0% found this document useful (0 votes)
115 views2 pages

East Halmahera Ferronickel Development Project (P3Fh Project)

This document outlines the sequence of energizing the LSS-13 electrical distribution system for the East Halmahera Ferronickel Development Project. It details the status of circuit breakers in the 6.6kV switchgear, 6.6kV/415V transformer, 415V panel, and motor control centers during each step of the energization process. The sequence involves opening or closing specific circuit breakers in a coordinated manner to safely energize components and equipment in a specific order.

Uploaded by

nailulfalah17
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
115 views2 pages

East Halmahera Ferronickel Development Project (P3Fh Project)

This document outlines the sequence of energizing the LSS-13 electrical distribution system for the East Halmahera Ferronickel Development Project. It details the status of circuit breakers in the 6.6kV switchgear, 6.6kV/415V transformer, 415V panel, and motor control centers during each step of the energization process. The sequence involves opening or closing specific circuit breakers in a coordinated manner to safely energize components and equipment in a specific order.

Uploaded by

nailulfalah17
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

EAST HALMAHERA FERRONICKEL DEVELOPMENT

PROJECT (P3FH PROJECT)

SEQUENCE OF ENERGIZING LSS-13


MV Switchgear 6.6 kV 1006MVP01
Status Status During Energize
No. Feeder
Pre-Condition Step 1 Step 2
1 Incoming from 4001MVP11 Open Close Close
2 Outgoing to 1006TRF01 Open Open Close
3 Outgoing to 1008MVP01 Open Open Open
4 Outgoing to 1006PFC01 Open Open Open
5 Spare Open Open Open
6 Outgoing to Rotary Kiln 1601BM01 Open Open Open
7 Outgoing to Rotary Kiln 1601AM01 Open Open Open
8 Outgoing to Exhaust Fan 1703M01 Open Open Open
9 Outgoing to Roots Blower 1723M01 Open Open Open

LV Panel 1006LVP01
Status Status During Energize
No. Feeder
Pre-Condition Step 1 Step 2A Step 2B Step 2C
1 Incoming from 1006TRF01 Open Close Close Close Close
2 Outgoing to 1702LCP01-04 Open Open Open Open Open
3 Outgoing to 1006MCC01 Open Open Close Close Open
4 Outgoing to 1006MCC02 Open Open Open Open Close
5 Spare Open Open Open Open Open
6 Outgoing to LDP13 Open Open Open Open Open
7 Outgoing to 1007MCC01 Open Open Open Open Open

MCC Panel 1006MCC01 & 1006MCC02


Status Status During Energize
No. Feeder
Pre-Condition Step 1A Step 2A Step 1B Step 2B
1 Incoming 1006MCC01 from 1006LVP01 Open Close Close Close Close
2 Outgoing to 4001UPS01 Open Open Open Open Close
3 Outgoing to 1006UPS01 Open Open Close Open Open
4 Incoming 1006MCC02 from 1006LVP01 Open Open Open Open Open
5 Outgoing to 1006UPS02 Open Open Open Open Open

Note :
1 Before Energize panel, Busbar must be finished Insulation Test
2 Before Energize panel, Incoming Breaker Setting must be checked first
3 Before Energize panel, Transformer signal for Trip/Alarm must be checked
4 All Feeder that not energized must be racked out
5 a. Blue highlight is general sequence
b. Brown highlight is sequence for Energize 1006UPS01
c. Yellow highlight is sequence for Energize 4001UPS01
d. Green highlight is sequence for Energize 1006UPS02
OF ENERGIZING LSS-13

Status During Energize


Step 1C Step 2C
Open Open
Open Open
Open Open
Close Close
Open Close

You might also like