Final Circuit and Load Estimation British Standard
Final Circuit and Load Estimation British Standard
Final Circuit and Load Estimation British Standard
CHAPTER 2
FINAL CIRCUIT AND LOAD ESTIMATION
Authors: 16
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
Authors: 17
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
314-2 A separate circuit shall be provided for each part of the installation which needs
to be separately controlled for compliance with the Regulations or otherwise to
prevent danger, so that such circuits remain energised in the event of failure of any
other circuit of the installation, and due account shall be taken of the consequences of
the operation of any single protective device.
314-3 The number of final circuits required, and the number of points supplied by any
final circuit, shall be such as to facilitate compliance with the requirements of Chapter
43 for overcurrent protection, Section 537 for isolation and switching and Chapter 52
as regards current carrying capacities of conductors.
314-4 Where an installation comprises more than one final circuit, each final circuit
shall be connected to a separate way in a distribution board (DB). The wiring of each
final circuit shall be electrically separate from that of every other final circuit, so as to
prevent the indirect energising of a final circuit intended to be isolated.
For finals circuits the nominal current rating of the fuse or circuit breaker (overcurrent
device) and cable will depend on the types of final circuit.
Authors: 18
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
The main advantages of the 13A socket with fused plug are that any appliance with a
loading not exceeding 3.12kW (13A at 240V) may be connected with perfect safety to
any 13A socket, and under certain conditions an unlimited number of socket may be
connected to any one circuit.
One point which must be borne in mind by the designer is the question of the use of
outdoor equipment. IEE Regulation 411.3.3 states that where a socket outlet may be
expected to supply portable equipment for use outdoors, it shall be protected by an
RCD with a rated residual current not exceeding 30mA.
13A socket outlets circuits can be fed by either radial or ring circuits. Figure 3 shows
a radial circuit arrangement and in Figure 4, a ring circuits utilises one additional
conductor to loop back to the sending end. In other words, the socket outlets in the
ring circuit are fed by two parallel conductors. The sharing of the load between the
two parallel conductors will depend on the load distribution within the ring.
Authors: 19
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
Authors: 20
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
If the estimated load for any given floor area exceeds that of the protective device
given above then the number of circuits feeding this area must be increased
accordingly.
2.2.1.1 Spurs
Non fused spurs: A spur is a branch cable connected to a 13A circuit. The total
number of non fused which may be connected to a 13A circuit must not exceed the
total number of sockets connected direct the circuit. Not more than one single or one
twin socket outlet or one fixed appliance may be connected to any one spur. Non
fused spurs may be looped from the terminals of the nearest sockets, or by means of a
joint box in the circuit. The size of the cable feeding non fused spurs must be the same
size as the circuit cable.
Fused spurs: The cable forming a fused spur must be connected to the ring circuit by
means of fused connection unit or spurbox. The rating of the fuse in this unit shall not
exceed the rating of the cable forming the spur and must not exceed 13A.
There is no limit to the number of fused spurs that may be connected to a ring. The
minimum size of cables forming a fused spur shall be 1.5mm2 PVC with copper
conductor.
Fixed appliances permanently connected to 13A circuits (not connected to a plug and
socket), must be protected by a fuse not exceeding 13A and double pole switch or
fused connection unit which must be separate from the appliance and in an accessible
position.
When planning circuits for 13A sockets it must be always remembered that these are
mainly intended for general purpose use and that comprehensive heating installations,
including floor warming, should be circuited according to the connected load, and
should not use 13A sockets.
Authors: 21
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
Authors: 26
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
These socket outlets are of the heavy industrial type (Figure 5), and are suitable for
single or three phase with a scraping earth. Fuses are not fitted in the sockets or the
plugs. Current ratings range from 16A to 125A.
The 16A sockets whether single or three phase, may be wired only on radial circuits.
The number of sockets connected to a circuit is unlimited, but the protective
overcurrent device must not exceed 20A. It is obvious that if these 16A sockets are
likely to be fully loaded then only one should be connected to any one circuit. The
higher ratings will of course each be wired on a separate circuit.
