Dcu Abb
Dcu Abb
Dcu Abb
Hardware Manual
Drive Control Unit
RDCU-02(C)
3
RDCU-02(C) layout
Designations A…C and J1 refer to the section Mechanical installation below. The
connectors (X…) are explained under Technical data further below.
A B A
X39
C
X20
X34
X21 X31
J1
X32
X22
X23 X33
C
X25
X26
X68
X27 X57
A B A
Safety instructions
Do not attempt any work on a powered drive. After switching off the mains, always
allow the intermediate circuit capacitors 5 minutes to discharge before working on
the frequency converter, the motor or the motor cable. It is good practice to check
(with a voltage indicating instrument) that the drive is in fact discharged before
beginning work.
Avoid touching the circuit board (RMIO) inside the RDCU-02(C) unit in order to
minimise the risk of damage caused by static electricity.
Do not use excessive force when detaching connectors or removing the cover of the
unit.
Mechanical installation
General
The RDCU-02(C) can be mounted on a vertical or horizontal 35 × 7.5 mm DIN rail.
The unit should be mounted so that air can freely pass through the ventilation holes
in the housing. Mounting directly above heat-generating equipment should be
avoided.
Wiring
General
The shields of the I/O cables should be grounded to the chassis of the cubicle as
close to the RDCU as possible.
Use grommets at all cable entries.
Handle fibre optic cables with care. When unplugging fibre optic cables, always grab
the connector, not the cable itself. Do not touch the ends of the fibres with bare
hands as the fibre is extremely sensitive to dirt.
The maximum long-term tensile load for the fibre optic cables included is 1 N; the
minimum short-term bend radius is 25 mm (1”).
Other connections
See also the wiring diagram below.
Powering the RDCU
The RDCU is powered through connector X34. The unit can be powered from the
power supply board of the inverter (or IGBT supply) module, provided that the
maximum current of 1 A is not exceeded.
The RDCU can also be powered from an external 24 V DC supply. Note also that the
current consumption of the RDCU is dependent on the optional modules attached.
(For current consumption of optional modules, see their respective user manuals.)
Fibre optic connection to inverter/IGBT supply module
Connect the PPCS link of the AINT (ACS 800 series modules) or NINT (ACS 600
series modules) board of the inverter (or IGBT supply) module to fibre optic
connectors V57 and V68 of the RDCU.
Note: The recommended maximum distances for the fibre optic link is 10 m (for
plastic [POF] cable). In case longer distances are required, contact an ABB
representative.
I 0 I 0
V41 V42 1 2 V1 V2 1 2
R2i/R3i: NINT/X34 R7i/R8i: APOW/X3
R4i/R5i: NPOW/X34
R6i/R12i: NPOW/X35
NINT 1 A max. AINT 1 A max.
Technical data
General
Mounting: Onto 35 × 7.5 mm DIN mounting rail
Housing materials: Zinc-plated steel (base); ABS/PC (cover)
Connector types
X20 (Constant voltage output): 2-pole detachable screw terminal block*
X21 (Analogue I/O): Four 3-pole detachable screw-type terminal blocks*
X22 (Digital inputs): One 3-pole and two 4-pole detachable screw-type terminal
blocks*
X23 (24 VDC output): 2-pole detachable screw-type terminal block*
X25-X27 (Relay outputs): Three 3-pole detachable screw-type terminal blocks*
X31 (Slot 1), X32 (Slot 2): 38-pin header (female), pitch 2 mm
X33 (DDCS): 20-pin header (female), pitch 2.54 mm
X34 (24 VDC power input): 3-pole detachable screw-type terminal block*
X39 (Control panel): 12-pin header (male), pitch 2.54 mm
V57, V68 (PPCS link): Fibre optic transmitter/receiver (10 MBd)
*Wire: 0.3 … 3.3 mm2 (22…12 AWG). Torque: 0.2 … 0.4 Nm (2…4 lbf.in.).
Pitch: 5.0 mm.
Slot 1 (X31)
General: For connection of I/O extension modules (such as RAIO and RDIO), pulse
encoder interface (RTAC), or fieldbus adapters (such as RPBA and RMBA)
Slot 2 (X32)
General: For connection of I/O extension modules (such as RAIO and RDIO) or
pulse encoder interface (RTAC)
DDCS (X33)
General: For connection of RDCO-0x(C) DDCS Communication module
Jumper J1
General: See Isolation and grounding below
Pitch: 2.54 mm
LEDs
“Power”: Green; denotes +5 V power OK
“Fault”: Red
Ambient conditions
Operating temperature: +0 … +60 °C (32…140 °F)
Storage temperature: -40 … +70 °C (-40 … +158 °F)
Applicable standards
Immunity: IEC 61800-3 (Limits: Industrial, Second environment); EN 50081-2
(Limits: Industrial)
Emission: EN 50081-2 (Limits: Industrial)
PELV requirements: The terminals of the RMIO board as well as on the optional
modules attachable to the board fulfil the Protective Extra Low Voltage (PELV)
requirements stated in EN 50178 provided that the external circuits connected to the
terminals also fulfil the requirements.
9 AO1+
10 AO1-
11 AO2+
12 AO2-
X22
1 DI1
2 DI2
3 DI3
4 DI4
Jumper J1 settings:
9 DGND
Dimensions