor correction and harmonic filtering in elec-
trical plants”
– Technical Application Paper, volume 9 “Bus communication with ABB circuit-breakers”
8/13
1SDC210033D0201
Notes
1SDC210033D0201
Notes
1SDC210033D0201
Notes
1SDC210033D0201
Notes
1SDC210033D0201
Notes
1SDC210033D0201
Notes
1SDC210033D0201
SACE Tmax XT. New low voltage moulded-case circuit-breakers up to 250 A
Contact us
ABB SACE The data and illustrations are not binding. We reserve
www.abb.com
SACE Tmax XT
New low voltage moulded-case
circuit-breakers up to 250 A