Due to their robust nature these sockets are often used in industrial installations to
feed small three phase motors, and if the total estimated load of the motors does not
exceed 20A there is no reason why a considerable number should be connected to one
such circuit.
The same rule which applies to all final circuits must be complied with, which is that
the conductors and protective devices must be suitably rated as already explained.
IEE Regulation 552-1-1 states all equipment, including cable, of every circuit
carrying the starting, accelerating and load current of a motor shall be suitable for
current at least equal to the full load current of the motor when rated in accordance
with appropriate British Standard. Where the motor is intended for intermittent duty
and for frequent starting and stopping, account shall be taken of any cumulative
effects of the starting or braking current upon the temperature rise of the equipment
of the circuit.
Authors: 27
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
Every electric motor exceeding 0.37kW shall be provided with control equipment
incorporating protection against overload of the motor. Several motors not exceeding
0.37kW each can be supplied by one circuit, providing protection is provided at each
motor.
All isolators must be ‘suitably placed’ which means they must be near the starter, but
if the motor is remote and out of sight of the starter then an additional isolator must be
provided near the motor. All isolators, of whatever kind, should be labelled to indicate
which motor they control.
The cutting off of voltage does not include the neutral ins systems where the neutral is
connected to earth. For the purposes of mechanical maintenance, isolators enable the
person carrying out maintenance to ensure that all voltage is cut off from the machine
and the control gear being worked upon, and to be certain that it is not possible for
someone else to switch it on again inadvertently. Where isolators are located remote
from the machine, they should have removable or lockable handles to prevent this
occurrence.
Every motor having a rating exceeding 0.37kW (1/2 hp) must also be controlled by a
starter which incorporates an overcurrent device with a suitable time lag to look after
starting current (IEE Regulation 552-1-2). These starters are generally fitted with
thermal overloads which have an inherent time lag, or with the magnetic type usually
have oil dashpot time lags. These time lags can usually be adjusted, and are normally
set to operate at 10% above full load current. Electronic protective relays are also
available now and these provide a fine degree of protection.
Short circuit protection must be provided to protect the circuit, and shall be placed
where a reduction occurs in the value of the current carrying capacity of the
conductors of the installation (i.e such as in a distribution board). The device may,
however, be placed on the load side of a circuit providing the conductors between the
point where the value of current carrying capacity is reduced and the position of the
Authors: 28
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
protective device do not exceed 3m length and providing the risk of fault current, fire
and danger to persons is reduced to a minimum (IEE Regulation 433-2-2).
When motors take very heavy and prolonged starting currents it may well be that
fuses will not be sufficient to handle the starting current of the motor, and it may be
necessary to install an overcurrent device with the necessary time delay characteristic,
or to install larger cables.
With three phase motors, if fuses protecting the circuit are not large enough to carry
the starting current for a sufficient time, it is possible that one may operate, thus
causing the motor to run on two phases. This could cause serious damage to the
motor, although most motor starters have inherent safeguards against this occurrence.
The ideal arrangement is to back up the overcurrent device in the motor starter with
HBC fuselinks which have discriminating characteristics which will carry heavy
starting currents for longer periods than the overload device. If there is a short circuit
the HBC fuses will operate and clear the short circuit before the short circuit kVA
reaches dangerous proportions.
The diversity applicable to the current demand for a cooker is shown in Table 3 as
10A plus 30% of the remainder of the total connected load, plus 5A if the control unit
includes a socket outlet. A little thought will show that whilst this calculation will give
satisfactory results under most circumstances, there is a danger of triggering the
protective device under some circumstances. For example, at Christmas it is quite
likely that both ovens, all four hotplates and a 3 kW kettle could he simultaneously
connected. Just imagine the chaos which a blown fuse would cause! This alone is a
very good reason for being generous with cable and protective ratings.
