Data Sheet N2XH-J, N2XH-O: DB 1550556EN Application
Data Sheet N2XH-J, N2XH-O: DB 1550556EN Application
Data Sheet N2XH-J, N2XH-O: DB 1550556EN Application
Lapp
GmbH DATA SHEET
N2XH-J, N2XH-O DB 1550556EN
Valid from: 13.02.2017
Application
N2XH are halogen free, highly flame retardant power cables for installation indoors, in the air or concrete. For outdoor use
the cable should be protected against sunlight and the temperature range should be considered. Not intended for direct-
buried installations or in water. Strains of more than 15 N/mm² are not allowed.
Application range:
Especially for use in power stations, in transformer stations and for power supply and particularly where human life as well
as valuable property are exposed to high risk of fire hazards.
Core insulation irradiated Polyethylene compound 2XI1 acc. to VDE 0276-604 (VDE 0276-604)
Outer sheath Halogen free, thermoplastic Polyolefin-compound HM4 acc. to VDE 0276-604
(VDE 0276-604)
Electrical properties
Nominal voltage U0/U 0,6 / 1 kV
Flammability Flame retardant acc. IEC 60332-1-2 resp. EN 60332-1-2 (VDE 0482-332-1-2)
No Flame propagation acc. IEC 60332-3-24 resp. EN 60332-3-24 (VDE 0482-332-3-24)
EC-Directives This cable is conform to the EC-Directives 2006/95/EG (Low Voltage Directive) and
2011/65/EU (RoHS, Restriction of the use of certain hazardous substances).