2400
2400
OVERVIEW
The MicroPanel comes equipped standard with four relays (MicroPanel-4) and provides integration
features simply not available anywhere else, particularly in its daylight harvesting properties. In its
extended version, the MicroPanel is a compact lighting controller with up to eight switching (iDH)
and four 0 - 10V dimming (iDM) outputs. For more points of control, the MicroPanel-8 provides 8
switching outputs, 4 of which can be dimmed outputs using a single control card. For applications
that require more than four 0-10V dimming outputs, a second control card may be added.
FEATURES
• Digital (global) or local wall switches
GR 2400™
• Digital (global) or local photosensors and occupancy sensors MicroPanel
• GR 2400 system integration
• Time-of-day scheduling
• Back plate mounting to allow enclosure only to be shipping for rough-inK
• Normal or Emergency Power rating
Warranty
Three-year limited warranty. Complete warranty terms located at:
www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx
Note: Actual performance may differ as a result of end-user environment and application.
Specifications subject to change without notice.
ORDERING INFORMATION
MicroPanel INTERIOR and ENCLOSURE must be ordered on separate lines, see Examples.
MicroPanel Interior Relay Type Clock Option Transformer Voltage Barrier Input Card 2,3
GR2404 INT 4 Relay [qty]NCL Normally closed, Latching IDH4 iDH control card for DV Dual voltage [blank] No barrier [blank] No card
[qty]NOL Normally open, Latching GR2404 120/277V 1VB 1 barrier1 D14 14 inputs
GR2408 INT 8 Relay
[qty]DPNC Double pole, normally IDH8 iDH control card for 347 347V (no
closed GR2408 enable/
IDIM4 iDim control card for disable)
[qty]DPNO Double pole, normally
open GR2404
[qty]RRP Reed relay pair IDIM8 iDim control card for
GR2408
[qty]SPDT Single pole, Double throw
[qty]SPDTC Single pole, Double throw
contractor
Notes:
1. Compliance with all codes concerning any internal barrier for normal and emergency power separation is up to the discretion of the authority having jurisdiction.
2. Input card option for GR2404 INT requires a GR2408 ENC. Input card option for GR2408 INT requires an additional GR2404 ENC to be specified.
3. Input card option requires NEMA1 enclosure.
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com GR2400_MICROPANEL
© 2014-2018 Acuity Brands Lighting, Inc. All rights reserved. Rev. 10/23/18 1 of 2
OVERVIEW
2nd CONTROL CARD PROVIDES OCCUPANCY SENSOR
AN ADDITIONAL 100mA FOR 300mA AVAILABLE FOR POWER
OCCUPANCY SENSORS. 3-WAY WALL SWITCH
(WITHOUT ON/OFF LABEL AS PER CODE) WIRING SHOWN IS NOT APPLICABLE FOR CERTAIN NOVITAS BRAND SENSORS.
UP TO 8 INPUTS PER CARD SHARED WITH CHECK WITH LC&D FOR A LIST OF APPROVED MANUFACTURERS.
DO NOT CONNECT 24V
UNIVERSAL INDOOR VISIT www.lightingcontrols.com FOR OCC SENSOR CONNECTION GUIDES or
TERMINAL TO ANY OTHER OCC SENSOR
PHOTOSENSORS CARD’S 24V TERMINAL BRAND SPECIFIC WIRING DETAILS
(PCELL 3WI TZ/SLI TZ)
GR2400 BUS
TO NEXT DIGITAL GND
UP TO 4 PER CARD, ONE PER EACH FROM PREVIOUS DIGITAL
INPUT WITH EACH PHOTOCELL DEVICE 24V
DEVICE
CONTROLLING NO MORE THAN TWO
INPUTS. CONTACT
CLOSURE
REFER TO SUBMITTAL
RELAY
DOCUMENTATION WHERE APPLICABLE **SEE NOTE BELOW COMMON
-OR- DOCUMENT THE INPUTS USED AND
FORWARD INFORMATION TO LC&D TECH
SUPPORT
RED
GREEN
BLUE
ADDITIONAL
BLUE
BALLASTS
TERMI-
NATOR
GND
24V
1
4
3
2
GND
24V
ADDRESS RJ45 RJ45
PHOTOCELL
BUTTON
INPUTS 10-0V
ON LINE
*REFER TO SUBMITTAL DOCUMENTATION WHERE
TO ANY
APPLICABLE -OR- DOCUMENT THE SCENE INPUTS
COM
OPTIONAL: 0-10V SCENE
USED AND FORWARD INFORMATION TO LC&D TECH
1
INPUT*
4
3
2
DIMMING OUTPUTS
SUPPORT
(ON iDIM CARDS)
DIODE
CONTROL CARD **UNBLOCKED BLOCKED**
**SEE NOTE BELOW
EACH CHANNEL IS LINKED TO ITS
CORRESPONING REALY NUMBER
DIMMING BALLST
TYPICAL 0-10V BALLAST
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LINE
LINE
LINE
LINE
LINE
LINE
LINE
LINE
NEUTRAL
OR
LINE
DIMENSIONS
Seismic Certification:
MICRO PANEL-4 (2 OR 4 RELAYS)
• NEMA 1 - 8.375” W x 8.375” H x 3.125” D • Preapproved for use in Category IV structures with an Importance Factor of 1.5
• NEMA 4/4X/12 - 12”W x 16”H x 6”D • California Office of Statewide Health Planning and Development (OSHPD) Special
Seismic Certification Preapproval (# OSP-0091-10)
MICRO PANEL-8 (6 OR 8 RELAYS)
• NEMA 1 - 12.875” W x 8.375” H x 3.125” D Evaluated per the requirements of:
• NEMA 4/4X/12 - 16”W x 20”H x 6”D • 2007/ 2010 California Building Code
• Section 13.2.5 of (American Society of Civil Engineers / Structural Engineering
SPECIFICATIONS Institute) ASCE/SEI 7-05
• Tested to: ICC-ES AC156
Electrical
• Power Supply Input: 120/277VAC or 120/347VAC Standard Relay NCL (Normally Closed)
• Accessory Power (For Occupancy Sensor): 24VDC, 450mA • 30A@277VAC Ballast
• 20A@120VAC Tungsten
Mechanical • 20A@347VAC Ballast
• Surface mount,, NEMA 1, screw cover door, • SCCR 18kA @ 277VAC
• EZ-Find™ yellow powder coat • Rated 250,000 Cycles
• Flush mount NEMA 1 available
• Surface mount NEMA 4, 4X, 12 available Optional Relays
• Normally Open (NOL)
Environmental • Two Pole - NOL or NCL (480VAC)
• Ambient: 32°F to 104°F (0°C to 40°C) • Double Throw - 20A@ 277VAC
• Relative Humidity: 10-90% non-condensing
Inputs/Outputs
Standards • Photosensor Inputs - 4 (8 with optional 2nd control card)
• UL and cUL to UL 916, available for mounting in an air plenum (with • Local Switch Inputs - 8 (16 with optional 2nd control card)
suitable enclosure) for City of Chicago • 0-10V Dimmed Outputs - 4 (8 with optional 2nd control card, 15mA
• ETL Listed to UL 924 (for emergency circuit use) per channel
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com GR2400_MICROPANEL