2.2.5 Final circuits feeding fluorescent and other types of discharge lighting
Electric discharge lighting may be divided into two groups: those which operate in the
200V/250V range, and the high voltage type which may use voltage up to 5000V to
earth. The first group includes tubular fluorescent lamps which are available in rating
8W to 125W, sodium lamps which are rated from 35W to 400W, also high pressure
mercury vapour lamps rated from 80W to 1000W, and other forms of discharge
lighting. The second group includes neon signs and similar means of high voltage
lighting.
Authors: 29
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
2.2.5.1 Low voltage discharge lighting circuits: Regulations governing the design of
final circuits for this group are the same as those which apply to final circuits feeding
tungsten lighting points, but there are additional factors to be taken into account. The
current rating is based upon the ‘total steady current’ which includes the lamp, and
any associated control gear, such as chokes or transformers, and also their harmonic
currents. In absence of manufacturers’ data, this can be arrived at by multiplying the
rated lamp power in watts by 1.8, and is based on the assumption that the power factor
is not less than 0.85 lagging.
For a circuit consisting of twelve 36W fluorescent lamps, the loading will be 12 x
777.6
36W x 1.8 = 777.6W. For a 240V supply the current will be 3.24 A .
240
Some fluorescent lamp circuits (especially the 125W switch start type) have very poor
characteristics, and manufacturers should be consulted as to the line current which
may be expected. In some instances it has been found necessary to multiply the rated
power (Watts) of the lamp by 2. This means that the line current would be
125 x 2
1.04 A per lamp.
240
The control gear for tubular fluorescent lamps is usually enclosed in the casing of the
luminaire, but for other of discharge lighting, such as h.p mercury and sodium, the
control gear is sometimes mounted remote from the luminaire. Here is necessary to
check the current which will flow between the control gear and the lamp. The remote
control gear must be mounted in a metal box, must be provided with adequate means
for the dissipation of heat, and spaced from any combustible materials.
Another disadvantage of locating control gear remote from discharge lamps is that, if
a fault develops in the wiring between the inductor and the lamp, the presence of the
inductor will limit the fault current so that it may not rise sufficiently to operate fuse.
Such a fault could very remain undetected. If any faults develop in these circuits this
possibility should be investigated.
2.3.1 General
Part 3 of BS 7671 requires the electrical installation designer to make an assessment
of the entire electrical system. An electrical installation forms part of the complete
system, the other constituent parts being the LV supply source and the interlinking LV
distribution lines.
Regulation 301-01 (pg 38) requires this assessment to include the characteristics of
the installation, such as the purpose for which the installation is to be used, its
Authors: 30
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
structure generally, the nature of the supply to the installation, the external influences
to which equipment will be exposed, the compatibility and maintainability of that
equipment in service, any safety services (such as emergency lighting and fire alarm
systems) and the need for continuity of service. The need for this assessment is
obvious, in that the particular characteristics of the supply and installation will
influence, if not dictate, the methods used to protect against the hazards referred to in
Chapter 13 (electric shock, excessive temperatures, and so on).They will also have a
bearing on the choice of equipment, including wiring systems.
2.4.1 General
Whilst ‘maximum demand’ and ‘diversity’ are not defined in BS 7671, it is necessary
to be clear that such terms are understood by all concerned in the design process. For
example, ‘maximum demand’ may mean different things to the supply engineer and
the installation design engineer. In this text, the following meanings have been
assigned to the terms used.
Diversity is the engineering principle that in any given installation, some of the
connected loads will not be running at the same time instant as other loads. This
principle can be further broken down into two types of load as follows:
1. Loads that, due to the law of averages, will not be on at the same time.
2. Loads that, due to fact, will not be on at the same time.
Apart from indicating that diversity and maximum demand must be assessed, the
Regulations themselves give little help. Suggestions of values for the allowances for
diversity are given in Table 2.
