ADDITIONAL TESTS:
esult
•Continuity (Buzzer-sound)
Fail R
• Insulation - L / N, L / PE, N / PE
• Phase Rotation
/
Pass
EN 61010
EN 50081
EN 50082
11
Electrical Installation Test Equipment Installcheck
TYPICAL APPLICATIONS
CONTINUITY PHASE ROTATION OUTLET WIRING
BUZZER
PE
collector
INSULATION L/PE and N/PE Auto Test (no RCD RCD): Line, Loop
Disconnected
mains voltage!
Auto Test (trip-out RCD): Line, Loop (RE), UC, t∆, ISO Auto Test (no-trip RCD): Line, Loop (RE), UC
Technical Specification
Mains Socket Wiring Analysis .................. Eight states recognized and Standard set Order No.: MI 2150
displayed
Phase rotation ...................................................... Un 440 V, 50 Hz – Instrument
– Carrying strap
PE Test (presence of phase voltage) .............................................. yes – Shuko-plug test cable,
Continuity Limit value .................................................... 2 Ω ±0.5 Ω 1m
Insulation Resistance Limit value ................... 0.6 ÷1.2 MΩ ±0.2 MΩ – Safety test leads with fixed
test tips, 1.5 m, 2 pcs
Nominal test voltage ......................................................... 500 V DC – Instruction Manual
RCD Test – Quick quide
Nominal differential current I∆N ...................... 30, 100, 300 or 500 mA – Calibration Certificate
Contact voltage Limit value ..................................... 25 V at I∆N ±5 V
– Declaration of Conformity
– Declaration of warranty
Test current ........................................................................ <0.5 I∆N
Trip-out time of RCD Limit value .................. 0.3 s (I∆N) or 0.04 s (5I∆N)
Test current ......................... I∆N (any selected I∆N) and 5I∆N (30 mA only) Optional accessories Order No.:
Fault Loop Resistance (RCD built-in) Limit value .............. 25 V / I∆N A 1111 S 1112 A 1020
Test current .......................................................................... <0.5I∆N
Fault Loop Resistance (RCD not built-in)
Limit value ................................................................. 1.5 Ω ±0.3 Ω
Test current ........................................................................... 0.5 A
Line Resistance Limit value ........................................ 1.5 Ω ±0.3 Ω
Test current ............................................................................ 0.5 A
A 1114 A 1115
General data
– Three phase adapter A 1111
Power supply ........................... 6 V (4 × 1.5 V alkaline battery IEC LR6) – Universal test cable 3 x 1.5 m
Battery capacity ........................................................... approx. 35 h with 3 safety test tips S 1112
Results displayed ...................... OK, or not OK by means of LED lamps – Alligator clip (insulated) A 1114
Sound signals .............................. ............................................. yes – Protection case A 1115
Operating voltage .......................................... 220/230/240 V, 50 Hz – Soft carrying bag A 1020
Dimensions (w × l × d) ......................................... 100 × 200 × 50 mm
Weight (without accessories, with batteries) ............................... 0.6 kg
Overvoltage category .................................................. CAT III / 300 V
Working temperature range ........................................... 0 up to 40 °C
Auto power OFF ............ yes, 10 minutes after completion of last action
12