Authors: 31
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
Table 2: Allowance for diversity (Table H1 of IEE Guidance Note 1 Selection and
erection)
Purposes of final Type of premises
circuit fed from Individual household Small shops, stores, Small hotels,
conductors or installations, including offices and business boarding houses,
switchgear to which individual dwellings of premises guess houses, etc
diversity applies a block
1. Lighting 66% of total current 90% of total current 75% of total current
demand demand demand
2. Heating and power 100% of total current 100% f.l of largest 100% f.l of largest
(but see 3 and 8 demand up to 10 appliance + 75% f.l of appliance + 80% f.l of
below) amperes + 50% of any remaining appliances second largest
current demand in appliance + 60% f.l of
excess of 10 amperes remaining appliances
3. Cooking appliances 10 amperes + 30% f.l of 100% f.l of largest 100% f.l of largest
connected cooking appliance + 80% f.l of appliance + 80% f.l of
appliances in excess of second largest second largest
10 amperes + 5 amperes appliance + 60% f.l of appliance + 60% f.l of
if socket outlet remaining appliances remaining appliances
incorporated in unit
4. Motors (other than 100% f.l of largest 100% f.l of largest
lift motors which are motor + 80% f.l of motor + 50% f.l of
subject to special second largest motor + remaining motors
consideration) 60% of f.l of remaining
motors
5. Water-heaters 100% f.l of largest 100% f.l of largest 100% f.l of largest
(instantaneous type)* appliance + 100% f.l of appliance + 100% f.l of appliance + 100% f.l
second largest appliance second largest of second largest
+ 25% f.l of remaining appliance + 25% f.l of appliance + 25% f.l of
appliances remaining appliances remaining appliances
6. Water-heaters No diversity allowable**
(thermostatically
controlled)
7. Floor warming No diversity allowable**
installations
8. Thermal storage No diversity allowable**
space heating
installations
Type of premises
Authors: 32
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
Authors: 33
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
Where luminaires operate at a power factor less than unity (e.g. power-factor-
uncorrected fluorescent luminaires), and in the absence of more precise information, a
multiplying factor of 1.8 (see Section 10.4.2 of this Guide) must be applied to the
calculated current derived from the wattage rating. Where the actual wattage of a
luminaire is not known, a minimum of 100W per lamp must be allowed (see item H
of Table 4.1 of this Guide).
Diversity for lighting circuits will depend on the type of premises, and in Table H2 of
IEE Guidance Note 1 Selection and erection these are given as
domestic premises – households, including flats 66%;
commercial premises – shops, offices, stores and other business premises
90%;
commercial premises – guest houses, small hotels, boarding houses 75%.
By way of example, three shop lighting circuits with connected load (and maximum
demand) of 15A, 7A and 12A would represent (after applying an allowance for
diversity of 0.9) a load of 30.6A – i.e. 0.9(15 + 7 + 12) – on the supplying distribution
board.
Diversity for heating circuits will depend on the type of premises, and in Table H2 of
IEE Guidance Note 1 Selection and erection these are given as
domestic premises – households, including flats: 100% of first 10 A plus 50%
of remainder;
commercial premises – shops, offices, stores and other business premises:
100% of largest heater plus 75% of remaining heaters;
commercial premises – guest houses, small hotels, boarding houses: 100% of
largest heater plus 80% of next largest heater plus 60% of remaining heaters.
By way of example, five boarding house heaters, three rated at 3kW and two rated at
2kW, are fed from a common distribution board. With allowance for diversity, these
heaters would represent a load of 9.6kW, i.e. (1 x 3) + (0.8 x 3) + (0.6 x 3) + (0.6 x 2)
+ (0.6 x 2).
Authors: 34
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
By way of example, three small hotel cookers, two rated at 12kW and one rated at
10kW, are fed from a common distribution board. With allowance for diversity, these
cookers would represent a load of 27.6kW, i.e. 12 + (0.8 x 12) + (0.6 x 10).
There is no allowable diversity for water heaters which are thermostatically controlled
(e.g. immersion heaters and storage water heaters).
By way of example, three office instantaneous water heaters, two rated at 7kW and
one rated at 3kW, are fed from a common distribution board. With allowance for
diversity, these water heaters would represent a load of 14.75kW, i.e. 7 + 7 + (0.25 x
3).
By way of example, three motors in an office boiler house, two rated at 11A and one
rated at 5A, (and all operating at 0.8 power factor), are fed from a common
distribution board. With allowance for diversity, these motors would represent a load
of 32.5A, i.e. [11 + 11 + (0.8 × 5)]/0.8. This value represents the steady-state loading,
and allowance should also be made for the high starting currents associated with the
particular motors. The motor manufacturer must be consulted where there is doubt
Authors: 35
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
about the starting currents (typically six times the steady-state current). Consideration
should also be given to simultaneous starting of motors and the effects on distribution
circuits. Sequential starting may need to be adopted to prevent unacceptable
cumulative starting currents. Lift motors are the subject of special consideration, and
reference should be made to the requirements of BS 5655 or BS EN 81-1, as
applicable.
By way of example, three conventional circuits in a shop, two rated at 32A (ring final
circuits) and two rated at 20A (radial circuits), are fed from a common distribution
board. With allowance for diversity, these circuits would represent a load of 68A, i.e.
32 + 0.5(32 + 20 + 20).
There will be many occasions where the designer will find the installation will not fall
neatly into any one of the above three categories and will need to use professional
judgement and experience to assess diversity.
Authors: 36
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
Example 1:
A shop has the following single-phase loads, which are balanced as evenly as possible
across the 415 V three-phase supply.
2 x 6 kW and 7 x 3kW thermostatically controlled water heaters
2 x 3 kW instantaneous water heaters
2 x 6 kW and 1 x 4 kW cookers
12 kW of discharge lighting (Sum of tube ratings)
8 x 30A ring circuits feeding 13A sockets.
Calculate the total demand of the system, assuming that diversity can be applied.
Calculations will be based on Table 3.
Solution:
415
The single-phase voltage for a 415V three-phase system is 240V .
3
All loads with the exception of the discharge lighting can be assumed to be at unity
power factor, so current may be calculated from
P
I
V
Authors: 37
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
Cookers
Discharge lighting
90% of total which must be increased to allow for power factor and control gear
losses.
90 12000
Lighting current x x1.8 81.1 A
100 240
Ring circuits
First circuit 100%, so current is 30 A
50
75% of remainder x30Ax 7 105A
100
Total current demand for ring circuits = 135A
Example 2
A 240 V domestic cooker has the following connected loads:
top oven 1.5kW
main oven 2.5kW
grill 2.0kW
four hotplates 2.0kW each
The cooker control unit includes a 13 A socket outlet. Calculate a suitable rating for
the protective device. Calculate the total demand of the system, assuming that
diversity can be applied.
Solution:
Assume the power factor, cos θ is 1.
The total cooker load is 1.5 + 2.5 + 2.0 + (4 x 2.0) kW = 14 kW
3
P 14 x10
Total current 58.3 A
V 240
Authors: 38
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
Example 3
A domestic premise with a 240V 50 Hz supply protected by a 100A BS 1361 supply
fuse has the following loads:
Calculate the total demand of the system, assuming that diversity can be applied.
Example 4
A retail jeweler has the following connected load supplied at 240V 50 Hz:
a) Direct heaters 2×2kW, 3×1.5kW, 1×1.0kW
b) Cooker 5kW (cooker unit has socket outlet)
c) Water heating (thermostatic) 3kW
d) Socket outlets 30A ring circuit
e) Shop and window lighting 2.5kW total.
Determine the assumed maximum demand. Assumed maximum demand using IEE
On-Site Guide Table 1B (small shop premises).
Example 5
A small hotel supplied at 400/230 V 50 Hz has the following connected load:
a) 100 lighting outlets
b) 50×13 A socket outlets on 6×30 A ring circuits
c) 30×1 kW convection heaters on coin-operated meters
d) 16 kW thermal storage central heating boiler
e) Cooking equipment – 2×14 kW cookers, 1×4 kW hot cupboard, 3×2 kW
fryers,
f) 4×600W microwave ovens plus 5kW machines.
Authors: 39
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
The examination of actual values of apparent power required by each load enables the
establishment of:
A declared power demand which determines the contract for the supply of
energy. Need to deal with TNB.
The rating of the MV/LV transformer, where applicable (allowing for expected
increased load).
Level of load current at each distribution board.
Induction Motor
Current demand
The full load current, Im,fl supplied to the motor is given by the following formulae:
Authors: 40
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
Prated
I m , fl
3 xVxx cos
Where:
I m , fl = nominal full load current of the motor
Prated = Rated power
V = voltage between phases for three phase motor and voltage between
the
terminals voltage for single phase motors (in volts)
η = efficiency of the motor
cos θ = power factor
Motor-starting current
Starting current (Istart) for 3-phase induction motors, according to motor type, will be:
for direct-on-line starting of squirrel-cage motors:
Istart = 4.2 to 9 Im,fl for 2-pole motors
Istart = 4.2 to 7 Im,fl for motors with more than 2 poles (mean value = 6 Im,fl),
where
Im,fl = nominal full-load current of the motor
for wound-rotor motors (with slip-rings), and for D.C. motors:
Istart depends on the value of starting resistances in the rotor circuits:
Istart = 1.5 to 3 Im,fl (mean value = 2.5 Im,fl ).
Appendix 2.1 shows, as a function of the rated nominal power of motors, the current
supplied to them at different voltage levels under normal uncompensated conditions,
and the same motors under the same conditions, but compensated to operate at a
power factor of 0.93 (tan θ = 0.4). These values are averages and will differ to some
extent according to the type of motor and the manufacturer concerned.
Note: the rated voltages of certain loads listed in table B4 are still based on 220/380V.
The international standard is now (since 1983) 230/400V.
To convert the current values indicated for a given motor rating in the 220V and 380V
columns to the currents taken by 230V and 400V motors of the same rating, multiply
by a factor of 0.95.
For an incandescent lamp, the use of halogen gas allows a more concentrated light
source. The light output is superior and the life of the lamp is doubled.
Note: at the instant of switching on, the cold filament gives rise to a very brief but
intense peak of current.
where V = the voltage applied to the lamp, complete with its related equipment.
If no power-loss value is indicated for the ballast, a figure of 25% of Pn may be used.
Authors: 42
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
Table 4 gives the current taken by a complete unit, including all associated ancillary
equipment. These lamps depend on the luminous electrical discharge through a gas or
vapour of a metallic compound, which is contained in a hermetically sealed
transparent envelope at a predetermined pressure. These lamps have a long start up
time, during which the current, I is greater than the nominal current, I n. Power and
current demands are given for different types of lamp (typical average values which
may differ slightly from one manufacturer to another.
The power in watts indicated on the tube of a discharge lamp does not include the
power dissipated in the ballast.
Circuit supplying discharge lighting must be capable of carrying the total steady
current of the lamp and associated control gear, including their harmonic currents.
Where more exact information is not available and the resulting power factor of the
circuit is not less that 0.85 lagging, the current demand can be determined from the
following formula:
The multiplier of 1.8 is based on the assumption that the circuit is corrected to the
power factor of not less than 0.85 lagging, and it takes into account control gear losses
and harmonic currents. The 1.8 multiplier applied to the lamp watts is projected
demand in volt amperes.
For example:
A circuit supplying 8 x 36W fluorescent luminaries connected to a 240V supply
would take a current of:
8x36Wx1.8
I 2.16A
240
Authors: 43
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
Authors: 44
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
Authors: 52
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
Authors: 53
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
APPENDIX 2.2: DIVERSITY FACTOR UPDATE 2009
Note: If S/S/O are to much, the diversity factor need to decrease to 0.2
Authors: 54
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis