Fan Application Manual
Fan Application Manual
APPLICATION
MANUAL
Part 1 of the Fan Application Manual. Provides basic information necessary for the design of
energy efficient air systems. This edition includes examples in both the Inch-Pound and SI
systems as the reader is provided with basic information on air systems.
Part 2 of the Fan Application Manual. Discusses the effect of inlet and outlet connections on fan
performance. It includes separate axial fan factors and is aimed primarily at the designer of the
air moving system.
Part 3 of the Fan Application Manual. Helps to identify and correct problems with the
performance and operation of the air moving system after fan installation.
Part 4 of the Fan Application Manual. Reviews the methods of making field measurements for
calculating the actual performance of the fan and system.
AMCA
Publication 200-95
(R2007)
Air Systems
Air Systems
All rights reserved. Reproduction or translation of any part of this work beyond that permitted by Sections 107 and
108 of the United States Copyright Act without the permission of the copyright owner is unlawful. Requests for
permission or further information should be addressed to the Executive Director, Air Movement and Control
Association International, Inc. at 30 West University Drive, Arlington Heights, IL 60004-1893 U.S.A.
Authority
AMCA Publication 200-95 was adopted by the membership of the Air Movement and Control Association
International, Inc. in 1995, and it was reaffirmed in 2000 and 2007.
Foreword
This publication is intended to provide basic information needed to design effective and energy efficient air
systems. in those cases where the system handles a gas other than air, the design data must be modified to allow
for the different physical properties of the gas being used.
Discussion is limited to systems where there is a clear separation of the fan inlet and outlet and does not cover
applications in which fans are used only to circulate air in an open space.
The design of most air sytems is based on airflow velocities which result in turbulent airflow. Some applications
require very low velocities, resulting in laminar flow conditions; others may require very high velocities, approaching
the speed of sound (Mach 1). The information given in this publication applies only to turbulent flow conditions and
not to these special systems using very low or very high flow velocities.
The flow through an air system will stabilize when the total pressure provided by the fan is exactly equal to the total
pressure losses in the system.
To achieve the desired airflow in the system the diesgner must have complete information on:
a) System Pressure Losses: The total pressure loss due to friction losses, shock losses, dissipation of velocity
pressure at the system discharge, and static pressure differences between the entry and discharge
openings. System pressure losses are discussed in detail in Section 4.
b) Fan Performance Characteristics: The relationship of the total pressure rise and the volume flow generated
by the fan. Fan performance characteristics are reviewd in Section 5. More complete information is
contained in AMCA Publication 201, Fans and Systems.
c) System Effect: The effect on the performance of the fan resulting from the difference between the fan inlet
and outlet connections to the installed system and the standardized connections used in laboratory tests
to obtain fan performance ratings. A practical approach to estimating System Effects is explained in AMCA
Publication 201, Fans and Systems.
This manual has been prepared by the Air Movement and Control Association, Inc. The information contained in
this manual has been derived from many sources and is believed to e accurate. Please note that the
recommendations contained herein do not necessarily represent the only methods or procedures appropriate for
the situation discussed, but rather are inteded to present consensus opinions and practices of the air movement
and control industry which may be helpful, or of interest to those who design, test, install, operate or maintain fan-
duct systems. Thus, AMCA disclaimes any and all warranties, expressed or implied, regarding the accuracy of the
information contained in this maual and further disclaims any liability for the use or misuse of this information.
AMCA does not guarantee, certify or assure the performance of any fan-duct system designed, tested, installed,
operated or maintained on the basis of the information provided in this manual.
Air Movement and Control Association International, Inc. will consider and decide all written complaints regarding
its standards, certification programs, or interpretations thereof. For information on procedures for submitting and
handling complaints, write to:
or
Air Systems is intended to provide basic information needed to design effective and energy efficient air systems.
Discussion is limited to systems where there is a clear separation of the fan inlet and outlet and does not cover
applications in which fans are used only to circulate air in an open space.
Fans and Systems is aimed primarily at the designer of the air moving system and discusses the effect on inlet and
outlet connections of the fan's performance. System Effect Factors, which must be included in the basic design
calculations, are listed for various configurations. AMCA 202 and AMCA 203 are companion documents.
System Checklist
Fan Manufacturer's Analysis
Master Troubleshooting Appendices
Troubleshooting is intended to help identify and correct problems with the performance and operation of the air
moving system after installation. AMCA 201 and AMCA 203 are companion documents.
Acceptance Tests
Test Methods and Instruments
Precautions
Limitations and Expected Accuracies
Calculations
Field Performance Measurements of Fan Systems reviews the various problems of making field measurements
and calculating the actual performance of the fan and system. AMCA 201 and AMCA 202 are companion
documents.
TABLE OF CONTENTS
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.2 Subscripts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3. Properties of Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4. Airflow ...................................................................... 5
Air systems are often required to operate 1.1.4 Control devices. In many air systems it is
satisfactorily in a wide range of environmental necessary to regulate and control the flow through
conditions. The conditions which will be encountered the system in response to some monitoring signal,
must be considered in the design of the ducts, pipes, usually temperature or pressure. It may be also
etc., which will contain the airflow and constitute the necessary to regulate the flow in the individual
boundary of the system. branches of the system. Control devices such as
dampers function by controlling the amount of airflow.
1.1 Air system components In some cases, the output of the fan can be varied by
other methods (variable speed motor, variable inlet
A typical air system may contain one or more of the vanes, variable pitch impeller, etc.)
following (see Figure 1):
1.1.5 Conditioning device. Most air systems are
a) System inlet designed to take air from the inlet and change its
b) Distribution system condition before discharging it at the outlet. Changes
c) Fan may include the temperature, humidity, pressure,
d) Control device contaminant level and cleanliness, etc., of the air.
e) Conditioning device Many conditioning devices require outside energy
f) System outlet sources, for example, heating and cooling coils; other
components such as filters are passive devices and
1.1.1 System inlet. An air system usually includes have no external energy connection. All conditioning
devices such as louvers, filters, screens, guards, devices increase the pressure drop across the
grilles, etc., where the air enters the system. These system and this effect must be considered in the
are used for safety reasons as well as to inhibit the selection of the fan.
entry of rain, dust, and other unwanted matter. Their
appearance may be important as they are usually 1.1.6 System outlet. An air system usually includes
visible on the exterior of a structure. a special component at the termination of the system
or at the end of each of the system's branches, such
1.1.2 Distribution system. Most air systems are as a simple screen or louver. In many cases the
made up of ducts specially designed and constructed distribution of the air at the outlet to the receiving
to convey air from the system inlet(s) to the system space is very important, e.g., in an occupied air
outlet(s). In some cases, enclosed spaces in the conditioned room. These systems require carefully
structure such as plenums above ceilings or holes in selected outlets and diffusing devices to achieve
walls may be used to confine and direct the flow. desirable air motion and temperature conditions in
the conditioned space. Typical devices are ceiling
1.1.3 Fan. Understanding the design and opera-tion diffusers and grilles. In some cases these may
of air systems begins with an understanding of the incorporate control devices such as dampers and
mixing boxes.
1
AMCA 200-95 (R2007)
SYSTEM
INLET
COIL BRANCH
DUCT
FILTER
LOUVER
DAMPER
DIFFUSER
2
AMCA 200-95 (R2007)
2. Symbols and Subscripts
A Area m2 (ft2)
Ae Area-Orifice Equivalent to System m2 (ft2)
Ao Area-Nozzle with no loss m2 (ft2)
ah Absolute Humidity kg/m3 (lb/ft3)
C Dynamic Loss Coefficient Dimensionless
Cd Coefficient of Discharge Dimensionless
Cn Coefficient of Nozzle Discharge Dimensionless
c Speed of Sound m/s (ft/s)
D Duct Diameter and Equivalent Diameter m (ft)
E System Resistance Curve Dimensionless
ε Absolute Surface Roughness Height m (ft)
f Friction Coefficient Dimensionless
g Gravity m/s2 (ft/s2)
γ Ratio of Specific Heats Dimensionless
K System Effect Factor (System) Dimensionless
L Length m (ft)
μ Air Viscosity, Absolute N-s/m2 (lbm/ft-s)
ΔP Pressure Differential Pa (in. wg)
P Pressure Pa (in. wg)
Ps Static Pressure Pa (in. wg)
Psx Static Pressure at Plane x Pa (in. wg)
Pt Total Pressure Pa (in. wg)
Ptx Total Pressure at Plane x Pa (in. wg)
Pv Velocity Pressure Pa (in. wg)
p Atmospheric Pressure Pa (in. Hg)
Q Airflow Rate m3/s (cfm)
Qx Airflow Rate at Plane x m3/s (cfm)
R Gas Constant J/kg-K (ft-lb/lbm-°R)
Re Reynolds Number Dimensionless
rh Relative Humidity % (%)
ρ Air Density kg/m3 (lbm/ft3)
ρx Air Density at Plane x kg/m3 (lbm/ft3)
SEF System Effect Factor (Fan) Pa (in. wg)
SR System Resistance Factor m-4 (ft-4)
sh Specific Humidity (_/_ dry air) kg/kg dry air (lb/lb) dry air
t Temperature °C (°F)
td Dry-Bulb Temperature °C (°F)
tw Wet-Bulb Temperature °C (°F)
V Average Velocity m/s (ft/min)
v Velocity - At any Point m/s (ft/min)
Y Expansion Factor Dimensionless
Z Altitude m (ft)
~ Is Proportional to Dimensionless
2.2 Subscripts
3
AMCA 200-95 (R2007)
3.1.1 Density. The density of a gas is defined as the P = ρRT Eq. 3.1-2
total mass of the molecules in a unit volume. In the
SI system density is given in kilograms per cubic Where:
meter (kg/m3); in the I-P system, density is given in
pounds per cubic foot (lbm/ft3). P = Pressure
V = Volume
For purposes of uniformity, standard air has been m = mass
defined as air with a density of 1.2 kg/m3 (0.075 R = Gas Constant
lbm/ft3) and an absolute viscosity of 18.19 × 10-6 T = Absolute Temperature
ρ = m/V = density
4
AMCA 200-95 (R2007)
In the design of most air systems, it is acceptable to mixture is defined as the ratio of the vapor pressure
assume that the gas is incompressible, therefore, the existing compared to the vapor pressure at saturation
air density may be considered constant, and for the same dry-bulb temperature. This is also equal
therefore, the absolute pressure and absolute to the ratio of the mole fractions under the same
temperature are directly proportional. condition. Relative humidity is always expressed as a
percent.
3.1.3.2 Dry-bulb, wet-bulb and dew point
temperature. Unless otherwise specified, the Specific humidity (sh) is the actual mass (weight) of
temperature of an air-water vapor mixture is that the water vapor existing per unit mass (unit weight) of
temperature which is indicated by an ordinary or dry- dry air or gas. Absolute humidity (ah) may be
bulb thermometer. This dry-bulb temperature is the expressed in kilograms (pounds) of water vapor per
temperature of both the air and the water vapor in the cubic meter (cubic foot) of mixture. The humidity of
mixture. The wet-bulb temperature may be an air-water vapor mixture is often expressed by
determined by exposing a wetted bulb in a moving giving either relative humidity or a wet-bulb
air-water vapor mixture until equilibrium is obtained. depression.
The wet-bulb temperature will be lower than the dry-
bulb temperature as long as evaporation continues. 4. Airflow
If no evaporation is possible, the mixture is saturated
and the wet and dry-bulb temperatures for this The flow of any fluid between two points is caused by
condition will be identical. The dew point temperature the existence of a pressure differential between the
of an air-water vapor mixture is the saturation two points. It is the purpose of this section to explain
temperature corresponding to the absolute humidity the parameters that may affect the flow of a gas
of the mixture. The dew point temperature may also between two points.
be considered as that temperature at which
condensation begins when the mixture is gradually 4.1 Flow conditions
cooled.
Most air systems are designed in the incompressible
3.1.4 Viscosity. A non-perfect gas, such as air, is range. Where compressibility is a factor, Mach
capable of exerting a force parallel to the surface of a number and Reynolds number must be considered.
body which is moving with respect to the gas. The
magnitude of the force parallel to the surface is used The magnitude of these parameters gives an
to define an important property of non-perfect gases indication of the effects which can be expected from
- viscosity. The effects of viscosity on the behavior of the deviations in the non-perfect gas behavior from
real gases cause resistance to flow; the resistance is that of a perfect gas.
proportional to the velocity gradients which exist in
the gas. The absolute viscosity (µ) is defined as the 4.1.1 Mach number. Mach number, for our purposes
shearing stress for a unit rate of change of velocity. here, is the ratio of the velocity of an airstream to the
The absolute viscosity has units of newton-sec per speed of sound in that airstream.
meter squared (N-s/m2) in the SI system and pound
mass per foot-second (lbm/ft-s) using I-P units. Mach number = V/c
5
AMCA 200-95 (R2007)
4.1.2 Reynolds number. The ratio of the inertia when in contact with the body. This is called skin
force to the viscous force caused by changes in friction drag, and, for streamlined bodies closely
velocity within the fluid element is known as the aligned with the flow, represents the entire drag force.
Reynolds number. For blunt bodies, which may be streamlined bodies at
large angles to the flow, profile drag exists. Profile
drag is caused by the inability of the flow, due to its
⎛ρ⎞
Re = DV ⎜ ⎟ Eq. 4.1-1A SI viscous effects, to follow the body shape. The
⎝μ⎠ inability to follow the body shape creates a wake of
⎛ ρ ⎞ very turbulent flow which in effect creates the profile
Re = DV ⎜ ⎟ Eq. 4.1-1A I-P drag force. These wake effects are the predominant
⎝ 60 μ ⎠ cause of flow losses in systems.
⎛ DV ⎞
=⎜ ⎟
⎝ γ ⎠
Where:
6
AMCA 200-95 (R2007)
energy from the high velocity section in the center of In addition to the losses in total pressure in a system
the duct to the low velocity section near the duct wall caused by friction losses and dynamic losses, there
causes a marked resistance to the flow. This are losses due to System Effects.
resistance varies linearly with the length of the duct
and approximately with the square of the average System Effects occur because of the differences
velocity in the duct. The resistance is also a function between the fan inlet and outlet connections to the
of the Reynolds number of the flow, which is installed system and the standardized connections
calculated using the average velocity in the duct, the used in laboratory tests to obtain fan performance
duct diameter, and the surface roughness of the duct ratings. AMCA Publication 201, Fans and Systems,
wall. gives specific details on System Effects related to
fans. System Effects related to series system
The velocity profiles in a duct system for fully elements are covered further in Section 4.5 of this
developed flow will vary depending on whether the publication.
flow is laminar or turbulent and the degree of duct
roughness. Velocity profiles of various flow conditions 4.4.1 Duct friction losses. In the normal range of air
are shown in Figure 4C. systems for HVAC and industrial applications, the
flow falls into the transition region between laminar
The absolute velocity of the air stream will vary flow and complete turbulent flow. In this region the
substantially over the cross-sectional duct area, but losses due to friction are a function of Reynolds
for duct systems the velocity used for determining the number and the relative roughness of the duct wall.
velocity pressure is always the average velocity given The pressure loss in the transition region will vary at
by: slightly less than the square of the velocity. The
pressure loss due to friction for flow in ducts may be
V average = Q/A Eq. 4.3-1 calculated from the Darcy-Weisbach equation:
4.4 System losses Using duct friction charts (see Annex D) is the most
common method of determining friction losses.
The losses in total pressure for flow through a system These charts are based on ducts having average
are caused by two factors: friction losses due to roughness and standard air density. Correction
viscosity as the air flows along the surface of ducts factors must be applied for ducts having different
and other system elements, and dynamic losses roughness, and for variations in air density and
due to the turbulent wake caused by changes in viscosity.
direction and separation of the flow around obstructions.
7
AMCA 200-95 (R2007)
r LAMINAR
TURBULENT
SMOOTH Re = 107
SMOOTH Re = 105
ε = 0.03D ROUGH
ε = 0.008D ROUGH
0 0.5 1.0 1.5 2.0
v
V
D = Duct Diameter
ε = Duct Roughness
Re = Reynolds Number
v = Velocity at any Point
V = Average Velocity
r = Radius
8
AMCA 200-95 (R2007)
0.10
0.09
0.08
0.05
0.07
0.04
0.06
0.03
0.05
0.02
0.015
FULLY ROUGH (EQ 18)
0.04 Eq. (29a)
0.006
RO
0.03
UG
0.004
H
W
IT Eq.
H (2
Re 9a
DE )
0.002
PE
N
DE
NC
0.02 0.0010
E
0.0008
Eq. (27) 0.0006
0.0002
TRANSITION
LAMINAR TURBULENT
REGION
0.00010
0.00005
0.010
0.009
0.008 0.00001
103 2 3 5 104 2 3 5 105 2 3 5 106 2 3 5 107 2 3 5 108
REYNOLDS NUMBER, Re
Reprinted by permission of the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta, Georgia, from the 1993
ASHRAE Handbook-Fundamentals. (Moody 1944). Values on the chart are the same for both the SI and I-P systems. Equation numbers refer
to equations in the source document.
9
AMCA 200-95 (R2007)
Loeffler1 has developed simplified equations for the Correction factors for density and viscosity variations
friction factor in the normal range of flow conditions need to be applied for conditions other than standard
found in industrial and HVAC air systems. The air. See Annexes B and E.
equations provide for direct calculation of duct friction
total pressure losses. These equations yield results 4.4.2 Dynamic losses. Dynamic losses occur where
that are accurate within ±5% and are conservative there are changes in velocity or direction in the air
over most of the range of flow. system and are due primarily to the profile drag.
Dynamic losses are proportional to the square of
For aluminum ducts, medium smooth: velocity, and therefore, are proportional to the
velocity pressure.
ε = 0.0000457 m (0.00015 ft)
ΔPt ~ V 2 ~ Pv
⎛ LQ1.863 ⎞
Pt loss = a ⎜ 4.93 ⎟ Dynamic pressure loss data are given in a number of
⎝ D ⎠ forms such as pressure loss for given volume or
Where: velocity, equivalent length of duct, or velocity
pressure multiplier, and is available from
a = 1.764 × 10-2 Eq. 4.4-2 SI manufacturers' data and handbooks such as:
ASHRAE, the Industrial Ventilation Guide and
a = 4.816 × 10-9 Eq. 4.4-2 I-P SMACNA.
For galvanized steel ducts, average: Except at duct exits, dynamic losses occur along
some length and cannot be separated from friction
ε = 0.0001524 m (0.0005 ft) losses. For practical purposes the dynamic losses
are assumed to be concentrated at one point and the
friction losses are included as part of the duct friction.
⎛ LQ1.921 ⎞ Dynamic loss coefficients for duct fittings are based
Pt loss = a ⎜ 5.066 ⎟
⎝ D ⎠ on zero length. For friction loss calculations, the
Where: centerline length of the duct fitting is taken as the
length of the fitting.
a = 1.717 × 10-2 Eq. 4.4-3 SI
4.4.3 Dynamic loss coefficient. There are two
common methods of expressing dynamic losses.
a = 3.534 × 10-9 Eq. 4.4-3 I-P
These are: 1) The equivalent length of duct method,
and 2) the loss coefficient method. The equivalent
For fiberglass ducts or lined ducts, fabric and wire
length of duct method replaces the dynamic loss of
flexible ducts (wire covered with fabric), medium
fittings (elbows, tees, branches, etc.) with a length of
rough,
duct that will have an equivalent loss. The equivalent
length of duct for all of the dynamic losses are added
ε = 0.00091443 m (0.003 ft)
to the straight duct length. A friction chart showing
the loss is then used to determine the total loss in the
⎛ LQ1.965 ⎞ system.
Pt loss = a ⎜ 5.208 ⎟
⎝ D ⎠
The dynamic loss coefficient method is based on the
Where: fact that all losses in a system are functions of the
velocity pressure and can be calculated by a
a = 2.093 × 10-2 Eq. 4.4-4 SI corresponding dynamic loss factor multiplied by the
velocity pressure. These losses are added to the
a = 3.64 × 10-9 Eq. 4.4-4 I-P straight duct friction loss to determine the total loss in
the system.
Where:
The dynamic loss coefficient method is preferred
Pt loss = Total pressure loss, Pa (in. wg) because it is usually quicker and offers the
Q = Flow rate, m3/s (cfm) advantage of faster recalculation when other branch
D = Duct diameter, m (ft) (or equivalent diameter duct sizes are tried.
of rectangular ducts) D equivalent = (4ab/)0.5
where a and b are the sides in m (ft) Dynamic losses are proportional to the velocity
L = Duct length in m (ft) pressure occurring in the system element and,
1. Loeffler, J. J., Simplified Equations for HVAC Duct Friction Factors, ASHRAE Journal, January, 1980
10
AMCA 200-95 (R2007)
therefore, the pressure loss in the fitting can be 4.5.2 Element System Effects in series. System
related to the velocity pressure by use of a dynamic Effects for other air system elements occur when two
loss coefficient. or more elements are in close proximity to one
another. Loss coefficients for duct fittings, coils,
The dynamic loss coefficient Co is defined as: filters, dampers, etc., are determined with a sufficient
length of straight duct (normally 10 diameters) ahead
Co = ΔPt/Pvo Eq. 4.4-5 of the element to allow for a normally distributed
velocity profile entering the element, and a sufficient
Where: length of straight duct (normally 10 diameters)
downstream from the element to allow a normally
Co = Dynamic loss coefficient, reference to section distributed velocity profile to be re-established. When
o, dimensionless two elements, such as elbows, or an elbow and a
ΔPt = Dynamic pressure loss, Pa (in. wg) damper, are placed close together the air entering
Pvo = Velocity pressure at section o, Pa (in. wg) the second element will be highly turbulent and
asymmetrical in profile, causing a higher loss than
expected. In addition, any static regain occurring
The coefficient relates the pressure loss in the
downstream of the first element would also be lost
element to the velocity pressure at a given cross-
when sufficient length of straight duct is not present.
sectioned area of the element.
To illustrate System Effects for duct elements, the
The pressure loss of duct system elements with
loss coefficients for a single 90° elbow and two
known dynamic loss coeffients can be calculated by:
elbows in series are shown in Figure 4F.
ΔPt = Co Pvo Eq. 4.4-6
In the case of the two elbows in series, the difference
between twice the loss of the single elbow and the
Where there are changes in area or divided flow in
actual combined loss is the System Effect. The
the fitting, the designer must be careful to use the
System Effect varies substantially depending on how
proper area as noted in the loss tables for the
close the two elbows are to each other.
determination of the velocity pressure to be used with
the dynamic loss coefficient. The ASHRAE
Similar effects can be expected when any system
Handbook: Fundamentals, Chapter on Duct Design,
elements are in close proximity. The amount of the
provides a detailed discussion of the dynamic loss
System Effect will vary over a rather wide range
coefficient and tables for coefficients of many
depending upon the physical characteristics of each
common duct elements.
element and their relationship to each other in the
system.
4.5 System Effects
Very little actual data is available on System Effects
Additional losses can occur in air systems because of of various combinations of system elements, and the
the physical relationship of various elements in the system designer must, of necessity, estimate the
system. These System Effect losses occur because System Effects. The following tables for estimating
of the difference between the way the performance of System Effects, and Equation 4.5-1, are given as a
the element was determined by testing and the way guide to the designer. Actual data should be used
the element is actually installed in the system. whenever it is available.
4.5.1 Fan System Effects. Fan System Effects Cc = (Ca + Cb) K Eq. 4.5-1
occur because of the difference in inlet and outlet
conditions under laboratory test conditions and the
Where:
inlet and outlet conditions as the fan is installed in the
system. Detailed information on Fan System Effects
Cc = Loss coefficient of combined elements,
is contained in AMCA Publication 201, Fans and
dimensionless
Systems. The System Effect is accounted for as a
Ca = Loss coefficient of element a, dimensionless
pressure loss which must be included with the other
system losses. The sum of the pressure losses is Cb = Loss coefficient of element b, dimensionless
then used as the basis for selecting the fan. K = System Effect Factor, dimensionless
11
AMCA 200-95 (R2007)
C2 = VARIES
FLOW From SMACNA Duct Design Manual
L
Figure 4G - Element System Effects for
D Straight Through Flow
L
for two 2.63 4.18 3.08 2.45 D
elbows in
series**
2 C1 Two
times the
loss
2.30 L/D .50 1 2 3 4 5 7.5 10
coefficient
of a single
elbow K 1.0 1.08 1.75 1.5 1.30 1.2 1.1 1.0
System
Effect
+0.33 +81.7% +33.98% +6.5% Figure 4H - Element System Effect for
14.3% 1.88 0.78 0.15 Turning Elements
(Difference)
12
AMCA 200-95 (R2007)
5. The Flow System ρ is equal to the air density in kg/m3 (lbm/ft3), and
standard air density equals 1.2 kg/m3 (0.075 lbm/ft3).
5.1 Concepts of pressure Pv is always positive and this pressure is always
exerted in the direction of airflow. Air confined within
The flow of air between two zones (or spaces) is due a duct or a tank, whether in motion or not, creates
to a pressure difference between the two zones. This another kind of pressure which exerts itself in all
pressure difference forces the air to flow from the directions at once, including perpendicular to the
high pressure zone to the low pressure zone. walls of the enclosure. This is known as static
Ductwork is used in most air systems to convey the pressure Ps. Static pressure is negative when it is
air from one zone to another. The quantity of air Q in below atmospheric pressure, and positive when
m3/s (cfm) that will flow is equal to the cross-sectional above atmospheric pressure. Total pressure Pt at any
area A of the duct in m2(ft2) times the air velocity V in point in an air system is equal to the algebraic sum of
m/s (ft/min). the static pressure Ps and velocity pressure Pv. Pt
can be either positive or negative, depending on its
Q = AV Eq. 5.1-1 components.
13
AMCA 200-95 (R2007)
In Figure 5A, the sealed length of duct has a static pressure of 345 Pa (1.39 in. wg) above atmospheric pressure.
Since there is no airflow, velocity pressure is equal to zero. The total pressure Pt can then be calculated according
to equation 5.1-3.
SI I-P
Pt = Ps + Pv Pt = Ps + Pv
= 345 + 0 = 1.39 + 0
= 345 Pa = 1.39 in. wg
14
AMCA 200-95 (R2007)
In Figure 5B, with the duct open and a fan placed at one end blowing air through the duct, we find both static
pressure and velocity pressure as illustrated by the water gauge. The total pressure is the sum of velocity pressure
and static pressure.
20.3 m/s
AIRFLOW
(4005 FPM)
In this illustration, the static pressure will be above atmospheric pressure and the total pressure is numerically
greater than either static or velocity pressure.
15
AMCA 200-95 (R2007)
In Figure 5C, a fan is placed at the end of the duct and draws air through the duct. In this case, the static pressure
is below atmospheric pressure. In both Figures 5B and 5C, the total pressure rise across the fan is 345 Pa (1.39
in. wg); therefore, the energy used in both systems is equal.
20.3 m/s
AIRFLOW
(4005 FPM)
16
AMCA 200-95 (R2007)
The well known Bernoulli Theorem, frequently used Ps1 + Pv1 = Ps2 + Pv2 + losses1,2 Eq. 5.3-1
in the flow of fluids, states the law of conservation of
energy for fluid systems. In its simpler form for Simply stated, the sum of static pressure and velocity
airflow: pressure at any point in a flow system is equal to the
sum of static pressure and velocity pressure at any
(V12/2g) + (P1/ρg) + Z1 = (V22/2g) + (P2/ρg) other point in the system, plus any losses in pressure
+ Z2 + losses1,2 occurring between the two points.
Where:
Although it is very important to recognize that the
Vx2/2g = Kinetic energy or velocity pressure (Pv) sum of static and velocity pressure remains constant
at any point in the system when disregarding losses,
Px/ρg = Potential energy or static pressure (Ps)
it is the losses that are of real importance in the
Zx = The elevation (normally ignored in fan
design and function of air moving systems.
systems with minimal changes in
elevation) may need to be evaluated when To illustrate Bernoulli's Theorem, Figure 5D shows a
the system elevation change causes a typical venturi system commonly used to measure
noticeable change in air density. fluid flow.
Pt PS PV Pt PS PV Pt PS PV
Pt Pt
PS
PRESSURE PS
Pa (INCHES W.G.) PV
PV
17
AMCA 200-95 (R2007)
For the purposes of illustration, assume this is a If the plenum is very large relative to the nozzle
perfect device with no losses. The velocity pressure, diameter, the velocity in the plenum will approach
static pressure, and total pressure at each point in the zero, so the total pressure at point 1 (Pt1) will be equal
system are shown on the gauges as well as on the to the static pressure (Ps1). Assuming a perfect fluid
lower portion of the illustration. Part of the static at and no losses occurring in the nozzle, the static
point 1 is converted to velocity pressure as the fluid pressure in the plenum (point 1) is totally converted
is accelerated in the contracted flow area in the neck to velocity pressure at the discharge of the nozzle
of the venturi. At point 2, in the neck of the venturi, (point 2).
the velocity pressure reaches its maximum and the
static pressure is reduced, but the total pressure At point 2, just beyond the discharge end of the
remains constant. As the flow area is gradually nozzle, the static pressure (Ps2) will be zero (at
increased to point 3, the velocity is slowed down to atmospheric pressure) and the total pressure (Pt2) will
the original velocity and the velocity pressure is be equal to the velocity pressure of the air stream.
reduced to its original value. The static pressure Applying Bernoulli's Equation for points 1 and 2
increases back to its original value also, while the gives:
total pressure remains constant.
Ps1 + Pv1 = Ps2 + Pv2
In this illustration, part of the static pressure at point
1 is converted to increased velocity pressure at point
Since Pv1 is equal to 0 and Ps2 is equal to 0, the
2 and the velocity pressure is then converted back
equation reduces to:
into static pressure at point 3.
Ps1 = Pv2
The conversion of the velocity pressure into static
pressure by reducing the velocity is known as static
regain and it is very important to understand this In this case, the energy of the static pressure in the
phenomenon in the design of flow systems. plenum is totally converted to the velocity energy at
the discharge of the nozzle. It should also be noted
In air systems, changes in velocity often occur as the that the velocity pressure is totally lost as the
air flows through the various elements comprising the airstream discharges to atmosphere.
system. Some total pressure loss will occur any time
the velocity in the system is increased or decreased. Using Equation 5.1-2A (as reduced above) the
The magnitude of these losses is dependent on the relationship between static pressure and the throat
physical characteristics of the system element in velocity can be established in the above example.
which the velocity change takes place. Decreases in Using this in Equation 5.1-2A gives:
velocity occurring at abrupt enlargements in area
result in total pressure losses approaching one V2 = (2Ps1/ρ2)0.5 Eq. 5.3-2A SI
velocity pressure.
V2 = 1096(Ps1/ρ2)0.5 Eq. 5.3-2A I-P
Figure 5E illustrates air flowing from a large plenum
through a long radius flow nozzle and discharging to Or where: Ps1 = Pv2
atmosphere.
Then for standard air, the equations would be:
Where:
Ps1 = Pv2
18
AMCA 200-95 (R2007)
Then, for standard air, the equation would be: In practical system design both Cn and Y approach
unity and can normally be neglected. However, these
Pv2 = 0.6V 2 Eq. 5.3-3B SI factors are important when measuring fan
performance in accordance with ANSI/AMCA
Pv2 = (V2/4005)2 Eq. 5.3-3B I-P Standard 210.
In the above example, the quantity of flow would be In Figure 5F, the nozzle is replaced by a sharp edged
dependent on the area of the nozzle discharge and orifice. The flow through the orifice tends to neck
the velocity in the throat as given by the equation: down to a flow area smaller than the orifice diameter.
The point at which the flow area reaches its minimum
Q2 = V2A2 is called the vena contracta. The flow through the
orifice is given by the equation:
Where:
Q = Cd(2Ps/ρ)0.5A Eq. 5.3-6 SI
Q = Airflow rate, m3/s (cfm)
V = Velocity, m/s (ft/min) Q = Cd1096(Ps/ρ)0.5A Eq. 5.3-6 I-P
A = Area, m2 (ft2)
Where:
Substituting for V2 from Equation 5.3-2A and 5.3-2B
gives: A = Area of orifice, m2 (ft2)
Cd = Coefficient of discharge, dimensionless
Q = (2Ps1/ρ2)0.5A2 Eq. 5.3-4A SI
VENA CONTRACTA
Q = 1096(Ps1/ρ2 )0.5A2 Eq. 5.3-4A I-P
19
AMCA 200-95 (R2007)
If we plot the flow through these elements versus Resistance Curve (see Figure 5H) the point of
static pressure as shown in Figure 5G, we obtain a operation is at the intersection of the fan performance
squared curve which is typical of flow versus curve and the System Resistance curve.
pressure for any constant system.
SYSTEM
RESISTANCE
PRESSURE
PRESSURE
POINT OF
OPERATION
P = KQ2
FAN PRESSURE
CURVE
FLOW FLOW
These curves are called System Resistance curves, 5.4 Fan total and static pressure
and define the relationship of flow versus pressure
for any system with constant resistance. System The flow of a gas through a system of ducts and
Resistance curves are defined by the following various system elements requires energy:
equations:
a) To accelerate the air from ambient conditions at
Q = (2Ps/ρ)0.5Ae Eq. 5.3-7A SI the entry to the system
Q = 1096(Ps/ρ)0.5Ae Eq. 5.3-7A I-P b) To overcome the losses in the system from
friction and system element shock losses
Then for standard air:
c) For the loss of energy dissipated as velocity at
Q = 1.29(Ps)0.5Ae Eq. 5.3-7B SI the system outlet
The System Resistance concept is very useful in PtF = Pt2 - Pt1 Eq. 5.4-1
understanding flow in complete systems or elements
of flow systems. If we add a fan curve to the System Or:
20
AMCA 200-95 (R2007)
The velocity pressure of a fan is defined as: Figure 5J. Both static pressure and total pressure
curves of the fan and system resistance are shown.
PvF = Pv2 Eq. 5.4-3 Either set of curves can be used for the flow rate
because the point of operation is the same. The
The static pressure of a fan is defined as: difference in pressure at the point of operation
between the total pressure curve and the static
PsF = PtF - PvF Eq. 5.4-4 pressure curve is the velocity pressure at the fan
discharge (plane 2).
Fan static pressure, as defined, is a term that is
peculiar to fans and is not consistent with the normal Most fans are rated in terms of static pressure and
meaning of static pressure rise. Fan static pressure flow, however, fans having high discharge velocities
is derived from the method of testing fans where the such as vaneaxial fans are quite often rated in terms
fan static pressure is equal to gauge static pressure of total pressure. Be aware of these different
at the fan discharge when the fan draws air from methods of rating and be certain whether fan static
surrounding atmosphere through a well shaped inlet. pressure or fan total pressure was used to determine
the fan selection.
Special care must be used when using fan static
pressure for purposes of matching the required fan 5.4.2 Fan system pressure relationships. Figure
performance against system total pressure losses. 5K shows the relationship of total pressure, static
The relationship of these pressures is covered in pressure and velocity pressure for a fan with free inlet
detail for various systems further on in this section. conditions and discharging through a duct against
some system. In this example the fan is shown as
The static pressure of a fan can also be stated in being equipped with a short inlet duct and an inlet
several other forms. Substituting Equation 5.4-2 for bell. For simplicity's sake it is assumed that there are
the total pressure of the fan in Equation 5.4-4 gives: no losses at the inlet to the fan.
PsF = Ps2 + Pv2 - Ps1 - Pv1 - Pv2 Eq. 5.4-5 The total pressure prior to the entry of the fan in
Figure 5K is zero and since it was assumed that there
Simplifying: are no entry losses, the total pressure remains zero
until the flow is acted upon by the fan. As air enters
PsF = Ps2 - Ps1 - Pv1 Eq. 5.4-6 the fan, its velocity and the pressure due to that
velocity (velocity pressure) increases while static
Since: pressure decreases in direct proportion. (In actual
conditions there will be some entry losses which will
Ps1 + Pv1 = Pt1 be accounted for in the fan performance rating.)
Referring to Figure 5K, the fan total pressure is equal
to the total pressure at plane 2 minus the total
The equation can be restated as:
pressure at plane 1.
PsF = Ps2 - Pt1 Eq. 5.4-7
PtF = Pt2 - Pt1 Eq. 5.4-8
5.4.1 Fan performance specification. The system
The fan static pressure is equal to the total pressure
designer should be aware of the effect of the velocity
at plane 2 minus the velocity pressure at plane 2.
pressure at the outlet of the system and the velocity
pressure of the fan discharge (plane 2) on the
PsF = Pt2 - Pv2 Eq. 5.4-9
determination of fan total or static pressure for the
system. The net result of the fan total or static
pressure requirements at a given flow rate for the The static pressure of the fan can also be stated as
system is the fan performance specification, which is the static pressure at plane 2 minus the static
normally stated as flow at a specific static, or total pressure at plane 1 minus the velocity pressure at
pressure. This statement of required fan performance plane 1.
is, in reality, a statement of one point on a system
resistance or equivalent orifice curve, which then PsF = Ps2 - Ps1 - Pv1 Eq. 5.4-10
defines the flow and pressure relationship of the
system being designed. Or, as the static pressure at plane 2 minus the total
pressure at plane 1.
The actual point of operation of the combined fan
and system will be the intersection of the fan PsF = Ps2 - Pt1 Eq. 5.4-11
performance curve and the system curve as shown in
21
AMCA 200-95 (R2007)
The actual static pressure rise across the fan from 5.5 The total system
plane 1 to plane 2 will be greater than the fan static
pressure by the amount of the velocity pressure at A fan provides the total pressure to move the air
the fan inlet, plane 1. The difference in the actual through a system and the flow rate will reach a point
static pressure rise across the fan and the fan static of equilibrium (point of operation) when the total
pressure represents the energy required to pressure provided by the fan equals the total
accelerate the air to its entry velocity. This kinetic pressure losses in the system at that flow rate. A
energy is retained by the moving air stream until typical system with inlet and discharge resistance is
there is a change in velocity in the system or it is illustrated in Figure 5L.
dissipated at the point of discharge, and as such
does not represent a loss in total pressure until it is Applying Bernoulli's Equation at the point of entry and
discharged. the outlet:
The equipment arrangement shown in Figure 5K is PtE = PtO + Pt loss E,O - PtF Eq. 5.5-1
typical of the test conditions for fans in ANSI/AMCA
Standard 210, and is the basis for fan performance Rearranging:
ratings. When fans are tested in accordance with
ANSI/AMCA Standard 210, the inlet and discharge PtF = Pt loss, E,O + PtO - PtE Eq. 5.5-2
conditions are rigidly specified for each test method.
Restating in terms of Ps and Pv:
When a fan is installed in an air system where the
actual entry and exit conditions are different than the PtF = Pt loss E,O + PsO + PvO - PsE - PvE
test conditions, the performance of the fan may be
altered and System Effect factors must be used to
PtF = Pt loss E,O + PvO + (PsO - PsE - PvE) Eq. 5.5-3
account for the altered performance. AMCA
Publication 201, Fans and Systems describes
Substituting from Equation 5.4-4 for PtF :
various System Effects and provides quantitative
data for calculating System Effect losses.
PvF
PRESSURE
SYSTEM RESISTANCE
(TOTAL PRESSURE) PtF
PsF
SYSTEM RESISTANCE
(STATIC PRESSURE)
22
AMCA 200-95 (R2007)
PsF = [Pt loss E,O + PvO + (PsO - PsE - PvE)] - PvF is included in the total pressure loss of the discharge
Eq. 5.5-4 element.
Equations 5.5-3 and 5.5-4 are the general statements System total pressure loss = total pressure loss
of fan total pressure or fan static pressure required internal to the system, plus the velocity pressure loss
for flow through a system. The Pt loss term is the loss at the outlet(s) of the system.
internal to the system from friction and shock losses.
The PvO term represents the energy loss to the The term (PsO - PsE - PvE) represents the change in fan
system contained in the velocity at the outlet of the total pressure or fan static pressure requirements
system. because of the static pressure conditions existing at
the system entry or outlet and any velocity pressure
In Equation 5.5-4, the items enclosed in large present at the system entry. Velocity and velocity
brackets represent the fan total pressure. pressure generated by external sources, such as
wind, at the system entry are seldom encountered,
In the normal method of calculating system total so the PvE term can generally be disregarded.
pressure losses, the velocity pressure at the outlet(s)
0
FAN
PtF = Pt2 - Pt1
PsF = PtF - Pv2
Pt
+ Pv Pt2 = PtF
Ps2 = PsF
Pv1 Pv2
PtE= 0 0
Ps1
_ Ps ABSOLUTE
PRESSURE
23
AMCA 200-95 (R2007)
RESISTANCE RESISTANCE
ELEMENT PLANE 1 PLANE 2 ELEMENT
E
O
ENTRY FLOW FAN OUTLET
PtF Pv2
ATMOSPHERIC
PRESSURE
Pv Pt2
PvO = PtO
+ Ps2
PtE = 0 0
_
Pt PsF
ABSOLUTE
Ps PRESSURE
Ps1
PLANE 1 PLANE 2
E O
ENTRY OUTLET
FLOW
FAN
24
AMCA 200-95 (R2007)
RESISTANCE
E ELEMENT
PLANE 1 PLANE 2
ATMOSPHERIC
PRESSURE Pt FAN PtO = Pv2
Pv
+ Pt
PtE = 0
_
Ps
Ps
Pt1 ABSOLUTE
FAN
PRESSURE
Pv Ps1
PtF = Pt LOSS + PvO
Where:
PsF = Pt LOSS + PvO - Pv2
Pv1
since PvO = Pv2
PsF = Pt LOSS
(Pressure Loss Internal to System)
25
AMCA 200-95 (R2007)
5.6 Types of fan system PsF = Pt loss + PvO - Pv2 Eq. 5.6-2
There are four basic system Installation Types: In the special case where the velocity pressure at the
outlet is equal to the velocity pressure at the fan
AMCA INSTALLATION TYPE A: discharge, the fan static pressure will equal the total
Free Inlet, Free Outlet pressure loss. If these velocity pressures are different
the fan total pressure and fan static pressure must be
increased or decreased by the amount of the
difference in these velocity pressures.
AMCA INSTALLATION TYPE D: Fans designed for use at the end of a system, such
Ducted Inlet, Ducted Outlet as power roof ventilators, include the loss at the
discharge in the fan ratings and no system effect loss
is needed.
26
AMCA 200-95 (R2007)
27
AMCA 200-95 (R2007)
RESISTANCE RESISTANCE
ELEMENT PLANE 1 PLANE 2 ELEMENT
E 0
Pvt
Figure 5Q - Fan with Inlet and Discharge Resistance - Evasé Outlet Added
RESISTANCE 1 Q1
QT
RESISTANCE 2 Q2
28
AMCA 200-95 (R2007)
2 2
⎡ Q1 ⎤ ⎡ Q2 ⎤ ⎡ 0.4472 ⎤
⎢ C ⎥ SR1 = ⎢ C ⎥ SR2 = QT ⎢ ⎥
⎣ ⎦ ⎣ ⎦ ⎣ 0.9949 ⎦
Where: = QT (0.4495)
C = 1.29 (for SI units)
= 4005 (for I-P units) If:
29
AMCA 200-95 (R2007)
and total the losses. In systems that include parallel ITEM DUCT,
branches it is customary to determine the loss of the 6.096 m (20 ft.) of 0.4064 m (16 in.) diameter.
branch path that has the highest resistance to Airflow = 0.94 m3/s (2000 cfm)
establish the fan requirements. Other branch paths Pt Loss = 8.94 Pa (0.036 in. wg)
that have lower losses must have resistance added
to them to balance the system since the total ITEM D - DIVIDED FLOW FITTING,
pressure loss of each path must be equal. 0.4572 m (18 in.) to 0.4064 m (16 in.) and 0.3048 m
(12 in.) diameter, with a main branch dynamic loss
5.8.1 Example: System loss calculations for coefficient of 0.
branch 1 (dynamic loss coefficient method) Airflow = 1.416 m3/s (3000 cfm)
Pv = 44.70 Pa (0.18 in. wg)
ITEM K - DISCHARGE DIFFUSER Pt Loss = 44.70 × 0 (0.18 × 0)
0.3048 m (12 in.) diameter with a dynamic loss
= 0 Pa (0 in. wg)
coefficient of 0.50.
NOTE: The net loss in the main branch of this fitting
Airflow = 0.47 m3/s (1000 cfm) is zero (0), since there is static regain to offset the
Pv = 25.08 Pa (0.101 in. wg) loss.
Pt Loss = 0.50 × 25.08 (0.50 × 0.101)
= 12.54 Pa (0.051 in. wg) ITEM DUCT,
NOTE: Loss coefficient includes velocity lost at 12.192 m (40 ft.), 0.4572 m (18 in.) diameter.
discharge and static regained by diffusion. Airflow = 1.42 m3/s (3000 cfm)
Pt Loss = 21.36 Pa (0.086 in. wg)
ITEM J - BALANCING DAMPER,
0.3048 m (12 in.) diameter with a dynamic loss E through H - These losses may be included in the
coefficient of 0.52. manufacturer's rating data.
Airflow = 0.47 m3/s (1000 cfm)
Pv = 25.08 Pa (0.101 in. wg) ITEM E - ENTRANCE,
Pt Loss = 0.52 × 25.08 (0.52 × 0.101) from plenum 0.4572 m (18 in.) diameter, dynamic
= 13.04 Pa (0.053 in. wg) loss coefficient of 0.5.
Airflow = 1.42 m3/s (3000 cfm)
ITEM DUCT, Pv = 44.70 Pa (0.18 in. wg)
6.096 m (20 ft.) of 0.3048 m (12 in.) diameter. Pt Loss = 44.70 × 0.5 (0.18 × 0.5)
Airflow = 0.47 m3/s (1000 cfm) = 22.35 Pa (0.09 in. wg)
Pt Loss = 10.18 Pa (0.041 in. wg)
(from Annex D) ITEM F - COIL
Airflow = 1.416 m3/s (3000 cfm)
ITEM A - ELBOW, Pt Loss = 74.51 Pa (0.3 in. wg)
0.3048 m (12 in.) diameter with dynamic loss (from manufacturer's data)
coefficient of 0.22.
Airflow = 0.47 m3/s (1000 cfm) ITEM G - FILTER
Pv = 25.08 Pa (0.101 in. wg) Airflow = 1.416 m3/s (3000 cfm)
Pt Loss = 0.22 × 25.08 (0.22 × 0.101) Pt Loss = 86.93 Pa (0.35 in. wg)
= 5.518 Pa (0.022 in. wg) (from manufacturer's data)
31
AMCA 200-95 (R2007)
0.46m DIA.
E B B
COIL
F 0.30m DIA. 0.30m DIA.
FILTER 0.472m3/s 0.472m3/s
G
LOUVER
H J J DAMPER J
DIFFUSER K K K
3 2 1
SI
18” DIA.
E B B
COIL
F 12” DIA. 12” DIA.
FILTER 1000 CFM 1000 CFM
G
LOUVER
H J J DAMPER J
DIFFUSER K K K
3 2 1
I-P
32
AMCA 200-95 (R2007)
300
PT vs FLOW
PT vs FLOW
0 1 2 3 4
CFM × 1000
33
AMCA 200-95 (R2007)
rate required at the design conditions. As an conditions (Annex E) has a density of 1.072 kg/m3
example, in a system requiring a mass flow rate of (0.067 lbm/ft3). The power at these conditions would
226.8 kg/min (500 lbm/min) at 121.1°C (250°F) and be the power for standard air multiplied by the density
at an altitude of 914.4 m (3000 ft), the air density from ratio:
Annex E is 0.800 kg/m3 (.05 lbm/ft3). The required
volume flow rate can then be determined by dividing SI (Power required at 20°C and 914.4 m)
the mass flow rate by the design density: 10.82 kW × (1.072 kg/m3 ÷ 1.2 kg/m3) = 9.67 kW
SI (Volume flow rate) I-P (Power required at 68°F and 3000 ft)
226.8 kg/min ÷ (60 s/min × 0.800 kg/m3) = 4.725 m3/s 14.5 BHP × (0.067 lbm/ft3 ÷ 0.075 lbm/ft3) = 12.95 BHP
I-P (Volume flow rate) In normal HVAC applications the effects of density
500 lbm/min ÷ 0.5 lbm/ft3 = 10000 cfm changes other than for operation at higher altitudes,
are quite often ignored and the system design is
The pressure loss in the system would be calculated based on handling standard air. The system designer
based on 4.725 m3/s (10000 cfm) at standard air should, however, be aware of the effects of density
density of 1.2 kg/m3 (.075 lbm/ft3). If in this example change and take them into consideration when
the pressure loss at standard air is 1490.16 Pa (6 in. making field measurements of system performance
wg) the pressure loss at actual conditions would be or balancing the system.
this value multiplied by the density ratio:
Use Annex C to determine the density of air over a
SI (Pressure loss - actual conditions) range of barometric pressures, temperatures, and
1490.15 Pa × (0.8 kg/m3 ÷ 1.2 kg/m3) = 993.44 Pa relative humidities. Annex E gives the density ratios
for a wide range of temperatures and altitudes. The
I-P (Pressure loss - actual conditions) air density at the various conditions is obtained by
6 in. wg × (.05 lbm/ft3 ÷ .075 lbm/ft3) = 4 in. wg multiplying standard air density of 1.2 kg/m3 (0.075
lbm/ft3) by the factors shown in the table.
A fan for this system must be selected based on its
performance at standard conditions. For this example 6. System Design and Tolerances
select the fan for a performance of 4.725 m3/s (10000
cfm) at 1490.16 Pa (6 in. wg) static pressure. Before making a final determination of the fan
Determine the fan power required at standard density selection there are several factors in the design of a
from the fan performance data. The power required system and the selection of a fan that need to be
at actual conditions would then be calculated by understood and evaluated:
multiplying the catalog fan power by the density ratio.
In this example the fan power required at standard a) The effect of variation in the resistance of the
conditions is 10.82 kW (14.5 BHP). At the actual actual installed system versus the resistance of
operating conditions of 121.1°C (250°F) air at 914.4 the designed system, i.e.; point of operation
m (3000 ft) altitude, the fan power required would be
the power for standard air multiplied by the density b) The fan performance characteristics and
ratio: system/performance tolerances
34
AMCA 200-95 (R2007)
a) The installed system is different from the These curves are only shown to make the system
designed system, such as the addition of elbows designer aware of the effect of the slope of the fan
and offsets to meet field conditions, failure to curve on the expected system performance with
provide turning vanes in elbows, or the change in variations in system resistance. Many other factors
position of various system elements with respect enter into the determination of the best fan type and
to each other; size for a given application.
b) Excessive leakage or increased resistance due 6.2.2 Fan performance tolerance. The fan
to poor quality workmanship at the installation; performance also has a tolerance which must be
considered. The AMCA Check Test Tolerances are
c) Loss coefficients of the various system elements described in AMCA Publication 211, Certified Ratings
such as coils, filters, dampers, diffusers, elbows, Program - Air Performance, Product Rating
etc., improperly accounted for; Requirement Subsection B. The AMCA Check Test
Tolerance is shown on Figure 6B. This tolerance is to
d) System Effects: be applied along a parabolic system line. The power
• not properly accounted for required by the AMCA Check Test Tolerances shall
• ignored in the original system design not exceed the rated data at the measured volume by
• not accounted for because of on-site more than 5% or 37 watts, whichever is greater. The
installation changes. fan curve in Figure 6B has dashed lines indicating the
tolerance range of fan performance, and when
The degree to which all of the various tolerances and combined with the system resistance tolerance
the field changes affect the actual system resistance curves, an area of probable system performance is
varies quite widely. Experience indicates that the indicated by the tolerance limits shown for the system
difference to be expected between the calculated and resistance and the tolerance limits shown for the fan
actual system resistance can be as much as ±10%. flow-pressure. As can be seen, the probable flow
In extreme cases, greater system resistance range could be from 3.15 m3/s (6674 cfm) to 3.39
differentials have been experienced. Not accounting m3/s (7185 cfm) which is -4.7 to +2.6%. An installed
for system effects in the design will result in a higher system tolerance range approaching ± 5.0% of flow
system resistance and reduced flow. could be expected.
6.2 Fan performance 6.2.3 Performance safety factor. Evaluate the fan
performance tolerance and system resistance
There is a wide variety of basic fan designs in axial, tolerances to determine if the lower or upper limits of
centrifugal and mixed flow variations. Curves of the probable flow in the system are acceptable. The
several typical basic fans, all selected for a point of combination of these tolerances should also be
operation of 3.30 m3/s (7000 cfm) at a static pressure evaluated to ensure that the high side system
of 1490.16 Pa (6 in. wg), are shown on Figure 6A. All resistance curve does not fall into the unstable
of these fans pass through the design point of portion of the fan curve. With a few exceptions, all
operation, but with different slopes. The point of fans have an unstable range of performance.
highest efficiency will typically occur somewhat to the Operation in this area of the curve should be avoided
right of the peak pressure point. and precautions taken to ensure operation outside of
the unstable area at the highest expected system
6.2.1 System resistance effect on performance. resistance.
The system resistance curves for the point of
operation and curves for ±10% and ±25% of the 6.2.3.1 Static pressure safety factor. It has been
design pressure are also shown in Figure 6A. The common practice among system designers to apply a
intersection of these system lines with the various fan performance safety factor to the calculated system
curves show what range of volume performance can requirements. This is often accomplished by adding
be expected for each fan over this range of system a nominal percentage of pressure to the system
resistance. The amount of variation in flow rate with pressure requirements. Some system designers will
changes in the system resistance will be dependent size the system for a higher flow rate than is required.
on the slope of the fan performance curve in the
range of operation. The use of safety factors is discouraged when all
system components and system effects are
properly accounted for. The use of safety factors
is not required when system effect factors and all
known losses are accounted for.
35
AMCA 200-95 (R2007)
6.3 Effects of system changes Figure 6D shows a typical fan curve with system
resistance curves for a variable system where the
Some air systems are designed to operate at more system pressure is allowed to vary as the system
than one system condition, such as an exhaust demand for airflow changes. The system may be
system serving multiple inlets where some of the varied by volume control, dampers, or other control
inlets can be closed off, or supply systems where devices to provide a varying flow rate as demanded
some of the outlets can be closed off or dampered for by the system.
reduced flow. The effect of these changes in the
system need to be evaluated in the system design The tolerance ranges are shown for both the fan and
and the selection of a fan for this service. The main the system resistance. The most critical point in the
concern would be that the fan is not forced to operate design of this type of system will be at the low flow-
in the unstable range. Also, the fan performance high pressure condition. The fan selection and
should be such that the system performance is system limits should be such that the fan will operate
acceptable over the range of operating conditions in the stable portion of the fan curve at the maximum
desired. The motor must be selected to cover this resistance condition. Make sure the fan power
range of operating conditions. The system resistance requirements over the tolerance range can be met by
and system performance, for the example used in the motor selected.
Section 5.8, were calculated for the design condition
and also for two other system conditions. [Figure 6C Figure 6E shows a typical set of fan curves for a
illustrates the effect of system changes.] The system centrifugal fan with inlet vane control with system
resistance and flow were calculated for the condition resistance curves for a variable resistance system.
where all the dampers were open and for the In this system, both the pressure and flow
condition where one of the dampers was closed. characteristics of the fan are varied by changing the
Each of these conditions has a different system inlet vanes position to meet the flow rate demand of
resistance curve resulting in a different operating the system. Similar systems employ axial fans with
point on the fan curve and a different total flow for the variable pitch control, or fans with variable speed
system. The flow in each branch of the system will capability.
also change. This leads to an important conclusion:
The critical area of fan selection is near the peak of
IN A FIXED SYSTEM, A CHANGE IN RESISTANCE the pressure curve. Almost all fans exhibit some
IN ANY ELEMENT WILL CHANGE THE TOTAL degree of instability to the left of the peak pressure
SYSTEM RESISTANCE, AND AS A RESULT, point. It is wise to avoid operation in this range
CHANGE THE POINT OF OPERATION ON THE without the expressed approval of the fan
FAN CURVE AND THE FLOW RATE THROUGH ALL manufacturer.
OTHER ELEMENTS OF THE SYSTEM.
There are many system variations to meet various
It is because of this interaction of the total system design criteria that the designer may encounter. Not
with changes in any part of the system that the job of all of the possibilities can be covered in the scope of
balancing a system is very difficult. this publication. If fan users apply the principles
outlined in this publication to the specific system,
6.4 Variable systems they can expect to design a good, functional system
and avoid many of the pitfalls often encountered in air
Where systems are designed to be variable over systems.
some range of operation, or where both the fan and
system are variable, the point of operation needs to
be evaluated at the upper and lower limits of
operation, relative to the tolerance of the fan and
system.
36
AMCA 200-95 (R2007)
+25%
+10%
-10%
PRESSURE
BACKWARD
1490.16 Pa
INCLINED FAN -25%
(6.0 in. wg)
RADIAL
BLADE FAN
3.3m/s VANEAXIAL
(7000 cfm) FAN
VOLUME FLOWRATE
+10%
DESIGN POINT
OF OPERATION
-10%
PRESSURE
FAN CURVE
POTENTIAL SYSTEM
FLOW RANGE
3.15 m3/s 3.39 m3/s
(6701 cfm) (7210 cfm)
3.3 m3/s AMCA CERTIFIED RATING
(7000 cfm) TOLERANCE
VOLUME FLOWRATE
37
AMCA 200-95 (R2007)
DWDI FAN
DESIGN
SYSTEM
TOTAL PRESSURE
Pt vs FLOW
VOLUME FLOWRATE
+10%
-10%
HIGH PRESSURE
DESIGN POINT
FAN CURVE
+10%
PRESSURE
VOLUME FLOWRATE
38
AMCA 200-95 (R2007)
+10%
-10% MAXIMUM FLOW
DESIGN POINT
PRESSURE
VARIABLE VOLUME
SYSTEM RESISTANCE
STATIC PRESSURE
CONTROL POINT
VOLUME FLOWRATE
39
AMCA 200-95 (R2007)
Viscosity:
Absolute (lbm/ft-s) 1.4882 = Pa s (Pa s) 0.6719 = (lbm/ft-s)
Kinematic (ft2/s) 0.0929 = m2/s (m2/s) 10.7639 = ft2/s
Gas Constant (ft lb/lbm-°R) 5.3803 = J-kg/K (j-kg/K) 0.1858 = (ft lb/lbm-°R)
40
AMCA 200-95 (R2007)
Z t p ρ μ ν c
Altitude Temperature Atmospheric Gas Absolute Kinematic Speed of
Pressure Density Viscosity Viscosity Sound
41
AMCA 200-95 (R2007)
Z t p ρ μ ν c
Altitude Temperature Atmospheric Air Dynamic Kinematic Speed of
Pressure Density Viscosity Viscosity Sound
42
AMCA 200-95 (R2007)
43
AMCA 200-95 (R2007)
44
AMCA 200-95 (R2007)
45
AMCA 200-95 (R2007)
46
100 VE 100
LO
CI
TY
70 90 m/ 70
s
30
80
50 50
25 70
50
40 40
30 60 30
63
20
ASHRAE Handbook-Fundamentals.
80
18 50
20 20
0
Annex D. Friction Charts
16 45
10
5
14 40
12
0
35
10 12 10
16
0
30
10
20
7 7
0
9
25
5 8 5
5
31
4 7 4
0
40
3 6 3
0
50
0
2 5 2
63
Chart D.1 - SI
0
4 80
00
1 3.5 1
50
20
3
12
0.7 0.7
00
16
2.5
00
0.5 0.5
20
mm
0.4 0.4
00
2.0
R,
25
E
31
M
1.6
00
0.2 0.2
DIA
40
1.4
T
DUC
1.2
9
0.1
20 50 100 200 500 1,000 2,000 5,000 10,000 20,000 50,000 200,000 400,000
Reprinted by permission of the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta, Georgia, from the 1993
AMCA 200-95 (R2007)
47
48
10 10
80
7 00 7
70
5 65 00 5
0
60 0 VE
4 0 LO 4
AMCA 200-95 (R2007)
55 0 CI
0 TY
3 50 0 , fp 3
00 m
ASHRAE Handbook-Fundamentals.
45
00
2 40 12 2
3
00 00
36 0
00
10
4
32 00
00 0
90
5
1 28 00 1
00 80
00
6
0.8 24 0.8
00
7
8
20
0.5 0 0.5
9
18 0
10
0.4 00 0.4
16 40
12
00 00
0.3 0.3
14
14
00
16
18
0.2 12 0.2
00
20
22
Chart D.2 - I-P
24
10
0
26
0
90
30
0
32
0.1 80 0.1
36
0
40
0.08 18 0.08
60
55
0.05 0 0.05
60
.
70
, in
0.04 50
0 0.04
R
80
TE
90
0.03 0.03
0
E
40
10
0
IAM D
0.02 0.02
CT
30
DU
0.01 0.01
50 100 200 500 1,000 2,000 5,000 10,000 20,000 50,000 100,000 200,000 400,000
AIR QUANTITY, cfm at 0.075 lb/ft3 (ε = 0.0003 ft)
Reprinted by permission of the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta, Georgia, from the 1993
AMCA 200-95 (R2007)
49
AMCA 200-95 (R2007)
50
AIR MOVEMENT AND CONTROL
ASSOCIATION INTERNATIONAL, INC.
30 West University Drive
Arlington Heights, IL 60004-1893 U.S.A.
Tel: (847) 394-0150 Fax: (847) 253-0088
E-Mail : [email protected] Web: www.amca.org
The Air Movement and control Association International, Inc. is a not-for-profit international association of the
world’s manufacturers of related air system equipment primarily, but limited to: fans, louvers, dampers, air
curtains, airflow measurement stations, acoustic attenuators, and other air system components for the industrial,
commercial and residential markets.
AMCA
Publication 201-02
(R2007)
Fans and Systems
All rights reserved. Reproduction or translation of any part of this work beyond that permitted by Sections 107 and
108 of the United States Copyright Act without the permission of the copyright owner is unlawful. Requests for
permission or further information should be addressed to the Executive Director, Air Movement and Control
Association International, Inc. at 30 West University Drive, Arlington Heights, IL 60004-1893 U.S.A.
Forward
ANSI/AMCA Standard 210 Laboratory Methods of Testing Fans for Aerodynamic Performance Rating, provides a
basis for accurately rating the performance of fans when tested under standardized laboratory conditions. The
actual performance of a fan when installed in an air moving system will sometimes be different from the fan
performance as measured in the laboratory. The difference in performance between the laboratory and the field
installation can sometimes be attributed to the interaction of the fan and the duct system, i.e., duct system design
can diminish the usable output of the fan.
AMCA Publication 201 Fans and Systems, introduced the concept of System Effect Factor to the air moving
industry. The System Effect Factor quantifies the duct system design effect on performance. The System Effect
Factor has been widely accepted since its inception in 1973. It must be remembered, however, that the "factors"
provided are approximations as it is prohibitive to test all fan types and all duct system configurations. The major
revision to this edition of AMCA Publication 201 Fans and Systems, is a change to the use of SI units of measure,
with Inch-Pound units being given secondary consideration.
Disclaimer
AMCA International uses its best efforts to produce standards for the benefit of the industry and the public in light
of available information and accepted industry practices. However, AMCA International does not guarantee, certify
or assure the safety or performance of any products, components or systems tested, designed, installed or
operated in accordance with AMCA International standards or that any tests conducted under its standards will be
non-hazardous or free from risk.
Air Movement and Control Association International, Inc. will consider and decide all written complaints regarding
its standards, certification programs, or interpretations thereof. For information on procedures for submitting and
handling complaints, write to:
or
Air Systems is intended to provide basic information needed to design effective and energy efficient air systems.
Discussion is limited to systems where there is a clear separation of the fan inlet and outlet and does not cover
applications in which fans are used only to circulate air in an open space.
Fans and Systems is aimed primarily at the designer of the air moving system and discusses the effect on inlet and
outlet connections of the fan's performance. System Effect Factors, which must be included in the basic design
calculations, are listed for various configurations. AMCA 202 and AMCA 203 are companion documents.
System Checklist
Fan Manufacturer's Analysis
Master Troubleshooting Appendices
Troubleshooting is intended to help identify and correct problems with the performance and operation of the air
moving system after installation. AMCA 201 and AMCA 203 are companion documents.
Acceptance Tests
Test Methods and Instruments
Precautions
Limitations and Expected Accuracies
Calculations
Field Performance Measurements of Fan Systems reviews the various problems of making field measurements
and calculating the actual performance of the fan and system. AMCA 201 and AMCA 202 are companion
documents.
TABLE OF CONTENTS
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1 Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
2.2 Subscripts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
3. Fan Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
4. Fan Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
4.2 Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
D.1 Example of fan (tested with free inlet, ducted outlet) applied to a
duct system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
D.2 Example of fan (tested with free inlet, ducted outlet), connected to a
duct system and then a plenum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
D.3 Example of fan with free inlet, free outlet - fan discharges directly
into plenum and then to duct system (abrupt expansion at fan outlet) . . . . . . . . . . . . . . . . . . .65
D.4 Example of fan used to exhaust with obstruction in inlet, inlet elbow,
inlet duct, free outlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66
Recognizing and accounting for losses that affect the Fans are tested in setups that simulate installations.
fan’s performance, in the design stage, will allow the The four standard installation types are as shown in
designer to predict with reasonable accuracy, the Figure 3.1.
installed performance of the fan.
AMCA INSTALLATION TYPE A:
1.1 Purpose Free Inlet, Free Outlet
1
AMCA 201-02 (R2007)
UNITS OF MEASURE
SYMBOL DESCRIPTION SI I-P
SUBSCRIPT DESCRIPTION
a Atmospheric conditions
c Converted Value
x Plane 0, 1, 2, ...as appropriate
1 Fan Inlet Plane
2 Fan Outlet Plane
3 Pitot Traverse Plane
5 Plane 5 (nozzle inlet station in chamber)
6 Plane 6 (nozzle discharge station in chamber)
8 Plane 8 (inlet chamber measurement station)
2
AMCA 201-02 (R2007)
of ANSI/AMCA 210 is to establish uniform methods The angle of the transition between the test duct and
for laboratory testing of fans and other air moving the fan outlet is limited to ensure that uniform airflow
devices to determine performance in terms of airflow, will be maintained. A steep transition, or abrupt
pressure, power, air density, speed of rotation and change of cross section would cause turbulence and
efficiency, for rating or guarantee purposes. Two eddies. The effect of this type of airflow disturbance
methods of measuring airflow are included: the Pitot at the fan outlet is discussed later.
tube and the long radius flow nozzle. These are
incorporated into a number of "setups" or "figures". Uniform airflow conditions ensure consistency and
In general, a fan is tested on the setup that most reproducibility of test results and permit the fan to
closely resembles the way in which it will be installed develop its maximum performance. In any installation
in an air system. Centrifugal and axial fans are where uniform airflow conditions do not exist, the
usually tested with an outlet duct. Propeller fans are fan's performance will be measurably reduced.
normally tested in the wall of a chamber or plenum.
Power roof ventilators (PRV) are tested mounted on As illustrated in Figure 3.3 Plane 2, the velocity
a curb exhausting from the test chamber. profile at the outlet of a fan is not uniform. The section
of straight duct attached to the fan outlet controls the
It is very important to realize that each setup in diffusion of the outlet airflow and establishes a more
ANSI/AMCA 210 is a standardized arrangement that uniform velocity as shown in Figure 3.3 Plane X.
is not intended to reproduce exactly any installation
likely to be found in the field. The infinite variety of The energy loss when a gas, such as air, passes
possible arrangements of actual air systems makes it through a sudden enlargement is related to the
impractical to duplicate every configuration in the fan square of the velocity. Thus the ducted outlet with its
test laboratory. more uniform velocity significantly reduces the loss at
the point of discharge to the atmosphere.
3.2 Ducted outlet fan tests
A manufacturer may test a fan with or without an inlet
Figure 3.2 is a reproduction of a test setup from duct or outlet duct. For products licensed to use the
ANSI/AMCA 210. Note that this particular setup AMCA Certified Ratings Seal, catalog ratings will
includes a long straight duct connected to the outlet state whether ducts were used during the rating tests.
of the fan. A straightener is located upstream of the
Pitot traverse to remove swirl and rotational If the fans are not to be applied with the same duct(s)
components from the airflow and to ensure that as in the test setup, an allowance should be made for
airflow at the plane of measurement is as nearly the difference in performance that may result.
uniform as possible.
1 2
Transition Straightener
Piece
3
AMCA 201-02 (R2007)
3.3 Free inlet, free outlet fan tests calculated from the performance of smaller fans in
the series using the appropriate equations.
Figure 3.4 illustrates a typical multi-nozzle chamber
test setup from ANSI/AMCA 210. This simulates the Because of the relationship between the airflow,
conditions under which most exhaust fans are tested pressure and power for any given fan, each set of
and rated. Fan performance based on this type of equations for changes in speed, size or density,
test may require adjustment when additional applies only to the same Point of Rating, and all the
accessories are used with the fan. Fans designed for equations in the set must be used to define the
use without duct systems are usually rated over a converted condition. A Point of Rating is the specified
lower range of pressures. They are commonly fan operating point on its characteristic curve.
cataloged and sold as a complete unit with suitable
drive and motor. The Fan Law equations are shown below as ratios.
The un-subscripted variable is used to designate the
3.4 Obstructed inlets and outlets initial or test fan values for the variable and the
subscript c is used to designate the converted,
The test setups in ANSI/AMCA 210 result in dependent or desired variable.
unobstructed airflow conditions at both the inlet and
the outlet of the fan. Appurtenances or obstructions Qc = Q × (Dc/D)3 × (Nc/N) × (Kp/Kpc)
located close to the inlet and/or outlet will affect fan
performance. Shafts, bearings, bearing supports and Ptc = Pt × (Dc/D)2 × (Nc/N)2 × (ρc/ρ) × (Kp/Kpc)
other appurtenances normally used with a fan should
be in place when a fan is tested for rating. Pvc = Pv × (Dc/D)2 × (Nc/N)2 × (ρc/ρ)
Since changes in performance will be different for ηtc = (Qc × Ptc × Kp) / (6362 • Hc) (I-P)
various product designs, it will be necessary to make
suitable allowances based on data obtained from the ηsc = ηtc × (Psc/Ptc)
applicable fan catalog or directly from the
manufacturer. These equations have their origin in the classical
theories of fluid mechanics, and the accuracy of the
Most single width centrifugal fans are tested using results obtained is sufficient for most applications.
Arrangement 1 fans. Some allowance for the effect Better accuracy would require consideration of
of bearings and bearing supports in the inlet may be Reynolds number, Mach number, kinematic viscosity,
necessary when using Arrangement 3 or dynamic viscosity, surface roughness, impeller blade
Arrangement 7. The various AMCA standard thickness and relative clearances, etc.
arrangements are shown on Figures 3.5, 3.6, and
3.7. 4.2 Limitations
4
AMCA 201-02 (R2007)
PL X
BLAST AREA PL 2 DISCHARGE DUCT
OUTLET AREA
CUTOFF
CENTRIFUGAL FAN
PL 2 PL X
AXIAL FAN
38mm ±6mm
(1.5in. ±0.25 in.)
PL.5 PL.6 PL.8 PL.1 PL.2
0.5 M MIN.
0.2M 0.5M 0.2 M MIN.
MIN. MIN. 0.3 M MIN.
t d2
AIRFLOW M FAN
VARIABLE
SUPPLY t d3
SYSTEM 0.1 M MIN.
SETTLING SETTLING
MEANS MEANS
(See note 4)
Ps5 P Pt8
5
AMCA 201-02 (R2007)
ISO 13349
AMCA Drive Alternative Fan
Drive Description Fan Configuration
Arrangement Configuration
Arrangement
AMCA International, Inc. | 30 W. University Dr. | Arlington Heights, IL, 60004-1893 | U.S.A
6
AMCA 201-02 AMCA 201-02 (R2007)
ISO 13349
AMCA Drive Alternative Fan
Drive Description Fan Configuration
Arrangement Configuration
Arrangement
AMCA International, Inc. | 30 W. University Dr. | Arlington Heights, IL, 60004-1893 | U.S.A
7
AMCA 201-02 (R2007)
ISO 13349
AMCA Drive Alternative Fan
Drive Description Fan Configuration
Arrangement Configuration
Arrangement
integrally mounted.
AMCA International, Inc. | 30 W. University Dr. | Arlington Heights, IL, 60004-1893 | U.S.A
8
AMCA 201-02 (R2007)
has adopted the term Fan Reynolds Number. calculated using the proper specific heat ratio for the
gases being handled.
Re = (πND2ρ) / (60μ)
d. Specific Heat Ratio (Cp). Model fan tests are
where: N = impeller rotational speed, rpm usually based on air with a specific heat ratio of 1.4.
D = impeller diameter, m(ft) Induced draft fans may handle flue gas with a specific
ρ = air density, kg/m3 (lbm/ft3) heat ratio of 1.35. Even though these differences may
μ = absolute viscosity, normally be considered small, they make a
1.8185 × 10-3 Pa•s (5°C to 38°C) (SI) noticeable difference in the calculation of the
(1.22 × 10-05 lbm/ft•s (40°F to 100°F)) (I-P) compressibility coefficient. Refer to AMCA
Publication 802, Annex A, for calculation procedures.
The threshold fan Reynolds number for centrifugal
and axial fans is about 3.0 × 106. That is, there is a e. Tip Speed Mach Parameter (Mt). Tip speed Mach
negligible change in performance between the two parameter is an expression relating the tip speed of
fans due to differences in Reynolds number if both the impeller to the speed of sound at the fan inlet
fans are operating above this threshold value. When condition.
the Reynolds number of a model fan is below 3.0 ×
106, there may be a gain in efficiency (size effect) for When airflow velocity at a point approaches the
a full size fan operating above the threshold speed of sound, some blocking or choking effects
compared to one operating below the threshold. This occur that reduce the fan performance.
occurs only when both fans are operating near peak
efficiency. Therefore, when a model test is being 4.3 Fan performance curves
conducted to verify the rating of a full size fan, the
Reynolds number should be above 3.0 ×106 to avoid A fan performance curve is a graphic presentation of
any uncertainty relating to Reynolds number effects. the performance of a fan. Usually it covers the entire
range from free delivery (no obstruction to airflow) to
b. Point of Rating. To predict the performance of a no delivery (an air tight system with no air flowing).
fan from a smaller model using the Fan Laws, both One, or more, of the following characteristics may be
fans must be geometrically similar (homologous), plotted against volume airflow (Q).
and both fans must operate at the same
corresponding rating points on their characteristic Fan Static Pressure Ps
curves. Two or more fans are said to be operating at Fan Total Pressure Pt
corresponding “points of rating” if the positions of the Fan Power H
operating points, relative to the pressure at shutoff Fan Static Efficiency ηs
and the airflow at free delivery, are the same. Fan Total Efficiency ηt
c. Compressibility. Compressibility is the characteristic Air density (ρ), fan size (D), and fan rotational speed
of a gas to change its volume as a function of (N) are usually constant for the entire curve and must
pressure, temperature and composition. The be stated.
compressibility coefficient (Kp) expresses the ratio of
the fan total pressure developed with an A typical fan performance curve is shown in Figure
incompressible fluid to the fan total pressure 4.1. Figure 4.2 illustrates examples of performance
developed with a compressible fluid (See curves for a variety of fan types.
ANSI/AMCA 210). Differences in the compressibility
coefficient between two similar fans must be
9
AMCA 201-02 (R2007)
Pt
100
Ps
90
80
PRESSURE, P
POWER, H
ηt
EFFICIENCY, η PERCENT
70
60
50
ηs
40
H
30
20
OPERATION AT 10
STANDARD DENSITY
0
AIRFLOW, Q
10
AMCA 201-02 (R2007)
• Highest efficiency of all centrifugal fan designs. • Scroll-type design for efficient conversion of velocity
• Ten to 16 blades of airfoil contour curved away from pressure to static pressure.
AIRFOIL
direction of rotation. Deep blades allow for efficient • Maximum efficiency requires close clearance and
expansion within blade passages alignment between wheel and inlet
• Air leaves impeller at velocity less than tip speed.
• For given duty, has highest speed of centrifugal
fan designs
• Efficiency only slightly less than airfoil fan. • Uses same housing configuration as airfoil design.
BACKWARD-
BACKWARD-
• Higher pressure characteristics than airfoil, • Scroll. Usually narrowest of all centrifugal designs.
backward-curved, and backward-inclined fans. • Because wheel design is less efficient, housing
RADIAL
• Curve may have a break to left of peak pressure dimensions are not as critical as for airfoil and
R R
and fan should not be operated in this area. backward-inclined fans.
• Power rises continually to free delivery.
M
M
• Flatter pressure curve and lower efficiency than the • Scroll similar to and often identical to other centrifugal
airfoil, backward-curved, and backward-inclined. fan designs.
FORWARD-
CURVED
• Do not rate fan in the pressure curve dip to the left • Fit between wheel and inlet not as critical as for airfoil
of peak pressure. and backward-inclined fans.
• Power rises continually toward free delivery. Motor
selection must take this into account.
• Limited to low-pressure applications. • Optimum design is close to blade tips and forms
• Usually low cost impellers have two or more blades of smooth airfoil into wheel.
single thickness attached to relatively small hub.
• Primary energy transfer by velocity pressure.
• Somewhat more efficient and capable of developing • Cylindrical tube with close clearance to blade tips.
AXIAL FANS
• Good blade design gives medium- to high-pressure • Cylindrical tube with close clearance to blade tips.
capability at good efficiency. • Guide vanes upstream or downstream from impeller
VANEAXIAL
• Most efficient of these fans have airfoil blades. increase pressure capability and efficiency.
• Blades may have fixed, adjustable, or controllable
pitch.
• Hub is usually greater than half fan tip diameter.
• Performance similar to backward-curved fan except • Cylindrical tube similar to vaneaxial fan, except
CENTRIFUGAL
• Lower efficiency than backward-curved fan. • Air discharges radially from wheel and turns 90° to
• Performance curve may have a dip to the left of flow through guide vanes.
peak pressure.
SPECIAL DESIGNS
A
• Low-pressure exhaust systems such as general • Normal housing not used, since air discharges from
CENTRIFUGAL
• Low-pressure exhaust systems such as general • Essentially a propeller fan mounted in a supporting
factory, kitchen, warehouse, and some commercial structure
installations. • Hood protects fan from weather and acts as safety
AXIAL
11
AMCA 201-02 (R2007)
a
PERFORMANCE CURVES PERFORMANCE CHARACTERISTICS APPLICATIONS
10
Pt • Highest efficiencies occur at 50 to 60% of wide open • General heating, ventilating, and air-conditioning
PRESSURE-POWER
8
Ps 10 volume. This volume also has good pressure applications.
6 8 characteristics. • Usually only applied to large systems, which may be
EFFICIENCY
ηt
4 ηs 6 • Power reaches maximum near peak efficiency and low-, medium-, or high-pressure applications.
wo 4 becomes lower, or self-limiting, toward free delivery. • Applied to large, clean-air industrial operations for
2
VOLUME FLOW RATE, Q 2 significant energy savings.
0 0
0 2 4 6 8 10
10
• Similar to airfoil fan, except peak efficiency slightly lower. • Same heating, ventilating, and air-conditioning
PRESSURE-POWER
8
10 applications as airfoil fan.
6 8 • Used in some industrial applications where airfoil
EFFICIENCY
4
6 blade may corrode or erode due to environment.
4
2
VOLUME FLOW RATE, Q 2
0 0
0 2 4 6 8 10
10
• Higher pressure characteristics than airfoil and backward- • Primarily for materials handling in industrial plants.
PRESSURE-POWER
8
10 curved fans. Also for some high-pressure industrial requirements.
6 8 • Pressure may drop suddenly at left of peak pressure, but • Rugged wheel is simple to repair in the field. Wheel
EFFICIENCY
4
6 this usually causes no problems. sometimes coated with special material.
4 • Power rises continually to free delivery. • Not common for HVAC applications.
2
2
VOLUME FLOW RATE, Q
0 0
0 2 4 6 8 10
10
• Pressure curve less steep than that of backward-curved • Primarily for low-pressure HVAC applications, such as
PRESSURE-POWER
8
10 fans. Curve dips to left of peak pressure. residential furnaces, central station units, and
6 8 • Highest efficiency to right of peak pressure at 40 to 50% packaged air conditioners.
EFFICIENCY
4
6 of wide open volume.
4 • Rate fan to right of peak pressure.
2
VOLUME FLOW RATE, Q 2 • Account for power curve, which rises continually toward
0
0
0 2 4 6 8 10 free delivery, when selecting motor.
10
• High flow rate, but very low-pressure capabilities. • For low-pressure, high-volume air moving applications,
• Maximum efficiency reached near free delivery. such as air circulation in a space or ventilation through
PRESSURE-POWER
8
10
6 8 • Discharge pattern circular and airstream swirls. a wall without ductwork.
EFFICIENCY
10
• High flow rate, medium-pressure capabilities. • Low- and medium-pressure ducted HVAC applications
PRESSURE-POWER
8
10 • Performance curve dips to left of peak pressure. Avoid where air distribution downstream is not critical.
6 8 operating fan in this region. • Used in some industrial applications, such as drying
EFFICIENCY
4
6 • Discharge pattern circular and airstream rotates or swirls. ovens, paint spray booths, and fume exhausts.
4
2
2
VOLUME FLOW RATE, Q
0 0
0 2 4 6 8 10
10
• High-pressure characteristics with medium-volume flow • General HVAC systems in low-, medium-, and high-pressure
PRESSURE-POWER
8
10 capabilities. applications where straight-through flow and compact
6 8 • Performance curve dips to left of peak pressure due to installation are required.
EFFICIENCY
4
6 aerodynamic stall. Avoid operating fan in this region. • Has good downstream air distribution
4 • Guide vanes correct circular motion imprated by wheel and • Used in industrial applications in place of tubeaxial fans.
2
2 improve pressure characteristics and efficiency of fan. • More compact than centrifugal fans for same duty.
VOLUME FLOW RATE, Q
0 0
0 2 4 6 8 10
10
• Performance similar to backward-curved fan, except • Primarily for low-pressure, return air systems in HVAC
PRESSURE-POWER
8
10 capacity and pressure is lower. applications.
6 8 • Lower efficiency than backward-curved fan because air • Has straight-through flow.
EFFICIENCY
4
6 turns 90°.
4 • Performance curve of some designs is similar to axial flow
2
VOLUME FLOW RATE, Q 2 fan and dips to left of peak pressure.
0 0
0 2 4 6 8 10
10
• Usually operated without ductwork; therefore, operates at • Low-pressure exhaust systems, such as general factory,
PRESSURE-POWER
8
10 very low pressure and high volume. kitchen, warehouse, and some commercial installations.
6 8 • Only static pressure and static efficiency are shown for • Low first cost and low operating cost give an advantage over
EFFICIENCY
4
6 this fan. gravity flow exhaust systems.
4 • Centrifugal units are somewhat quieter than axial flow units.
2
2
VOLUME FLOW RATE, Q 0
0
0 2 4 6 8 10
10
• Usually operated without ductwork; therefore, operates at • Low-pressure exhaust systems, such as general factory,
very low pressure and high volume. kitchen, warehouse, and some commercial installations.
PRESSURE-POWER
8
10
6 8 • Only static pressure and static efficiency are shown for • Low first cost and low operating cost give an advantage
EFFICIENCY
a: These performance curves reflect general characteristics of various fans as commonly applied. They are not intended to provide complete selection criteria, since other parameters,
such as diameter and speed, are not defined.
12
AMCA 201-02 (R2007)
Fans designed for use other than with duct systems The performance of fans intended for use with duct
are usually rated over a lower range of pressures. systems is usually published in the form of a "multi-
They are commonly cataloged and sold as a rating" table. A typical multi-rating table, as illustrated
complete unit with suitable drive and motor. in Figure 5.2 shows:
Typical fans in this group are propeller fans and a) the speed (N) in rpm
power roof ventilators. They are usually available in b) the power (H) in kw (hp)
direct or belt-drive arrangements and performance c) the fan static pressure (Ps) in Pa (in. wg)
ratings are published in a modified form of the multi- d) the outlet velocity (V) in m/s, (fpm)
rating table. Figure 5.1 illustrates such a table for part e) the airflow (Q) in m3/s (cfm)
of a line of belt-drive propeller fans.
Figure 5.3 shows constant speed characteristic
5.2 Ducted fans curves superimposed on a section of the multi-rating
table for the same fan. A brief study of this figure will
There are three types of ducted fans, as described in assist in understanding the relationship between
Section 3: curves and the multi-rating tables.
SIZE No. of Motor Peak AIRFLOW (ft3/min) @ STATIC PRESSURE (in. wg)
rpm
(in.) Blades hp bhp 0 1/8 1/4 3/8 1/2 5/8 3/4 7/8 1
1/4 862 0.18 4,283 3,350 1,230
1/4 960 0.27 4,770 3,960 2,050
24 3
1/3 1071 0.36 5,321 4,620 3,730 1,600
1/2 1220 0.54 6,062 5,450 4,750 3,600 1,710
1/4 806 0.27 6,123 4,990 2,230
1/3 883 0.36 6,708 5,675 4,100 1,620
27 3
1/2 1035 0.57 7,862 7,000 6,035 3,315 2,020
3/4 1165 0.83 8,850 8,110 7,290 6,385 3,400 2,330
1/2 825 0.56 9,240 7,970 6,430 2,700
3/4 945 0.83 10,580 9,500 8,300 5,040 3,010
33 3 1 1045 1.1 11,710 10,755 9,685 8,490 4,890 3,215
1½ 1190 1.6 13,335 12,490 11,580 10,610 9,500 5,905 4,100
2 1306 2.2 14,630 13,845 13,030 12,185 11,280 10,200 6,470 4,740 3,900
TYPICAL RATING TABLE FOR A SERIES OF BELT-DRIVEN PROPELLER FANS
Figure 5.1 - Propeller Fan Performance Table
13
AMCA 201-02 (R2007)
TYPICAL MULTISPEED RATING TABLE FOR A SINGLE WIDTH, SINGLE INLET CENTRIFUGAL FAN
14
PRESSURE IN IN. WG
BRAKE HORSEPOWER
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
VOLUME OUTLET
390 RPM
490 RPM
CFM VELOCITY
6885 900 292 .450 317 .579 343 .716 366 .856 389 1.01 411 1.17
7650 1000 314 .560 337 .695 360 .840 332 .992 403 1.15 424 1.31 443 1.48
8415 1100 338 .682 358 .822 378 .981 399 1.144 419 1.31 438 1.48 458 1.60 494 2.04
9180 1200 361 .826 379 .988 398 1.149 417 1.314 436 1.49 455 1.58 472 1.86 507 2.25 540 2.67
9945 1300 335 .988 482 1.163 419 1.340 437 1.514 454 1.69 472 1.89 489 2.09 522 2.49 554 2.92 584 3.37
10710 1400 409 1.175 426 1.360 441 1.553 457 1.741 473 1.93 489 2.12 506 2.34 538 2.76 568 3.28 598 3.66
11475 1500 434 1.387 449 1.587 464 1.78 479 1.995 494 2.19 509 2.40 524 2.61 555 3.06 584 3.52 612 3.99
12240 1600 456 1.626 473 1.837 488 2.048 501 2.269 515 2.49 529 2.70 543 2.92 572 3.49 600 3.87 627 4.36
13005 1700 482 493 2.115 511 2.346 525 2.570 537 2.80 550 3.03 564 3.26 590 3.73 617 4.24 643 4.76
CFM
13770 1800 508 2.19 522 2.424 535 2.665 538 2.901 560 3.15 572 3.40 585 3.84 610 4.12 635 4.63 661 5.18
14535 1900 547 2.767 559 3.017 571 3.276 584 3.52 595 606 4.04 630 4.55 654 5.07 678 5.63
15300 2000 571 3.744 584 3.403 596 607 3.93 618 4.21 629 4.48 651 5.02 674 5.56 696 6.11
16830 2200 629 4.003 633 4.289 644 4.577 654 4.87 665 5.16 675 5.46 695 6.06 715 6.65 736 7.24
18360 2400 682 5.335 693 5.632 703 5.76 712 6.28 721 6.81 741 7.24 759 7.90 778
19890 2600 742 6.885 752 7.22 761 7.56 769 7.91 788 8.60 9.30 822 10.02
21420 2800 791 8.308 801 8.67 810 9.03 818 8.48 834 10.15 852 10.88 867 11.65
22950 3000 850 10.32 859 10.71 867 11.09 883 11.89 898 12.70 914 13.48
24480 3200 908 12.60 916 13.01 932 13.84 946 14.70 960 15.56
26010 3400 965 15.16 981 16.03 995 16.92 1009 17.83
27540 3600 1015 17.52 1030 18.47 1044 19.39 1057 20.35
29070 3800 1079 21.16 1093 22.13 1106 23.12
30600 4000 1129 24.11 1142 25.16 1155 26.18
15
AMCA 201-02 (R2007)
RECOMMENDED
SELECTION RANGE
PR
ES
SU
RE
PRESSURE
E
RV
CU
SELECTION
NOT USUALLY
EM
RECOMMENDED
ST
SY
IN THIS RANGE
E
RV
CT
CU
DU
EM
YST
C TS
DU
AIRFLOW
16
AMCA 201-02 (R2007)
In a later section, the effects of some system The system curve of a "fixed system" plots as a
components and fan accessories on fan performance parabola in accordance with the above relationship.
are discussed. The System Effects presented will Typical plots of the resistance to flow versus volume
assist the system designer to determine fan airflow for three different and arbitrary fixed systems,
selection. (A, B, and C) are illustrated in Figure 6.1. For a fixed
system an increase or decrease in airflow results in
6.3 The system curve an increase or decrease in the system resistance
along the given system curve only. Also, as the
At a fixed airflow through a given air system a components in a system change, the system curve
corresponding pressure loss, or resistance to this changes.
airflow, will exist. If the airflow is changed, the
resulting pressure loss, or resistance to airflow, will Refer to Figure 6.1, Duct System A. With a system at
also change. The relationship between airflow the design airflow (Q) and at a design system
pressure and loss can vary as a function of type of resistance (P), an increase in airflow to 120% of Q
duct components, their interaction and the local will result in an increase in system resistance P of
velocity magnitude. In many cases, typical duct 144% since system resistance varies with the square
systems operate in the turbulent flow regime and the of the airflow. Likewise, a decrease in airflow Q to
pressure loss can be approximated as a function of 50% would result in a decrease in system resistance
velocity (or airflow) squared. The simplifying P to 25% of the design system resistance.
relationship used in this publication governing the
change in pressure loss as a function of airflow for a In Figure 6.1, System Curve B is representative of a
fixed system is: system that has more component pressure loss than
System Curve A, and System Curve C has less
Pc/P = (Qc/Q)2 component pressure loss than System Curve A.
A more through discussion of duct system pressure Notice that on a percentage basis, the same
losses can be found in AMCA Publication 200 Air relationships also hold for System Curves B and C.
Systems. These relationships are characteristic of typical fixed
systems.
200
180
PERCENT OF SYSTEM RESISTANCE
160
C
E M
140
ST
SY
120
100
SYSTEM
80 A DESIGN
EM
B
POINT
ST
ME
SY
ST
60
SY
40
20
0
0 20 40 60 80 100 120 140 160 180 200
17
AMCA 201-02 (R2007)
6.4 Interaction of system curve and fan is now at Point 3 (the intersection of the fan curve and
performance curve the new System C), with the airflow at approximately
120% of Q.
If the system characteristic curve, composed of the
resistance to system airflow and the appropriate SEF 6.5 Effect of changes in speed
have been accurately determined, then the fan will
deliver the designated airflow when installed in the Increases or decreases in fan rotational speed will
system. alter the airflow through a system. According to the
Fan Laws (see below), the % increase in airflow is
The point of intersection of the system curve and the directly proportional to the fan rotational speed ratio,
fan performance curve determines the actual airflow. and the fan static pressure is proportional to the
System Curve A in Figure 6.2 has been plotted with a square of the fan rotational speed ratio. Thus, a 10%
fan performance curve that intersects the system increase in fan rotational speed will result in a new
design point. fan curve with a 10% increase in Q, as illustrated in
Figure 6.3. Since the system components did not
The airflow through the system in a given installation change, System Curve A remains the same. With
may be varied by changing the system resistance. airflow increasing by 10% over the original Q, the
This is usually accomplished by using fan dampers, system resistance increases along System Curve A
duct dampers, mixing boxes, terminal units, etc. to Point 2, at the intersection with the new fan curve.
Figure 6.2 shows the airflow may be reduced from The greater airflow moved by the fan against the
design Q by increasing the resistance to airflow, i.e., resulting higher system resistance to airflow is a
changing the system curve from System A to System measure of the increased work done. In the same
B. The new operating point is now at Point 2 (the system, the fan efficiency remains the same at all
intersection of the fan curve and the new System B) points on the same system curve.
with the airflow at approximately 80% of Q. Similarly,
the airflow can be increased by decreasing the This is due to the fact that airflow, system resistance,
resistance to airflow, i.e., changing the system curve and required power are varied by the appropriate
from System A to System C. The new operating point ratio of the fan rotational speed.
200
PERCENT OF SYSTEM RESISTANCE
180
EM
C
M
ST
160 E
ST
SY
SY
140
FAN CURVE
120 2
SYSTEM
100 1 DESIGN
POINT
80
3
60 B
T EM
40 SYS
20
0
0 20 40 60 80 100 120 140 160 180 200
18
AMCA 201-02 (R2007)
6.5.1 Fan Laws - effect of change in speed - (fan air density of 1.2 kg/m3 (0.075 lbm/ft3) is standard in
size and air density remaining constant) the fan industry throughout the world. Figure 6.4
illustrates the effect on the fan performance of a
For the same size fan, Dc = D and, therefore, (Dc/D) density variation from the standard value.
= 1. When the air density does not vary, ρc = ρ and
the air density ratio (ρc/ρ) = 1. Kp is taken as equal to 6.6.1 Fan Laws - effect of change in density - (fan
unity in this and following examples. size and speed remaining constant)
Psc = Ps × (Nc/N)2 Qc = Q
Psc = Ps × (ρc/ρ)
Hc = H × (Nc/N)3
Pvc = Pv × (ρc/ρ)
6.6 Effect of density on system resistance
Hc = H × (ρc/ρ)
The resistance of a duct system is dependent upon
the density of the air flowing through the system. An
A
EM
ST
SY
PERCENT OF SYSTEM RESISTANCE
CT
DU
H (AT 1.1N)
160 S (AT 1.1N)
PRESSURE
133
PERCENT OF POWER
140
S (AT N)
PRESSURE
120 2
H (AT N)
100 1
100
80
60
40 50
20
110%
0
0 20 40 60 80 100 120 140 160 180 200
19
AMCA 201-02 (R2007)
100
SYSTEM A
PERCENT OF SYSTEM
60
40
20
100
PERCENT OF POWER
POWER @ DENSITY ρ
80
60
40
0
0 20 40 60 80 100 120 140 160 180 200
20
AMCA 201-02 (R2007)
6.7 Fan and system interaction condition results in an actual airflow at Point 2, which
is at a higher pressure and lower airflow than was
When system pressure losses have been accurately expected.
estimated and desirable fan inlet and outlet
conditions have been provided, design airflow can be If the actual duct system pressure loss is greater than
expected, as illustrated in Figure 6.5. Note again that design, an increase in fan speed may be necessary
the intersection of the actual system curve and the to achieve Point 5, the design airflow.
fan curve determine the actual airflow. However,
when system pressure losses have not been CAUTION: Before increasing fan rotational
accurately estimated as in Figure 6.6, or when speed, check with the fan manufacturer to
undesirable fan inlet and outlet conditions exist as in determine whether the fan rotational speed can
Figure 6.7, design performance may not be obtained. be safely increased. Also determine the expected
increase in power. Since the power required
6.8 Effects of errors in estimating system increases as the cube of the fan rotational speed
resistance ratio, it is very easy to exceed the capacity of the
existing motor and that of the available electrical
6.8.1 Higher system resistance. In Figure 6.6, service.
System Curve B shows a situation where a system
has greater resistance to airflow than designed 6.8.2 Lower system resistance. Curve C in Figure
(Curve A). This condition is generally a result of 6.6 shows a system that has less resistance to airflow
inaccurate allowances of system resistance. All than designed. This condition results in an actual
pressure losses must be considered when airflow at Point 3, which is at a lower pressure and
calculating system resistance or the actual system higher airflow than was expected.
will be more restrictive to airflow than intended. This
1
FAN PRESSURE
CURVE
DESIGN RESISTANCE
DESIGN AIRFLOW
21
AMCA 201-02 (R2007)
6.9 Safety factors the fan speed, adjusting the variable inlet vane (VIV),
if installed, or inlet dampers. The system resistance
It has been common practice among system could also be increased to Point 1 on Curve A, Figure
designers to add safety factors to the calculated 6.6. The change in fan operating point should be
system resistance to account for the “unexpected”. evaluated carefully, since a change in fan power
In some cases, safety factors may compensate for consumption may occur.
resistance losses that were unaccounted for and the
actual system will deliver the design airflow, Point 1, The system designer should also evaluate the fan
Figure 6.6. If the actual system resistance is lower performance tolerance and system resistance
than the design system resistance, including the tolerance to determine if the lower or upper limits of
safety factors, the fan will run at Point 3 and deliver the probable airflow in the system are acceptable.
more airflow. This result may not be advantageous The combination of these tolerances should be
because the fan may be operating at a less efficient evaluated to ensure that the “high-side” system
point on the fan’s performance curve and may require resistance curve does not fall into the unstable range
more power than a properly designed system. Under of performance. Operation in this area of the curve
these conditions, it may be desirable to reduce the should be avoided and precautions taken to ensure
fan performance to operate at Point 4 on Curve C, operations outside of the unstable area, especially at
Figure 6.6. This may be accomplished by reducing the highest expected system resistance.
CURVE B:
ACTUAL SYSTEM
5
CURVE C
ACTUAL SYSTEM
PEAK FAN
PRESSURE 2
ACTUAL SYSTEM
LESS THAN
3 DESIGN
DESIGN RESISTANCE
FAN PRESSURE
CURVE
DESIGN AIRFLOW
22
AMCA 201-02 (R2007)
6.10 Deficient fan/system performance • Include adequate allowance for the effect of all
accessories and appurtenances on the
The most common causes of deficient fan/system performance of the system and the fan. If
performance are improper fan inlet duct design, fan possible, obtain from the fan manufacturer
outlet duct design, and fan installation into the duct data on the effect of installed appurtenances
system. Any one or a combination of these conditions on the fan's performance (See Section 10).
that alter the aerodynamic characteristics of the air
flowing through the fan such that the fan’s full airflow • Use field measurement techniques that can be
potential, as tested in the laboratory and cataloged, is applied effectively on the particular system.
not likely to be realized. Be aware of the probable accuracy of
measurement and conditions that affect this.
Other major causes of deficient performance are: Refer to AMCA Publication 203 Field
Performance Measurement of Fan Systems;
• The air performance characteristics of the for more precise measurement see AMCA
installed system are significantly different from Standard 803 Industrial Process/Power
the system designer's intent (See Figure 6.6). Generation Fans: Site Performance Test
This may be due to a change in the system by Standard. Also, refer to AABC National
others or unexpected behavior of the system Standards, Chapter 8, Volume Measurements,
during operation. Associated Air Balance Council, 5th Edition,
1989.
• The system design calculations did not include
adequate allowances for the effect of accessories 6.12 System Effect
and appurtenances (See Section 10).
Figure 6.7 illustrates deficient fan/system
• The fan selection was made without allowing performance resulting from one or more of the
for the effect of appurtenances on the fan's undesirable airflow conditions listed in Section 6.10.
performance (See Section 10). It is assumed that the system pressure losses, shown
in system curve A, have been accurately determined,
• Dirty filters, dirty ducts, dirty coils, etc., will and a suitable fan selected for operation at Point 1.
increase the system resistance, and However, no allowance has been made for the effect
consequently, reduce the airflow - often of the system connections on the fan's performance.
significantly. To account for this System Effect it will be necessary
to add a System Effect Factor (SEF) to the calculated
• The "performance" of the system has been system pressure losses to determine the actual
determined by field measurement techniques system curve. The SEF for any given configuration is
that have a high degree of uncertainty. velocity dependent and will vary across a range of
airflow. This will be discussed in more detail in
Other "on-site" problems are listed in AMCA Section 7. (See Figure 7.1).
Publication 202 Troubleshooting, which includes
detailed checklists and recommendations for the In Figure 6.7 the point of intersection between the fan
correction of problems with the performance of air performance curve and the actual system curve B is
systems. Point 4. The actual airflow will be deficient by the
difference 1-4. To achieve design airflow, a SEF
6.11 Precautions to prevent deficient equal to the pressure difference between Point 1 and
performance 2 should have been added to the calculated system
pressure losses and the fan selected to operate at
• Use appropriate allowances in the design Point 2. Note that because the System Effect is
calculations when space or other factors velocity related, the difference represented between
dictate the use of less than optimum Points 1 and 2 is greater than the difference between
arrangement of the fan outlet and inlet Points 3 and 4.
connections (See Sections 8 and 9).
The System Effect includes only the effect of the
• Design the connections between the fan and system configuration on the fan's performance.
the system to provide, as nearly as possible,
uniform airflow conditions at the fan outlet and
inlet connections (See Sections 8 and 9).
23
AMCA 201-02 (R2007)
A System Effect Factor is a value that accounts for Figure 7.1 shows a series of 19 System Effect
the effect of conditions adversely influencing fan Curves. By entering the chart at the appropriate air
performance when installed in the air system. velocity (on the abscissa), it is possible to read
across from any curve (to the ordinate) to find the
SEF for a particular configuration.
CURVE B
ACTUAL SYSTEM
WITH SYSTEM EFFECT
CURVE A
CALCULATED SYSTEM
WITH NO ALLOWANCE
FOR SYSTEM EFFECT
2
AIRFLOW
DEFICIENCY
DESIGN AIRFLOW
24
AMCA 201-02 (R2007)
FG H I J K L M N O P
1000
900
Q
800
700
R
600
500
400 S
SYSTEM EFFECT FACTOR PRESSURE, Pa
300
T
U
200
100
90 W
80
70
60
X
50
40
30
20
2.5 3 4 5 6 7 8 9 10 20 30
25
AMCA 201-02 (R2007)
FG H I J K L M N O
5.0
P
4.0
Q
3.0
2.5 R
SYSTEM EFFECT FACTOR - PRESSURE, in. wg
2.0
S
1.5
1.0
0.9 U
0.8
0.7
0.6
V
0.5
0.4 W
0.3
0.25
X
0.2
0.15
0.1
5 6 7 8 9 10 15 20 25 30 40 50 60
26
AMCA 201-02 (R2007)
F 16.00
G 14.20
H 12.70
I 11.40
J 9.50
K 7.90
L 6.40
M 4.50
N 3.20
O 2.50
P 1.90
Q 1.50
R 1.20
S 0.75
T 0.50
U 0.40
V 0.25
W 0.17
X 0.10
2
⎛ V ⎞
SEF = C ⎜ ⎟ ρ
⎝ 1.414 ⎠ SI
2
⎛ V ⎞
SEF = C ⎜ ⎟ ρ
⎝ 1097 ⎠ I-P
27
AMCA 201-02 (R2007)
The SEF is given in Pascals (in. wg) and must be The System Effect Curves are plotted for standard air
added to the total system pressure losses as shown at a density of 1.2 kg/m3 (0.075 lbm/ft3). Since the
on Figure 7.2. System Effect is directly proportional to density,
values for other densities can be calculated as below:
The velocity used when entering Figure 7.1 will be
either the inlet or the outlet velocity of the fan. This
⎛d ⎞
will depend on whether the configuration in question SEF2 = SEF1 ⎜ 2 ⎟
is related to the fan inlet or the fan outlet. Most ⎝ d1 ⎠
catalog ratings include outlet velocity figures but, for
centrifugal fans, it may be necessary to calculate the Where:
inlet velocity (See Figure 9.14). The inlet velocity and SEF2 = SEF at actual density
outlet velocity of an axial fan can be approximated by
SEF1 = SEF at standard density
using the fan impeller diameter to determine the
d2 = actual density
airflow area. The necessary dimensioned drawings
are usually included in the fan catalog. d1 = standard density
In Sections 8 and 9, typical inlet and outlet Alternatively, the SEF may be calculated by the
configurations are illustrated and the appropriate method shown in Table 7.1. Determine the
System Effect Curve is listed for each configuration. configuration being evaluated and use the
If more than one configuration is included in a appropriate loss coefficient, Cp, and application
system, the SEF for each must be determined velocity, V. The SEF can then be calculated using the
separately and the total of these System Effects must equations shown in Table 7.1.
be added to the total pressure losses.
FAN POWER
CALCULATED
ACTUAL SYSTEM RESISTANCE
FAN PRESSURE
DESIGN AIRFLOW
28
AMCA 201-02 (R2007)
As previously discussed, fans intended primarily for Figure 8.1 shows changes in velocity profiles at
use with duct systems are usually tested with an various distances from centrifugal and axial flow fan
outlet duct in place (See Figure 3.2). In most cases outlets. By definition, 100% "effective duct length" is
it is not practical for the fan manufacturer to supply a minimum of two and one half (2½) equivalent duct
this duct as part of the fan, but rated performance will diameters. For velocities greater than 13 m/s (2500
not be achieved unless a comparable duct is included fpm), add 1 duct diameter for each additional 5 m/s
in the system design. The system design engineer (1000 fpm).
BLAST AREA
DISCHARGE DUCT
OUTLET AREA
CUTOFF
25%
50%
75%
CENTRIFUGAL FAN
100% EFFECTIVE DUCT LENGTH
AXIAL FAN
To calculate 100% duct length, assume a minimum of 2½ duct diameters for 12.7 m/s (2500 fpm) or less. Add 1
duct diameter for each additional 5.08 m/s (1000 fpm).
EXAMPLE: 25.4 m/s (5000 fpm) = 5 equivalent duct diameters. If the duct is rectangular with side dimensions a
and b, the equivalent duct diameter is equal to (4ab/π)0.5.
29
AMCA 201-02 (R2007)
8.1.1 Axial flow fan - outlet ducts. Most exhaust full-length outlet duct, then a SEF must be added to
axial flow fans are tested and/or rated with two to the system resistance losses. System Effect Curves
three equivalent duct diameters attached to the fan for centrifugal fans with less than optimum outlet duct
outlet. Often, fans are installed without an outlet length are shown in Figure 8.3.
duct, either because of available space or for
economic reasons. Tubeaxial fans installed with no 8.2 Outlet diffusers
outlet ducts have System Effect Factors (SEF)
approaching zero. Many air systems are space-constricted and must, of
necessity, use relatively small ducts having high
Vaneaxial fans, however, do not perform as static pressure losses. If space is not severely
cataloged when they are installed with less than 50% constricted, the use of larger ductwork and moving
"effective duct length." System Effect Curves for air at a lower velocity may be beneficial. Larger
tubeaxial and vaneaxial fans with less than optimum ductwork (within reason) reduces system pressure
outlet duct are shown in Figure 8.2. requirements.
To determine the applicable SEF, calculate the To effectively transition from a smaller duct size to a
average velocity in the outlet duct and enter the larger duct size it is necessary to use a connection
System Effect Curve (Figure 7.1) at this velocity, piece between the duct sections that allows the
utilizing the appropriate System Effect Curve airstream to expand gradually. This piece is called a
selected from Figure 8.2, then read over horizontally diffuser, or evasé. These terms are used
to the System Effect Factor, Pascals (in. wg) on the interchangeably in the industry. A properly designed
ordinate. evasé has a smooth and gradual transition between
the duct sizes so that airflow is relatively undisturbed.
8.1.2 Centrifugal flow fan - outlet ducts.
Centrifugal fans are sometimes installed with a less An evasé operates on a very simple principle: air
than optimum outlet duct. If it is not possible to use a flowing from the smaller area to the larger area loses
AXIAL FAN
To calculate 100% duct length, assume a minimum of 2½ duct diameters for 12.7 m/s (2500 fpm) or less. Add 1
duct diameter for each additional 5.08 m/s (1000 fpm).
Figure 8.2 - System Effect Curves for Outlet Ducts - Axial Fans
30
AMCA 201-02 (R2007)
velocity as it approaches the larger area, and a See AMCA Publication 200 Air Systems, for an
portion of the change (reduction) in velocity pressure example showing the effect of a diffuser on a duct
is converted into static pressure. This process is exit.
called “static regain”, and is simply defined as the
conversion of velocity pressure to static pressure. 8.3 Outlet duct elbows
The efficiency of conversion (or loss of total pressure)
will depend upon the angle of expansion, the length Values for pressure losses through elbows, which are
of the evasé section, and the blast area/outlet area published in handbooks and textbooks, are based
ratio of the fan. upon a uniform velocity profile at entry into the elbow.
Any non-uniformity in the velocity profile ahead of the
The fan manufacturer will, in most cases, be able to elbow will result in a pressure loss greater than the
provide design information for an efficient diffuser. industry-accepted value.
BLAST AREA
DISCHARGE DUCT
OUTLET AREA
CUTOFF
CENTRIFUGAL FAN
To calculate 100% duct length, assume a minimum of 2½ duct diameters for 2500 fpm or less. Add 1 duct diameter
for each additional 1000 fpm.
EXAMPLE: 5000 fpm = 5 equivalent duct diameters. If the duct is rectangular with side dimensions a and b, the
equivalent duct diameter is equal to (4ab/π)0.5.
Pressure
0% 50% 80% 90% 100%
Recovery
Blast Area
System Effect Curve
Outlet Area
0.4 P R-S U W —
0.5 P R-S U W —
0.6 R-S S-T U-V W-X —
0.7 S U W-X — —
0.8 T-U V-W X — —
0.9 V-W W-X — — —
1.0 — — — — —
Figure 8.3 - System Effect Curves for Outlet Ducts - Centrifugal Fans
31
AMCA 201-02 (R2007)
Since the velocity profile at the outlet of a fan is not 8.3.1 Axial fans - outlet duct elbows. Tubeaxial
uniform, an elbow located at or near the fan outlet will fans with two-piece and four-piece mitered elbows at
develop a pressure loss greater than the industry- varying distances from the fan outlet have a
accepted value. negligible SEF (see Figure 8.4).
The amount of this loss will depend upon the location Vaneaxial fans with two and four-piece mitered
and orientation of the elbow relative to the fan outlet. elbows at varying distances from the fan outlet
In some cases, the effect of the elbow will be to resulted in System Effect Curves as shown in Figure
further distort the outlet velocity profile of the fan. 8.4.
This will increase the losses and may result in such
uneven airflow in the duct that branch- takeoffs near 8.3.2 Centrifugal fans - outlet duct elbows. The
the elbow will not deliver their design airflow. (See outlet velocity of centrifugal fans is generally higher
Section 8.6) toward one or adjacent sides of the rectangular duct.
If an elbow must be located near the fan outlet it
Wherever possible, a length of straight duct should should have a minimum radius-to-duct-diameter ratio
be installed at the fan outlet to permit the diffusion of 1.5, and it should be arranged to give the most
and development of a uniform airflow profile before uniform airflow possible. Figure 8.5 gives System
an elbow is inserted in the duct. If an elbow must be Effect Curves that can be used to estimate the effect
located near the fan outlet then it should be a radius of an elbow at the fan outlet. It also shows the
elbow having a minimum radius-to-duct-diameter reduction in losses resulting from the use of a straight
ratio of 1.5. outlet duct.
% EFFECTIVE
DUCT LENGTH
% EFFECTIVE
DUCT LENGTH
Figure 8.4 - System Effect Curves for Outlet Duct Elbows - Axial Fans
32
AMCA 201-02 (R2007)
POSITION C
POSITION D
POSITION B
E
C TIV TH
FE G
EF LEN
% CT
DU
INL
ET
POSITION A
Note: Fan Inlet and elbow positions must be oriented as shown for the proper application of the table on the facing
page.
33
AMCA 201-02 (R2007)
A N O P-Q S
B M-N N O-P R-S
0.4
C L-M M N Q
D L-M M N Q
A O-P P-Q R T
B N-O O-P Q S-T
0.5
C M-N N O-P R-S
D M-N N O-P R-S
A Q Q-R S U
B P Q R T
0.6
C N-O O Q S
A R-S S T V
B Q-R R-S S-T U-V
0.7
C P Q R-S T
D P Q R-S T
A S S-T T-U W
B R-S S T V
0.8
C Q-R R S U-V
D Q-R R S U-V
A T T-U U-V W
B S S-T T-U W
0.9
C R S S-T V
D R S S-T V
A T T-U U-V W
B S-T T U W
1.0
C R-S S T V
D R-S S T V
For DWDI fans determine SEF using the curve for SWSI
fans. Then, apply the appropriate multiplier from the
tabulation below
34
AMCA 201-02 (R2007)
35
AMCA 201-02 (R2007)
0.4 7.5
0.5 4.8
0.6 3.3
0.7 2.4
0.8 1.9
0.9 1.5
1.0 1.2
Figure 8.7 - Pressure Drop Multipliers for Volume Control Dampers on a Fan Discharge
36
AMCA 201-02 (R2007)
8.6 Duct branches In Figure 8.8 branch takeoffs or splits are located
close to the fan outlet. Non-uniform airflow conditions
Standard procedures for the design of duct systems will exist and pressure loss and airflow may vary
are based on the assumption of uniform airflow widely from the design intent. Wherever possible a
profiles in the system. length of straight duct should be installed between
the fan outlet and any split or branch takeoff.
Note: Avoid location of split or duct branch close to fan discharge. Provide a straight section of duct to allow for air
diffusion.
37
AMCA 201-02 (R2007)
9. Inlet System Effect Factors loss of energy, or even a flat flange (e) on the end of
the duct or fan will reduce the loss to about one half
Fan performance can be greatly affected by non- of the loss through an un-flanged entry.
uniform or swirling inlet flow. Fan rating and catalog
performance is typically obtained with unobstructed ANSI/AMCA 210 limits an inlet duct to a cross-
inlet flow. Any disruption to the inlet airflow will reduce sectional area no greater than 112.5% or less than
a fan’s performance. Restricted fan inlets located 92.5% of the fan inlet area. The slope of transition
close to walls, obstructions or restrictions caused by elements is limited to 15° converging and 7° diverging.
a plenum or cabinet will also decrease the
performance of a fan. The fan performance loss due 9.2 Inlet duct elbows
to inlet airflow disruption must be considered as a
System Effect. Non-uniform airflow into a fan inlet is a common
cause of deficient fan performance. An elbow located
9.1 Inlet ducts at, or in close proximity to the fan inlet will not allow
the air to enter the impeller uniformly. The result is
Fans intended primarily for use as "exhausters" may less than cataloged air performance.
be tested with an inlet duct in place, or with a special
bell-mouthed inlet to simulate the effect of a duct. A word of caution is required with the use of inlet
Figure 9.1 illustrates variations in inlet airflow that will elbows in close proximity to fan inlets. Other than the
occur. The ducted inlet condition is shown as (a), and incurred System Effect Factor, instability in fan
the effect of the bell-mouth inlet as (b). operation may occur as evidenced by an increase in
pressure fluctuations and sound power level. Fan
Fans that do not have smooth entries (c), and are instability, for any reason, may result in serious
installed without ducts, exhibit airflow characteristics structural damage to the fan. Axial fan instabilities
similar to a sharp edged orifice that develops a vena were experienced in some configurations tested with
contracta. A reduction in airflow area is caused by the inlet elbows in close proximity to the fan inlet.
vena contracta and the following rapid expansion Pressure fluctuations approached ten (10) times the
causes a loss that should be considered as a System magnitude of fluctuations of the same fan with good
Effect. inlet and outlet conditions. It is strongly advised
that inlet elbows be installed a minimum of three
If it is not practical to include such a smooth entry, a (3) diameters away from any axial or centrifugal
converging taper (d) will substantially diminish the fan inlet.
a. b. c.
IDEAL SMOOTH ENTRY TO BELL MOUTH INLET PRODUCES VENA CONTRACTA AT INLET
DUCT ON A DUCT SYSTEM FULL FLOW INTO FAN REDUCES EFFECTIVE FAN INLET AREA
d. e.
CONVERGING TAPERED ENTRY FLANGED ENTRY INTO
INTO FAN OR DUCT SYSTEM FAN OR DUCT SYTEM
Figure 9.1 Typical Inlet Connections for Centrifugal and Axial Fans
38
AMCA 201-02 (R2007)
9.2.1 Axial fans - inlet duct elbows. The System listed on Figure 9.4, and the System Effect Curves for
Effect Curves shown in Figure 9.2 for tubeaxial and various square duct elbows of given radius/diameter
vaneaxial fans are the result of tests run with two and ratios are listed on Figure 9.5. The SEF for a
four piece mitered inlet elbows at or in close proximity particular elbow is found in Figure 7.1 at the
to the fan inlets. Other variables tested included hub- intersection of the average fan inlet velocity and the
to-tip (H/T) ratio and blade solidity. The number of tabulated System Effect Curve.
blades did not have a significant affect on the inlet
elbow SEF. This pressure loss should be added to the friction and
dynamic losses already determined for the particular
9.2.2 Centrifugal fans - inlet duct elbows. Non- elbow. Note that when duct turning vanes and/or a
uniform airflow into a fan inlet, Figure 9.3A, is a suitable length of duct is used (three to eight
common cause of deficient fan performance. The diameters long, depending on velocities) between the
System Effect Curves for mitered 90° round section fan inlet and the elbow, the SEF is not as great.
elbows of given radius/diameter (R/D) ratios are These improvements help maintain uniform airflow
DUCT LENGTH
DUCT LENGTH
H/T 90° Elbow No Duct [1][2] 0.5D [1][2] 1.0D [1][2] 3.0D
Notes:
[1] Instability in fan operation may occur as evidenced by an increase in pressure fluctuations and sound level.
Fan instability, for any reason, may result in serious structural damage to the fan.
[2] The data presented in Figure 9.2 is representative of commercial type tubeaxial and vaneaxial fans, i.e. 60%
to 70% fan static efficiency.
Figure 9.2 - System Effect Curves for Inlet Duct Elbows - Axial Fans
39
AMCA 201-02 (R2007)
into the fan inlet and thereby approach the airflow A counter-rotating vortex at the inlet may result in a
conditions of the laboratory test setup. slight increase in the pressure-volume curve but the
power will increase substantially.
Occasionally, where space is limited, the inlet duct
will be mounted directly to the fan inlet as shown on There are occasions, with counter-rotating swirl,
Figure 9.3B. The many possible variations in the when the loss of performance is accompanied by a
width and depth of a duct influence the reduction in surging airflow. In these cases, the surging may be
performance to varying degrees and makes it more objectionable than the performance change.
impossible to establish reliable SEF. Note: Capacity Inlet spin may arise from a great variety of approach
losses as high as 45% have been observed in conditions and sometimes the cause is not obvious.
poorly designed inlets such as in Figure 9.3B.
This inlet condition should be AVOIDED.
40
AMCA 201-02 (R2007)
— N P R-S
Figure 9.4A - Two Piece Mitered 90° Round Section Elbow - Not Vaned
R/D NO 2D 5D
DUCT DUCT DUCT
LENGTH 0.5 O Q S
OF DUCT
D
0.75 Q R-S T-U
+
1.0 R S-T U-V
R
3.0 S T-U V
Figure 9.4B - Three Piece Mitered 90° Round Section Elbow - Not Vaned
R/D NO 2D 5D
DUCT DUCT DUCT
Figure 9.4C - Four or More Piece Mitered 90° Round Section Elbow - Not Vaned
Figure 9.4 - System Effect Curves for Various Mitered Elbows without Turing Vanes
41
AMCA 201-02 (R2007)
R
1.0 R S-T U-V
1.0 S T-U V
R/D NO 2D 5D
LENGTH H DUCT DUCT DUCT
OF DUCT
0.5 S T-U V
+
R
1.0 T U-V W
Figure 9.5B - Square Elbow with Inlet Transition - 3 Long Turning Vanes
R/D NO 2D 5D
LENGTH H DUCT DUCT DUCT
OF DUCT
R 0.5 S T-U V
+
1.0 T U-V W
Figure 9.5C - Square Elbow with Inlet Transition - Short Turning Vanes
D = Diameter of the inlet collar
The inside area of the square duct (H x H) should be equal to the inside area of the fan inlet collar.
* The maximum permissible angle of any converging element of the transition is 15°, and for a diverging element, 7°.
Figure 9.5 - System Effect Curves for Various Square Duct Elbows
42
AMCA 201-02 (R2007)
Figure 9.6 - Improved Flow Conditions with a Special Designed Inlet Box
IMPELLER
ROTATION
COUNTER-ROTATING SWIRL
IMPELLER IMPELLER
ROTATION ROTATION
43
AMCA 201-02 (R2007)
9.4 Inlet turning vanes airflow entering a duct elbow with turning vanes will
leave the duct elbow with non-uniform airflow.
Where space limitations prevent the use of optimum
fan inlet conditions, more uniform airflow can be 9.5 Airflow straighteners
achieved by the use of turning vanes in the inlet
elbow (see Figure 9.9). Numerous variations of Figure 9.10 shows two airflow straighteners used in
turning vanes are available, from a single curved testing setups to reduce fan swirl before measuring
sheet metal vane to multi-bladed "airfoil" vanes. stations. Figure 9.10A is the egg-crate straightener
used in ANSI/AMCA 210; larger cell sizes made
The pressure drop (loss) through these devices must proportionately longer could be used.
be added to the system pressure losses.
Figure 9.10B shows the star straightener used in the
The amount of loss for each device is published by ISO standard. A single splitter sheet may be used to
the manufacturer, but it should be realized that the eliminate swirl in some cases. Straighteners are
cataloged pressure loss will be based upon uniform intended to reduce swirl before or after a fan or a
airflow at the entry to the elbow. If the airflow process station. Do not install straighteners where
approaching the elbow is significantly non-uniform the air profile is known to be non-uniform, the
because of a disturbance farther upstream in the device will carry the non-uniformity further
system, the pressure loss through the elbow will be downstream.
higher than the published figure. A non-uniform
TURNING
VANES
TURNING
VANES
TURNING
IMPELLER
IMPELLER VANES
ROTATION
ROTATION
44
AMCA 201-02 (R2007)
0.45D
0.075D
DUCT
0.075D
DUCT DUCT
2D
45
AMCA 201-02 (R2007)
9.6 Enclosures (plenum and cabinet effects) one-half impeller diameter between an enclosure wall
and the fan inlet. Adjacent inlets of multiple double
Fans within plenums and cabinets or next to walls width centrifugal fans located in a common enclosure
should be located so that air may flow unobstructed should be at least one impeller diameter apart if
into the inlets. Fan performance is reduced if the optimum performance is to be expected. Figure 9.11
space between the fan inlet and the enclosure is too illustrates fans with restricted inlets and their
restrictive. It is common practice to allow at least applicable System Effect Curves.
2L
L L
EQUAL
INLET
DIA.
EQUAL
DIAMETER L
OF INLET
Figure 9.11A - Fans and Plenum Figure 9.11B - Axial Fan Near Wall
L L L L
DWDI SWSI
Figure 9.11C - Centrifugal Fan Near Wall(s) Figure 9.11D - DWDI Fan Near Wall on One Side
Figure 9.11 - System Effect Curves for Fans Located in Plenums and Cabinet
Enclosures and for Various Wall-to-inlet Dimensions
46
AMCA 201-02 (R2007)
The manner in which the air stream enters an common inlet obstructions. Some accessories such
enclosure in relation to the fan inlets also affects fan as fan bearings, bearing pedestals, inlet vanes, inlet
performance. Plenum or enclosure inlets or walls that dampers, drive guards and motors may also cause
are not symmetrical with the fan inlets will cause inlet obstruction and are discussed in more detail in
uneven airflow and/or inlet spin. Figure 9.12A Section 10.
illustrates this condition that must be avoided to
achieve maximum performance from a fan. If this is Obstruction at the fan inlet may be defined in terms
not possible, inlet conditions can usually be improved of the unobstructed percentage of the inlet area.
with a splitter sheet to break up the inlet vortex as Because of the shape of the inlet cones of many fans
illustrated in Figure 9.12B. it is sometimes difficult to establish the area of the fan
inlet. Figure 9.14 illustrates the convention adopted
For proper performance of axial fans in parallel for this purpose. Where an inlet collar is provided, the
installations minimum space of one impeller diameter inlet area is calculated from the inside diameter of
should be allowed between fans, as shown in Figure this collar. Where no collar is provided, the inlet plane
9.13. Placing fans closer together can result in erratic is defined by the points of tangency of the fan
or uneven airflow into the fans. housing side with the inlet cone radius.
SPLITTER SHEET
Figure 9.12A - Enclosure Inlet Not Figure 9.12B - Flow Condition of Figure 9.12A
Symmetrical with Fan Inlet. Pre- Improved with a Splitter Sheet. Substantial
Rotational Vortex Induced Improvement Would Be To Relocate
Enclosure Inlet as Shown in Figure 9.11A
1 DIA.
MIN
47
AMCA 201-02 (R2007)
ER
ET
AM AR
DI LL
DE CO
SI T
IN E
INL
INLET PLANE
R
TE
E NT
AM GE
DI N
TA
OF
INLET PLANE
100 - - - - -
95 - - X W V
90 - X V-W U-V T-U
85 X W-X V-W U-V S-T
75 W-X V U S-T R-S
50 V-W U S-T R-S Q
25 U-V T S-T Q-R P
48
AMCA 201-02 (R2007)
10. Effects of Factory Supplied Accessories If possible, the necessary information should be
obtained directly from the manufacturer. The data
Unless the manufacturer's catalog clearly states to presented in this section are offered only as a guide
the contrary, it should be assumed that published fan in the absence of specific data from the fan
performance data does not include the effects of any manufacturer. See Figure 10.1 for terminology.
accessories supplied with the fan.
Cone Type
Variable
Inlet Vanes
49
AMCA 201-02 (R2007)
10.1 Bearing and supports in fan inlet 10.3 Belt tube in axial fan inlet or outlet
Arrangement 3 and 7 fans (see Figure 3.5) require With a belt driven axial flow fan it is usually necessary
that the fan shaft be supported by a bearing and that the fan motor be mounted outside the fan
bearing support in the fan inlet or just adjacent to it. housing (see Figure 3.7 Arrangement 9, and Annex B
Figure B.7).
These components may have an effect on the flow of
air into the fan inlet and consequently on the fan To protect the belts from the airstream, and also to
performance, depending upon the size of the prevent any air leakage through the fan housing,
bearings and supports in relation to the fan inlet manufacturers in many cases provide a belt tube.
opening. The location of the bearing and support,
that is, whether it is located in the actual inlet or Most manufacturers include the effects of an axial fan
"spaced out" from the inlet, will also have an effect. belt tube in their rating tables. In cases where the
effect is not included, the appropriate SEF is
In cases where manufacturer's performance ratings approximated by calculating the percentage of
do not include the effect of the bearings and unobstructed area of air passage way and using
supports, it will be necessary to compensate for this Figure 9.14.
inlet restriction. Use the fan manufacturer's
allowance for bearings in the fan inlet if possible. 10.4 Inlet box
If no better data are available, use the procedures When an inlet box configuration is supplied by the fan
described in Section 9.7 as an approximation. manufacturer, the fan performance should include
the effect of the inlet box.
10.2 Drive guards obstructing fan inlet
The System Effect of fan inlet boxes can vary widely
All fans have moving parts that require guarding for depending upon the design. This data should be
safety in the same way as other moving machinery. available from the fan manufacturer. In the absence
Fans located less than 2.1 m (7 ft) above the floor of fan manufacturer's data, a well-designed inlet box
require special consideration as specified in the should approximate System Effect Curves "S" or "T"
United States’ Occupational Safety and Health Act. of Figure 7.1.
National, federal, state and local rules, regulations,
and codes should be carefully considered and 10.5 Inlet box dampers
followed.
Inlet box dampers may be used to control the airflow
Arrangement 3 and 7 fans may require a belt drive through the system. Either parallel or opposed blades
guard in the area of the fan inlet. Depending on the may be used (see Figure 10.1).
design, the guard may be located in the plane of the
inlet, along the casing side sheet, or it may be The parallel blade type is installed with the blades
"spaced out" due to "spaced out" bearing pedestals. parallel to the fan shaft so that, in a partially closed
position, a forced inlet vortex will be generated. The
In any case, depending on the location of the guard, effect on the fan characteristics will be similar to that
and on the inlet velocity, the fan performance may be of a variable inlet vane control.
significantly affected by this obstruction. It is
desirable that a drive guard located in this position be The opposed blade type is used to control airflow by
furnished with as much opening as possible to allow the addition of pressure loss created by the damper
maximum flow of air to the fan inlet. in a partially closed position.
If available, use the fan manufacturer's allowance for If possible, complete data should be obtained from
drive guards obstructing the fan inlet. SEF for drive the fan manufacturer giving the System Effect of the
guard obstructions situated at the inlet of a fan may inlet box and damper pressure drop over the range of
be approximated using Figure 9.14. application. If data are not available, System Effect
Curves "S" or "T" from Figure 7.1 should be applied
Where possible, open construction on guards is for the inlet box and pressure loss from the damper
recommended to allow free air passage to the fan manufacturer for the damper in making the fan
inlet. Guards and sheaves should be designed to selection.
obstruct, as little of the fan inlet as possible and in no
case should the obstruction be more than 1/3 of the
fan inlet area.
50
AMCA 201-02 (R2007)
10.6 Variable inlet vane (VIV) When variable inlet vanes are supplied by the fan
manufacturer, the performance should include the
Variable inlet vanes are mounted on the fan inlet to effects of the variable inlet vane unit.
maintain fan efficiency at reduced airflow. They are
arranged to generate an inlet vortex (pre-rotation) The System Effect of a wide-open VIV (see Figure
that rotates in the same direction as the fan impeller. 10.2) must be accounted for in the original fan
Variable inlet vanes may be of two different basic selection. If data are not available from the fan
types: 1) cone type integral with the fan inlet, 2) manufacturer the following System Effect Curves
cylindrical type add-on (Figures 10.1 and 10.2). should be applied in making the fan selection.
FAN PERFORMANCE
W/OUT VARIABLE INLET VANES
120
100 VARIABLE
INLET VANES
PERCENT OF SHUT-OFF PRESSURE
CONE TYPE 80
VARIABLE INLET
VANES 75% OPEN
60
40
75% OPEN
20
CYLINDRICAL TYPE
VARIABLE INLET
VANES 0 20 40 60 80 100 120
PERCENT OF WIDE OPEN VOLUME
Figure 10.2 - Typical Variable Inlet Vanes for a Backward Inclined Fan
51
AMCA 201-02 (R2007)
Viscosity:
Absolute (lbm/ft-s) 1.4882 = Pa s (Pa s) 0.6719 = (lbm/ft-s)
Kinematic (ft2/s) 0.0929 = m2/s (m2/s) 10.7639 = ft2/s
Gas Constant (ft lb/lbm-°R) 5.3803 = J-kg/K (j-kg/K) 0.1858 = (ft lb/lbm-°R)
52
AMCA 201-02 (R2007)
Annex B. Dual Fan Systems - Series and These types of systems normally have common inlet
Parallel and outlet sections, or they may have individual ducts
of equal resistance that join together at equal
It is sometimes necessary to install two or more fans velocities. In either case, the characteristic curve is
in systems that require higher pressures or airflow the sum of the separate airflows for a given static or
than would be attainable with a single fan. Two fans total pressure (Figure B.2).
may offer a space, cost, or control advantage over a
single larger fan, or it may be simply a field The total performance of the multiple fans will be less
modification of an existing system to boost pressure than the theoretical sum if inlet conditions are
or airflow. restricted or the airflow into the inlets is not straight
(see Section 9.6). Also, adding a parallel fan to an
existing system without modifying the resistance
B.1 Fans operating in series
(larger ducts, etc.) will result in lower than anticipated
airflow due to increased system resistance.
To obtain a system pressure boost, fans are often
installed in series. The fans may be mounted as close
Fans that have a “positive” slope in the pressure-
as the outlet of one fan directly attached to the inlet
volume curve to the left of the peak pressure curve,
of the next fan, or they may be placed in remote
typical of some axial and forward curved centrifugal
locations with considerable distance between fans.
fans (see Figure 4.2), can experience unstable
operation under certain conditions. If fans are
The fans must handle the same mass airflow,
operated in parallel in the region of this “positive”
assuming no loss or gains between stages. The
slope, multiple operating conditions may occur.
combined total pressure will then be the sum of each
Figure B.2 illustrates the combined pressure-volume
fan’s total pressure (Figure B.1). The velocity
curve of two such fans operating in parallel.
pressure corresponds to the air velocity at the outlet
of the last fan stage. The static pressure for the
The closed loop to the left of the peak pressure point
combination is the total pressure minus the velocity
is the result of plotting all the possible combinations
pressure and is not the sum of the individual fan
of volume airflow at each pressure. If the system
static pressures.
curve intersects the combined volume-pressure
curve in the area enclosed by the loop, more than
In practice there is some reduction in airflow due to
one point of operation is possible. This may cause
the increased air density in the later fan stage(s).
one of the fans to handle more of the air and could
There can also be significant loss of airflow due to
cause a motor overload if the fans are individually
non-uniform airflow into the inlet of the next fan.
driven. This unbalanced airflow condition tends to
reverse readily with the result that the fans will
Sometimes multiple impellers are assembled in a
intermittently load and unload. This "pulsing" often
single housing and this assembly is known as a
generates noise and vibration and may cause
“multi-stage” fan. This combination is seldom used in
damage to the fans, ductwork or driving motors.
conventional ventilating and air conditioning systems
but it is not uncommon in special industrial systems.
Aileron controls in forward curved fan outlets or
dampers near the inlets or outlets may be used to
It is advisable to request the fan manufacturer to
correct unbalanced airflow or to eliminate pulsations
review the proposed system design and make some
or reversing operation (See Figure B.3).
estimate of its installed performance.
53
AMCA 201-02 (R2007)
SYSTEM
RESISTANCE
PERCENT OF FAN STATIC PRESSURE
200%
SERIES FAN
COMBINED
PRESSURE
CURVE
100%
SINGLE FAN
PRESSURE
CURVE
100%
PERCENT OF FAN AIRFLOW
54
AMCA 201-02 (R2007)
M
M
TE
TE
YS
YS
ES
ES
BL
BL
STA
PERCENT OF FAN STATIC PRESSURE
STA
UN
100
SINGLE FAN -
PRESSURE
CURVE
200
PERCENT OF FAN AIRFLOW
AILERON
55
AMCA 201-02 (R2007)
Annex C. Definitions and Terminology C.1.8 Temperature. The dry-bulb temperature (td) is
the air temperature measured by a dry temperature
C.1 The air sensor. Temperatures relating to air density are
usually referenced to the fan inlet.
C.1.1 Air velocity. The velocity of an air stream is its
rate of motion, expressed in m/s (fpm). The velocity The wet-bulb temperature (tw) is the temperature
at a plane (Vx) is the average velocity throughout the measured by a temperature sensor covered by a
entire area of the plane. water-moistened wick and exposed to air in motion.
Readings shall be taken only under conditions that
C.1.2 Airflow. The airflow at a plane (Qx) is the rate assure an air velocity of 3.6 to 10.2 m/s (700 to 2000
of airflow, expressed in m3/s (cfm) and is the product ft/min) over the wet-bulb and only after sufficient time
of the average velocity at the plane and the area of has elapsed for evaporative equilibrium to be
the plane. attained.
C.1.3 Barometric pressure. Barometric pressure Wet bulb depression is the difference between dry-
(pb) is the absolute pressure exerted by the bulb and wet-bulb temperatures (td - tw) at the same
atmosphere at a location of measurement (per AMCA location.
99-0066).
C.2 The fan
C.1.4 Pressure-static. Static pressure is the portion
of the air pressure that exists by virtue of the degree C.2.1 Blast area. The blast area of a centrifugal fan
of compression only. If expressed as gauge pressure, is the fan outlet area less the projected area of the
it may be negative or positive (per AMCA 99-0066). cutoff; see Figure B.6 (per AMCA 99-0066).
Static pressure at a specific plane (Psx) is the C.2.2 Inlet area. The fan inlet area (A1) is the gross
arithmetic average of the gauge static pressures as inside area of the fan inlet (see Figure 9.14).
measured at specific points in the traverse of the
plane. C.2.3 Outlet area. The fan outlet area (A2) is the
gross inside area of the fan outlet.
C.1.5 Pressure-velocity. Velocity pressure is that
portion of the air pressure which exists by virtue of C.2.4 Fan. (1) A device, which utilizes a power-drive
the rate of motion only. It is always positive (per rotating impeller for moving air or gases. The internal
AMCA 99-0066). energy (enthalpy) increase imparted by a fan to a gas
does not exceed 25 kJ/kg (10.75 BTU/lbm). (2) A
Velocity pressure at a specific plane (Pvx) is the device having a power-driven rotating impeller
square of the arithmetic average of the square roots without a housing for circulating air in a room (per
of the velocity pressures as measured at specific AMCA 99-0066).
points in the traverse plane.
The volume airflow of a fan (Q) is the rate of airflow
C.1.6 Pressure-total. Total pressure is the air in m3/s (cfm) expressed at the fan inlet conditions.
pressure that exists by virtue of the degree of
compression and the rate of motion. It is the C.2.5 Fan impeller diameter. The fan impeller
algebraic sum of the velocity pressure and the static diameter is the maximum diameter measured over
pressure at a point. Thus if the air is at rest, the total the impeller blades.
pressure will equal the static pressure (per AMCA 99-
0066). C.2.6 Fan total pressure. Fan total Pressure (Pt) is
the difference between the total pressure at the fan
Total pressure at a specific plane (Ptx) is the algebraic outlet and the total pressure at the fan inlet. Pt = Pt1 -
sum of the static pressure and the velocity pressure Pt2 (Algebraic).
at that plane.
Ignoring the losses that exist between the planes of
C.1.7 Standard air density. A density of 1.2 kg/m3 measurement and the fan, Figures C.1, C.2 and C.3
(0.075 lbm/ft3) corresponding approximately to air at illustrate fan total pressures for three basic
20°C (68°F), 101.325 kPa (29.92 in. Hg) and 50% arrangements for fans connected to external
relative humidity (per AMCA 99-0066). systems.
56
AMCA 201-02 (R2007)
Where the fan inlet is open to atmospheric air or Where the fan outlet is open to atmospheric air or
where an inlet bell, as shown in the Figure C.1 is where an outlet duct three diameters or less in length
used to simulate an inlet duct, the total pressure at is used to simulate a fan with an outlet duct and the
the fan inlet (Pt1) is considered to be the same as the outlet duct is open to atmospheric air, the total
total pressure in the region near the inlet (Pta) where pressure at the fan outlet is equal to the fan velocity
no energy has been imparted to the air. This is the pressure (Pv). The following equations apply:
location of "still air". The following equations apply:
Pt = Pt2 - Pt1
Pta = 0 Pt2 = Pv
Pt = Pt2 - Pt1 Pt = Pv - Pt1
Pt1 = Pta = 0
Pt = Pt2
PLANE 1 PLANE 2
Pt2
Pt = Pt2
Figure C.1 - Fan Total Pressure for Installation Type B: Free Inlet, Ducted Outlet
57
AMCA 201-02 (R2007)
PLANE 1 PLANE 2
Pt1
Pt = Pv2 - Pt1
Figure C.2 - Fan Total Pressure for Installation Type C: Ducted Inlet, Free Outlet
PLANE 1 PLANE 2
Pt1 Pt Pt2
Pt = Pt2 - Pt1
Figure C.3 - Fan Total Pressure for Installation Type D: Ducted Inlet, Ducted Outlet
58
AMCA 201-02 (R2007)
C.2.7 Fan velocity pressure. Fan velocity pressure Where the fan outlet is open to atmospheric air
(Pv) is the pressure corresponding to the average air (ducted inlet, free outlet), ignoring the SEF, the fan
velocity at the fan outlet. Pv = Pv2 static pressure (Ps) is equal to the inlet static
pressure (Ps1) less the inlet velocity pressure (Pv1).
Assuming no change in air density or area between
the plane of measurement and the fan outlet, Figure Ps = -Ps1 - Pv1
C.4 illustrates fan velocity pressure. Ps = -(-Ps1) - Pv1
Ps = Ps1 - Pv1
C.2.8 Fan static pressure. The difference between
the fan total pressure and the fan velocity pressure. C.3 The system
Therefore, fan static pressure is the difference
between the static pressure at a fan outlet and the C.3.1 Equivalent duct diameter. The diameter of a
total pressure at a fan inlet (per AMCA 99-0066). circle having the same area as another geometric
shape. For a rectangular cross-section duct with
Ps = Pt - Pv width (a) and height (b), the equivalent diameter is:
(4ab/π)0.5 (per AMCA 99-0066).
Ignoring losses between the planes of measurement
and the fan, Figure C.5 illustrates the fan static C.3.2 Fan performance. Fan performance is a
pressure for a fan with ducted inlet and outlet. statement of the volume airflow, static or total
pressure, speed and power input at a stated inlet
Ps = Ps2 - Ps1 - Pv1 (Algebraic) density and may include total and static efficiencies.
Where the fan inlet is open to atmospheric air, (free C.3.3 Fan performance curve. Of the many forms of
inlet, ducted outlet), the fan static pressure (Ps) is fan performance curves, generally all convey
equal to the static pressure at the fan outlet. information sufficient to determine fan performance
as defined above. In this manual, ‘fan performance
Ps = Ps2 curve’ refers to the constant speed performance
PLANE 1 PLANE 2
Pv = Pv2
Pv2
Figure C.4 - Fan Velocity Pressure for Installation Type B: Free Inlet, Ducted Outlet
59
AMCA 201-02 (R2007)
curve. This is a graphical representation of static or C.3.7 Point of rating. The specified fan operating
total pressure and power input over a range of point on its characteristic curve (per AMCA 99-0066).
volume airflow at a stated inlet density and fan
speed. It may include static or total efficiency curves. C.3.8 System. A series of ducts, conduits, elbows,
The range of volume airflow that is covered generally branch piping, etc., designed to guide the flow of air,
extends from shutoff (zero airflow) to free delivery gas or vapor to and from one or more locations. A fan
(zero fan static pressure). The pressure curves that provides the necessary energy to overcome the
appear are generally referred to as the pressure- resistance to flow of the system and causes air or gas
volume curves. to flow through the system. Some components of a
typical system are louvers, grills, diffusers, filters,
C.3.4 Normalized fan curve. A normalized fan curve heating and cooling coils, air pollution control
is a constant speed curve in which the fan devices, burner assemblies, sound attenuators, the
performance values appear as percentages, with ductwork and related fittings.
100% airflow at free delivery, 100% fan static
pressure at shutoff, and 100% power at the maximum C.3.9 System curve. A graphic representation of the
power input point. pressure versus volume airflow characteristics of a
particular system.
C.3.5 Point of duty. Point of duty is a statement of
air volume flow rate and static or total pressure at a C.3.10 System Effect Factor (SEF). A pressure loss,
stated density and is used to specify the point on which recognizes the effect of fan inlet restrictions,
the system curve at which a fan is to operate. fan outlet restrictions, or other conditions influencing
fan performance when installed in the system (per
C.3.6 Point of operation. The relative position on a AMCA 99-0066).
fan or air curtain performance curve corresponding to
a particular airflow, pressure, power and efficiency
(per AMCA 99-0066).
PLANE 1 PLANE 2
Figure C.5 - Fan Static Pressure for Installation Type D: Ducted Inlet, Ducted Outlet
60
AMCA 201-02 (R2007)
HOUSING
DIVERTER
FF
TO
CU
CENTER PLATE
BLAST AREA
DISCHARGE
OUTLET AREA
SIDE SHEET
BACKPLATE
BLADE TO
FF
CU
INLET
SCROLL
IMPELLER
FRAME
RIM
BEARING
SUPPORT
INLET COLLAR
61
AMCA 201-02 (R2007)
CASING
BACKPLATE
RIM
HUB INLET
MOTOR BLADE
GUIDE VANE
IMPELLER
INLET BELL
Figure C.7A - Tubular Centrifugal Fan-
Direct Drive
CASING
BLADE
DIFFUSER
HUB
MOTOR
IMPELLER
CASING
BLADE
HUB
GUIDE VANE
Figure C.7C - Vaneaxial Fan-Belt Drive
IMPELLER
62
AMCA 201-02 (R2007)
Annex D. Examples of the Convertibility The Ps required at the fan outlet (C) will be equal to
of Energy from Velocity Pressure to the pressure drop at the desired airflow. Since there
are no inlet obstructions and the duct near the fan
Static Pressure
outlet is the same as used in the test setup, the
published fan performance can be used with no
SI CONVERSION was done using 249 Pa = 1 in. wg,
additional system effect factors applied.
1 m3/s = 2118 cfm, 1m/s = .00508 ft/min
SI I-P
Select a fan for Q = 1.42 m3/s (3000 cfm) and Ps = 747 Pa (3.0 in. wg).
996 4
747 3
Pt
Pv
498 2
Ps 124 Pa
249 1 (0.5 in.wg)
0 0
A B C D
ATMOSPHERIC PRESSURE
63
AMCA 201-02 (R2007)
D.2 Example of fan (tested with free inlet, to the duct, the Pt requirement in the plenum is
ducted outlet), connected to a duct system 871.15 Pa (3.5 in. wg), Pt at duct entrance = 49.8 Pa
and then a plenum (0.2 in. wg) in contraction loss, or 921.3 Pa (3.7 in.
wg) Pt.
This example includes the same duct system as
described in Example C.1. However, there is a short Air flowing across the plenum from D to E will have a
outlet duct on the fan followed by a plenum chamber relatively low velocity and the Pv in the plenum will be
with cross-sectional area more than 10 times larger 0.0 Pa (0.0 in. wg) since the velocity is negligible.
than the area of the duct.
At point D, there is an abrupt expansion energy loss
The velocity in the duct from E to F is 14.4 m/s (2830 equal to the entire Pv in the duct discharging into the
fpm), equal to a velocity pressure of 124.5 Pa (0.5 in. plenum. The outlet duct between the fan and the
wg). At point "F" the Pv is 124.5 Pa (0.5 in. wg), the plenum is 2.5 equivalent diameters long. It is the
Ps is 0.0 Pa (0.0 in. wg), and the Pt is 124.5 Pa (0.5 same as used during the fan rating test. The Ps in the
in. wg). The friction of duct will cause a gradual outlet duct (also the Ps in the plenum) is the same as
increase in Ps and Pt back to point E. If the duct has the Ps as measured during the rating test.
a uniform cross-sectional area the Pv will be constant
through this part of the system. This example requires a fan to be selected for 921.30
Pa (3.7 in. wg) at 1.42 m3/s (3000 cfm). Compare this
Since there is an energy loss of 49.8 Pa (0.2 in. wg) with the previous selection of 747 Pa (3.0 in. wg) Ps
as a result of the abrupt contraction from the plenum at 1.42 m3/s (3000 cfm).
SI I-P
C-D Outlet duct on fan as tested 0.00 Pa (no SEF) 0.0 in. wg
E Ps energy required to
create velocity at E 124.50 Pa (part of duct system) 0.5 in. wg
Solution:
Select a fan for Q = 1.42 m3/s (3000 cfm) and Ps = 921.30 Pa (3.7 in. wg)
Use manufacturer's data for rpm (N) and power (H).
64
AMCA 201-02 (R2007)
2.5 DIA.
1245 5
922 Pa (3.7 in.wg)
996 4
747 3 922 Pa Pt
(3.7 in.wg) Pv
498 2 124 Pa
747 Pa (3.0 in.wg) Ps (0.5 in.wg)
249 1
0 0
F
A B C D E ATMOSPHERIC PRESSURE
65
AMCA 201-02 (R2007)
D.3 Example of fan with free inlet, free outlet the velocity energy is lost. In these applications, the
- fan discharges directly into plenum and energy loss and the System Effect Factor may
then to duct system (abrupt expansion at fan exceed the fan outlet velocity pressure as defined in
outlet) terms of "fan outlet area".
This example is similar to the plenum effect example The SEF for fans without outlet duct was obtained as
except the duct at the fan outlet has been omitted. follows:
The fan discharges directly into the plenum.
GIVEN:
It may seem unreasonable that the System Effect Blast Area
Fan = 0 .6
loss at the fan outlet is greater than the defined fan Outlet Area
outlet velocity. Fans with cutoffs must generate
higher velocities at the cutoff plane (blast area) than
Fan outlet velocity = 14.4 m/s
in the outlet duct (outlet area). This higher velocity
(2830 fpm) No outlet duct
(at cutoff) is partially converted to Ps when outlet
ducts are used as on fan tests. When fans with System Effect Curve = R-S, (from Figure 8.3)
cutoffs are "bulk-headed" into plenums or discharge SEF = 149.4 Pa (0.6 in. wg), (from Figure 7.1) at 14.4
directly into the atmosphere as with exhausters, all m/s (2830 fpm) velocity and system curve R)
SI I-P
D Ps energy required to
create velocity at D 124.50 Pa (part of duct system) 0.5 in. wg
Solution:
Select a fan for 1.42 m3/s (3000 cfm) Q and 1070.70 Pa (4.3 in. wg) Ps.
Use manufacturer's data for rpm (N) and power (H).
66
AMCA 201-02 (R2007)
1245 5
872 Pa (3.5 in.wg)
996 4
747 3
Pt
Pv
498 2 124 Pa
747 Pa (3.0 in.wg) Ps (0.5 in.wg)
249 1
0 0
A B C D ATMOSPHERIC PRESSURE E
67
AMCA 201-02 (R2007)
D.4 Example of fan used to exhaust with Three SEFs are shown in this example:
obstruction in inlet, inlet elbow, inlet duct,
free outlet 1) System Effect Curve R (see Figure 9.5 for a 3
piece inlet elbow with R/D ratio of 1 and no duct
This example is an exhaust system. Note the entry between the elbow and the fan inlet).
loss at point A. An inlet bell will reduce this loss.
2) System Effect Curve U (see Figure 9.14 for a
On the suction side of the fan, Ps will be negative, but bearing in the fan inlet which obstructs 10% of the
Pv is always positive. inlet).
SI I-P
A-B Duct friction at 1.42 m3/s (3000 cfm) 747.00 Pa (duct design) 3.0 in. wg
Solution:
Select a fan for 1.42 m3/s (3000 cfm) Q and 1195.2 Pa (4.8 in. wg) Ps
Use manufacturer's data for rpm (N) and power (H).
68
AMCA 201-02 (R2007)
ABRUPT
Pv = 124 Pa (0.5 in.wg) DISCHARGE SEF
149 Pa (0.6 in.wg)
(I-P) in.wg
ELBOW SEF OBSTRUCTION SEF
149 Pa (0.6 in.wg) 50 Pa (0.2 in.wg)
(SI) Pa
+249 +1
ATMOSPHERIC PRESSURE
0 0
100 Pa (0.4 in.wg)
149 Pa (0.6 in.wg)
-249 -1 REQUIRED
Pt
-847 Pa (-3.4 in.wg)
Pv
-498 -2
Ps -996 Pa (4.0 in.wg)
-747 -3
224 Pa (0.9 in.wg)
-996 -4
-1245 -5
-1171 Pa (4.7 in.wg)
-971 Pa (3.9 in.wg)
A B C D E
-1121 Pa (4.5 in.wg)
FAN INLET
69
AMCA 201-02 (R2007)
Annex E. References
These references contain additional information related to the subject of this manual:
1. ANSI/AMCA 210-99, Laboratory Methods of Testing Fans for Aerodynamic Performance Rating, Air Movement
and Control Association International, Inc., 30 West University Drive, Arlington Heights, IL, 60004-1893 U.S.A.,
1999.
2. AMCA Publication 200-95, Air Systems, Air Movement and Control Association International, Inc., 30 West
University Drive, Arlington Heights, IL, 60004-1893 U.S.A., 1995.
3. AMCA Publication 202-98, Troubleshooting, Air Movement and Control Association International, Inc., 30 West
University Drive, Arlington Heights, IL, 60004-1893 U.S.A., 1997.
4. ASHRAE Handbook, HVAC Systems and Equipment, 1996, The American Society of Heating, Refrigerating
and Air Conditioning Engineers, Inc., 1791 Tullie Circle N.E., Atlanta, GA, 30329 U.S.A., 1996, (Chapter 18
Fans).
5. Traver, D. G., System Effects on Centrifugal Fan Performance, ASHRAE Symposium Bulletin, Fan Application,
Testing and Selection, The American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc.,
1791 Tullie Circle N.E., Atlanta, GA, 30329 U.S.A., 1971.
6. Christie, D. H., Fan Performance as Affected By Inlet Conditions, ASHRAE Transactions, Vol. 77, The
American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc., 1791 Tullie Circle N.E.,
Atlanta, GA, 30329 U.S.A., 1971.
7. Zaleski, R. H., System Effect Factors For Axial Flow Fans, AMCA Paper 2011-88, AMCA Engineering
Conference, Air Movement and Control Association International, Inc., 30 West University Drive, Arlington
Heights, IL, 60004-1893 U.S.A., 1988.
8. Roslyng, O., Installation Effect on Axial Flow Fan Caused Swirl and Non-Uniform Velocity Distribution,
Institution of Mechanical Engineers (IMechE), 1 Birdcage Walk, London SW1H 9JJ, England, 1984.
9. Clarke, M. S., Barnhart, J. T., Bubsey, F. J., Neitzel, E., The Effects of System Connections on Fan
Performance, ASHRAE RP-139 Report, The American Society of Heating, Refrigerating and Air Conditioning
Engineers, Inc., 1791 Tullie Circle N.E., Atlanta, GA, 30329 U.S.A., 1978.
10. Madhaven, S., Wright, T., J. DiRe, Centrifugal Fan Performance With Distorted Inflows, The American Society
of Mechanical Engineers, 345 East 47th Street, New, York, NY, 10017 U.S.A., 1983.
11. Cory, W. T. W., Fan System Effects Including Swirl and Yaw, AMCA Paper 1832-84-A5, AMCA Engineering
Conference, Air Movement and Control Association International, Inc., 30 West University Drive, Arlington
Heights, IL, 60004-1893 U.S.A., 1984.
12. Cory, W. T. W., Fan Performance Testing and Effects of the System, AMCA Paper 1228-82-A5, AMCA
Engineering Conference, Air Movement and Control Association International, Inc., 30 West University Drive,
Arlington Heights, IL, 60004-1893 U.S.A., 1984.
13. Galbraith, L.E., Discharge Diffuser Effect on Performance - Axial Fans, AMCA Paper 1950-86-A6, AMCA
Engineering Conference, Air Movement and Control Association International, Inc., 30 West University Drive,
Arlington Heights, IL, 60004-1893 U.S.A., 1986.
14. Industrial Ventilation –23rd Edition, American Conference of Governmental Industrial Hygienists, 1330 Kemper
Meadow Drive, Cincinnati, OH 45240-1634 U.S.A., 1998.
15. Fans and Systems, John E. Thompson and C. Jack Trickler, The New York Blower Company, Chemical
Engineering, March 21, 1983, pp. 48-63
16. AABC National Standards, Chapter 8, Volume Measurements, Associated Air Balance Council, 1518 K Street
NW, Suite 503, Washington, DC 20005 U.S.A.
70
AIR MOVEMENT AND CONTROL
ASSOCIATION INTERNATIONAL, INC.
30 West University Drive
Arlington Heights, IL 60004-1893 U.S.A.
Tel: (847) 394-0150 Fax: (847) 253-0088
E-Mail : [email protected] Web: www.amca.org
The Air Movement and control Association International, Inc. is a not-for-profit international association of the
world’s manufacturers of related air system equipment primarily, but limited to: fans, louvers, dampers, air
curtains, airflow measurement stations, acoustic attenuators, and other air system components for the industrial,
commercial and residential markets.
AMCA
Publication 202-98
(R2007)
Troubleshooting
Troubleshooting
All rights reserved. Reproduction or translation of any part of this work beyond that permitted by Sections 107 and
108 of the United States Copyright Act without the permission of the copyright owner is unlawful. Requests for
permission or further information should be addressed to the Executive Director, Air Movement and Control
Association International, Inc. at 30 West University Drive, Arlington Heights, IL 60004-1893 U.S.A.
Authority
AMCA Publication 202 was approved by the AMCA Membership on 13 February 1998. It was reaffirmed October
20, 2007
Disclaimer
AMCA uses its best efforts to produce standards for the benefit of the industry and the public in light of available
information and accepted industry practices. However, AMCA does not guarantee, certify or assure the safety or
performance of any products, components or systems tested, designed, installed or operated in accordance with
AMCA standards or that any tests conducted under its standards will be non-hazardous or free from risk.
Air Movement and Control Association International, Inc. will consider and decide all written complaints regarding
its standards, certification programs, or interpretations thereof. For information on procedures for submitting and
handling complaints, write to:
or
Air Systems is intended to provide basic information needed to design effective and energy efficient air systems.
Discussion is limited to systems where there is a clear separation of the fan inlet and outlet and does not cover
applications in which fans are used only to circulate air in an open space.
Fans and Systems is aimed primarily at the designer of the air moving system and discusses the effect on inlet and
outlet connections of the fan's performance. System Effect Factors, which must be included in the basic design
calculations, are listed for various configurations. AMCA 202 and AMCA 203 are companion documents.
System Checklist
Fan Manufacturer's Analysis
Master Troubleshooting Appendices
Troubleshooting is intended to help identify and correct problems with the performance and operation of the air
moving system after installation. AMCA 201 and AMCA 203 are companion documents.
Acceptance Tests
Test Methods and Instruments
Precautions
Limitations and Expected Accuracies
Calculations
Field Performance Measurements of Fan Systems reviews the various problems of making field measurements
and calculating the actual performance of the fan and system. AMCA 201 and AMCA 202 are companion
documents.
TABLE OF CONTENTS
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
3. Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
4. System Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
6. Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Troubleshooting
1. Introduction
After the installation of an air moving system is completed, a system sometimes fails to achieve its designed
performance.
This part of the AMCA Fan Application Manual will help you identify what is wrong and decide how to correct it.
2.1 Look in the "Master Troubleshooting Appendices" for a subject which corresponds with the apparent problem.
2.3 If the cause of the trouble is not found proceed through the "System Checklist" (see Section 4).
2.4 If the problem has still not been solved, it is now advisable to contact the representative of the fan manufacturer.
He should be given the results of the "System Checklist" and the additional information listed in Section 5.1.
2.5 The fan manufacturer or his representative will analyze the information submitted, as outlined in Section 5.2.
With this information and, if necessary, an on-site inspection, he may be able to explain why the system is not
achieving its design performance and may recommend changes in the system or the fan installation which will
overcome the problem.
3. Safety Precautions
Before checking the fan and system it will be necessary to shut down the fan. During inspection the fan must be
electrically isolated and all disconnect switches and other controls LOCKED in the "OFF" position. Where these
are in locations remote from the fan, prominent DO NOT START signs should also be in place.
CAUTION - Even when LOCKED out electrically, fans located outdoors or in a parallel or series fan system may
be subject to "wind-milling." Therefore, as an added precaution, the impeller should be secured to physically restrict
rotational movement.
4. System Checklist
A systematic check of the items listed here should help identify the problem - or problems - and allow suitable
corrective action to be taken.
1
AMCA 202-98 (R2007)
SYSTEM CHECKLIST
A) While the impeller is coasting to a stop, see if it is rotating in the proper direction (see Figures 4.1, 4.2 and
4.3).
B) Make certain the impeller rotation is correct for the housing (guide vanes of vaneaxial and tubular centrifugal
fans) and not installed backwards (see Figures 4.1, 4.2, and 4.3).
Note: Tubeaxial fan rotation is the same as shown in Figure 4.2 except without the guide vanes.
ROTATION
Note: Fan manufacturers describe the rotation of the fan impeller as being "clockwise" or "counterclockwise”.
• For AXIAL fans when viewing the INLET or OUTLET as specified by the Fan Manufacturer
• For CENTRIFUGAL fans when viewing the DRIVE SIDE (see AMCA Standard 99-2406)
• For TUBULAR CENTRIFUGAL fans when viewing the OUTLET (see AMCA Standard 99-2410).
2
AMCA 202-98 (R2007)
ROTATION ROTATION
INLET
GUIDE VANES
OUTLET
GUIDE VANES
AIRFLOW AIRFLOW
ROTATION
GUIDE
VANES AIRFLOW
3
AMCA 202-98 (R2007)
1) Are the drive pulley (Motor Sheave) and the driven pulley (Fan Sheave) in alignment? Improper
alignment of the sheaves can cause excessive power consumption (high amperage), squealing belts,
shortened belt and sheave life and high axial vibration.
FAN FAN
MOTOR MOTOR
2) Are the belts loose? Loose belts that flap or slip can cause excessive noise and vibration. Slipping belts
will also affect fan speed and reduce belt and sheave life.
Belts should be tensioned to the belt manufacturer's recommendations. Tension of the drive belts should
be adjusted for stretching after the first 48 hours of operation. Caution! Excessive belt tension will reduce
fan and motor bearing life.
3) Are the belts and/or sheaves worn? If so, an immediate replacement could save down time at a later
date. Where more than one belt is used, replace with a new set of matched belts.
D) Check the flow surfaces (passages between the inlets, impeller blades and inside of housing) for
cleanliness. A 2 mm (0.0625 in.) buildup of dirt on the flow surface could impair fan performance and/or
cause vibration.
E) Are there any gouges, tears, holes, erosion or corrosion in the impeller blades, rims or backplate: inlets
and/or housing? If so, report the approximate size and location to the fan manufacturer and discontinue
operation until repairs are made.
F) Is any foreign matter trapped in the impeller, housing or ductwork (loose insulation, papers, ice, etc.)? If so,
remove.
4
AMCA 202-98 (R2007)
G) Are coils, heaters, filters, ducts, etc. dirt laden? If so, clean or replace. Remove any non-essential
obstructions to airflow in elbows, shutters, transformations, dampers, bird-screens, etc. Verify that all
dampers (control, backdraft, fire, etc.) are adjusted to the proper settings.
H) Have all the parts supplied with the fan been installed?
I) Are there any obstructions to airflow near the fan inlets? Objects such as pipes, airflow measurement
stations, ductwork, columns, belt guards, belt drives, etc. could adversely affect the output of the fan. For
more information, see AMCA Publication 201 Fans and Systems.
J) Are the fan outlet connections correctly designed and installed? Duct takeoffs, or obstructions in the fan
outlet could adversely affect the output of the fan (see AMCA Publication 201).
K) See Figure 4.6A for typical centrifugal fan inlet-impeller relationships and Figure 4.6A for typical axial fan
housing-impeller relationships. A few simple measurements as indicated on these figures can tell the
manufacturer if a problem exists in this area. Note: several measurements should be taken around the
entire inlet/housing circumference to determine the average, maximum and minimum values.
I.S. I.S.
I.S. SHOULD BE SAME BOTH SIDES
FOR DOUBLE WIDTH FAN
R.C. C.
C. = VANE CLEARANCE
5
AMCA 202-98 (R2007)
L) On a double-width fan, is the approach to both inlets identical? Airflow should be symmetrical about the
centerline of the fan housing (see Figure 4.7A). Non-symmetrical airflow can lead to decreased air
performance. Belt drives, belt guards and motors can cause non-symmetrical airflow to the inlets if too
severely restricted (see AMCA Publication 201).
L L
P AIRFLOW
L NOT EQUAL TO M
L M
N NOT EQUAL TO R
N AIRFLOW
M) Are turning vanes installed in elbows that are too close to the fan inlet or discharge (see Figures 4.8A and
4.8B). Published pressure losses through elbows are based on a uniform velocity profile. Turning vanes
help achieve this uniform flow (see AMCA Publication 201).
6
AMCA 202-98 (R2007)
N) If the fan is equipped with an inlet vane damper, check the operation as follows:
1) Do not rely on the control arm position alone for locating the position of the inlet vane damper blades
without first checking visually to see that the inlet vane damper position agrees with the position of the
control arm.
2) If the unit is a double-width fan equipped with inlet vanes or inlet vane damper control, both inlet vane
dampers must be synchronized (the inlet vane dampers must be in the same relative position with
respect to the impeller on both inlets). If the inlet vane dampers are not synchronized, there will be
unbalanced airflow between inlets resulting in deficient air performance, unbalanced thrust on the
bearings and/or a surge condition in the fan.
3) Make certain that inlet vane dampers are of the proper rotation with respect to the impeller. As the
vanes close they should cause the entering air to spin in the same direction as the impeller.
4) Are the inlet vane dampers correctly positioned for the design operating conditions? If not, the desired
pressure-volume of the fan will not be realized (see Figure 4.9).
100% Open
100
75% Open
Percent of No Delivery Pressure
50% Open
80
60
25% Open
40
20
0 20 40 60 80 100
Figure 4.9 - Typical Pressure-Volume Curve for Operation with Inlet Vane Damper Control
7
AMCA 202-98 (R2007)
O) Inspect any ductwork or plenums approaching the fan inlets for the possibility of inducing swirl of air into the
inlet. Pre-swirl of air entering the fan inlet can reduce the fan performance (see Figures 4.10A and 4.10B).
(See AMCA Publication 201.)
IMPELLER IMPELLER
ROTATION ROTATION
P) After completing the above steps and making sure the fan and system are safe to start, remove all DO NOT
START signs on disconnect switches and override systems and put the unit back into operation.
Q) Inspect the entire system including the fan, fan plenum and all ductwork for significant air leaks. Air leaks
may be detected by sound, smoke, feel, soapy solution, etc. Some common air leak sources are: access
doors, coils, duct seams, fan outlet connection, etc. Significant air leaks must be sealed.
If the cause of the trouble has still not been found after completing the "System Checklist," the fan manufacturer
should be consulted.
The fan manufacturer will review the information provided concerning the system and recommend an appropriate
course of action.
To make a complete analysis of the problem, in addition to the results of the "System Checklist," the manufacturer
will need:
A) Complete plans (drawings) including all ductwork, location, size, model and manufacturer of all fans,
motors, coils, dampers, etc. with all pertinent dimensions for the complete system as actually installed.
B) If the fan/air handling system fails to achieve the design performance, the measured performance and the
design performance figures should be supplied.
8
AMCA 202-98 (R2007)
E) If a separate air performance test has been conducted on the installed fan, a statement of measured fan
performance along with a copy of the test data, the type of test and instrumentation, and the measurement
location of the airflow rate and pressure determinations should be supplied. A statement of fan performance
should contain:
3) Power (H)
A) Assess the probable accuracy of the field performance measurements (see AMCA Publication 203 Field
Performance Measurements of Fan Systems).
B) Examine the system drawings (plans) for any System Effect losses (see AMCA Publication 201) which were
not allowed for in the system design calculations or the original fan selection.
C) Reassess the fan performance, accounting for System Effect losses established in step B to the designed
fan/system performance (see Figure 5.1).
SYSTEM EFFECT
FAN CATALOG
PRESSURE-VOLUME CURVE
W/SYSTEM EFFECT
THEORETICAL PRESSURE-VOLUME
CURVE ACCOUNTING FOR SYSTEM EFFECT
LOSSES (FIELD PERFORMANCE MEASUREMENTS
TO BE COMPARED AGAINST THIS CURVE).
DESIGN VOLUME
Figure 5.1
9
AMCA 202-98 (R2007)
The information obtained through the checklists in this manual should help in defining the necessary corrective
action.
In most cases, if the troubleshooting procedure has been followed carefully and impartially it will be apparent
whether the system has been built and installed in accordance with the design drawings, whether the fan was
properly selected and suitable allowances made for the appropriate System Effect Factors, or whether the fan is
not performing up to its published ratings.
6. Conclusion
By intelligent application of the procedures outlined in this manual it should be possible to find the cause of a
performance problem in any air moving system.
Identification of a problem associated directly with the fan may require the assistance of the fan manufacturer.
Recognition of the cause of the trouble will usually be a major step toward curing it. Corrective measures may
include alterations to the system, modifications to the fan outlet or inlet connections, adjustments to the fan, etc.
In many cases an increase in the fan speed may be decided upon but it is extremely important that the fan shall
not be operated above its cataloged maximum speed or the maximum speed recommended by the
manufacturer. Excessive speed may result in catastrophic impeller failure. If a speed increase proves to be
an acceptable alternative, then the motor should also be checked for its capacity to handle the increased fan power.
10
AMCA 202-98 (R2007)
Annex A. Noise
A-1 IMPELLER HITTING INLET OR HOUSING . . . . . . . . . . . . . a. Impeller not centered in inlet or housing.
b. Inlet or housing damage.
c. Crooked or damaged impeller.
d. Shaft loose in bearing.
e. Impeller loose on shaft.
f. Bearing loose in bearing support.
g. Bent shaft.
h. Misaligned shaft and bearings.
11
AMCA 202-98 (R2007)
12
AMCA 202-98 (R2007)
13
AMCA 202-98 (R2007)
14
AMCA 202-98 (R2007)
B-7 NO STRAIGHT DUCT AT FAN OUTLET . . . . . . . . . . . . . . . a. Fans which are normally used in duct
system are tested with a length of
straight duct at the fan outlet. If there is
no straight duct at the fan outlet,
decreased performance may result. If it
is not practical to install a straight
section of duct at the fan outlet, the fan
speed may need to be increased to
overcome this pressure loss (see
System Effects in AMCA Publication
201).
CAUTION! DO NOT INCREASE FAN
SPEED BEYOND THE FAN MANUFA-
CTURER'S RECOMMENDATIONS.
ALSO, WHEN INCREASING FAN
SPEED, MONITOR MOTOR AMPS SO
AS NOT TO EXCEED MOTOR
NAMEPLATE AMPS.
B-8 OBSTRUCTION IN HIGH VELOCITY AIR STREAM . . . . . . a. Obstruction near fan outlet or inlet(s).
b. Sharp elbows near fan outlet or inlet(s).
c. Improperly designed turning vanes.
d. Projections, dampers or other
obstruction in a part of the system
where air velocity is high.
15
AMCA 202-98 (R2007)
16
AMCA 202-98 (R2007)
17
AMCA 202-98 (R2007)
18
AMCA 202-98 (R2007)
19
AMCA 202-98 (R2007)
a. Blown fuses.
b. Broken belts.
c. Loose pulleys.
d. Electricity turned off.
e. Impeller touching housing.
f. Wrong voltage.
g. Motor too small and overload protector
has broken circuit.
h. Low voltage, excessive line drop or
inadequate wire size.
i. Load inertia too large for motor.
j. Seized bearing.
20
AMCA 202-98 (R2007)
21
AMCA 202-98 (R2007)
Annex H. Vibration
MECHANICAL VIBRATION
22
AMCA 202-98 (R2007)
23
AIR MOVEMENT AND CONTROL
ASSOCIATION INTERNATIONAL, INC.
30 West University Drive
Arlington Heights, IL 60004-1893 U.S.A.
Tel: (847) 394-0150 Fax: (847) 253-0088
E-Mail : [email protected] Web: www.amca.org
The Air Movement and control Association International, Inc. is a not-for-profit international association of the
world’s manufacturers of related air system equipment primarily, but limited to: fans, louvers, dampers, air
curtains, airflow measurement stations, acoustic attenuators, and other air system components for the industrial,
commercial and residential markets.
AMCA
Publication 203-90
(R2007)
Field Performance
Measurement of Fan Systems
All rights reserved. Reproduction or translation of any part of this work beyond that permitted by Sections 107 and
108 of the United States Copyright Act without the permission of the copyright owner is unlawful. Requests for
permission or further information should be addressed to the Executive Director, Air Movement and Control
Association International, Inc. at 30 West University Drive, Arlington Heights, IL 60004-1893 U.S.A.
Forward
The original edition of Publication 203 was released in 1976. This, the second edition, updates much of the
information that was presented.
Annex K (estimating the power output of three phase motors) and Annex L (estimating belt drive losses) were
rewritten and adjusted based on new information received from motor and drive manufacturers. Over four hundred
belt drive loss tests were analyzed.
New axial fan System Effect Factors were established based on a test project conducted and underwritten by
AMCA. These factors were incorporated in their respective, applicable field test examples shown in Annex A.
The intent of this publication is to provide information from which test procedures can be developed to meet the
conditions and requirements encountered in specific field test situations. They include the proper procedure for
determining various System Effect Factors. Numerous examples of actual field tests are presented in detail in
Annex A. These examples provide sufficient guidance for the proper field testing of most fan system installations.
Authority
AMCA Publication 203 was approved by the Air Movement Control Association Membership in 1990. It was
reaffirmed July, 2007.
Disclaimer
AMCA uses its best efforts to produce standards for the benefit of the industry and the public in light of available
information and accepted industry practices. However, AMCA does not guarantee, certify or assure the safety or
performance of any products, components or systems tested, designed, installed or operated in accordance with
AMCA standards or that any tests conducted under its standards will be non-hazardous or free from risk.
Air Movement and Control Association International, Inc. will consider and decide all written complaints regarding
its standards, certification programs, or interpretations thereof. For information on procedures for submitting and
handling complaints, write to:
or
Air Systems is intended to provide basic information needed to design effective and energy efficient air systems.
Discussion is limited to systems where there is a clear separation of the fan inlet and outlet and does not cover
applications in which fans are used only to circulate air in an open space.
Fans and Systems is aimed primarily at the designer of the air moving system and discusses the effect on inlet and
outlet connections of the fan's performance. System Effect Factors, which must be included in the basic design
calculations, are listed for various configurations. AMCA 201-02 and AMCA 203-90 are companion documents.
System Checklist
Fan Manufacturer's Analysis
Master Troubleshooting Appendices
Troubleshooting is intended to help identify and correct problems with the performance and operation of the air
moving system after installation.
Acceptance Tests
Test Methods and Instruments
Precautions
Limitations and Expected Accuracies
Calculations
Field Performance Measurements of Fan Systems reviews the various problems of making field measurements
and calculating the actual performance of the fan and system. AMCA 203-90 and AMCA 201-02 are companion
documents.
TABLE OF CONTENTS
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
2. Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
6. Fan Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
7. Referenced Planes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
9.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
9.6 Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
10.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Because these problems and others will require C) Proof of Performance Test - A test in response
special consideration on each installation, it is not to a complaint to demonstrate that the fan is
practical to write one standard procedure for the meeting the specified performance requirement.
measurement of the performance of all fan-systems
in the field. This publication offers guidelines to As acceptance and proof of performance tests are
making performance measurements in the field related to contract provisions, they are usually
which are practical and flexible enough to be applied subject to more stringent requirements and are
to a wide range of fan and system combinations. usually more costly than a general evaluation test. In
the case of large fans used in industrial applications
Because of the wide variety of fan types and systems and of mechanical draft fans used in the electrical
encountered in the field, Annex A includes examples power generation industry the performance of a field
of a number of different field tests. In most cases, test may be part of the purchase agreement between
these examples are based on actual tests which have the fan manufacturer and the customer. In addition to
been conducted in the field. Publication 203, AMCA Standard 803 Site
Performance Test Standard-Power Plant and
Before performing any field test, it is strongly Industrial Fans defines the conditions which must be
recommended that the following AMCA publications met to achieve higher accuracy of measurement. In
be carefully reviewed: new installations of this type, it is desirable to include
a suitable measuring section in the design.
AMCA Publication 200 - Air Systems Agreement must be reached on the test method to be
AMCA Publication 201 - Fans and Systems used prior to performance of the test.
AMCA Publication 202 - Troubleshooting
AMCA Standard 210 - Laboratory Methods of Testing
1
AMCA 203-90 (R2007)
AMCA Publication 201, Fans and Systems, deals in Plane 1: Plane of fan inlet
detail with the effect of system connections on fan Plane 2: Plane of fan outlet
performance. It gives system effect factors for a wide Plane 3: Plane of Pitot-static tube traverse for
variety of obstructions and configurations which may purposes of determining flow rate
affect a fan’s performance. Plane 4: Plane of static pressure measurement
upstream of fan
System Effect Factor (SEF) is a pressure loss which Plane 5: Plane of static pressure measurement
recognizes the effect of fan inlet restrictions, fan downstream of fan
outlet restrictions, or other conditions influencing fan
performance when installed in the system. The use of the numerical designations as subscripts
indicate that the values pertain to those locations.
SYSTEM EFFECT FACTORS (SEFs) ARE
INTENDED TO BE USED IN CONJUNCTION WITH
THE SYSTEM RESISTANCE CHARACTERISTICS
IN THE FAN SELECTION PROCESS. Where SEFs
are not applied in the fan selection process, SEFs
must be applied in the calculations of the results of
field tests. This is done for the purpose of allowing
direct comparison of the test results to the design
static pressure calculation. Thus, for a field test, the
fan static pressure is defined as:
2
AMCA 203-90 (R2007)
A Area of cross-section ft2 Determine fan flow rate using the area, velocity
D Diameter ft pressure, and density at the traverse plane and the
De Equivalent diameter ft density at the fan inlet. The velocity pressure at the
FLA Full load amps amps traverse plane is the root mean square of the velocity
H Fan power input hp pressure measurements made in a traverse of the
HL Power transmission loss hp plane. The flow rate at the traverse plane is
Hmo Motor power output hp calculated by converting the velocity pressure to its
kW Electrical power kilowatts equivalent velocity and multiplying by the area of the
L Length ft traverse plane.
N Speed of rotation rpm
NLA No load amps amps 9.2 Velocity measuring instruments
NPH Nameplated horsepower hp
NPV Nameplated volts volts Use a Pitot-static tube of the proportions shown in
Ps Fan static pressure in. wg Annex B or a double reverse tube, shown in Annex C,
Psx Static pressure at Plane x in. wg and an inclined manometer to measure velocity
Pt Fan total pressure in. wg pressure. The velocity pressure at a point in a gas
stream is numerically equal to the total pressure
Ptx Total pressure at Plane x in. wg
diminished by the static pressure. The Pitot-static
Pv Fan velocity pressure in. wg
tube is connected to the inclined manometer as
Pvx Velocity pressure at Plane x in. wg shown in Annex F. The double reverse tube is
pb Barometric pressure in. Hg connected to the inclined manometer as shown in
pe Saturated vapor pressure at tw in. Hg Annex C.
pp Partial vapor pressure in. Hg
px Absolute pressure at Plane x in. Hg 9.2.1 Pitot-static tube. The Pitot-static tube is
Q Fan flow rate cfm considered to be a primary instrument and need not
Qi Interpolated flow rate cfm be calibrated if maintained in the specified condition.
Qx Flow rate at Plane x cfm It is suited for use in relatively clean gases. It may be
SEF System effect factor in. wg used in gases that contain moderate levels of
T Torque lb-in. particulate matter such as dust, water, or dirt,
td Dry-bulb temperature °F provided certain precautions are employed (see
tw Wet-bulb temperature °F Section 15).
V Velocity fpm
9.2.2 Double reverse tube. The double reverse tube
ΔPx,x’ Pressure loss between
is used when the amount of particulate matter in the
Planes x and x’ in. wg gas stream impairs the function of the Pitot-static
ΔPs Pressure loss across damper in. wg tube. The double reverse tube requires calibration. It
ρ Fan gas density lbm/ft3 is important that the double reverse tube be used in
ρx Gas density at Plane x lbm/ft3 the same orientation as used during calibration. Mark
Σ Summation sign --- the double reverse tube to indicate the direction of
Airflow direction --- the gas flow used in its calibration.
3
AMCA 203-90 (R2007)
The accuracy of the manometer used in the than 75% of the velocity pressure measurements
measurement of velocity pressures is of prime are greater than 1/10 of the maximum
importance. Select a manometer that will provide an measurement (see Figure 9.1)
acceptable degree of accuracy; consider the range,
slope, quality, scale graduations, indicating fluid of 2) The flow streams should be at right angles to the
the instrument and the range of the velocity traverse plane. Variations from this flow condition
pressures to be measured. The graph in Annex G as a result of swirl or other mass turbulence are
indicates the effect of expected resolution of considered acceptable when the angle between
manometer readings on the accuracy of velocity the flow stream and the traverse plane is within
determinations. The basis for this graph is described 10 degrees of a right angle. The angle of the flow
in Section 9.6. Determine velocities in the very low stream in any specific location is indicated by the
range more accurately by using a manometer with a orientation of the nose of the Pitot-static tube that
slope of 20:1. Due to practical limitations in length, its produces the maximum velocity pressure reading
use is restricted to measurements where the at the location.
velocities are very low. Also, errors in velocity
determinations made by using a Pitot-static tube and 3) The cross-sectional shape of the airway in which
manometer exceed normally acceptable values at the traverse plane is located should not be
velocity pressure readings less than 0.023 in. wg. irregular. Proper distribution of traverse points
This corresponds to a velocity of approximately 600 and accurate determination of the area of the
fpm for air of 0.075 lbm/ft3 density. traverse plane are difficult to achieve when the
airway does not conform closely to a regular
9.2.4 Low velocity instruments. Normally, velocities shape.
encountered in the field test situations are well in
excess of 600 fpm. Therefore, recommendations 4) The cross-sectional shape and area of the airway
regarding alternate test procedures and should be uniform throughout the length of the
instrumentation for use for velocities less than 600 airway in the vicinity of the traverse plane. When
fpm are not presented in this publication. the divergence or convergence of the airway is
Descriptions of various types of instruments used to irregular or more than moderate in degree,
determine range velocities are presented in Annex J. significantly nonuniform flow conditions may
Most of the instruments require frequent calibration, exist.
and some are not suited for use in high temperature,
dirty, wet, corrosive, or explosive atmospheres. If it is 5) The traverse plane should be located to minimize
necessary to use one of these instruments, the the effects of gas leaks between the traverse
procedure for its use, its calibration, and the expected plane and the fan.
accuracy of results should be agreed upon by all
interested parties. 6) When it is necessary to locate the traverse plane
in a converging or diverging airway (not
9.3 Location of traverse plane recommended), note that the traverse plane and
area is located at the tip of the Pitot-static tube.
For field tests, suitable test measurement station
locations must be provided in the system. When A location well downstream in a long, straight run of
suitable locations are not available, consider making uniform cross-section duct will usually provide
temporary or permanent alterations to the ducting for acceptable conditions for the Pitot traverse plane.
improved test accuracy. When locating the traverse plane close to the fan, as
is often done in order to minimize the effect of
For free inlet, free outlet fans, convert a free inlet, leakage, flow conditions upstream of the fan are
free outlet fan to a ducted inlet, free outlet fan by the usually more suitable. In some installations, more
addition of a temporary duct. Estimate free inlet, free than one traverse plane may be required in order to
outlet fan flow rate by measuring other parameters account for the total flow (Annex A contains
and interpreting certified ratings performance (see examples).
Section 17.1).
When a field test is anticipated, particularly when the
A Pitot traverse plane suitable for the measurements requirement for a field test is an item in the
used to determine flow rate are as follows: specifications, the system designer should provide a
suitable traverse plane location in the system.
1) The velocity distribution should be uniform
throughout the traverse plane. The uniformity of When the fan is ducted outlet and the traverse plane
distribution is considered acceptable when more is to be located downstream from the fan, the
4
AMCA 203-90 (R2007)
60%
80%
40% 35%
20% 35%
MEASUREMENT PLANE
De
MIN.
2
12 in. MIN.
4YZ
WHERE: De =
π INLET BOX DAMPERS
Z
Note: The measurement plane should be located a minimum of ½ De from the inlet cone, but not less than 12 in.
from the leaving edge of the damper blades.
Figure 9.2
STACK
VELOCITY
PROFILE
Note: Spiral vortex may form when fan discharges directly into a stack or similar arrangement.
Figure 9.3
6
AMCA 203-90 (R2007)
traverse plane should be situated a sufficient equivalent diameters from the inlet of the duct.
distance downstream from the fan to allow the flow to Where the duct is small, its length may
diffuse to a more uniform velocity distribution and to necessarily be greater than 2 equivalent
allow the conversion of velocity pressure to static diameters in order to ensure that the tip of the
pressure. Annex P provides guidance for the location Pitot-static tube is a minimum of 1½ equivalent
of the traverse plane in these cases. The location of diameters from the duct inlet. This short length of
the traverse plane on the inlet side of the fan should duct should produce no significant addition to the
not be less than ½ equivalent diameter from the fan system resistance, but in some cases it may alter
inlet. Regions immediately downstream from elbows, the pattern of flow into the fan impeller, and
obstructions and abrupt changes in airway area are thereby affect the performance of the fan slightly.
not suitable traverse plane locations. Regions where
unacceptable levels of swirl are usually present, such 9.4 The traverse
as the region downstream from an axial flow fan that
is not equipped with straightening vanes, should be Annex H contains recommendations for the number
avoided. Swirl may form when a fan discharges and distribution of measurement points in the
directly into a stack or similar arrangement (see traverse plane. If the flow conditions at the traverse
Figure 9.2). plane are less than satisfactory, increase the number
of measurement points in the traverse to improve
9.3.1 Inlet box location. When the traverse plane accuracy.
must be located within an inlet box, the plane should
be located a minimum of 12 inches downstream from Since the flow at a traverse plane is never strictly
the leaving edges of the damper blades and not less steady, the velocity pressure measurements
than ½ equivalent diameter upstream from the edge indicated by the manometer will fluctuate. Each
of the inlet cone (see Figure 9.3). Do not locate velocity pressure measurement should be mentally
traverse points in the wake of individual damper averaged on a time-weighted basis. Any velocity
blades. In the case of double inlet fans, traverses pressure measurement that appears as a negative
must be conducted in both inlet boxes in order to reading is to be considered a velocity pressure
determine the total flow rate. measurement of zero and included as such in the
calculation of the average velocity pressure.
9.3.2 Alternative locations. On occasion, an
undesirable traverse plane location is unavoidable, or When it is necessary to locate the traverse plane in a
each of a limited number of prospective locations converging or diverging airway, orient the nose of the
lacks one or more desirable qualities. In such cases, Pitot-static tube such that it coincides with the
the alternatives are: anticipated line of the flow stream. This is particularly
important at measurement points near the walls of
1) Accept the most suitable location and evaluate the airway (see Annex A-1A).
the effects of the undesirable aspects of the
location on the accuracy of the test results. In No appreciable effect on Pitot-static tube readings
some instances, the estimated accuracy may occur until the angle of misalignment between the
indicate that the results of the test would be airflow and the tube exceeds 10 degrees.
meaningless, particularly in acceptance tests and
proof of performance tests. 9.5 Flow rate calculations
2) Provide a suitable location by modifying the 9.5.1 Flow rate at traverse plane. The flow rate at
system. This course of action is recommended the traverse plane is calculated as follows:
for acceptance tests and proof of performance
tests. The modifications may be temporary, Q3 = V3A3
permanent, minor or extensive, depending on the
specific conditions encountered. When the inlet Where:
side of the fan is not ducted but is designed to
accept a duct, consider installing a short length of A3 = the area of the traverse plane
inlet duct to provide a suitable traverse plane V3 = the average velocity at the traverse plane
location. This duct should be of a size and shape
= 1096 (Pv3/ρ3)0.5
to fit the fan inlet, a minimum of 2 equivalent
diameters long and equipped with a bell shaped ρ3 = the density at the traverse plane
or flared fitting at its inlet. The traverse plane Pv3 = the root mean square velocity pressure at the
should be located a minimum of ½ equivalent traverse plane
diameters from the fan inlet and not less than 1½ = [∑(Pv3r)0.5 / number of readings]2
7
AMCA 203-90 (R2007)
Pv3r is the velocity pressure reading, corrected for determinations. This graph indicates the effect of
manometer calibration and where applicable, expected resolution of velocity determinations. This
corrected for the calibration of the double reverse effect is shown for several manometer slope ratios.
tube. It is important that the calibration of the double For all ratios, the expected resolution used as a basis
reverse tube be applied correctly. The use of the for the graph is the length of indicating column
calibration of the double reverse tube is described in equivalent to 0.05 in. wg in a manometer with slope
Annex C. ratio of 1:1. As indicated in the graph, reading
resolution uncertainty can be significant. However,
9.5.2 Continuity of mass. The calculations of fan this uncertainty can be controlled by selecting a
flow rate are based on considerations of continuity of manometer with a slope suited to the velocity
mass, and as such, it is assumed that no mass is pressures to be measured and by avoiding regions of
added or removed from the gas stream between the very low velocity in the selection of the traverse plane
traverse plane and the fan inlet. In the general location. Reading resolution uncertainties exceed
application, having determined the flow rate and normally acceptable values at velocity pressures less
density at the traverse plane, the flow rate at any than 0.023 in. wg. This corresponds to a velocity of
location, (x), in the fan-system installation may be approximately 600 fpm for air of 0.075 lbm/ft3 density.
calculated, providing the density at this location is Generally, ducts are sized for velocities considerably
known and the assumption noted above is valid, i.e.: in excess of 600 fpm. Velocities less than 600 fpm
may exist in certain sections of the system in some
Qx = Q3 (ρ3/ρx) installations, but these sections can usually be
avoided. Do no use a Pitot-static tube and
9.5.3 Fan flow rate, single traverse plane. Where a manometer to determine velocities in the low ranges
single traverse plane is used, the calculation of the associated with filters and cooling coils in air
fan flow rate is: conditioning, heating, and ventilating units. In some
instances, the uncertainties incurred in the
Q = Q1 determinations of low velocity flows may be
= Q3 (ρ3/ρ1) acceptable. For example, an uncertainty of 15% in
the determination of the flow rate in a branch duct
Where: that accounts for 20% of the total flow rate for the
system affects the accuracy of the total flow rate
Q3 and ρ3 = as described in Section 9.5.1 determination by only 3%.
ρ1 = the density at the fan inlet In addition to low range velocities, other conditions
may exist at the traverse plane which can
significantly affect the accuracy of the flow rate
9.5.4 Fan flow rate, multiple traverse planes.
determination. These include nonuniform velocity
When it is necessary to use more than one traverse
distribution, swirl, and other mass turbulence.
plane in order to account for the total flow:
Improve the accuracy of the flow rate determination
by avoiding these conditions in the selection of the
Q = Q1
traverse plane location, or improve the conditions by
= Q3a (ρ3a/ρ1) + Q3b (ρ3b/ρ1) + ... + Q3n (ρ3n/ρ1)
modifying the system.
8
AMCA 203-90 (R2007)
determined by making pressure measurements at between the measurement plane and the plane of
other locations, upstream and downstream of the fan. interest is straight and without change in cross-
In the latter case, the determinations must account sectional area. Then the duct friction loss between
for the effects of velocity pressure conversions and the measurement plane and the plane of interest is
pressure losses, as may occur between the usually insignificant, and considerations of velocity
measurement planes and the planes of interest. pressure conversions and calculations of pressure
losses for duct fitting and other system components
10.2 Pressure measuring instruments can be avoided.
This section describes only the instruments for use in When a system component is situated between the
measuring static pressure. Instruments for use in the measurement plane and the plane of interest, the
other measurements involved in the determination of pressure loss of the component must be calculated
fan static pressure are described in Section 13. and credited to the fan. The calculation of the
pressure loss is usually based on the component’s
Use a Pitot-static tube of the proportions shown in performance ratings, which may be obtained from the
Annex B, a double reverse tube as shown in Annex manufacturer of the item.
C, or a side wall pressure tap as shown in Annex E,
and a manometer to measure static pressure. If there is a change in area between the
measurement plane and the plane of interest, then
10.2.1 Pitot-static tube. The comments that appear the calculation of the static pressure at the plane of
in Section 9.2 regarding the use and calibration of the interest must account for velocity pressure
Pitot-static tube are applicable to its use in the conversion and include any associated pressure
measurement of static pressures. loss. When the change in area is moderate and
gradual, the conversion of velocity pressure is
10.2.2 Double reverse tube. The double reverse considered to occur without loss and the static
tube cannot be used to measure static pressure pressure is calculated on the basis of no change in
directly. It must be connected to two manometers and total pressure between the measurement plane and
the static pressure for each point of measurement the plane of interest. This assumes that the duct
must be calculated. Both the manometer connections friction loss between the two planes is negligible.
and the method of calculation are shown in Annex C. When the change in area is an abrupt and sizable
enlargement, as in a duct leading into a large
10.2.3 Pressure tap. The pressure tap does not plenum, the loss is considered to be equivalent to the
require calibration. Use no fewer than four taps velocity pressure in the smaller area, and the static
located 90 degrees apart. In rectangular ducts, a pressure at the plane of interest is considered to be
pressure tap should be installed near the center of the same as the static pressure at the measurement
each wall. It is important that the inner surfaces of the plane. This assumes that the velocity pressure in the
duct in the vicinities of the pressure taps be smooth larger area and the duct friction loss are negligible.
and free from irregularities, and that the velocity of
the gas stream does not influence the pressure 10.3.1 Location of the measuring plane. When the
measurements. fan is ducted outlet, the static pressure measurement
plane downstream of the fan should be situated a
10.2.4 Manometers. A manometer with either sufficient distance from the fan outlet to allow the flow
vertical or inclined indicating column may be used to to diffuse to a more uniform velocity distribution and
measure static pressure. Inclined manometers used to allow the conversion of velocity pressure to static
to measure static pressures require calibration and pressure. See Annex P for guidance in locating the
should be selected for the quality, range, slope, scale measurement plane in these cases. In general,
graduations, and indicating fluid necessary to pressure taps should be used if it is necessary to
minimize reading resolution errors. measure static pressure in the immediate vicinity of
the fan outlet. The static pressure at this location is
10.3 Static pressure measurements difficult to measure accurately with a Pitot-static tube
due to the existence of turbulence and localized high
It is important that all static pressure measurements velocities. If the surface conditions or the velocities at
be referred to the same atmospheric pressure, and the duct walls are unsuited for the use of pressure
this atmospheric pressure be that for which the taps, then a Pitot-static tube must be used with
barometric pressure is determined. extreme care, particularly in aligning the nose of the
tube with the lines of the flow streams.
Make static pressure measurements near the fan
inlet and the fan outlet, and where the airway The location of the static pressure measurement
9
AMCA 203-90 (R2007)
plane upstream of the fan should not be less than ½ negative. By definition, positive values are those
equivalent diameter from the fan inlet. In the event measured as being greater than atmospheric
that static pressure measurements must be made in pressures; negative values are those measured as
an inlet box, the measurement plane should be being less than atmospheric pressure. In all of the
located as indicated in Figure 9.2. In the case of equations in this publication, the values of static
double inlet fans, static pressure measurements must pressures must be entered with their proper signs
be made in both inlet boxes in order to determine the and combined algebraically.
average static pressure on the inlet side of the fan.
10.4.1 Static pressure at measuring planes. The
In general, the qualifications for a plane well suited static pressure at a plane of measurement (x) is
for the measurement of static pressure are the same calculated as follows:
as those for the measurement of velocity pressure,
as indicated in Section 9.3:
Psx =
∑P sxr
If in any fan-system installation the prospective Pt4 = the total pressure plane of measurement
locations for static pressure measurement planes Pt1 = the total pressure at the fan inlet
lack one or more desirable qualities, the alternatives ΔP4,1 = the sum of the pressure losses between the
are to accept the best qualified locations and two planes
evaluate the effects of the undesirable aspects of the
conditions on the accuracy of the test results or These losses (ΔP) include those attributable to duct
provide suitable locations by modifying the system. friction, duct fittings, other system components, and
changes in airway area. Although ΔP represents a
10.3.2 When using a Pitot-static tube or a double loss in all cases, it is considered a positive value as
reverse tube to measure static pressure, a number of used in the equations in this publication. By
measurements must be made throughout the plane. substitution and rearrangement:
Use Annex H to determine the number and
distribution of the measurement points. When using Ps1 = Ps4 + Pv4 - Pv1 - ΔP4,1
pressure taps, a single measurement at each of the
taps located at the plane is sufficient. Similarly, for static pressure at the fan outlet, Ps2:
Static pressure measurements may be positive or Ps2 = Ps5 + Pv5 - Pv2 + ΔP2,5
10
AMCA 203-90 (R2007)
The velocity pressures at the various planes can be The uncertainty analyses in Annex T indicate that the
determined from the following general equations for uncertainties in fan static pressure determinations
the velocity pressure at a plane of measurement (x): are expected range from 2% to 8%. This range is
based on considerations of the conditions expected
Pvx = Pv3 (A3/Ax)2 (ρ3/ρx) to be encountered in most field test situations.
11
AMCA 203-90 (R2007)
11. Fan Power Input 11.2.2 Typical motor performance data. Typical
motor performance data may be used to determine
11.1 General fan power input. These data, which are referred to as
typical in that the data and the actual performance of
Fan power input data included as part of the fan the motor are expected to correspond closely, can
performance ratings are normally defined and limited usually be obtained from the motor manufacturer.
to either: The data provided can be in a variety of forms, but
are sufficient to determine motor power output based
• power input to the fan shaft on electrical input measurements. It is important that
the power supplied to the motor during the field test
• the total of the power input to the fan shaft and be consistent with that used as the basis for the
the power transmission loss motor performance data. The phase voltage should
be stable and balanced, and the average should be
The losses in fan shaft bearings are included in either withing 2% of the voltage indicated in the
case. Since the results of field tests are usually performance data.
compared to the rated performance characteristics of
the fan, field test values of fan power input should be Depending on the form of the typical motor
determined on the same basis as that used in the fan performance data, motor power output is determined
ratings. For belt driven fans, the rated fan power input by one of the following methods:
may or may not include belt drive losses. The
information regarding the basis of the rated fan 1) Given the typical motor performance chart of
power input accompanies the rating data or is watts input versus motor power output at a stated
otherwise available from the fan manufacturer. In voltage.
most instances, when a power transmission loss Hmo, is the value in the typical motor performance
occurs, the loss will have to be determined and data that corresponds to the field test
subtracted from the motor output in order to obtain measurement of watts input to the motor.
the fan power input.
2) Given the typical motor performance chart of
11.2 Power measurement methods watts input versus torque output and speed at a
stated voltage.
In view of the fact that accuracy requirements for field Use the field test measurement of watts input
test determinations of fan power input vary and the corresponding typical motor performance
considerably, a number of test methods are data values of torque output and speed; the
recommended. These methods are intended to motor power output is calculated as:
provide economical and practical alternatives for
dealing with various levels of accuracy requirements. T ×N
Hmo =
63025
11.2.1 Phase current method. This method for
estimating the power output of three phase motors is
3) Given the typical motor performance chart of
based on the relationship of motor current and motor
watts input versus motor efficiency at a stated
power output. The method, described in Annex K,
voltage.
requires measurements of the phase currents and
Use the field test measurement of watts input
voltages supplied to the motor while driving the fan.
and the corresponding typical motor performance
Depending on the operating load point of the motor, it
data value of motor efficiency, the motor power
may also involve the measurements of the no load
output is calculated as:
phase currents.
The phase current method is convenient and watts input × motor efficiency
Hmo =
sufficiently accurate for most field tests. In this 746
method, the closer the actual phase current is to the
motor nameplate value of full load amps, the greater 4) Given the typical motor performance chart of
the accuracy. Since fan motors are normally selected amps versus power factor and motor efficiency at
for operation at or near the full load point, this method a stated voltage.
provides a reasonably accurate estimate of the Use the field test measurements of amps input
power output of the fan motor. Determine fan power and volts, and the typical motor performance
input by using the motor power output and, where data values of power factor (pf) and motor
applicable, the power transmission loss. efficiency, corresponding to the measured amps
input; the motor power output is calculated as:
12
AMCA 203-90 (R2007)
A calibrated motor provides accurate data to 11.4.1 Estimating belt drive losses. In view of the
determine motor power output. However, the cost of lack of published information available for use in
the calibration is a limiting factor in the use of this calculating belt drive losses, a graph is included in
method in field tests. For low horsepower Annex L for this purpose. As indicated in the graph,
applications, the fan manufacturer may be able to belt drive loss, expressed as a percentage of motor
calibrate a motor. power output, decreases with increasing motor
power output and increases with increasing speed.
11.2.4. Torquemeters. Another method to determine This graph is based on the results of over 400 drive
fan power input involves the use of a torquemeter loss tests provided to AMCA by drive manufacturers.
installed between the fan and the driver. The use of a The graph serves as a reasonable guide in
torquemeter requires some prearrangement with the evaluating belt drive losses. The calculation of belt
purchaser, who would normally have specified such drive loss, using this graph, is included in many of the
equipment, so that site conditions can be altered to examples in Annex A.
13
AMCA 203-90 (R2007)
11.4.2 Estimating other transmission losses. For determination is required. The pressures at Planes 1
other types of power transmission equipment, consult and 2 are based on the static pressure
the fan manufacturer to establish whether measurements made for the purpose of determining
transmission losses are included in the fan ratings, the fan static pressure. The pressure at Plane 3 is
and if so, request the magnitudes of the losses obtained by averaging static pressure measurements
allowed in the ratings. Otherwise, it will be necessary made concurrent with the velocity pressure
to consult the manufacturer of the power measurements made in a traverse of Plane 3. The
transmission equipment for the information regarding absolute pressure at a plane is calculated by using
transmission losses. the static pressure at the plane and the barometric
pressure. For this reason, it is important that the
11.5 Accuracy barometric pressure be determined for the
atmosphere to which static pressure measurements
The uncertainty analyses presented in Annex T are referred. The temperatures used in density
indicate that the uncertainties in fan power input determinations are measured at the planes of
determinations are expected to range from 4% to 8%. interest.
This range is based on considerations of the
conditions encountered in most field test situations, 13.3 Additional data
estimated accuracies of the various test methods
presented in this publication and allowances for Additional data required in the determination of
uncertainties in the determinations of power density depends on the gas stream as indicated
transmission losses. below:
14
AMCA 203-90 (R2007)
inversely proportional to absolute temperature. thermometer should be accurate within 5°F of the
measured value and readable to 5°F or finer.
13.4.1 Example calculation - ρ3 from ρ1. Use Figure
N.1 of Annex N to establish the density of air at Plane The temperature determination should be
1 based on the test determinations of barometric representative of the average temperature of the gas
pressure, pb, and the following Plane 1 values: stream throughout the plane of interest. When the
temperature varies with time or temperature
Ps1, static pressure, in. wg stratification exists at the measurement plane,
td1, dry-bulb temperature, °F several temperature measurements may be
tw1, wet-bulb temperature, °F necessary in order to obtain a representative
average. At elevated temperatures, the thermometer
may have to be shielded to prevent radiation effects
The following data are obtained for Plane 3:
from exposed heat sources.
Ps3, static pressure, in. wg
Locate the wet-bulb thermometer downstream from
td3, dry-bulb temperature, °F
the dry-bulb thermometer in order to prevent the dry-
bulb temperature measurement from being adversely
Calculate the density at Plane 3 as follows: affected. The wet-bulb thermometer wick should be
clean, closely fitted, and wetted with fresh water. The
⎛ P + 13.6 pb ⎞ ⎛ t d1 + 460 ⎞ velocity of the air over the wick should be between
ρ3 = ρ1 ⎜ s3 ⎟⎜ ⎟ 700 and 2000 fpm. Use a sling psychrometer to
⎝ 13.6 p1 ⎠ ⎝ t d3 + 460 ⎠ obtain dry and wet-bulb air temperature
measurements at the fan inlet for free inlet fans.
Where:
13.6 Barometric pressure
p1 = the absolute pressure, in. Hg at Plane 1,
calculated as follows: Use a portable aneroid barometer for field test
determinations of barometric pressure when an
p1 = pb + (Ps1/13.6) acceptable site barometer is not available. The
barometer should be accurate within 0.05 in. Hg of
In this manner, ρ3 can be calculated without having to the measured value. Determine the test value of
measure the wet-bulb temperature at Plane 3. These barometric pressure by averaging measurements
equations can be used for gases other than air and made at the beginning and end of the test period.
can be adapted for use in calculations involving any
two planes, subject to the limitations noted earlier. When the test value of barometric pressure is to be
based on data obtained from a nearby airport, it is
In the example calculation of ρ3, pb is determined for important that the data include the barometric
the atmosphere to which the measurements of Ps1 pressure for the airport site and the elevation for
and Ps3 are referred. Refer static pressure which the pressure was determined (often the
measurements to a common atmosphere. When barometric pressure is corrected to sea level). This
the pressures cannot be referred to a common pressure value must then be corrected to the test site
atmosphere, the absolute pressure for each plane is elevation. Barometric pressure decreases
calculated by using the static pressure measurement approximately 0.1 in. Hg for every 100 ft increase in
at the plane and the barometric pressure for the elevation
atmosphere to which the static pressure
measurement is referred. However, for the purposes 13.7 Accuracy
of accuracy, static pressure measurements that are
used in the determination of fan static pressure must As indicated in Annex T, uncertainties in density
be referred to a common atmosphere. determinations are expected to be less than 3%.
However, care must be exercised in obtaining
13.5 Temperatures representative test measurements in order to prevent
the uncertainties from exceeding this value.
Measure temperatures with mercury-in-glass, dial, or
thermocouple type thermometers. For temperatures 14. Conversion Calculations
through 220°F, the thermometer should be accurate
within 2°F of the measured value and readable to 1°F Generally, the test fan will be operating at a speed
or finer. For temperatures above 220°F, the and inlet density that are somewhat different from the
15
AMCA 203-90 (R2007)
fan performance rating values of fan speed and inlet Work required to accommodate test
density. In order to provide a common basis for measurements (drilling of traverse holes,
comparing the field test results to the fan installation of static pressure taps and
performance ratings, each of these two items must thermometer wells, etc.) should be completed
be the same in both sets of data. This can be prior to the test date.
accomplished by converting the results of the field
test to the speed and density conditions of the fan 4) System Effect Factors, if any, must be
performance ratings. The equations for the established prior to the conduct of the test.
conversion are as follows.
5) The expected test uncertainties must be agreed
Qc = Q (Nc / N) upon prior to the test (see Annex T).
Psc = Ps (Nc / N)2 (ρc / ρ) 6) Responsibility for the cost of the test or any fan-
system modifications required as a result of the
Ptc = Pt (Nc / N)2 (ρc / ρ) test should be established.
16
AMCA 203-90 (R2007)
15.2 It is recommended that as a minimum, the 2) Static and total pressure manometer tubing must
following equipment be taken to or be otherwise be “pinched off” prior to inserting or removing the
available at the job site: Pitot-static tube from the test duct. Release both
legs of the tubing simultaneously after the Pitot-
1) Pitot-static tubes of suitable lengths for the static tube is inside the test duct and properly
maximum duct size to be traversed. oriented. Failure to release simultaneously may
Considerations should be given to the use of a result in manometer fluid being blown from the
double reverse tube in dirty atmospheres. manometer.
2) Manometers suitable for measuring static 3) Loop the manometer tubing well above the
pressures. Manometer fluids other than water are manometer so that any fluid which is
acceptable, provided the specific gravity is inadvertently blown from the gauge will drain
known. A spare bottle of manometer fluid is back into the manometer.
advisable.
4) The Pitot-static tube is intended for measuring
3) Inclined manometer suitable for measuring pressures in relatively clean gases. When using
velocity pressures. Pitot-static tubes in dirty, wet, or corrosive
atmospheres, both legs of the Pitot-static tube
4) Flexible tubing of suitable length to enable must be cleaned out frequently during the test.
manometers to be installed at a convenient Since fan pressure readings are never strictly
location. steady, absence of fluctuations is an
indication of a plugged Pitot-static tube.
5) Tubing couplings and “T” type tubing connectors. Consider using a double reverse tube in these
situations.
6) Thermometers to cover the range of anticipated
temperatures. 5) When making measurements in wet gas
streams, continually check for the presence of
7) Sling psychrometer for obtaining dry-bulb and moisture in the tubing. Clear plastic tubing is
wet-bulb temperatures. ideal from this standpoint. If moisture collects in
the tubing, immediately remove the Pitot-static
8) Clip-on ammeter-voltmeter, power analyzer, or tube and clean the inside of the tubing and Pitot-
other suitable electrical measurement static tube before proceeding with the test.
instruments for the determination of fan power
input. 6) Before performing any work inside a fan,
ductwork, or other system components, make
9) Fan speed measurement instrument. certain that the fan motor starter is “locked out.”
13) Complete AMCA Fan Application Manual 9) Measure temperatures on both sides of double
containing Publications 200, 201, 202, and 203. inlet fans as temperature differences may exist
between each side.
16. Precautions
10) When measuring in high temperature, corrosive
The following precautions should be observed when or explosive atmospheres, instruments should be
conducting a field test: selected for suitability for such atmospheres.
1) Connect the Pitot-static tube to the manometers 17. Typical Fan-System Installations
according to anticipated pressures, i.e., whether
the pressures are positive or negative, and the A fan assembly may include any number of
magnitudes of pressures. appurtenances: variable inlet vanes, inlet boxes, inlet
17
AMCA 203-90 (R2007)
box dampers, outlet dampers, inlet screens, belt a) The operations of ovens, furnaces, paint booths,
guards, inlet bells, diffusers (evasés). Alternately, air conditioning equipment, other fans, and
these items may be included in the fan-system similar items that may supply or exhaust air from
installation, but not be a part of the fan assembly. In the building in intermittent or modulating
order to determine the proper field test procedure fashions.
and to provide a valid basis for comparing field test
results to the fan performance ratings, it is important b) The use of doors providing access to the
to establish which of these items are considered a building. The effect is most significant when large
part of the fan and which are considered a part of the doors that are normally closed are kept open for
system. The fan performance ratings may be extended periods such as in loading operations.
assumed to include the appurtenances that are
established as being a part of the fan assembly. c) The velocity and direction of the wind outside the
building, particularly in conjunction with the item
The locations of the fan inlet and fan outlet depend immediately above and as it may affect the flow
on whether specific appurtenances are considered of air from the outlet of the ventilator.
to be a part of the fan assembly. If the assembly
includes an inlet box, the fan inlet is the inlet to the d) The use of interior doors that my restrict the flow
inlet box. For a fan assembly that includes a diffuser, of air from areas normally expected to be
the fan outlet is the outlet of the diffuser. ventilated.
In the case of heating, ventilating, and air- Assuming that these difficulties can be resolved and
conditioning equipment, the field test procedure will the desired system is fixed for the duration of the test,
depend on whether the equipment is a factory determine the fan performance by using one of the
assembled central station unit, a built-up unit, or a following methods:
packaged unit (see Section 17.4).
1) Make field test measurements sufficient for
The performance ratings for a fan that includes inlet determining fan static pressure, fan power input,
box dampers, variable inlet vanes or outlet dampers fan speed, and the density of the air at the fan
cover operation of the fan with these items in the full inlet. In this method for testing a free inlet, free
open positions. In order to be able to compare the outlet fan, the fan static pressure is calculated as
field test results to the fan performance ratings, it is the static pressure on the outlet side of the fan
essential that these items be fixed in their full open less the static pressure on the inlet side of the
positions for the duration of the test. In addition, when fan: Ps = Ps2 - Ps1. The static pressure
the loss through a damper must be calculated, it is measurements involved must be referred to the
essential that the damper blades be fixed in their full same atmospheric pressure and made at
open positions during the test since this is the locations sufficiently distant from the fan inlet and
condition on which the damper pressure loss ratings outlet so as to be unaffected by the velocity of the
are based. This consideration arises when a damper, air entering and leaving the fan. Using the fan
which is not considered a part of the fan is located manufacturer’s certified performance ratings,
between a static pressure measurement plane and draw a performance curve for the fan for
the fan. In order to determine the fan static pressure, operation at the test values of fan speed and
the loss through the damper must be calculated. In entering air density. Determine the fan air flow
these cases, the calculation of the loss is based on rate by entering this curve at the test values of
the performance ratings for the damper. fan static pressure and fan power input (see
Example 5C in Annex A).
17.1 Free inlet, free outlet fans
2) Use the method as described above with the
It is difficult to achieve an accurate field test of a free exception that the performance curve is
inlet, free outlet fan. The most obvious problem is the established by a laboratory test of the fan,
lack of a suitable location for the velocity pressure conducted in accordance with AMCA Standard
measurement plane. In addition, in the case of 210. For the laboratory test, the fan must be set
ventilators that supply or exhaust air from a building- up in a manner that duplicates the field
the most commonly encountered applications of free installation conditions. That is, all appurtenances
inlet, free outlet fans-it is extremely difficult to define, must be in place and any restrictions or
set, and maintain for the duration of the test the obstructions to the free flow of air into the fan
“normal” system condition. Items affecting the system inlet and away from the fan outlet must be
include: accurately duplicated in the laboratory test setup.
18
AMCA 203-90 (R2007)
3) Install a duct on the inlet side of the fan for the Ps = Ps2 + SEF 1 +SEF 2 + ... + SEF n
purpose of providing a location for the velocity
pressure measurement plane. All of the test 17.3 Ducted inlet, ducted outlet fans
measurements and calculations in this method
for testing a free inlet, free outlet fan are the In this type of fan-system configuration, there is no
same as those required for a fan with a ducted special consideration in the calculation of fan static
inlet and a free outlet. The cross-sectional shape pressure. The equation for this calculation is:
and area of the duct, which is temporarily
installed for purposes of the test, should be Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2 + ... + SEF n
selected on the basis of minimizing its
interference with the flow of air into the fan inlet In this configuration, the flow conditions on the inlet
while providing velocity pressure of magnitudes side of the fan are usually more favorable for the
that can be accurately measured. The length of location of the velocity pressure measurement plane.
the duct should be a minimum of twice its
diameter or equivalent diameter, and the 17.4 Ducted inlet, free outlet fans
entrance to the duct should be flared in order to
reduce the entrance loss. The velocity pressure In this type of fan-system configuration, the static
measurement plane should be located a pressure at the fan outlet, Ps2, is zero gauge
minimum of 1.5 diameters or equivalent
pressure, referred to the atmospheric pressure in the
diameters downstream from the duct inlet. The
region of the fan outlet. However, the gas stream may
effect of this duct on the system is negligible, but
be discharging from the fan into a region in which the
in changing the pattern of the flow of air into the
atmospheric pressure is somewhat different from that
fan inlet, it may affect the performance of the fan
to which all other pressure measurements are
slightly. Applications of this method of test are
referred. When this possibility exists, it is essential
presented in Examples 5A and 5B in Annex A.
that the static pressure measurements in the region
The equation for calculating fan static pressure
of the fan outlet be referred to the same atmospheric
for this configuration is:
pressure as used in all other pressure
measurements.
Ps = Ps2 - (Ps1 + Pv1)
Ps = -Ps1 - Pv1 + SEF 1 + SEF 2 + ... + SEF n
17.2 Free inlet, ducted outlet fans
17.5 Air handling units
In the calculation of fan static pressure for this type of
fan-system configuration, the sum of the static
This category consists of draw-through and blow-
pressure at the fan inlet, Ps1, and the velocity
through types of equipment assemblies used in
pressure at the fan inlet, Pv1, is considered to be heating, ventilating, and air-conditioning applications.
equal to the sum of the static pressure, Psx, and the In addition to fans, these equipment assemblies may
velocity pressure, Pvx, at a point sufficiently distant include any number of combinations of coils, filters,
from the fan inlet as to be in still air. At this point, the access sections, humidifiers, mixing boxes, dampers,
static pressure is zero, and the velocity pressure in etc. Air handling units include packaged units, factory
still air is zero. assembled central station units, and built-up units.
The basis used in establishing the air performance
Ps1 + Pv1 = Psx + Pvx = 0 ratings for each of these unit types is described
below. It is important that the field test method
This consideration, which is the same as that used in correspond to the rating method in each case.
the methods for testing fans for performance rating
purposes, charges to the fan the losses incurred in 17.5.1 Packaged units. This type of unit is supplied
accelerating the air into the fan inlet and eliminates and rated by the manufacturer as an assembly. The
inaccuracies which may occur in any attempt to static pressures at the inlet and outlet to the
measure velocity pressure and static pressure at the assembly and the velocity pressure at the inlet to the
fan inlet. Since Ps1 + Pv1 = 0, the equation for assembly are used in calculating the static pressure
calculating fan static pressure for this configuration generated by this type of air handling unit. See
is: Examples 4C and 4D in Annex A.
20
AMCA 203-90 (R2007)
This annex contains examples of field tests. The examples are presented in detail and cover several types of fan-
system combinations. Field test procedures are illustrated in a variety of situations. Portions of the procedures are
typical for all fan-system installations. Other portions of the procedures demonstrate methods for dealing with the
more difficult features encountered in some installations. Not all of the possible fan-system combinations are
included in the examples, but it is expected that the examples will provide sufficient guidance for dealing with those
cases not covered.
5A: Free Inlet, Free Outlet Roof Ventilator with temporary duct
5B: Free Inlet, Free Outlet Propeller Fan with temporary duct
5C: Free Inlet, Free Outlet Roof Ventilator as installed
21
AMCA 203-90 (R2007)
SEF 1
DIFFUSER
3 2
L
A2
VARIABLE
INLET VANES
A3
LOCATIONS OF
PLANES 2 AND 3
ORIENTATION
OF PITOT TUBE
COMMENTS
1. The variable inlet vanes are considered part of the 3. Measure td1 and tw1 in the path of the air flowing
fan. Performance ratings for fans with inlet vanes into the fan inlets. Determine pb for the general
cover operation with the inlet vanes in their full open vicinity of the fan. Measure td3 in Plane 3. All of these
position. In order to be able to compare the test measurements are used in the determination of
results to the fan performance ratings, it is essential densities at the various planes of interest.
that the inlet vanes be fixed in their full open positions
for the duration of the test. 4. Measure the fan speed and the motor amps, volts,
and, if possible, watts. Record all pertinent motor
2. Determine Pv3 by using the root mean square of nameplate data, including volts (NPV) and full load
the velocity pressure measurements made in a amps (FLA). If the motor power output is to be
traverse of Plane 3, located near the end of the fan estimated by using the phase current method
diffuser (evasé). Determine Ps3 by averaging the described in Annex K, it is not necessary to measure
static pressure measurements made in the same motor watts; however, it may be necessary to
traverse. Procedures for the traverse are described in disconnect the drive and measure the no load amps
Section 9.4. These velocity pressure and static (NLA) if the motor is not operating at or near its full
pressure measurements are susceptible to error due load point (refer to Annex K).
to the turbulence existing in the region of the fan
outlet. In addition, it is undesirable to have Plane 3 5. SEF 1 is due to the effect of insufficient length of
located in a diverging airway. However, no other duct at the fan outlet. In order to calculate the value
more suitable location for Plane 3 exists in this of SEF 1, it is necessary to measure the length of the
example. It is recommended that the Pitot-static tube outlet duct, L; the outlet area of the fan, A2; and the
be oriented so that its nose is aligned with the blast area of the fan.
anticipated flow streams, particularly near the walls of
the diffuser, as shown in the diagram. Determine the 6. The sum of the static pressure, Ps1, and velocity
area of the traverse plane, A3, which is located at the pressure, Pv1, at the inlets of a fan with unrestricted
tip of the Pitot-static tube, as shown in the diagram, inlets is considered to be equal to the sum of the
not at the location of the Pitot-static tube access static pressure, Psx, and the velocity pressure, Pvx, at
holes in the diffuser. a point sufficiently distant from the fan inlets as to be
in still air. At this point, the static pressure is zero, and
22
AMCA 203-90 (R2007)
23
AMCA 203-90 (R2007)
V2 = (Q2/A2) Qc = Q
= (57223/11.94) = 58121 cfm
= 4793 fpm Psc = Ps
= 14.97 in. wg
Duct diameter equivalent to the diffuser outlet area: Hc = H
= 178 hp
De2 = 4 A2 / π
= ( 4 × 11.94 ) / π
= 3.9 ft.
= De2 (V2/1000)
= 3.9 (4793/1000)
= 18.7 ft
24
AMCA 203-90 (R2007)
TEMPORARY
DUCT
DIFFUSER
STATIC 3a 3b
PRESSURE TAPS 0.5 De
SILENCERS
A2
SEF 1
COMMENTS
1. This fan, as supplied and rated by the entrances to the inlet boxes (Plane 1). Determine Ps2
manufacturer, includes the variable inlet vanes and by averaging the pressure measurements at each of
inlet boxes, but does not include the silencers. four static pressure taps located near the end of the
Performance ratings for fans with inlet vanes cover fan diffuser (evasé). See Annex E for details of static
operation with the inlet vanes in the full open pressure taps.
positions. In order to be able to compare the test
results to the fan performance ratings, it is essential 4. Measure td3 and tw3 near the inlet ducts. Determine
that the inlet vanes be fixed in their full open positions pb for the general vicinity of the fan. Measure td2 in
for the duration of the test. Plane 2. All of these measurements are used in the
determination of densities at the various planes of
2. Determine Pv3a and Pv3b by using the root mean interest.
square of the velocity pressure measurements made
in traverses of Planes 3a and 3b. A3a and A3b are the 5. Measure the fan speed and the motor amps, volts,
areas traversed. Determine Ps3a and Ps3b by and if possible, watts. Record all pertinent motor
averaging each of the two sets of static pressure nameplate data, including volts (NPV) and amps
measurements made in the same traverses. (FLA). If the motor power output is to be estimated by
Procedures for traverses are described in Section using the phase current method described in Annex
9.4. Ps3a and Ps3b are used in determining the density K, it is not necessary to measure motor watts;
at the traverse plane. A location for Plane 3 however, it may be necessary to disconnect the drive
measurements may be obtained by installing ducts and measure the no load amps (NLA) if the motor is
on each silencer inlet, as shown in the diagram. The not operating at or near its full load point. Refer to
ducts should be a minimum of one equivalent Annex K.
diameter in length, and have flared inlets to reduce
entrance losses and provide more uniform velocity 6. SEF 1 is due to the effect of there being no duct
profiles at the pressure measurement planes. at the fan outlet. In order to calculate the value of
SEF 1, it is necessary to measure the fan outlet area,
3. Measure Ps1a and Ps1b at locations close to the A2, and the blast area of the fan.
entrances to the inlet boxes and in planes which are
substantially equal in area to the planes of the 7. To calculate the fan static pressure:
25
AMCA 203-90 (R2007)
Where: DENSITIES
VIVs in full open positions. Fan direct connected to V3b = 1096 (Pv3b/ρ3)0.5
motor. The motor manufacturer advises that this = 1096 (0.62/0.0712)0.5
motor type has a peak efficiency of 91% at a power = 3234 cfm
factor of approximately 0.89.
Q3b = V3bA3b
= 3234 × 12.5
= 40425 cfm
26
AMCA 203-90 (R2007)
Annex K indicates that Equation A will provide a For a blast area ratio of 0.75, and no duct, Figure 8.3
reasonably accurate estimate of motor power output shows System Effect Curve T applies. For 4418 fpm
for a 250 hp motor operating at 90% FLA. velocity and curve T, Figure 7.1 shows SEF 1 = 0.65
in. wg at 0.075 lbm/ft3. At 0.0720 lbm/ft3:
Hmo = 250 (257/285) (460/460)
= 225 hp SEF 1 = 0.65 (0.0721/0.075)
= 0.62 in. wg
As a check of this value, using the motor efficiency
data and the appropriate equation in Section 11.2.2: FAN STATIC PRESSURE
Since the fan is direct-connected to the motor, there Psc = 11.33 (0.075/0.0711)
is no drive loss, and: = 11.95 in. wg
27
AMCA 203-90 (R2007)
TEMPORARY
PLANE 3
SHORT DUCT
LOCATION
3 STATIC PRESSURE TAPS
SILENCER
TRANSITION
0.5 De 5
DIFFUSER
INLET SECTION 2
BOX INNER
1 CYLINDER
SIDE VIEW L
GUIDE VANES
COMMENTS
1. This is a variable pitch axial flow fan. The fan See Annex E for details of static pressure taps. In this
assembly, as supplied and rated by the manufacturer, example, Ps2 is considered to be equal to Ps5.
includes the inlet box and diffuser section, but does
not include the silencer. It is essential that the blade 4. Measure td3 and tw3 near the entrance to the short
pitch angle be fixed for the duration of the test. This inlet duct. Determine pb for the general vicinity of the
blade angle should be agreed upon by all interested fan. Measure td5 in Plane 5. All of these
parties. measurements are used in the determination of
densities at the various planes of interest.
2. A temporary short duct is installed upstream of the
silencer to establish Plane 3 in which more uniform 5. Measure the fan speed and the motor amps, volts,
pressures can be obtained. The duct should be a and if possible, watts. Record all pertinent motor
minimum of one equivalent diameter in length, and nameplate data, including volts (NPV) and full load
have a flared inlet to reduce entrance losses and amps (FLA). If the motor power output is to be
provide a more uniform velocity profile at the estimated by using the phase current method
pressure measurement plane. Determine Pv3 by described in Annex K, it is not necessary to measure
using the root mean square of the velocity pressure motor watts; however, it may be necessary to
measurements made in a traverse of Plane 3. Ps3 is disconnect the drive and measure the no load amps
determined by averaging the static pressure (NLA) if the motor is not operating at or near its full
measurements made in the same traverse. load point. Motor performance data, supplied by the
Procedures for traverses are described in Section motor manufacturer, are used in the determination of
9.4. Ps3 is used in determining the density at the motor power output for this example.
traverse plane.
6. SEF 1 is due to the effect of insufficient length of
3. Measure Ps1 at a location close to the entrance to duct between the diffuser outlet and the elbow
the inlet box and in a plane which is substantially downstream of the diffuser. In order to calculate the
equal in area to the plane of the entrance to the inlet value of SEF 1, it is necessary to measure the length
box (Plane 1). Determine Ps5 by averaging the of the transition, L, and the outlet area of the diffuser,
pressure measurements at each of four static A2.
pressure taps located near the end of the fan diffuser.
28
AMCA 203-90 (R2007)
29
AMCA 203-90 (R2007)
Since the fan is direct connected to the motor, there Ps2 = Ps5
is no drive loss, and: = 20.8 in. wg
30
AMCA 203-90 (R2007)
OUTLET DAMPER
SEF 1
PLENUM
COMMENTS
1. Each of the fans, as supplied and rated by the between the outlet damper and the plenum. See
manufacturer, includes an outlet damper. Annex E for details of static pressure taps. Measure
Performance ratings for fans with outlet dampers td2 in Plane 2 for each fan.
cover operation with the outlet damper in the full
open position. In order to be able to compare the test 4. For each fan, measure td1 and tw1 in the path of the
results to the fan performance ratings it is essential air flowing into the fan inlet. Determine pb for the
that the outlet dampers be fixed in the full open general vicinity of the fans. Measure td3 in Plane 3. All
positions for the duration of the test. of these measurements are used in the determination
of densities at the various planes of interest.
2. In this example, there are no suitable locations for
traverse planes for use in determining directly the 5. Measure the fan speed and the motor amps, volts,
flow rate for each fan. The alternative is to determine and if possible, watts for each fan. Record all
the total flow rate and since the fans and their pertinent motor nameplate data, including volts
operating speeds are alike, assume that each fan (NPV) and full load amps (FLA). If the motor power
delivers a flow rate proportional to its actual speed. outputs are to be estimated by using the phase
Determine Pv3 by using the root mean square of the current method described in Annex K, it is not
velocity pressure measurements made in a traverse necessary to measure motor watts; however, it may
of Plane 3, located near the end of a straight run of be necessary to disconnect the drives and measure
duct, such as shown in the diagram. Determine Ps3 by the no load amps (NLA) if the motors are not
averaging the static pressure measurements made in operating at or near their full load points. Refer to
the same traverse. Procedures for traverses are Annex K.
described in Section 9.4. Ps3 is used in determining
the density at the traverse plane. Measure the area of 6. SEF 1 is due to the effect of insufficient length of
traverse plane, A3, which is located at the tip of the duct between the outlet of each fan and the plenum.
Pitot-static tube. In this case, the duct length is so short as to be
judged equivalent to there being no duct at all. In
3. Determine Ps2 for each fan by averaging the order to calculate the value of SEF 1, it is necessary
pressure measurements at each of four static to measure the outlet areas of the fans, A2, and their
pressure taps located in the short length of duct blast areas.
31
AMCA 203-90 (R2007)
RH Fan
8. In order to compare the test results to the quoted
25 hp, 3 phase, 60 hertz
fan curve drawn for operation at 1900 rpm and 0.075
575 volts, 1780 rpm, 23 FLA
lbm/ft3 density, it is necessary to convert the results
to the specified conditions. The basis for the
GENERAL
calculations is described in Section 14.
Outlet dampers in full open positions. Fans
OBSERVATIONS
connected to motors through belt drives.
SITE MEASUREMENTS
CALCULATIONS
pb = 29.05 in. Hg
DENSITIES
td3 = 78°F
Ps3 = 5.6 in. wg For inlet conditions for both fans of:
Pv3 = 0.47 in. wg
A3 = 7.4 ft2 td1 = 75°F
tw1 = 57°F
LH Fan p1 = pb
td1 = 75°F = 29.05 in. Hg
tw1 = 57°F
td2 = 79°F Use Figure N.1 in Annex N to obtain ρ1 = 0.0718
Ps2 = 6.4 in. wg lbm/ft3
N = 1910 rpm, LH fan speed
A2 = 3.2 ft2 The density at Plane 2:
Blast Area = 2.25 ft2
RH Fan
td1 = 75°F
tw1 = 57°F
td2 = 79°F
32
AMCA 203-90 (R2007)
Q = Q1 LH Motor
= Q3 (ρ3/ρ1) HL = 0.05 Hmo
= 20661 (0.0724/0.0718) = 0.05 × 16.66
= 20834 cfm = 0.83 hp
Assume that the air flow rate for each fan is H = Hmo - HL
proportional to its speed. = 16.66 - 0.83
= 15.83 hp
LH Fan
Q = Q1 RH Motor
= 20834 [1910/(1910 + 1890)] HL = 0.05 Hmo
= 10472 cfm = 0.05 × 15.31
= 0.77 hp
RH Fan H = Hmo - HL
Q = Q1 = 15.31 - 0.77
= 20834 [1890/(1910 + 1890)] = 14.54 hp
= 10362 cfm
SYSTEM EFFECT FACTOR
FAN POWER INPUT
AMCA Publication 201-90, Figures 7.1 and 8.3
LH Fan indicate the following calculations:
Measured amps/FLA = (16.7/23)
= 0.73 LH Fan
= 73% Q2 = Q1 (ρ1/ρ2)
= 10472 (0.0718/0.0724)
RH Fan = 10385 cfm
Measured amps/FLA = (15.7/23)
= 0.68 V2 = (Q2/A2)
= 68% = (10385/3.2)
= 3245 fpm
33
AMCA 203-90 (R2007)
Ps = Ps2 + SEF 1
LH Fan
Ps = 6.4 + 0.48
= 6.88 in. wg
RH Fan
Ps = 6.4 + 0.48
= 6.88 in. wg
34
AMCA 203-90 (R2007)
PLAN VIEW 2
3-PIECE
ELBOW
R/D = 1
SEF 1
SEF 2
L
SIDE VIEW OUTLET SIDE VIEW
COMMENTS
1. Determine Pv3 by using the root mean square of described in Annex K, it is not necessary to measure
the velocity pressure measurements made in a motor watts; however, it may be necessary to
traverse of Plane 3, located near the end of a straight disconnect the drive and measure the no load amps
run of duct, such as shown in the diagram. Determine (NLA) if the motor is not operating at or near its full
Ps3 by averaging the static pressure measurements load point. Refer to Annex K.
made in the same traverse. Procedures for traverses
are described in Section 9.4. Ps3 is used in 5. SEF 1 is due to the effect of the elbow located at
determining the density at the traverse plane. the fan inlet. SEF 2 is due to the effect of insufficient
Measure the area of the traverse plane, A3, which is length of duct between the fan outlet and the elbow
located at the tip of the Pitot-static tube. downstream of the fan. In order to calculate the
values of the SEFs, it is necessary to measure the
2. Determine Ps1 by averaging the pressure inlet area and the outlet area of the fan, A1 and A2;
measurements at each of four static pressure taps in the length of the outlet duct, L; and the blast area of
the collar connection at the fan inlet. Determine Ps2 the fan.
by averaging the pressure measurements at each of
6. To calculate the Fan Static Pressure:
four static pressure taps located near the fan outlet.
Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2
3. Measure td3 and tw3 in the traverse plane. Assume
td1 is equal to td3. Determine pb for the general vicinity
Where:
of the fan. Measure td2 in Plane 2. All of these
measurements are used in determining densities at
Pv1 = Pv3 (A3/A1)2 (ρ3/ρ1)
the various planes of interest.
7. In order to compare the test results to the quoted
4. Measure the fan speed and the motor amps, volts,
fan curve drawn for operation at 1880 rpm and 0.075
and if possible, watts. Record all pertinent motor
nameplate data, including volts (NPV) and full load lbm/ft3 density, it is necessary to convert the results
amps (FLA). If the motor power output is to be to the specified conditions. The basis for the
estimated by using the phase current method calculations is described in Section 14.
35
AMCA 203-90 (R2007)
SITE MEASUREMENTS
⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
ρ1 = ρ3 ⎜ s1 ⎟⎜ ⎟
pb = 29.20 in. Hg ⎝ 13.6 p3 ⎠ ⎝ t d1 + 460 ⎠
td2 = 72°F ⎛ −2.18 + 13.6 × 29.20 ⎞ ⎛ 532 ⎞
= 0.0719 ⎜ ⎟ ⎜ 532 ⎟
td3 = 72°F ⎝ 13.6 × 29.06 ⎠⎝ ⎠
tw3 = 66°F = 0.0718 lbm/ft 3
Ps1 = -2.18 in. wg
Ps2 = 0.35 in. wg
The density at Plane 2:
Ps3 = -1.95 in. wg
Pv3 = 0.45 in. wg
N = 1730 rpm ⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
ρ2 = ρ3 ⎜ s2 ⎟⎜ ⎟
A1 = 1.07 ft2 ⎝ 13.6 p3 ⎠ ⎝ t d2 + 460 ⎠
A2 = 1.17 ft2 ⎛ 0.35 + 13.6 × 29.20 ⎞ ⎛ 532 ⎞
= 0.0719 ⎜ ⎟ ⎜ 532 ⎟
A3 = 1.07 ft2 ⎝ 13.6 × 29.06 ⎠⎝ ⎠
Blast Area = 0.7 ft2 = 0.0723 lbm/ft 3
L = 0.83 ft
For Plane 3 conditions of: Annex K indicates that the average of the results of
Equation A and Equation B will provide a reasonably
td3 = 72°F accurate estimate of motor power output for a 5 hp
tw3 = 66°F motor operating at 74% FLA.
36
AMCA 203-90 (R2007)
Figure L.1 in Annex L indicates estimated belt drive L in % effective duct length
loss of 6.5%.
= (L/3.05) 100
HL = 0.065 Hmo = (0.83/3.05) 100
= 0.065 × 2.98 = 27%
= 0.19 hp
Blast area ratio = Blast Area/A2
H = Hmo - HL = 0.7/1.17
= 2.98 - 0.19 = 0.6
= 2.79 hp
For blast area ratio of 0.6, 27% effective duct length
SYSTEM EFFECT FACTORS and elbow position C, Figure 8.5 shows System
Effect Curve P - Q applies. For 2494 fpm velocity and
To determine the value of SEF 1, calculate the curve P - Q, Figure 7.1 shows SEF 2 = 0.7 in. wg at
velocity at the fan inlet: 0.075 lbm/ft3. At 0.0723 lbm/ft3:
De2 = (4A2/π)0.5
= (4 × 1.17/π)0.5
= 1.22 ft
= 2.5 × 1.22
= 3.05 ft
37
AMCA 203-90 (R2007)
SEF 2 2
1
SEF 1
4-PIECE ELBOW
R/D = 1
L2
L1
COMMENTS
1. Determine Pv3 by using the root mean square of atmospheric pressure as used in all other pressure
the velocity pressure measurements made in a measurements. In this case, the pressure was
traverse of Plane 3, located near the end of a straight measured as 0.1 in. wg.
run of duct, such as shown in the diagram. Determine
Ps3 by averaging the static pressure measurements 3. Measure td3 and tw3 in the traverse plane.
made in the same traverse. Procedures for traverses Determine pb for the general vicinity of the fan.
are described in Section 9.4. Ps3 is used in Measure td1 and td2. All of these measurements are
determining the density at the traverse plane. used in determining densities at the various planes of
Measure the area of the traverse plane, A3, which is interest.
located at the tip of the Pitot-static tube.
4. Measure the fan speed and the motor amps, volts,
2. Determine Ps1 by using a Pitot-static tube or static and if possible, watts. Record all pertinent motor
pressure taps in the duct connection at the fan inlet. nameplate data, including volts (NPV) and full load
If a Pitot-static tube is used, it should not project into amps (FLA). If the motor power output is to be
the upstream elbow but be located well within the estimated by using the phase current method
length of the duct connection as shown in the described in Annex K, it is not necessary to measure
diagram. The friction loss in the short length of outlet motor watts; however, it may be necessary to
duct is assumed to be negligible, and Ps2 is disconnect the drive and measure the no load amps
considered to be equal to the static pressure at the (NLA) if the motor is not operating at or near its full
duct outlet. The static pressure at the outlet of the load point. Refer to Annex K.
duct is zero gauge pressure, referred to the
atmospheric pressure in the region of the duct outlet. 5. SEF 1 is due to the effect of insufficient length of
In situations such as this example, the air may be duct between the fan inlet and the elbow upstream of
discharging from the duct into a region in which the the fan. SEF 2 is due to the effect of insufficient
atmospheric pressure is somewhat different from that length of duct at the fan outlet. In order to calculate
to which all other pressure measurements are the values of the SEFs, it is necessary to measure
referred. When this possibility exists, it is essential the inlet area and the outlet area of the fan, A1 and
that the static pressure in the region of the A2; the lengths of the inlet connection and the outlet
discharging air be measured, referred to the same duct, L1 and L2; and the blast area of the fan.
38
AMCA 203-90 (R2007)
pb = 29.82 in. Hg
⎛ P + 13.6 pb ⎞ ⎛ t d2 + 460 ⎞
td1 = 86.6°F ρ1 = ρ2 ⎜ s1 ⎟⎜ ⎟
td2 = 91.3°F ⎝ 13.6 p2 ⎠ ⎝ t d1 + 460 ⎠
tw2 = 70.4°F ⎛ −11.4
4 + 13.6 × 29.82 ⎞ ⎛ 551.3 ⎞
= 0.0714 ⎜ ⎟ ⎜ 546.6 ⎟
td3 = 86°F ⎝ 13.6 × 29.83 ⎠⎝ ⎠
Ps1 = -11.4 in. wg = 0.0700 lbm/ft 3
Ps2 = 0.1 in. wg
Ps3 = -8.9 in. wg
The density at Plane 3:
Pv3 = 1.24 in. wg
N = 2120 rpm, fan speed
A1 = 1.40 ft2 ⎛ P + 13.6 pb ⎞ ⎛ t d2 + 460 ⎞
ρ3 = ρ2 ⎜ s3 ⎟⎜ ⎟
A2 = 1.40 ft2 ⎝ 13.6 p3 ⎠ ⎝ t d3 + 460 ⎠
A3 = 1.57 ft2 ⎛ −8.9 + 13.6 × 29.82 ⎞ ⎛ 551.3 ⎞
= 0.0714 ⎜ ⎟ ⎜ 546 ⎟
⎝ 13.6 × 29.83 ⎠⎝ ⎠
Blast Area = 1.26 ft2 = 0.0705 lbm/ft 3
L1 = 1.33 ft
L2 = 3.0 ft
FLOW RATES
MEASURED MOTOR DATA
V3 = 1096 (Pv3/ρ3)0.5
Volts = 460, 460, 459 = 1096 (1.24/0.0705)0.5
= 460 av = 4596 fpm
Amps = 26.5, 25.5, 26
= 26 av Q3 = V3A3
NLA = 11.3 = 4596 × 1.57
= 7216 cfm
MOTOR NAMEPLATE DATA
Q = Q1
30 hp, 3 phase, 60 hertz = Q3 (ρ3/ρ1)
460 volts, 1750 rpm, 36 FLA = 7216 (0.0705/0.0700)
= 7268 cfm
GENERAL
FAN POWER INPUT
Fan connected to motor through belt drive.
Measured amps/FLA = (26/36)
= 0.72
= 72%
39
AMCA 203-90 (R2007)
Annex K indicates that the average of the results of For SEF 2, AMCA Publication 201-90, Figure 8.3
Equation A and Equation B will provide a reasonably indicates the following calculations:
accurate estimate of motor power output for a 30 hp
motor operating at 72% FLA. Q2 = Q3 (ρ3/ρ2)
= 7216 (0.0705/0.0714)
Eqn A = 30 (26/36) (460/460) = 7125 cfm
= 21.67 hp
V2 = (Q2/A2)
Eqn B = 30 [(26 - 11.3)/(36 - 11.3)] (460/460) = (7125/1.40)
= 17.85 hp = 5089 fpm
Hmo = (21.67 + 17.85)/2 Duct diameter equivalent to the fan outlet area:
= 19.76 hp
De2 = (4A2/π)0.5
Figure L.1 in Annex L indicates estimated belt drive = (4 × 1.40/π)0.5
loss of 4.8%. = 1.34 ft
HL = 0.048 Hmo Figure 8.3 shows that for velocities over 2500 fpm,
= 0.048 × 19.76 100% effective duct length is one duct diameter per
= 0.95 hp 1000 fpm:
H = Hmo - HL = D2 (V2/1000)
= 19.76 - 0.95 = 1.34 (5089/1000)
= 18.81 hp = 6.82 ft
SYSTEM EFFECT FACTORS The length of the outlet duct in % effective duct
length:
To determine the value of SEF 1, calculate the
velocity at the fan inlet: = (L2/6.82) 100
= (3.0/6.82) 100
V1 = (Q1/A1) = 44%
= (7268/1.40)
= 5191 fpm Blast ratio area = Blast Area/A2
= 1.26/1.40
The diameter of the fan inlet: = 0.9
D1 = (4A1/π)0.5 For blast area ratio of 0.9 and 44% effective duct
= (4 × 1.40/π)0.5 length, Figure 8.3 shows no System Effect Curve
= 1.34 ft. applies and SEF 2 = 0.
The length of the duct between the elbow and the fan FAN STATIC PRESSURE
inlet in terms of D1:
Pv1 = Pv3 (A3/A1)2 (ρ3/ρ1)
= (L1/D1) = 1.24 (1.57/1.40)2 (0.0705/0.0700)
= (1.33/1.34) = 1.57 in. wg
= 1.0
Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2
AMCA Publication 201-90, Figure 9.5 indicates that = 0.1 - (-11.4) - 1.57 + 1.2 + 0
for a four piece elbow with a radius to diameter ratio = 11.13 in. wg
of 1, and with a length of duct between the elbow and
the fan inlet equal to 1 equivalent diameter, System CONVERSIONS TO SPECIFIED CONDITIONS
Effect Curve S applies. For 5191 fpm velocity and
curve S, Figure 7.1 shows SEF 1 = 1.3 in. wg at Qc = 7268 (2075/2120)
0.075 lbm/ft3. At 0.0700 lbm/ft3: = 7114 cfm
40
AMCA 203-90 (R2007)
41
AMCA 203-90 (R2007)
4 5 STRAIGHTENING VANES
2 3
1
SEF 2 STATIC PRESSURE TAPS
A3
PLAN VIEW
SEF 1
INNER CYLINDER
LOCATION OF PLANE 3
SIDE VIEW
COMMENTS
1. This type of installation is normally classified as located at the tip of the Pitot-static tube, as shown in
one in which a satisfactory test cannot be conducted. the diagram, not at the location of the Pitot-static tube
Due to the configurations of the airways, there are no access holes.
locations at which reasonably accurate pressure
measurements can be made. In addition, the 3. Determine Ps4 by averaging the pressure
judgments required in determining the values of the measurements at each of four static pressure taps
SEFs are susceptible to error. The purpose of located near the fan inlet. In the same manner,
presenting this example is to illustrate the not determine Ps5 at a location near the fan outlet. It is
uncommon instance in which a test must be conducted undesirable to have pressure measurement planes
in order to provide performance information, even located in converging and diverging airways, but
though the results will be innaccurate to a degree there are no other more suitable locations for these
which is not normally acceptable. planes in this installation. Measure A4 and A5, the
cross-sectional areas of the airways at Planes 4 and 5.
2. Determine Pv3 by using the root mean square of
the velocity pressure measurements made in a 4. Measure td3, tw3, and td4. Determine pb for the
traverse of Plane 3, located as shown in the diagram. general vicinity of the fan. These measurements are
Determine Ps3 by averaging the static pressure used in the determination of densities at the various
measurements made in the same traverse. planes of interest.
Procedures for traverses are described in Section
9.4. These velocity pressure and static pressure 5. Measure the fan speed and the motor amps, volts,
measurements are susceptible to error due to the and if possible, watts. Record all pertinent motor
turbulence existing in the region of the fan outlet. In nameplate data, including volts (NPV) and full load
addition, it is undesirable to have Plane 3 located in amps (FLA). If the motor power output is to be
a diverging airway. However, no other more suitable estimated by using the phase current method
location for Plane 3 exists in this example. It is described in Annex K, it is not necessary to measure
recommended that the Pitot-static tube be oriented motor watts; however, it may be necessary to
so that its nose is aligned with the anticipated flow disconnect the drive and measure the no load amps
streams, particularly near the walls of the diffuser. (NLA) if the motor is not operating at or near its full
Determine the area of the traverse plane, A3, which is load point. Refer to Annex K.
42
AMCA 203-90 (R2007)
43
AMCA 203-90 (R2007)
Annex K indicates that the average of the results of Pv1 = Pv3 (A3/A1)2 (ρ3/ρ1)
Equation A and Equation B will provide a reasonably
accurate estimate of motor power output for a 25 hp = 0.044 (29.8/8.0)2 (0.0694/0.0691)
motor operating at 80% FLA. = 0.61 in. wg
Figure L.1 in Annex L indicates estimated belt drive Pv2 = Pv3 (A3/A2)2 (ρ3/ρ2)
loss of 4.9%. = 0.044 (29.8/8.0)2 (0.0694/0.0694)
= 0.61 in. wg
HL = 0.049 Hmo
= 0.049 × 18.46 Ps2 + Pv2 = Ps5 + Pv5
= 0.90 hp Ps2 = Ps5 + Pv5 - Pv2
= 1.22 + 0.42 - 0.61
H = Hmo - HL = 1.03 in. wg
= 18.46 - 0.90 Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2
= 17.56 hp = 1.03 - (-1.92) - 0.61 + 0 + 0.24
= 2.58 in. wg
SYSTEM EFFECT FACTORS
Losses between Planes 1 and 4 and between Planes
SEF 1 = 0 See item 6 under COMMENTS. 2 and 5 have been ignored.
To determine the value of SEF 2, AMCA Publication CONVERSION TO SPECIFIED CONDITIONS
201-90, Figure 8.2 indicates that a vaneaxial fan with
no outlet duct will use System Effect Curve U. Qc = 26128 (1580/1590)
= 25964 cfm
Q2 = Q3 (ρ3/ρ2)
= 26015 (0.0694/0.0694)
Psc = 2.58 (1580/1590)2 (0.0690/0.0691)
= 26015 cfm
= 2.54 in. wg
V2 = (Q2/A2)
Hc = 17.56 (1580/1590)3 (0.0690/0.0691)
= (26015/8.0)
= 3252 fpm = 17.21 hp
44
AMCA 203-90 (R2007)
SEF 1
3
1
L
INLET BOX
DIFFUSER
COMMENTS
1. This fan, as supplied and rated by the 5. Measure the fan speed and the motor amps, volts,
manufacturer, includes the inlet box damper and the and if possible, watts. Record all pertinent motor
inlet box. Performance ratings for fans with inlet box nameplate data, including volts (NPV), and full load
dampers cover operation with the dampers in the full amps (FLA). If the motor power output is to be
open positions. In order to be able to compare the estimated by using the phase current method
test results to the fan performance ratings, it is described in Annex K, it is not necessary to measure
essential that the damper be fixed in the full open motor watts; however, it may be necessary to
position for the duration of the test. disconnect the drive and measure the no load amps
(NLA) if the motor is not operating at or near its full
2. Determine Pv3 by using the root mean square of load point. Refer to Annex K.
the velocity pressure measurements made in a
traverse of Plane 3, located shortly upstream of the 6. SEF 1 is due to the effect of insufficient length of
inlet damper. Determine Ps3 by averaging the static duct at the fan outlet. In order to calculate the value
pressure measurements made in the same traverse. of SEF 1, it is necessary to measure the length of the
Procedures for traverses are described in Section outlet duct, L; the fan outlet area, A2; and the blast
9.4. Measure A3, the area of the traverse plane, area of the fan.
located at the tip of the Pitot-static tube and A1, the
area of the inlet to the damper. 7. To calculate the Fan Static Pressure:
45
AMCA 203-90 (R2007)
For Plane 3 conditions of: Annex K indicates that the average of the results of
Equation A and Equation B will provide a reasonably
td3 = 63°F accurate estimate of motor power output for a 500 hp
tw3 = 62°F motor operating at 84% FLA.
46
AMCA 203-90 (R2007)
Since the fan is direct-connected to the motor, there Blast area ratio = Blast Area/A2
is no drive loss, and: = 1.89/5.32
= 0.36
H = Hmo
= 405 hp For a blast area ratio of 0.36, and 25% effective duct
length, Figure 8.3 shows System Effect Curve U
SYSTEM EFFECT FACTOR applies. For 3802 fpm velocity and curve U, Figure
7.1 shows SEF 1 = 0.36 in. wg at 0.075 lbm/ft3. At
AMCA Publication 201-90, Figures 7.1 and 8.3 0.0696 lbm/ft3:
indicate the following calculations.
SEF 1 = 0.36 (0.0696/0.075)
Q2 = Q3 (ρ3/ρ2) = 0.33 in. wg
= 23075 (0.0610/0.0696)
= 20224 cfm FAN STATIC PRESSURE
Figure 8.3 shows that for velocities over 2500 fpm Qc = 23075 (1780/1790)
100% effective duct length is one duct diameter for = 22946 cfm
every 1000 fpm:
Psc = 71.0 (1780/1790)2 (0.059/0.0610)
= De2 (V2/1000) = 67.9 in. wg
= 2.60 (3802/1000)
= 9.89 ft. Hc = 405 (1780/1790)3 (0.059/0.0610)
= 385 hp
L in % effective duct length:
= (L/9.89) 100
= (2.50/9.89) 100
= 25%
47
AMCA 203-90 (R2007)
INLET BOXES
INLET BOX 1a 1b
DAMPERS 3a 3b
COMMENTS
1. This fan, as supplied and rated by the 4. Measure td3a, td3b, and td5. Since flue gas is being
manufacturer, includes the inlet box dampers and the handled by the fan, the Orsat apparatus is used by
inlet boxes, but does not include the outlet damper. process personnel to determine the density of the
Performance ratings for fans with inlet box dampers gas. Determine pb for the general vicinity of the fan.
cover operation with the dampers in the full open These data are used in the determination of densities
positions. Also, performance ratings for items such as at the various planes of interest.
the outlet damper are for operation in the full open
position. In order to be able to compare the test 5. Measure the fan speed and the motor amps, volts,
results to the fan performance ratings, it is essential and if possible, watts. Record all pertinent motor
that the outlet damper and the inlet dampers be fixed nameplate data, including volts (NPV) and full load
in their full open positions. amps (FLA). If the motor power output is to be
estimated by using the phase current method
2. Determine Pv3a and Pv3b by using the root mean described in Annex K, it is not necessary to measure
square of the velocity pressure measurements made motor watts; however, it may be necessary to
in Planes 3a and 3b. Determine Ps3a and Ps3b by disconnect the drive and measure the no load amps
averaging each of the two sets of static pressure (NLA) if the motor is not operating at or near its full
measurements made in the same traverses. load point. Motor performance data, supplied by the
Procedures for traverses are described in Section motor manufacturer, are used in the determination of
9.4. Measure A3a and A3b, the areas of the traverse motor power output for this example.
planes and A1a and A1b, the areas of the inlets to the
inlet dampers. 6. In this example, the duct downstream of the outlet
damper is of sufficient length, and no SEF applies.
3. Determine Ps5 by averaging the pressure
measurements of each of four static pressure taps 7. To calculate the Fan Static Pressure:
located downstream of the outlet damper.
Ps = Ps2 - Ps1 - Pv1
48
AMCA 203-90 (R2007)
Pv1 is calculated using the total flow rate and the total CALCULATIONS
area at the inlets to the inlet dampers.
DENSITIES
Pv1 = (Q1/1096A1)2 ρ1
The densities at Planes 3a and 3b are:
8. In order to compare the test results to the quoted
fan curve drawn for operation at 880 rpm and 0.049 ⎛ P + 13.6 pb ⎞ ⎛ 70 + 460 ⎞
ρ3a = 0.0725 ⎜ s3a ⎟⎜ ⎟
lbm/ft3 density, it is necessary to convert the results ⎝ 13.6 × 29.92 ⎠ ⎝ t d3a + 460 ⎠
to the specified conditions. The basis for calculations ⎛ −18.8 + 13.6 × 30.12 ⎞ ⎛ 530 ⎞
is described in Section 14. = 0.0725 ⎜ ⎟ ⎜ 805 ⎟
⎝ 13.6 × 29.92 ⎠⎝ ⎠
OBSERVATIONS = 0.0458 lbm/ft 3
SITE MEASUREMENTS
⎛ P + 13.6 pb ⎞ ⎛ 70 + 460 ⎞
ρ3b = 0.0725 ⎜ s3b ⎟⎜ ⎟
pb = 30.12 in. Hg ⎝ 13.6 × 29.92 ⎠ ⎝ t d3b + 460 ⎠
td3a= 345°F ⎛ −18.3 + 13.6 × 30.12 ⎞ ⎛ 530 ⎞
td3b= 359°F = 0.0725 ⎜ ⎟ ⎜ 819 ⎟
⎝ 13.6 × 29.92 ⎠⎝ ⎠
td5 = 363°F
= 0.0451 lbm/ft 3
Ps3a= -18.8 in. wg
Ps3b= -18.3 in. wg
Pv3a= 2.053 in. wg It is assumed that ρ1a = ρ3a and ρ1b = ρ3b.
Pv3b= 2.028 in. wg
The density at Plane 5:
Ps5 = -1.6 in. wg
N = 892 rpm
A1a = A1b ⎛ P + 13.6 pb ⎞ ⎛ 70 + 460 ⎞
ρ5 = 0.0725 ⎜ s5 ⎟⎜ ⎟
= 60.7 ft2 ⎝ 13.6 × 29.92 ⎠ ⎝ t d5 + 460 ⎠
A2 = 115 ft2 ⎛ −1.6 + 13.6 × 30.12 ⎞ ⎛ 530 ⎞
A3a = A3b = 0.0725 ⎜ ⎟ ⎜ 823 ⎟
⎝ 13.6 × 29.92 ⎠⎝ ⎠
= 60.7 ft2
= 0.0468 lbm/fft 3
A5 = 140 ft2
Blast Area = 80 ft2
It is assumed that ρ2 = ρ5.
The density of the gas, as determined by Orsat
analysis, is 0.0725 lbm/ft3 at 29.92 in. Hg and 70°F. FLOW RATES
Q = Q1 Ps1 = Ps3
= Q3 (ρ3/ρ1) = (Ps3a + Ps3b)/2
= 891501 (0.0455/0.0455) = (-18.8 - 18.3)/2
= 891501 cfm = -18.55 in. wg
The data supplied by the motor manufacturer indicate Hc = 3174 (880/892)3 (0.049/0.0455)
motor efficiency of 94% at the measured power input = 3282 hp
of 2519 kW. Using this information:
H = Hmo
= 3174 hp
50
AMCA 203-90 (R2007)
4 5
SEF 1
2-PIECE ELBOW
(TYPICAL)
INNER SEF 2
L1 L2
CYLINDER
1 2
COMMENTS
1. The unusual duct arrangement in this example 4. Measure td3 and tw3 in the traverse plane.
makes it very difficult to obtain accurate pressure Determine pb for the general vicinity of the fan.
measurements, and this fact should be understood Measure td4. These measurements are used in
before testing begins. Also, the use of a diverging determining densities at the various planes of
inlet fitting and a converging outlet fitting with this fan interest.
can pose additional problems. Unless the degrees of
divergence and convergence are moderate, as they 5. Measure the fan speed, motor amps, volts, and if
are in this example, the fan performance will be possible, watts. Record all pertinent motor nameplate
adversely affected. data, including volts (NPV) and full load amps (FLA).
If the motor power output is to be estimated by using
2. Determine Pv3 by using the root mean square of the phase current method described in Annex K, it is
the velocity pressure measurements made in a not necessary to measure motor watts; however, it
traverse of Plane 3, located well downstream in a may be necessary to disconnect the drive and
straight run of duct, such as shown in the diagram. measure the no load amps (NLA) if the motor is not
Determine Ps3 by averaging the static pressure operating at or near its full load point. Motor
measurements made in the same traverse. performance data, supplied by the motor
Procedures for traverses are described in Section manufacturer, are used in the determination of motor
9.4. Ps3 is used in determining the density at the power output for this example.
traverse plane. Measure the area of the traverse
plane, A3. 6. SEF 1 is due to the effect of insufficient length of
duct between the fan inlet and the elbow upstream of
3. Determine Ps5 by averaging the pressure the fan. SEF 2 is due to the effect of insufficient
measurements at each of four static pressure taps length of duct between the fan outlet and the elbow
located near the end of the duct connection at the fan downstream of the fan. In order to calculate the
outlet. Determine Ps4 by using static pressure taps in values of the SEFs, it is necessary to measure the
the duct connection at the fan inlet. Measure A4 and inlet area and the outlet area of the fan, A1 and A2;
A5, the cross-sectional areas of the duct connections and the lengths of the inlet and outlet duct
at the static pressure taps. connections, L1 and L2.
51
AMCA 203-90 (R2007)
7. To calculate the Fan Static Pressure: 460 volts, 1760 rpm, 24.6 FLA
52
AMCA 203-90 (R2007)
Hmo = (18.0 × 0.875)/0.746 Figure 8.1 shows that for velocities of 2500 fpm or
= 21.1 hp less, the 100% effective duct length is 2.5 diameters:
Since the fan is direct connected to the motor, there = 2.5 × 3.01
is no drive loss, and: = 7.53 ft
AMCA Publication 201-90, Figure 9.2 indicates that Ps2 + Pv2 = Ps5 + Pv5
for a two piece elbow with a length of duct between Ps2 = Ps5 + Pv5 - Pv2
the elbow and the fan inlet equal to 1.00 diameter = 0.82 + 0.783 - 0.37
System Effect Curve S-T applies. For a velocity of = 1.23 in. wg
2482 fpm and curve S-T, Figure 7.1 shows SEF 1 =
0.25 in. wg at 0.075 lbm/ft3. At 0.0729 lbm/ft3: Pv4 = Pv3 (A3/A4)2 (ρ3/ρ4)
SEF 1 = 0.25 (0.0729/0.075) = 0.783 (4.91/6.2)2 (0.0728/0.0729)
= 0.24 in. wg = 0.49 in. wg
For SEF 2, AMCA Publication 201-90, Figures 7.1, Pv1 = Pv3 (A3/A1)2 (ρ3/ρ1)
8.1, and 8.4 indicate the following calculations: = 0.783 (4.91/7.1)2 (0.0728/0.0729)
= 0.37 in. wg
Q2 = Q3 (ρ3/ρ2)
= 17647 (0.0728/0.0728) Ps1 + Pv1 = Ps4 + Pv4
= 17647 cfm Ps1 = Ps4 + Pv4 - Pv1
= -1.1 + 0.49 - 0.37
V2 = Q2/A2 = -0.98 in. wg
= 17647/7.1
= 2485 fpm
53
AMCA 203-90 (R2007)
Qc = 17623 (1750/1760)
= 17523 cfm
54
AMCA 203-90 (R2007)
2b
STATIC PRESSURE TAPS
1b
2a FAN B
1a
DAMPER
SIDE VIEW
COMMENTS
1. The two single inlet fans in this example have measurements are assumed to exist at the
been rated by the manufacturer as a two stage respective plane of interest because of the close
assembly. Although rated as an assembly, sufficient proximity and the fact that the two planes are equal in
measurements are made to provide performance area. The static pressure at each plane may be
data for each fan. The damper downstream of the determined by averaging the static pressure
second fan is not included as part of the rated measurements at each of four static pressure taps, or
assembly. In virtually all cases in which an air flow by averaging the static pressure measurements
control damper, such as the one shown in the made in a Pitot-static tube traverse of the plane.
diagram, is included in the system, the point of However, due to the turbulence existing in the
operation of major interest and for which the fan has regions of the outlets of the fans, it is recommended
been selected is at the maximum air flow rate. This that static pressure taps be used at Planes 1b-2a and
example is no exception. Therefore, it is essential 2b.
that the damper be fixed in its full open position for
the duration of the test. 4. Measure td3, tw3, td1b, and td2b; td1a is assumed to be
equal to td3. Determine pb for the general vicinity of
2. Determine Pv3 by using the root mean square of the fan. These measurements are used in
the velocity pressure measurements made in a determining densities at the planes of interest.
traverse of Plane 3. Determine Ps3 by averaging the
static pressure measurements made in the same 5. Measure the fan speed and the motor amps, volts,
traverse. Procedures for traverses are described in and if possible, watts for each fan. Record all
Section 9.4. Ps3 is used in determining the density at pertinent motor nameplate data, including volts
the traverse plane, A3, which is located at the tip of (NPV), and full load amps (FLA). If the motor power
the Pitot-static tube. outputs are to be estimated by using the phase
current method described in Annex K, it is not
3. Determine the static pressures at Planes 1a, 1b- necessary to measure motor watts; however, it may
2a, and 2b. As shown in the diagram, these planes be necessary to disconnect the drives and measure
are located shortly downstream of the inlets and the no load amps (NLA) if the motors are not
outlets of the fans, which are the planes of interest. In operating at or near their full load points. In this
each case, the conditions which exist at the plane of example, a watts input measurement is made for
55
AMCA 203-90 (R2007)
7. To calculate the static pressure for the two stage Data identical for each stage:
assembly: 350 hp, 3 phase, 60 hertz
4000 volts, 1790 rpm, 44.5 FLA
Ps = Ps2b - Ps1a - Pv1a
GENERAL
Where:
Fans direct connected to motors. Motor efficiency
Pv1a = Pv3 (A3/A1a)2 (ρ3/ρ1a) data supplied by motor manufacturer.
56
AMCA 203-90 (R2007)
Q2b = Q3 (ρ3/ρ2b)
= 21471 (0.0470/0.0624)
= 16172 cfm
57
AMCA 203-90 (R2007)
SEF 1
3a
2
3c
3b
COMMENTS
1. This fan, as supplied and rated by the Pitot-static tube is used, it should be positioned well
manufacturer, does not include the backdraft damper. within the inlet collar in which Plane 1 is located.
Measure the area of Plane 1 for use in calculating
2. Normally, velocity pressure measurements would Pv1. The static pressure at the outlet of the backdraft
be made in a single plane, located in a duct common damper is zero gauge pressure, referred to the
to all branches. In this example, a measurement atmospheric pressure in the region of the outlet of the
plane which provides a satisfactory velocity profile backdraft damper. In situations such as this example,
cannot be located within the short length of duct the air may be discharging from the damper into a
between the point of connection of the branch ducts region in which the atmospheric pressure is
and the fan inlet. The alternative, as indicated in the somewhat different from that to which all other
diagram, is to make a velocity pressure pressure measurements are referred. When this
measurement traverse in the longest available duct possibility exists, it is essential that the static
run of each branch. The velocity pressure for each pressure in the region of the discharging air be
branch is determined by using the root mean square measured, referred to the same atmospheric
of the velocity pressure measurements made in the pressure as used in all other pressure
traverse. The static pressure at each traverse plane measurements.
is determined by averaging the static pressure
measurements made in the same traverse. These 4. Measure the dry-bulb and wet-bulb temperatures
static pressure values are used in determining the at each velocity traverse plane and the dry-bulb
densities at the traverse planes. Procedures for temperature at Plane 1. In this example, td2 is
traverses are described in Section 9.4. In order to assumed to be equal to td1. Determine pb for the
determine the air flow rates it is necessary to general vicinity of the fan. These measurements are
measure the area of each traverse point. used in determining densities at the planes of
interest.
3. Ps1, the static pressure at the fan inlet may be
determined by averaging the static pressure 5. Measure the fan speed and the motor amps, volts,
measurements at each of four static pressure taps or and if possible, watts. Record all pertinent motor
by averaging the static pressure measurements nameplate data, including volts (NPV) and full load
made in a Pitot-static tube traverse of Plane 1. If a amps (FLA). If the motor power output is to be
58
AMCA 203-90 (R2007)
Q1 = Q3a (ρ3a/ρ1) + Q3b (ρ3b/ρ1) + Q3c (ρ3c/ρ1) Fan connected to motor through belt drive. Pressure
loss data supplied by manufacturer of backdraft
Ps2 is the sum of the static pressure in the region of damper.
the damper outlet, which was measured as zero, and
the backdraft damper pressure loss. CALCULATIONS
59
AMCA 203-90 (R2007)
60
AMCA 203-90 (R2007)
Qc = 41603 (810/800)
= 42123 cfm
61
AMCA 203-90 (R2007)
2-PIECE ELBOW
SEF 1
L1
1
STATIC GUIDE VANES
PRESSURE TAPS
INNER CYLINDER
2
SEF 2
L2
5
PLAN VIEW
COMMENTS
1. Determine Pv3 by using the root mean square of load amps (FLA). If the motor power output is to be
the velocity pressure measurements made in a estimated by using the phase current method
traverse of Plane 3, located near the end of a straight described in Annex K, it is not necessary to measure
run of duct, as shown in the diagram. Determine Ps3 motor watts; however, it may be necessary to
by averaging the static pressure measurements disconnect the drive and measure the no load amps
made in the same traverse. Procedures for traverses (NLA) if the motor is not operating at or near its full
are described in Section 9.4. Ps3 is used in load point. Refer to Annex K.
determining the density at the traverse plane.
Measure the area of the traverse plane, A3, which is 5. SEF 1 is due to the effect of insufficient length of
located at the tip of the Pitot-static tube. duct between the fan inlet and the elbow upstream of
the fan. SEF 2 is due to the effect of insufficient
2. Determine Ps5 by averaging the pressure length of duct between the fan outlet and the elbow
downstream of the fan. In order to calculate the
measurements at each of four static pressure taps
values of the SEFs, it is necessary to measure the
located near the end of the duct connection at the fan
inlet area and the outlet area of the fan, A1 and A2;
outlet. Determine Ps1 by using a Pitot-static tube or
and the lengths of the inlet and outlet duct
static pressure taps in the duct connection at the fan
connections, L1 and L2.
inlet. If a Pitot-static tube is used, it should not project
into the upstream elbow but be located well within the
6. To calculate the Fan Static Pressure:
length of the duct connection.
Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2
3. Measure td3 and tw3 in the traverse plane; td1 is
assumed to be equal to td3. Determine pb for the
Where: Pv1 = Pv3
general vicinity of the fan. Measure td5. These
measurements are used in determining densities at
Since:
the planes of interest.
A1 = A3
4. Measure the fan speed and the motors amps,
volts, and if possible, watts. Record all pertinent
And:
motor nameplate data, including volts (NPV), and full
62
AMCA 203-90 (R2007)
ρ1 = ρ3 CALCULATIONS
Q2 = Q5
= Q3 (ρ3/ρ5)
= 6384 (0.0719/0.0721)
= 6366 cfm
63
AMCA 203-90 (R2007)
FAN POWER INPUT R-S, Figure 7.1 shows SEF 1 = 0.24 in. wg at 0.075
lbm/ft3 density. At 0.0719 lbm/ft3:
Measured amps/FLA = (12.3/14.0)
= 0.88 SEF 1 = 0.24 (0.0719/0.075)
= 88% = 0.23 in. wg
Annex K indicates that the average of the results of
Equation A and Equation B will provide a reasonably For SEF 2, AMCA Publication 201-90, Figures 7.1,
accurate estimate of motor power output for a 5 hp 8.1, and 8.4 indicate the following calculations:
motor operating at 88% FLA.
V2 = (Q2/A2)
Eqn A = 5 (12.3/14) (228/230) = (6366/2.64)
= 4.35 hp = 2411 fpm
Eqn B = 5 [(12.3 - 7)/(14 - 7)] (228/230) The diameter of the fan outlet:
= 3.75 hp
D2 = (4A2/π)0.5
Hmo = (4.35 + 3.75)/2
= (4 × 2.64/π)0.5
= 4.05 hp = 1.83 ft
Figure L.1 in Annex L indicates estimated belt drive Figure 8.1 shows that for velocities of 2500 fpm or
loss of 6.3%. less, the 100% effective duct length is 2.5 diameters:
HL = 0.063 Hmo = 2.5 × 1.83
= 0.063 × 4.05 = 4.58 ft
= 0.26 hp
The length of the outlet duct in % effective duct
H = Hmo - HL length:
= 4.05 - 0.26
= 3.79 hp = (L2/4.58) 100
= (2.25/4.58) 100
SYSTEM EFFECT FACTORS = 49%
To determine the value of SEF 1, calculate the From Figure 8.4, for a vaneaxial fan with a 49%
velocity at the fan inlet: effective duct length between its discharge and a two
piece elbow, System Effect Curve W applies. From
V1 = (Q1/A1) Figure 7.1, for 2411 fpm velocity and curve W, SEF 2
= (6384/2.64) is less than 0.1 in. wg, and is considered negligible.
= 2418 fpm
SEF 2 = 0.00
Calculate the diameter of the fan inlet:
FAN STATIC PRESSURE
D1 = (4A1/π)0.5
= (4 × 2.64/π)0.5 Since:
= 1.83 ft.
A 1 = A3
Calculate the length of duct between the elbow and ρ1 = ρ3
the fan inlet in terms of the fan inlet diameter: Pv1 = Pv3
64
AMCA 203-90 (R2007)
Qc = 6384 (1730/1710)
= 6459 cfm
65
AMCA 203-90 (R2007)
3
WET CELL SCRUBBER
1
2
PLAN VIEW
SEF 1
SIDE VIEW
COMMENTS
1. Determine Pv3 by using the root mean square of amps (FLA). If the motor power output is to be
the velocity pressure measurements made in a estimated by using the phase current method
traverse of Plane 3, located in the duct connection at described in Annex K, it is not necessary to measure
the fan inlet, as shown in the diagram. Determine Ps3 motor watts; however, it may be necessary to
by averaging the static pressure measurements disconnect the drive and measure the no load amps
made in the same traverse. Procedures for traverses (NLA) if the motor is not operating at or near its full
are described in Section 9.4. Ps3 is used in load point. Refer to Annex K.
determining the density at the traverse plane.
Measure the area of the traverse plane, A3, which is 5. SEF 1 is due to the effect of there being no duct
located at the tip of the Pitot-static tube. In locating at the fan outlet. In order to calculate the value of
Plane 3 downstream of the scrubber, changes in the SEF 1, it is necessary to measure the outlet area of
composition of the air as a result of the action of the the fan, A2, and the blast area of the fan.
scrubber are properly taken into account in the
determination of fan air flow rate. Due to the close 6. To calculate the Fan Static Pressure:
proximity of Planes 1 and 3, and the fact that there is
no change in area between the two planes, the Ps = Ps2 - Ps1 - Pv1 + SEF 1
conditions which exist at Plane 3 are assumed to
exist at Plane 1. Where:
2. Ps2, the static pressure at the fan outlet, is zero. Pv1 = Pv3
Ps1 = Ps3
3. Measure td3 and tw3 in the traverse plane. Ps2 = 0
Determine pb for the general vicinity of the fan.
Measure td2. These measurements are used in 7. In order to compare the test results to the quoted
determining densities at the planes of interest. fan curve drawn for operation at 1700 rpm and 0.071
lbm/ft3 density, it is necessary to convert the results
4. Measure the fan speed and the motor amps, volts, to the specified conditions. The basis for the
and if possible, watts. Record all pertinent motor calculations is described in Section 14.
nameplate data, including volts (NPV), and full load
66
AMCA 203-90 (R2007)
OBSERVATIONS
⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
ρ2 = ρ3 ⎜ s2 ⎟⎜ ⎟
SITE MEASUREMENTS ⎝ 13.6 p3 ⎠ ⎝ t d2 + 460 ⎠
⎛ 0 + 13.6 × 29.80 ⎞ ⎛ 525 ⎞
pb = 29.80 in. Hg = 0.0732 ⎜ ⎟⎜ ⎟
⎝ 13.6 × 29.21 ⎠ ⎝ 530 ⎠
td3= 65°F
= 0.0740 lbm/ft 3
tw3= 64°F
td2= 70°F
Ps3= -8.0 in. wg FLOW RATES
Pv3= 0.337 in. wg
N = 1672 rpm V3 = 1096 (Pv3/ρ3)0.5
A1 = A3 = 1096 (0.337/0.0732)0.5
= 7.06 ft2 = 2352 fpm
A2 = 5.15 ft2
Q3 = V3A3
Blast Area = 3.67 ft2 = 2353 × 7.06
= 16605 cfm
MEASURED MOTOR DATA
Q = Q1
Volts = 450, 458, 462
= Q3 (ρ3/ρ1)
= 457 av
= 16605 (0.0732/0.0732)
Amps = 44, 45, 44.5
= 16605 cfm
= 44.5 av
Q2 = Q3 (ρ3/ρ2)
MOTOR NAMEPLATE DATA
= 16605 (0.0732/0.0740)
40 hp, 3 phase, 60 hertz = 16425 cfm
460 volts, 1780 rpm, 49 FLA
FAN POWER INPUT
GENERAL
Measured amps/FLA = (44.5/49)
Fan connected to motor through belt drive. = 0.91
= 91%
CALCULATIONS
Annex K indicates that Equation A will provide a
DENSITIES reasonably accurate estimate of motor power output
for a 40 hp motor operating at 91% FLA.
For Plane 3 conditions of:
td3 = 65°F Hmo = 40 (44.5/49) (457/460)
tw3 = 64°F = 36.1 hp
67
AMCA 203-90 (R2007)
V2 = (Q2/A2)
= (16425/5.15)
= 3189 fpm
Pv1 = Pv3
= 0.337 in. wg
Qc = 16605 (1700/1672)
= 16883 cfm
68
AMCA 203-90 (R2007)
2
1
BACKDRAFT DAMPER
4
STATIC PRESSURE TAPS
3a SIDE VIEW 3b
COMMENTS
1. This centrifugal roof ventilator, as supplied and 3. Ps4 may be determined by averaging the static
rated by the manufacturer, does not include the pressure measurements at each of four static
backdraft damper. It is essential that the backdraft pressure taps or by averaging the static pressure
damper blades be fixed in their full open positions, measurements made in a Pitot-static tube traverse of
otherwise uneven velocity distribution will occur at Plane 4. If a Pitot-static tube is used, it should be
the inlet to the ventilator, adversely affecting its positioned well within the duct in which Plane 4 is
performance. located, and not project into the upstream elbows.
Measure the area of Plane 1 for use in calculating
2. Normally, velocity pressure measurements would Pv1. In this example, A4 = A1. Ps2, the static pressure
be made in a single plane, located in a duct common at the outlet of the ventilator, is zero gauge pressure,
to all branches. In this example, a measurement referred to the atmospheric pressure in the region of
plane which provides a satisfactory velocity profile the ventilator outlet. In situations such as this
cannot be located within the short length of duct example, the air may be discharging from the
between the point of connection of the branch ducts ventilator into a region in which the atmospheric
and the ventilator inlet. The alternative, as indicated pressure is somewhat different from that to which all
in the diagram, is to make a velocity pressure other pressure measurements are referred. When
measurement traverse in each branch. The velocity this possibility exists, it is essential that the static
pressure for each branch is determined by using the pressure in the region of the discharging air be
root mean square of the velocity pressure measured, referred to the same atmospheric
measurements made in the traverse. The static pressure as used in all other pressure
pressure at each traverse plane is determined by measurements. In this case, Ps2 was measured as
averaging the static pressure measurements made in zero.
the same traverse. These static pressure values are
used in determining the densities at the traverse 4. Measure the dry-bulb and wet-bulb temperatures
planes. Procedures for traverses are described in at each velocity traverse plane. In this example, td1
Section 9.4. In order to determine the air flow rates, it and td4 are assumed to be equal to td3a. Determine pb
is necessary to measure the area of each traverse
for the general vicinity of the fan. These
plane.
measurements are used in determining densities at
the planes of interest.
69
AMCA 203-90 (R2007)
5. Measure the fan speed and the motor amps, volts, MEASURED MOTOR DATA
and if possible, watts. Record all pertinent motor
nameplate data, including volts (NPV) and full load Volts = 450, 455, 460
amps (FLA). If the motor power output is to be = 455 av
estimated by using the phase current method Amps = 5.7, 5.85, 5.9
described in Annex K, it is not necessary to measure = 5.82 av
motor watts; however, it may be necessary to
disconnect the drive and measure the no load amps MOTOR NAMEPLATE DATA
(NLA) if the motor is not operating at or near its full
load point. Refer to Annex K. 5 hp, 3 phase, 60 hertz
460 volts, 1780 rpm, 5.95 FLA
6. Determine the backdraft damper pressure loss by
using the performance ratings supplied by the GENERAL
manufacturer.
Fan connected to motor through belt drive. Pressure
7. To calculate the Fan Static Pressure: loss data supplied by manufacturer of backdraft
damper.
Ps = Ps2 - Ps1 - Pv1
CALCULATIONS
Where:
DENSITIES
Pv1 = (Q1/1096 A1)2 ρ1
For Planes 3a and 3b conditions of:
Q1 = Q3a (ρ3a/ρ1) + Q3b (ρ3b/ρ1)
td3a = td3b
Ps1 = Ps4 - backdraft damper pressure loss = 72°F
Ps2 = 0 tw3a = tw3b
= 66°F
8. In order to compare the test results to the quoted
fan curve drawn for operation at 620 rpm and 0.075 p3a = p3b
lbm/ft3 density, it is necessary to convert the results = pb + (Ps3a/13.6)
to the specified conditions. The basis for the = 29.20 + (-0.85/13.6)
calculations is described in Section 14. = 29.14 in. Hg
70
AMCA 203-90 (R2007)
Figure L.1 in Annex L indicates estimated belt drive Psc = 0.89 (620/625)2 (0.075/0.0721)
loss of 5.8%. = 0.91 in. wg
H = Hmo - HL
= 4.84 - 0.28
= 4.56 hp
71
AMCA 203-90 (R2007)
4 SEF 1 5
L
RETURN SEF 2
PLAN VIEW
AIR 3a
SPRAY
SECTION FAN SECTION
+
OUTSIDE
+
AIR
+
+
+ + +
+
+ +
COMMENTS
1. This is an air conditioning unit which has been is determined by using the root mean square of the
assembled at the installation site. The subject of the velocity pressure measurements made in the
test is the fan, which is rated by the manufacturer as traverse. the static pressure at each traverse plane is
free-standing, unencumbered by the cabinet in which determined by averaging the static pressure
it has been installed. The fan performance ratings are measurements made in the same traverse. These
based on operation with the fan outlet ducted. Before static pressure values are used in determining the
proceeding with the test, it is essential that all densities at the traverse planes. Procedures for
dampers--outside air, return air, mixing box, traverses are described in Section 9.4. In order to
multizone, face and bypass or volume control--be determine the air flow rates, it is necessary to
fixed in the positions agreed upon by all interested measure the area of each traverse plane.
parties as being applicable for the installation. Also,
the temperatures of the heating coils must be kept 3. Determine Ps4 by averaging the static pressure
constant throughout the test period. It may be measurements made in a traverse of Plane 4.
necessary to lock out, disconnect, or otherwise Determine Ps5 in a similar manner. Pitot-static tube
modify automatic control devices in order to prevent traverses are used in determining these static
the positions of the dampers and temperatures of the pressures because the installation of suitable
coils from changing during the test. Refer to Section pressure taps is usually prevented by the insulating
17.4.3 for additional considerations affecting the test material encountered in this type of equipment. Due
procedure for fans in this type of installation. to the abrupt expansion in area from Plane 2 to Plane
5, it is assumed that there is no conversion of velocity
2. Normally, velocity pressure measurements would pressure at Plane 2 to static pressure at Plane 5.
be made in a single plane, located in a duct common Therefore, it is assumed that Ps2 = Ps5. Measure the
to all branches. In this example, a measurement area of Plane 4 for use in calculating Pv4.
plane which provides a satisfactory velocity profile
cannot be located upstream of the fan or between the 4. Measure the dry-bulb and wet-bulb temperatures
point of connection of the branch ducts and the fan at Plane 4 and the dry-bulb temperatures at Planes
outlet. The alternative, as indicated in the diagram, is 3a, 3b, and 5. Determine pb for the general vicinity of
to make a velocity pressure measurement traverse in
the air conditioning unit. These measurements are
each branch. The velocity pressure for each branch
used in determining densities at the planes of interest.
72
AMCA 203-90 (R2007)
p4 = pb + (Ps4/13.6)
= 28.72 + (-1.75/13.6)
= 28.59 in. Hg
73
AMCA 203-90 (R2007)
74
AMCA 203-90 (R2007)
For a blast area ratio of 0.7 and no duct, Figure 8.3 Hc = 65.75 (1170/1160)3 (0.075/0.0731)
shows System Effect Curve S applies. For 2564 fpm = 69.22 hp
velocity and curve S, Figure 7.1 shows SEF 2 = 0.33
in. wg at 0.075 lbm/ft3 density. At 0.0739 lbm/ft3:
Since:
ρ4 = ρ1
Q4 = Q1
75
AMCA 203-90 (R2007)
EXAMPLE 4B: CENTRAL STATION AIR CONDITIONING UNIT, FACTORY ASSEMBLED DRAW-
THROUGH TYPE
1
L
SEF 1 5
2
OUTSIDE + +
AIR
+ +
FAN SECTION
SIDE VIEW
FILTER SECTION COIL SECTION
COMMENTS
1. This is a factory assembled, draw-through central Section 9.4. In order to determine the air flow rate, it
station unit. The subject of the test is the fan section, is necessary to measure the area of the traverse
which is rated by the manufacturer as an assembly of plane.
the fan and the cabinet in which the fan has been
installed. As a draw-through unit, the performance 3. Determine Ps1 by averaging the static pressure
ratings for the fan section are based on operation measurements made in a traverse of Plane 1. Ps5
with the fan outlet ducted. Before proceeding with the may be determined in a similar manner or by
test, it is essential that all dampers--outside air, return averaging the pressure measurements at each of
air, mixing box, multizone, face and bypass, or four static pressure taps. If it is possible to install
volume control--be fixed in the positions agreed upon suitable pressure taps, their use is preferred in the
by all interested parties as being applicable for the region of the fan outlet. due to the close proximity of
installation. Also, the temperatures of heating and Planes 2 and 5, and the fact that there is no change
cooling coils must be kept constant throughout the in area between the two planes, the conditions which
test period. It may be necessary to lock out, exist at Plane 5 are assumed to exist at Plane 2.
disconnect, or otherwise modify automatic control Measure the area of Plane 1 for use in calculating
devices in order to prevent the positions of the Pv1.
dampers and temperatures of the coils from changing
during the test. Refer to Section 17.4.2 for additional 4. Measure the dry-bulb and wet-bulb temperatures
considerations affecting the test procedure in this at Plane 3 and the dry-bulb temperatures at Planes 1
type of installation. and 5. Determine pb for the general vicinity of the air
conditioning unit. These measurements are used to
2. Determine Pv3 by using the root mean square of determine densities at the planes of interest.
the velocity pressure measurements made in a
traverse of Plane 3, located near the end of a straight 5. Measure the fan speed and the motor amps, volts,
run of duct, as shown in the diagram. Determine Ps3 and if possible, watts. Record all pertinent motor
by averaging the static pressure measurements nameplate data, including volts (NPV), and full load
made in the same traverse. This static pressure value amps (FLA). If the motor power output is to be
is used to determine the density at the traverse estimated by using the phase current method
plane. Procedures for traverses are described in described in Annex K, it is not necessary to measure
76
AMCA 203-90 (R2007)
Ps = Ps2 - Ps1 - Pv1 + SEF 1 Fan connected to motor through belt drive.
Where: CALCULATIONS
td3 = 49.3°F
The calculation of Pv1 is often ignored in instances
tw3 = 47.3°F
similar to this example on the basis that the
calculated value of Pv1 is relatively small, and it
p3 = pb + (Ps3/13.6)
omission does not affect the test results significantly.
= 29.27 + (1.31/13.6)
8. In order to compare the test results to the quoted = 29.37 in. Hg
fan section curve drawn for operation at 1430 rpm
Use Figure N.1 in Annex N to obtain ρ3 = 0.0762
and 0.075 lbm/ft3 density, it is necessary to convert
the results to the specified conditions. The basis for lbm/ft3.
the calculations is described in Section 14.
⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
OBSERVATIONS ρ1 = ρ3 ⎜ s1 ⎟⎜ ⎟
⎝ 13.6 p3 ⎠ ⎝ t d1 + 460 ⎠
SITE MEASUREMENTS ⎛ −0.847 + 13.6 × 29.27 ⎞ ⎛ 509.3 ⎞
= 0.0762 ⎜ ⎟ ⎜ 507.5 ⎟
⎝ 13.6 × 29.37 ⎠⎝ ⎠
pb = 29.27 in. Hg = 0.0760 lbm/ftt 3
td1 = 47.5°F
td3 = 49.3°F
tw3 = 47.3°F ⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
ρ5 = ρ3 ⎜ s5 ⎟⎜ ⎟
td5 = 49°F ⎝ 13.6 p3 ⎠ ⎝ t d5 + 460 ⎠
Ps1 = -0.847 in. wg
⎛ 1.39 + 13.6 × 29.27 ⎞ ⎛ 509.3 ⎞
Ps3 = 1.31 in. wg = 0.0762 ⎜ ⎟ ⎜ 509 ⎟
⎝ 13.6 × 29.37 ⎠⎝ ⎠
Pv3 = 0.294 in. wg
Ps5 = 1.39 in. wg = 0.0763 lbm/ft 3
N = 1402 rpm
A1 = 147.2 ft2 It is assumed ρ2 = ρ5.
A2 = A3 = A5
= 15.42 ft2 FLOW RATES
Blast Area = 9.4 ft2
L = 2.0 ft, length of outlet duct V3 = 1096 (Pv3/ρ3)0.5
= 1096 (0.294/0.0762)0.5
= 2153 fpm
77
AMCA 203-90 (R2007)
Q2 = Q5 = (L/11.1) 100
= Q3 (ρ3/ρ5) = (2.0/11.1) 100
= 18%
= 33199 (0.0762/0.0763)
= 33155 cfm
Blast area ratio = Blast Area/A2
FAN POWER INPUT = 9.4/15.42
= 0.61
Measured amps/FLA = (47.7/49.7)
= 0.96 For a blast area ratio of 0.6, 18% effective duct length
= 96% and elbow position A, Figure 8.5 shows System
Effect Curve R applies. For 2150 fpm velocity and
Annex K indicates that Equation A will provide a curve R, Figure 7.1 shows SEF 1 = 0.34 in. wg at
reasonably accurate estimate of motor power output 0.075 lbm/ft3 density. At 0.0762 lbm/ft3:
for a 40 hp motor operating at 96% FLA.
SEF 1 = 0.34 (0.0762/0.075)
Hmo = 40 (47.7/49.7) (442/440) = 0.35 in. wg
= 38.6 hp
FAN SECTION STATIC PRESSURE
Figure L.1 in Annex L indicates estimated belt drive
loss of 4.5%. Pv1 = (Q1/1096 A1)2 ρ1
= (33286/1096 × 147.2)2 0.0760
HL = 0.045 Hmo = 0.003 in. wg
= 0.045 × 38.6
= 1.74 hp It is assumed that Ps2 = Ps5
De2 = (4 A2/π)0.5
= (4 × 15.42/π)0.5
= 4.43 ft
78
AMCA 203-90 (R2007)
3
2
SEF 1
4 1 PLAN VIEW
INLET PLENUM FILTERS FANS 5
COMMENTS
1. The subject of the test in this example is the air 3. Ps4 may be determined by averaging the pressure
conditioning unit assembly. This assembly does not measurements at each of four static pressure taps or
include the inlet plenum. The performance ratings for by averaging the static pressure measurements
the unit assembly are based on operation with the made in a Pitot-static tube traverse of Plane 4. Ps5 is
outlets of the fans ducted. Before proceeding with the determined in a similar manner. However, if it is
test, it is essential that all system dampers be fixed in possible to install suitable static pressure taps, their
the positions agreed upon by all interested parties as use is preferred in the regions of the outlets of the
being applicable for the installation. Also, the fans. Due to the close proximity of Planes 1 and 4
temperature of the cooling coil must be kept constant and the fact that there is no change in area between
throughout the test period. It may be necessary to the two planes, the conditions which exist at Plane 4
lock out, disconnect or otherwise modify automatic are assumed to exist at Plane 1. Although Plane 5 is
control devices in order to prevent the positions of the greater in area that Plane 2, the degree of divergence
dampers and the temperature of the coil from is relatively small. Therefore, Ps2 will be calculated
changing during the test. Refer to Section 17.4.1 for based on Ps5 and the assumption that there is no
additional considerations affecting the test procedure change in total pressure from Plane 2 to Plane 5.
in this type of installation.
4. Measure the dry-bulb and wet-bulb temperatures
2. Determine Pv3 by using the root mean square of at Plane 4 and the dry-bulb temperatures at Planes 3
the velocity pressure measurements made in a and 5. In this example, the cooling medium, normally
traverse of Plane 3, located near the end of a straight circulated in the coil was shut off in order to maintain
run of duct, as shown in the diagram. Determine Ps3 constant air temperatures during the test. In order to
by averaging the static pressure measurements account for water vapor which may have been added
made in the same traverse. This static pressure value to the air as a result of evaporation of moisture
is used to determine the density at the traverse previously condensed on the coil, the wet-bulb
plane. Procedures for traverses are described in temperature at Plane 3 was measured. Determine pb
Section 9.4. in order to determine the air flow rate, it for the general vicinity of the air conditioning unit.
is necessary to measure the area of the traverse These measurements are used in determining
plane. densities at the planes of interest.
79
AMCA 203-90 (R2007)
80
AMCA 203-90 (R2007)
FLOW RATES Duct diameter equivalent to the outlet area of one fan:
Q3 = V3A3 Figure 8.3 shows that for velocities over 2500 fpm,
= 2390 × 16.4 100% effective duct length is one diameter for every
= 39196 cfm 1000 fpm:
Q2 = Q5 = De2 (V2/1000)
= Q3 (ρ3/ρ5) = 2.71 (3404/1000)
= 39196 (0.0736/0.0737) = 9.22 ft
= 39143 cfm
L in % effective duct length:
Q = Q1 = Q4
= Q3 (ρ3/ρ4) = (L/9.22) 100
= (2.0/9.22) 100
= 39196 (0.0736/0.0735)
= 22%
= 39249 cfm
Blast area ratio = Blast area/A2
FAN POWER INPUT
= (2 × 4.0)/11.5
Measured amps/FLA = (38.0/39.5) = 0.70
= 0.96
= 96% For a blast area ratio of 0.7, and 22% effective duct
length Figure 8.3 shows System Effect Curve W
Annex K indicates that Equation A will provide a applies. For 3404 fpm velocity and curve W, Figure
reasonably accurate estimate of motor power output 7.1 shows SEF 1 = 0.13 in. wg at 0.075 lbm/ft3
for a 25 hp motor operating at 96% FLA. density. At 0.0737 lbm/ft3:
Figure L.1 in Annex L indicates estimated belt drive STATIC PRESSURE OF UNIT
loss of 4.8%.
Pv5 = (Q5/1096 A5)2 ρ5
HL = 0.048 Hmo = (39143/1096 × 14.3)2 0.0737
= 0.048 × 24.1 = 0.46 in. wg
= 1.2 hp
Pv2 = (Q2/1096 A2)2 ρ2
H = Hmo - HL = (39143/1096 × 11.5)2 0.0737
= 24.1 - 1.2 = 0.71 in. wg
= 22.9 hp
81
AMCA 203-90 (R2007)
82
AMCA 203-90 (R2007)
3a
3b
PLAN VIEW
5
L
2
FILTER SECTION
SEF 1 1
+ +
SIDE VIEW
COMMENTS
1. The subject of the test in this example is the air pressure at each traverse plane is determined by
conditioning unit assembly. This assembly includes using the root mean square of the velocity
the filter section and the inlet louver. The measurement traverse in each of two branches. The
performance ratings for the unit assembly are based velocity pressure for each branch is determined by
on operation with the outlets of the fans ducted. using the root mean square of the velocity pressure
Before proceeding with the test, it is essential that all measurements made in the traverse. The static
system dampers be fixed in the positions agreed pressure at each traverse plane is determined by
upon by all interested parties as being applicable for averaging the static pressure measurements made in
the installation. Also, the temperature of the heating the same traverse. These static pressure values are
coil must be kept constant throughout the test period. used in determining the densities at the traverse
It may be necessary to lock out, disconnect or planes. Procedures for traverses are described in
otherwise modify automatic control devices in order Section 9.4. In order to determine the air flow rates, it
to prevent the positions of the dampers and the is necessary to measure the area of each traverse
temperature of the coil from changing during the test. plane.
Refer to Section 17.5.1 for additional considerations
affecting the test procedure in this type of installation. 3. Determine Ps5 by averaging the pressure
measurements at each of four static pressure taps
2. Normally, velocity pressure measurements would located in the duct fitting at the outlets of the fans.
be made in a single plane, located in a duct common The conditions which exist at Plane 5, including the
to all branches. In this example, a measurement static pressure, are assumed to exist at Plane 2,
plane which provides a satisfactory velocity profile based on their close proximity and the fact that there
cannot be located upstream of the fans or between is no change in area between the two planes. In
the point of connection of the branch ducts and the situations such as this example, it is important to be
outlets of the fans. The alternative, as indicated in the certain that all pressure measurements are referred
diagram, is to make a velocity pressure to the same atmospheric pressure.
measurement traverse in each of two branches. the
velocity pressure for reach branch is determined by 4. Measure the dry-bulb and wet-bulb temperatures
using the root mean square of the velocity pressure at Plane 1 and the dry-bulb temperatures at Planes
measurements made in the traverse. The static 3a, 3b, and 5. Determine pb for the general vicinity of
83
AMCA 203-90 (R2007)
the air conditioning unit. These measurements are 8. In order to compare the test results to the quoted
used to determine densities at the planes of interest. performance curve for the packaged unit drawn for
operation at 1720 rpm and 0.075 lbm/ft3 density, it is
5. Measure the fan speed and the motor amps, volts, necessary to convert the results to the specified
and if possible, watts. Record all pertinent motor conditions. The basis for the calculations is described
nameplate data, including volts (NPV), and full load in Section 14.
amps (FLA). If the motor power output is to be
estimated by using the phase current method OBSERVATIONS
described in Annex K, it is not necessary to measure
motor watts; however, it may be necessary to SITE MEASUREMENTS
disconnect the drive and measure the no load amps
(NLA) if the motor is not operating at or near its full pb = 29.65 in. Hg
load point. Motor performance data, supplied by the td1 = 72°F
motor manufacturer, are used in the determination of tw1 = 61°F
motor power output in this example. td5 = 85°F
td3a= 82.5°F
6. SEF 1 is due to the effect of insufficient length of
td3b= 83°F
duct between the outlets of the fans and the elbow
downstream of the fans. In order to determine the Ps5 = 1.25 in. wg
value of SEF 1, it is necessary to measure the outlet Ps3a= 1.15 in. wg
area and the blast area of one of the fans and the Ps3b= 1.22 in. wg
length of the duct, L, between the fan and the elbow. Pv3a= 0.56 in. wg
Pv3b= 0.60 in. wg
7. The sum of the static pressure, Ps1, and velocity N = 1710 rpm
pressure, Pv1, at the inlet to the unit assembly is A2 = A5
considered to be equal to the sum of the static = 5.64 ft2
pressure, Psx, and velocity pressure, Pvx, at a point A3a = 3.1 ft2
sufficiently distant from the inlet as to be in still air. At A3b = 2.2 ft2
this point, the static pressure is zero, and the velocity
Blast Area = 2.5 ft2 per fan
pressure in still air is zero.
L = 0.96 ft, length of outlet duct
Ps1 + Pv1 = Psx + Pvx = 0
MEASURED MOTOR DATA
This consideration, which is the same as that used in
Volts = 460, 458, 462
the methods for testing this type of unit for
= 460 av
performance rating purposes, charges to the unit
Amps = 10.0, 10.0, 9.8
losses incurred in accelerating the air into its inlet and
= 9.9 av
eliminates the inaccuracies which arise in any
attempt to measure the velocity pressure and static
MOTOR NAMEPLATE DATA
pressure at the inlet. To calculate the static pressure
for the unit assembly:
10 hp, 3 phase, 60 hertz
460 volts, 1750 rpm, 13.5 FLA
Ps = Ps2 - Ps1 - Pv1 + SEF 1
= Ps2 - (Ps1 + Pv1) + SEF 1 GENERAL
84
AMCA 203-90 (R2007)
DENSITIES Q = Q1
= Q3a (ρ3a/ρ1) + Q3b (ρ3b/ρ1)
For Plane 1 conditions of: = 9455 (0.0723/0.0735) + 6950 (0.0722/0.0735)
= 16128 cfm
td1 = 72°F
tw1 = 61°F Q2 = Q5
p1 = pb = Q1 (ρ1/ρ5)
= 29.65 in. Hg = 16128 (0.0735/0.0720)
= 16464 cfm
Use Figure N.1 in Annex N to obtain ρ1 = 0.0735
lbm/ft3. FAN POWER INPUT
85
AMCA 203-90 (R2007)
86
AMCA 203-90 (R2007)
EXAMPLE 4E: CENTRAL STATION AIR CONDITIONING UNIT, FACTORY ASSEMBLED BLOW-
THROUGH TYPE
2
1
5 STATIC PRESSURE TAPS
PLAN VIEW 3b 3a
RETURN
AIR SPRAY HEATING COIL
SECTION
+
+ +
+
OUTSIDE +
AIR +
+ +
SIDE VIEW
COMMENTS
1. This is a factory assembled, blow-through central be made in a single plane, located in a duct common
station unit. The subject of the test is the fan section, to all branches. In this example, a measurement
which is rated by the manufacturer as an assembly of plane which provides a satisfactory velocity profile
the fan and the cabinet in which the fan has been cannot be located upstream of the fan or between the
installed. As a blow-through unit, the performance point of connection of the branch ducts and the fan
ratings for the fan section are based on operation outlet. The alternative, as indicated in the diagram, is
without the fan outlet ducted. Before proceeding with to make a velocity pressure measurement traverse in
the test, it is essential that all dampers (outside air, each branch. The velocity pressure for each branch
return air, mixing box, multizone, face and bypass, or is determined by using the root mean square of the
volume control) be fixed in the positions agreed upon velocity pressure measurements made in the
by all interested parties as being applicable for the traverse. The static pressure at each traverse plane
installation. Also, the temperatures of heating and is determined by averaging the static pressure
cooling coils must be kept constant throughout the measurements made in the same traverse. These
test period. It may be necessary to lock out, static pressure values are used in determining the
disconnect, or otherwise modify automatic control densities at the traverse plane. Procedures for
devices in order to prevent the positions of the traverses are described in Section 9.4. In order to
dampers and temperatures of the coils from changing determine the air flow rates it is necessary to
during the test. In instances in which a cooling coil is measure the area of each traverse plane.
located between a velocity pressure traverse plane
and the fan, as in this example, the flow of the cooling 3. Determine Ps1 by averaging the static pressure
medium should be stopped or its temperature raised measurements made in a traverse of Plane 1. Ps5
to a level sufficient to prevent condensation on the may be determined in a similar manner or by
cooling coil, otherwise the moisture condensed will averaging the pressure measurements at each of
not be properly taken into account in the four static pressure taps. If it is possible to install
determination of fan air flow rate. Refer to Section suitable pressure taps, their use is preferred in the
17.5.2 for additional considerations affecting the test regions of the fan outlet. Due to the abrupt expansion
procedure in this type of installation. in area from Plane 2 to Plane 5, it is assumed that
there is no conversion of velocity pressure at Plane 2
2. Normally, velocity pressure measurements would to static pressure at Plane 5. Therefore, it is assumed
87
AMCA 203-90 (R2007)
that Ps2 = Ps5. Measure the area of Plane 1 for use in tw3a = 71.5°F
calculating Pv1. td3b = 60°F
tw3b = 58°F
4. Measure the dry-bulb and wet-bulb temperatures Ps1 = -2.43 in. wg
at Planes 1, 3a, and 3b. Determine pb for the general Ps5 = 6.55 in. wg
vicinity of the air conditioning unit. These Ps3a = 5.35 in. wg
measurements are used to determine densities at the Ps3b = 5.1 in. wg
planes of interest. The measurements of additional Pv3a = 0.53 in. wg
wet-bulb temperatures were made in this example in
Pv3b = 0.60 in. wg
order to provide data which may be used to
N = 1695 rpm
determine whether the moisture content of the air
changed between Plane 1 and Planes 3a and 3b. A1 = 68.9 ft2
A3a = 5.37 ft2
5. Measure the fan speed and the motor amps, volts, A3b = 6.78 ft2
and if possible, watts. Record all pertinent motor
nameplate data, including volts (NPV), and full load MEASURED MOTOR DATA
amps (FLA). If the motor power output is to be
estimated by using the phase current method Volts = 570, 575, 565
described in Annex K, it is not necessary to measure = 570 av
motor watts; however, it may be necessary to Amps = 81.5, 82.5, 81
disconnect the drive and measure the no load amps = 81.7
(NLA) if the motor is not operating at or near its full NLA = 19
load point. Refer to Annex K.
MOTOR NAMEPLATE DATA
6. Since the performance ratings for the fan section
are based on operation without the fan outlet ducted, 100 hp, 3 phase, 60 hertz
an SEF does not apply for the unducted position. 575 volts, 1790 rpm, 95 FLA
Where: CALCULATIONS
88
AMCA 203-90 (R2007)
89
AMCA 203-90 (R2007)
TEMPORARY DUCT 2 De
WITH SQUARE
CROSS-SECTION, 1.5 De
De = EQUIVALENT
DIAMETER OF DUCT
COMMENTS
1. The subject of the test in this example is the roof be discharging from the ventilator into a region in
ventilator assembly. Before proceeding with the test, which the atmospheric pressure is somewhat
refer to Section 17.4 for considerations affecting the different from that to which all other pressure
test procedure in this type of installation. measurements are referred. When this possibility
exists, it is essential that the static pressure in the
2. Determine Pv3 by using the root mean square of region of the discharging air be measured, referred to
the velocity pressure measurements made in a the same atmospheric pressure as used in all other
traverse of Plane 3, located in the duct which has pressure measurements. In this example, Ps2 was
been installed on the inlet side of the ventilator. measured, referred to the same atmospheric pressure
Determine Ps3 by averaging the static pressure as in the static pressure measurements made at
measurements made in the same traverse. Plane 3.
Procedures for traverses are described in Section
9.4. Measure the area of the traverse plane, A3, 4. Measure the dry-bulb and wet-bulb temperatures
which is located at the tip of the Pitot-static tube. The at the velocity traverse plane. Determine pb for the
duct, temporarily installed for purposes of the test, is general vicinity of the ventilator. These measurements
square in cross-section. Its cross-sectional dimensions are used to determine densities at the planes of interest.
were selected as the maximum permissible for its
installation into the opening in the ventilator mounting 5. Measure the fan speed and the motor amps and
curb. The length of the duct is twice its equivalent volts. Record all pertinent motor nameplate data. For
diameter and the entrance to the duct is flared in oder the horsepower rating of the motor in this example, it
to reduce inlet losses. The installation of a duct of this is recommended that the fan power input be
size and cross-sectional configuration is judged as determined by using the measured watts input to the
creating no significant effect on the performance of motor and motor performance data, obtained from
the ventilator in this example. the motor manufacturer.
3. Ps2, the static pressure at the outlet of the 6. To calculate the Fan Static Pressure:
ventilator, is zero gauge pressure, referred to the
atmospheric pressure in the region of the ventilator Ps = Ps2 - Ps1 - Pv1
outlet. In situations such as this example, the air may = Ps2 - (Ps1 + Pv1)
90
AMCA 203-90 (R2007)
p3 = pb + (Ps3/13.6)
= 29.37 + (-0.085/13.6)
= 29.36 in. Hg
91
AMCA 203-90 (R2007)
2 De
2
3
1.5 De
D2
TEMPORARY DUCT
WITH SQUARE
CROSS-SECTION,
De = EQUIVALENT
DIAMETER OF DUCT
COMMENTS
1. The subject of the test in this example is the such as this example, the air may be discharging
propeller fan assembly. Before proceeding with the from the fan into a region in which the atmospheric
test, refer to Section 17.4 for considerations affecting pressure is somewhat different from that to which all
the test procedure in this type of installation. other pressure measurements are referred. When
this possibility exists, it is essential that the static
2. Determine Pv3 by using the root mean square of pressure in the region of the discharging air be
the velocity pressure measurements made in a measured, referred to the same atmospheric
traverse of Plane 3, located in the duct which has pressure as used in all other pressure
been installed on the inlet side of the fan. Determine measurements. In this example, Ps2 was measured,
Ps3 by averaging the static pressure measurements referred to the same atmospheric pressure as in the
made in the same traverse. Procedures for traverses static pressure measurements made at Plane 3.
are described in Section 9.4. Measure the area of the
traverse plane, A3, which is located at the tip of the 4. Measure the dry-bulb and wet-bulb temperatures
Pitot-static tube. The duct, temporarily installed for at the velocity traverse plane. Determine pb for the
purposes of the test, is square in cross-section, with general vicinity of the fan. These measurements are
side dimension of 1.5 D2. The shape and area of the used to determine densities at the planes of interest.
duct cross-section were selected on the basis of
minimizing the effect of the duct on the performance 5. Measure the fan speed and the motor amps and
of the fan while providing velocity pressure readings volts. Record all pertinent motor nameplate data. For
of measurable magnitudes. The length of the duct is the horsepower rating of the motor in this example, it
twice its equivalent diameter, and the entrance to the is recommended that the fan power input be
duct is flared in order to reduce inlet losses. The determined by using the measured watts input to the
installation of the duct is judged as creating no motor and motor performance data obtained from the
significant effect on the performance of the fan in this motor manufacturer.
example.
6. To calculate the Fan Static Pressure:
3. Ps2, the static pressure at the outlet of the fan, is
zero gauge pressure, referred to the atmospheric Ps = Ps2 - Ps1 - Pv1
pressure in the region of the fan outlet. In situations = Ps2 - (Ps1 + Pv1)
92
AMCA 203-90 (R2007)
Fan direct connected to motor. Motor efficiency data This small value is attributed to the loss at the duct
supplied by motor manufacturer. inlet, and the fan is considered to be operating at free
delivery (Ps = 0).
CALCULATIONS
CONVERSION TO SPECIFIED CONDITIONS
DENSITIES
Qc = 3279 (1725/1775)
For Plane 3 conditions of: = 3187 cfm
It is assumed that ρ1 = ρ3
93
AMCA 203-90 (R2007)
COMMENTS
1. The subject of the test in this example is the roof 4. Measure the dry-bulb and wet-bulb temperatures
ventilator assembly. Before proceeding with the test, in the region of the inside pressure measurement.
refer to Section 17.1 for considerations affecting the Also, determine pb in the same vicinity.
test procedure in this type of installation.
5. Measure the fan speed and the motor amps and
2. Ps3, the static pressure in the vicinity of the volts. Record all pertinent motor nameplate data. For
ventilator inlet, would normally be determined by the horsepower rating of the motor in this example, it
averaging the static pressure measurements made in is recommended that the fan power input be
a Pitot tube traverse. But in this example, a determined by using the measured watts input to the
temporary duct was not installed and the Pitot tube motor and motor performance data obtained from the
traverse could not be accomplished. In this method motor manufacturer.
for testing a nonducted fan, consider the fan static
pressure (Ps) as the differential pressure, as read on 6. Airflow rates are determined from the fan
a manometer, between the pressure measured inside manufacturer’s certified performance ratings. Draw a
the room (Ps3) and the pressure measured outside fan performance curve from these ratings converted
the room in the vicinity of the ventilator outlet (Ps2). to operation at the test values of fan speed and
These pressures are measured at a sufficient entering air density. The basis for these calculations
distance from the ventilator so as to be unaffected by is described in Section 14. The fan airflow rate is then
the velocity of the entering or leaving air. determined by entering this curve at the test values of
fan static pressure and fan power input.
3. Ps2 is considered to be zero gauge pressure, but
since this measurement is actually part of the OBSERVATIONS
differential pressure described in paragraph 2, it is
necessary to make only one density correction; the SITE MEASUREMENTS
correction is to the differential pressure, which is the
fan static pressure. pb = 29.19 in. Hg
td3 = 79°F
tw3 = 63°F
Ps2 - Ps3 = 0.13 in. wg
N = 1735 rpm
94
AMCA 203-90 (R2007)
Volts = 229, 229, 232 The fan static pressure is considered to be the
= 230 av differential static pressure.
Watts = 1390
Ps = Ps2 - Ps3
MOTOR NAMEPLATE DATA = 0.13 in. wg
Use:
.40 1.50
x
x BHP
BHP (H)
x
.30 1.25
.20 1.00
STATIC PRESSURE IN. WG (Ps)
x
.10
SP
0 x
7000 8000 9000
CFM(Q)
96
AMCA 203-90 (R2007)
16D 8D
0.4D
3D Radius D
Static Pressure
Note: Surface finish shall be 32 micro in. or better. The static
orifices may not exceed 0.04 in. diameter. The minimum Pitot
tube stem diameter recognized under this standard shall be
0.10 in. In no case shall the stem diameter exceed 1/30 of the
Total Pressure test duct diameter.
Figure B.1
97
AMCA 203-90 (R2007)
SECTION VIEW
STAINLESS STEEL
TUBING PREFERRED
APPROX. 0.375 in. OD
FLEXIBLE TUBING
TOTAL PRESSURE = READING A
CORRECTED FOR MANOMETER
CALIBRATION
READING A ING B
READ
2. The double reverse tube must be calibrated and used in the same orientation as used in its calibration
3. Also referred to as impact reverse tube, combined reverse tube, and type S tube.
DUCT WALL
1½ in. PIPE
HALF-COUPLING
WELDED TO DUCT
Notes:
99
AMCA 203-90 (R2007)
100
AMCA 203-90 (R2007)
*SEF 1
Ps4 Ps3
FAN STATIC PRESSURE
Ps = - Ps1 - Pv1 + SEF 1
where Ps1 = Ps4 P v3
Pv1 = Pv3
Figure F.1 - Fan with Inlet Duct Only *SEF 1 is due to
Ps2 = 0
no duct at fan outlet
PLANE 3 PLANE 5 PLANE 2 PLANE 1
ALTERNATE
PLANE 3 PLANE 5 PLANE 2 PLANE 1 PLANE 4 PLANE 3
101
AMCA 203-90 (R2007)
10 in. wg
1:1
SLOPE
RATIO
2 in. wg
5:1 SLOPE RATIO
102
AMCA 203-90 (R2007)
Based on an uncertainty equivalent to an indicating column length of 0.05 in. wg in a vertical manometer (1:1 slope
ratio)
8.0
6.0
5.0
4.0
% UNCERTAINTY IN VELOCITY DETERMINATION
3.0
2.0
1.0
MA OPE
0.8 SL
NO RA
0.6 ME TIO
TE
1:1
0.5 R
2:1
0.4
5:1
10
20
:1
:1
0.3
0.2
103
AMCA 203-90 (R2007)
In order to obtain a representative average velocity in a duct, it is necessary to locate each traverse point
accurately. It is recommended that the number of traverse points increase with increasing duct size. The
distributions of traverse points for circular ducts, as indicated below, are based on log-linear Pitot traverse method.
60º X1 X2
X3
X4
D Xn
Xa = D × Ka
Where:
D is the inside diameter of the duct
Ka is the factor corresponding to the duct size and the traverse point location as indicated in the table below
NUMBER OF
INSIDE TRAVERSE
DIAMETER POINTS IN K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 K13 K14 K15 K16
OF DUCT EACH OF 3
DIAMETERS
LESS THAN
8 .021 .117 .184 .345 .655 .816 .883 .979
8 ft.
8 ft.
THROUGH 12 .014 .075 .114 .183 .241 .374 .626 .759 .817 .886 .925 .986
12 ft.
GREATER
16 .010 .055 .082 .128 .166 .225 .276 .391 .609 .724 .775 .834 .872 .918 .945 .990
THAN 12 ft.
The recommended minimum number of traverse points for rectangular ducts is indicated below in Figure H.3. For
rectangular ducts with cross-sectional areas of 24 square feet and less, the recommended minimum number is 24.
For cross-sectional areas greater than 24 square feet, the minimum number of points increases as indicated in
Figure H.3. The points are to be located in the centers of equal areas with the areas as nearly square as practical
(see Figure H.2). If the flow conditions at the traverse plane are less than satisfactory, the accuracy of the
determination of flow rate may be improved by using more than the recommended minimum number of points.
Fewer points may be used if the flow is very uniform; however, the maximum area covered per point should not
exceed 3 square feet.
Y Y
X
2
2
100
90
80
70
NUMBER OF TRAVERSE POINTS
60
50
40
30
25
20
15
10
10 15 20 25 30 40 50 60 70 80 100 150 200 250 300
105
AMCA 203-90 (R2007)
Approximate Precision
Range
No. Measurement Means Application F F Limitations
1. Glass-stem thermometers
Mercury-glass thermometer Temp of gases and liquids by contact -38/575 Less than In gases, accuracy af-
0.1 to 10 fected by radiation
Alcohol-glass thermometer ” -100/100 ” ”
Pentane-glass thermometers ” -200/70 ” ”
Jena or quartz mercury nitrogen
thermometers ” -38/1000 ” ”
2. Gas thermometer Primary standard -459/1000 Less than Requires consid-
0.01 erable skill to use
3. Resistance thermometers
Platinum-resistance thermometer Precision; remote readings; temp of -320/1800 Less than High cost; accuracy
fluids or solids by contact 0.02 to 5 affected by radiation
in gases
Nickel-resistance thermometer Remote readings; temp by contact -150/300 0.3 Accuracy affected by
radiation in gases
Thermistors ” Up to 600 0.1
4. Thermocouples
Pt-Pt-Rh thermocouple Standard for thermocouples 500/3000 0.1 to 5 High cost; also, re-
quires expensive
measuring device
Chromel-alumel thermocouple General testing of high temp; remote Up to 2200 0.1 to 15 Less accurate than
rapid readings by direct contact above
Iron-constantain thermocouple ” Up to 1500 0.1 to 15 Subject to oxidation
Copper-constantan thermocouple Same as above, especially suited for Up to 700 0.1 to 15
Chromel-constantan thermocouple low temp
5. Beckman thermometers For differential temp in same applica- 9 diff 0.018 Must be set for temp
(metastatic) tions as in glass stem thermometer to be measured
6. Bimetallic thermometers For approx temp 0/1000 1, usually Time lag; unsuitable
much more for remote use; un-
reliable
7. Pressure-bulb thermometers
Gas-filled bulb Remote-testing -100/1000 2 Caution must be ex-
ercised so that in-
stallation is correct
Vapor-filled bulb ” 20/500 2 ”
Liquid-filled bulb ” -50/2100 2 ”
8. Optical pyrometers For intensity of narrow spectra band 1500 upward 15
of high temp radiation (remote)
9. Radiation pyrometers For intensity of total high temp radi- Any range
ation (remote)
10. Seger cones (fusion pyrometers) Approx temp (within temp source) 1000/3600 50
11. Indicating crayons Approx temp (in surface) 125/900 ±1%
12. Melting and boiling points of Standards All except ex- Extremely For laboratory use
materials tremely high precise only
temp
106
AMCA 203-90 (R2007)
107
AMCA 203-90 (R2007)
Annex K. Phase Current Method for Use Equation A to estimate the Hmo for motors of 5
Estimating the Power Output of Three horsepower and greater, operating at 90% or more of
FLA. The uncertainties will be less than 5%.
Phase Fan Motors
Use the average of Equation A and Equation B to
The power output of three phase motors can be
estimate the Hmo for all motors operating at less than
estimated based on the relationship of motor current
and motor power output. Two equations can be used 90% of FLA and for 3 horsepower and smaller motors
in estimating the motor power output. The equations operating above 90% of FLA. An estimated Hmo less
are as follows: than 50% of NPH can contain 15% uncertainties or
greater.
Equation A:
Figure K.1 represents the relationship of motor
current and motor power output. The “dashed” lines
⎛ Measured amps ⎞ ⎛ Measured volts ⎞ between 0% NPH and 100% NPH for motor sizes
Hmo = NPH ⎜ ⎟⎜ ⎟
⎝ FLA ⎠⎝ NPV ⎠ shown represents Equation B. The solid lines
between these same end points for the motor sizes
Where: shown represent the general shape of typical motor
calibration amp/load curves. The solid line from
Hmo = motor power output 100% NPH and 100% FLA to 0% NPH and 0% FLA
NPH = nameplate horsepower represents Equation A. These curves indicate that if
FLA = full load amps you average the results of Equation A and Equation
NPV = nameplate volts B for a specific measured amp draw, that your results
measured volts = average of the measured phase approach the typical calibration curve. It also points
volts out that the uncertainties are low if just Equation A is
measured amps = average of the measured phase used above 90% FLA, especially in the larger integral
amps motor horsepowers.
108
AMCA 203-90 (R2007)
100
90
RATED
HORSEPOWER
1
80 2
70
3
60
5
50
10
40
400
30
2500
20
10
0
0 10 20 30 40 50 60 70 80 90 100
% NAMEPLATE HORSEPOWER
CAUTION: THIS CHART IS REPRESENTATIVE ONLY! SINCE THE AMP-LOAD CHARACTERISTICS OF THE
SAME SIZE MOTOR WILL VARY BETWEEN THE VARIOUS MOTOR MANUFACTURERS, IT CANNOT BE USED
TO DETERMINE THE HORSEPOWER OUTPUT OF A MOTOR. USE THE EQUATIONS AS DIRECTED ON THE
PREVIOUS PAGE.
109
AMCA 203-90 (R2007)
Annex L. Estimated Belt Drive Loss 3) A larger belt section than required will increase
the drive loss.
Drive loss is defined as follows:
4) A badly undertensioned drive will increase the
Percent drive loss equals power to driving sheave drive loss.
minus power from driven sheaves times 100, divided
by power to driving sheave. 5) Misaligned drives will increase the drive loss.
There are several things which can affect belt drive Drive loss is manifested as heat in belt drives. Under
efficiencies. Some of these are: ambient conditions of less than 100°F, well designed
drives that operate efficiently will be warm to the
1) Over-designed drives. This was considered good touch immediately after being shut down. If the drive
practice at one time because the drive would last is uncomfortable to the touch (approximately 140°F
longer. It will still last longer but it is more or more), then the drive loss is high. Obviously poorly
inefficient. tensioned and misaligned drives should be corrected
before estimating brake horsepowers and drive
2) Multiple belts on subminimum diameter sheaves losses.
are less efficient than fewer belts on larger
diameter sheaves. Both the National Electric
Motor Association and the Rubber
Manufacturer’s Association publish data dealing
with minimum recommended sheave diameters.
As these minimum sheave diameters are
approached, the drive loss becomes greater.
110
AMCA 203-90 (R2007)
100
80
60
40
DRIVE LOSS, % MOTOR POWER OUTPUT*
30
15
10
8
6
4
3
1.5
1
0.3 0.4 0.6 0.8 1 2 3 4 6 8 10 20 30 40 60 80 100 200 300 400 600
*Drive losses are based on the conventional V-belt, which has been the “work horse” of the drive industry for
several decades.
EXAMPLE
111
AMCA 203-90 (R2007)
The barometric pressure, pb, measured for the Barometric pressure, obtained from a nearby
atmosphere to which Ps1 is referred, is 28.15 in. Hg. airport, is 29.24 in. Hg at sea level.
The absolute pressure at the fan inlet is: Using the data in Figure N.3 in Annex N, the
barometric pressure at 1000 ft above seal level is:
p1 = pb + (Ps1 /13.6)
= 28.15 + (-8.75/13.6) pb = 29.24 × 0.964
= 27.51 in. Hg = 28.19 in. Hg
Use Figure N.2 in Annex N to obtain saturated vapor The absolute pressure at the fan inlet is:
pressure, pe, of 1.562 in. Hg for the wet-bulb
temperature of 93°F. p1 = pb + (Ps1/13.6)
= 28.19 + (-15/13.6)
Use the modified Apjohn equation for partial vapor = 27.09 in. Hg
pressure, pp, to obtain:
Dry air at 29.92 in. Hg and 70°F has a density of
pp = pe - p1 (td1 - tw1)/2700 0.075 lbm/ft3.
= 1.562 - 27.51 (146 - 93)/2700
= 1.022 in. Hg Consider the density of air to be directly
proportional to absolute pressure and inversely
ρ1 is calculated by using perfect gas relationships: proportional to absolute temperature. The density
of the air at the fan inlet is calculated as follows:
The procedures for the determination of the density Barometric pressure, obtained from a nearby
of air that are described in Section M.2 are valid for airport, is 29.66 in. Hg at sea level.
dry air, air that is saturated with water vapor and air
that is partially saturated with water vapor. This Using the data in Figure N.3 in Annex N, the
section contains alternate procedures for cases in barometric pressure at 1500 ft above sea level is:
which it is known that the air is either dry or saturated.
Knowledge that the air is either dry or saturated pb = 29.66 × 0.947
eliminates the usual requirement of the wet-bulb = 28.09 in. Hg
temperature determination; however, it should be
noted that an incorrect assumption of either of these The absolute pressure at the fan inlet is:
conditions can result in a significant uncertainty in the
density determination. p1 = pb + (Ps1/13.6)
= 28.09 + (-6.75/13.6)
EXAMPLE M3.1 = 27.59 in. Hg
Dry air is entering a fan inlet, located at an elevation Refer to Figure N.4 in Annex N to obtain saturated
of 1000 ft above sea level. The pressure and air density of 0.06868 at 103°F and 29.92 in. Hg.
temperature at the inlet are:
Assuming the density of saturated air to be directly
Ps1 = -15 in. wg proportional to absolute pressure, the density at the
td1 = 95°F fan inlet is calculated as follows:
113
AMCA 203-90 (R2007)
Assuming the density of saturated air to be directly The apparent molecular weight of the gas is
proportional to absolute pressure is an determined as follows:
approximation. The uncertainty in the density
determination as a result of this approximation Volume Molecular
increases with increasing temperature and Component Fraction × Weight = lb/mole
increases with increasing variation between the
actual absolute pressure and 29.92 in. Hg, which is CO2 0.055 44 2.42
the stated pressure for the data in Figure N.4. The CO 0.01 28 0.28
uncertainty will be approximately 1% or less under O2 0.15 32 4.80
the following conditions: H2 0.01 2 0.02
N2 0.775 28 21.70
• At 120°F and at an absolute pressure within 20%
of 29.92 in. Hg
• At 150°F and at an absolute pressure within 10% 1.00 29.22
of 29.92 in. Hg
• At 180°F and at an absolute pressure within 4% Apparent molecular weight = (29.22/1.00)
of 29.92 in. Hg = 29.22
M.4 DETERMINATION OF THE DENSITY OF A The density of the gas at 70°F and 29.92 in. Hg is
GAS OTHER THAN AIR calculated as follows:
The determination of the density of a gas other than Apparent molecular weight 29.22
=
air may require the use of complex equipment. 386.7 386.7
Unless specifically qualified, an expert should be
consulted for the proper use of the equipment. If the
gas is a complex mixture of various consitutuents, as = 0.0756 lbm/ft 3
found in certain industrial processes, it is suggested
that the company chemist be consulted for the gas Using the data in Figure N.3 in Annex N, the
analysis. Particular care should be used if the gas is barometric pressure at 2000 ft above sea level is:
toxic, corrosive or explosive; and in these cases,
consideration should be given to substituting air for pb = 29.92 × 0.930
the test. = 27.83 in. Hg
The first two examples in this section illustrate gas The absolute pressure at the fan inlet is:
density determinations based on analyses that
provide the relative amounts of the gas constituents. p1 = pb + (Ps1/13.6)
Typical flue gas density data, which is provided in = 27.83 + (-22/13.6)
Figure N.6 in Annex N, is illustrated in Example M4.3. = 26.21 in. Hg
Since the actual density may be significantly different
from the density determined by using typical data, it Consider the density of the gas to be directly
is recommended that the typical data be used only in proportional to absolute pressure and inversely
the even that more specific information is not proportional to absolute temperature. The density of
available. the gas at the fan inlet is calculated as follows:
114
AMCA 203-90 (R2007)
p1 = pb + (Ps1/13.6)
= 29.35 + (-19.5/13.6)
= 27.92 in. Hg
115
AMCA 203-90 (R2007)
116
AMCA 203-90 (R2007) AMCA 203-90 (R2007)
tw pe tw pe tw pe tw pe tw pe
°F in. Hg °F in. Hg °F in. Hg °F in. Hg °F in. Hg
Figure N.2 - Thermodynamic Properties of Water at Absolute Vapor Pressures, Inches of Mercury
117 118
AMCA 203-90 (R2007)
40 0.060
38 0.061
36 0.062
1. Calculate wet-bulb depression. Enter chart at the left.
34 2. Proceed horizontally to the appropriate dry-bulb 0.063
temperature.
32 3. Read vertically to the absolute pressure. 0.064
4. Then read horizontally to the density.
30 Example 0.065
g
• Given: td = 54°F; tw = 50°F; pb = 29.9 in. Hg
28 28.0 0.066
in. H
28.2 • Solution: Wet-bulb depression = 4°F; proceed hori-
28.4 zontally to 54°F dry-bulb temperature;
26 read vertically to 29.9 in. Hg; read horizon- 0.067
URE
28.6 tally to the density -- ρ = 0.0769 lbm/ft3.
SS
28.8
24 29.0 0.068
PRE
29.2
TE
22 29.4 0.069
OLU
29.6
29.8
ABS
20 0.070
30.0
18 0.071
AIR DENSITY, lbm/ft3
16 0.072
WET-BULB DEPRESSION, °F
14 0.073
12 0.074
10 0.075
8 0.076
6 0.077
4 0.078
2 0.079
98 96 94 92 90 88 86 84 82 80 78 76 74 72 70 68 66 64 62 60 58 56 54 52 50 48 46 44 42
0 0.080
DRY-BULB TEMPERATURE, °F
Note: Specific gravity of standard air at sea level and 29.92 in. Hg = 1.00
1. Robert Jorgensen, ed., Fan Engineering, 7th ed. (Buffalo, NY, Buffalo Forge Co., 1970) p.8 - Reprinted by Permission
119
AMCA 203-90 (R2007)
WEIGHT IN A WEIGHT IN A
WEIGHT OF WEIGHT OF
CUBIC FOOT VOLUME CUBIC FOOT VOLUME
THE VAPOR THE VAPOR
OF MIXTURE OF MIXTURE
Temp ft3/lb Temp ft3/lb
°F OF °F OF
TOTAL lb/lb lb/lb TOTAL lb/lb lb/lb
DRY AIR VAPOR DRY AIR VAPOR
WEIGHT DRY AIR OF OF WEIGHT DRY AIR OF OF
lb lb lb lb
lb DRY AIR MIXTURE lb DRY AIR MIXTURE
-25 .09134 .000018 .09136 10.95 .00020 .00020 46 .07768 .000509 .07819 12.87 .00655 .00651
-20 .09025 .000024 .09027 11.07 .00027 .00027 47 .00750 .000527 .07803 12.90 .00680 .00675
-15 .08922 .000031 .08925 11.21 .00035 .00035 48 .07731 .000545 .07785 12.93 .00705 .00700
-10 .08820 .000041 .08824 11.34 .00046 .00046 49 .07714 .000567 .07771 12.96 .00734 .00728
-5 .08723 .000053 .08728 11.46 .00061 .00061 50 .07694 .000587 .07753 12.99 .00762 .00756
0 .08625 .000068 .08632 11.59 .00080 .00080 51 .07676 .000608 .07737 13.02 .00792 .00786
5 .08529 .000087 .08538 11.72 .00102 .00102 52 .07657 .000632 .07720 13.06 .00823 .00819
10 .08434 .000110 .08445 11.85 .00130 .00130 53 .07637 .000651 .07702 13.09 .00854 .00845
15 .08340 .000140 .08354 11.99 .00168 .00168 54 .07620 .000675 .07687 13.12 .00884 .00877
20 .08247 .000176 .08264 12.12 .00213 .00213 55 .07600 .000700 .07670 13.15 .00921 .00913
21 .08230 .000185 .08248 12.15 .00225 .00224 56 .07582 .000723 .07654 13.19 .00952 .00943
22 .08210 .000193 .08229 12.18 .00235 .00234 57 .07562 .000749 .07637 13.22 .00989 .00980
23 .08193 .000202 .08213 12.20 .00246 .00245 58 .07544 .000775 .07622 13.25 .01026 .01016
24 .08173 .000213 .08194 12.23 .00260 .00259 59 .07524 .000801 .07604 13.29 .01063 .01052
25 .08156 .000222 .08178 12.26 .00272 .00271 60 .07506 .000829 .07589 13.32 .01103 .01091
26 .08136 .000233 .08159 12.29 .00285 .00284 61 .07486 .000857 .07572 13.35 .01143 .01130
27 .08117 .000243 .08141 12.32 .00300 .00299 62 .07468 .000886 .07557 13.39 .01185 .01171
28 .08099 .000254 .08124 12.34 .00314 .00313 63 .07447 .000916 .07539 13.42 .01229 .01214
29 .08083 .000264 .08109 12.37 .00328 .00327 64 .07429 .000947 .07524 13.46 .01273 .01257
30 .08063 .000277 .08090 12.40 .00345 .00344 65 .07408 .000979 .07506 13.49 .01320 .01303
31 .08043 .000290 .08072 12.43 .00362 .00361 66 .07390 .001012 .07491 13.53 .01368 .01349
32 .08025 .000303 .08055 12.46 .00378 .00376 67 .07369 .001045 .07473 13.57 .01417 .01397
33 .08006 .000315 .08038 12.49 .00393 .00392 68 .07350 .001080 .07458 13.60 .01468 .01447
34 .07989 .000327 .08022 12.51 .00409 .00408 69 .07330 .001115 .07441 13.64 .01520 .01497
35 .07970 .000339 .08004 12.54 .00426 .00425 70 .07310 .001152 .07425 13.68 .01576 .01551
36 .07952 .000353 .07987 12.57 .00444 .00442 71 .07290 .001189 .07409 13.71 .01630 .01604
37 .07933 .000364 .07969 12.60 .00460 .00458 72 .07270 .001229 .07393 13.75 .01691 .01662
38 .07916 .000380 .07954 12.63 .00480 .00478 73 .07250 .001268 .07377 13.79 .01748 .01717
39 .07897 .000394 .07936 12.66 .00499 .00496 74 .07229 .001310 .07360 13.83 .01812 .01780
40 .07880 .000409 .07921 12.69 .00519 .00516 75 .07208 .001352 .07343 13.87 .01876 .01841
41 .07860 .000425 .07902 12.72 .00541 .00538 76 .07188 .001395 .07328 13.91 .01941 .01904
42 .07843 .000440 .07887 12.75 .00561 .00558 77 .07166 .001439 .07310 13.95 .02008 .01968
43 .07825 .000456 .07871 12.78 .00583 .00579 78 .07144 .001485 .07293 13.99 .02079 .02036
44 .07805 .000473 .07852 12.81 .00606 .00602 79 .07124 .001532 .07277 14.03 .02150 .02106
45 .07788 .000491 .07837 12.84 .00630 .00626 80 .07104 .001579 .07262 14.08 .0223 .02174
Figure N.4 - Weights of Air, Water Vapor, and Saturated Mixture of Air and
Water Vapor at Different Temperatures and 29.92 in. Hg
120
AMCA 203-90 (R2007)
WEIGHT IN A WEIGHT IN A
WEIGHT OF WEIGHT OF
CUBIC FOOT VOLUME CUBIC FOOT VOLUME
THE VAPOR THE VAPOR
OF MIXTURE OF MIXTURE
Temp ft3/lb Temp ft3/lb
°F OF °F OF
TOTAL lb/lb lb/lb TOTAL lb/lb lb/lb
DRY AIR VAPOR DRY AIR VAPOR
WEIGHT DRY AIR OF OF WEIGHT DRY AIR OF OF
lb lb lb lb
lb DRY AIR MIXTURE lb DRY AIR MIXTURE
81 .07081 .001629 .07244 14.12 .02301 .02249 116 .06186 .004427 .06629 16.16 .07157 .06678
82 .07059 .001680 .07227 14.16 .02380 .02325 117 .06154 .004548 .06609 16.24 .07390 .06882
83 .07038 .001733 .07211 14.21 .02462 .02403 118 .06124 .004669 .06591 16.32 .07625 .07084
84 .07015 .001785 .07193 14.26 .02545 .02482 119 .06092 .004794 .06571 16.41 .07869 .07296
85 .06993 .001840 .07177 14.30 .02631 .02566 120 .06060 .004921 .06552 16.50 .08121 .07511
86 .06970 .001898 .07160 14.34 .02723 .02651 121 .06027 .005049 .06532 16.58 .08376 .07729
87 .06947 .001954 .07142 14.39 .02813 .02736 122 .05995 .005183 .06513 16.68 .08646 .07958
88 .06925 .002014 .07126 14.44 .02908 .02826 123 .05960 .005319 .06492 16.77 .08925 .08194
89 .06902 .002072 .07109 14.48 .03002 .02915 124 .05927 .005456 .06473 16.87 .09204 .08428
90 .06880 .002139 .07094 14.53 .03109 .03015 125 .05892 .005598 .06452 16.96 .09502 .08677
91 .06855 .002201 .07075 14.58 .03211 .03111 130 .05713 .006355 .06349 17.49 .11125 .10010
92 .06832 .002267 .07058 14.63 .03318 .03212 135 .05524 .007195 .06244 18.10 .13026 .11523
93 .06809 .002334 .07042 14.69 .03428 .03314 140 .05319 .008128 .06132 18.79 .15280 .13255
94 .06785 .002404 .07025 14.73 .03543 .03422 145 .05100 .009162 .06016 19.60 .17966 .15230
95 .06760 .002474 .07007 14.79 .03660 .03531 150 .04865 .010303 .05895 20.55 .21178 .17478
96 .06736 .002546 .06991 14.84 .03780 .03642 155 .04612 .011547 .05767 21.67 .25038 .20022
97 .06711 .002620 .06973 14.90 .03904 .03757 160 .04340 .012937 .05634 23.03 .29810 .22962
98 .06688 .002692 .06957 14.95 .04025 .03870 165 .04048 .014436 .05492 24.69 .35660 .26285
99 .06660 .002770 .06931 15.01 .04159 .03993 170 .03734 .016118 .05346 26.77 .43168 .30150
100 .06634 .002853 .06919 15.07 .04300 .04124 175 .03398 .017926 .05191 29.43 .52750 .34530
101 .06610 .002937 .06904 15.12 .04443 .04255 180 .03035 .019905 .05036 32.94 .65580 .39525
102 .06583 .003019 .06885 15.18 .04586 .04385 185 .02645 .022062 .04851 37.78 .83410 .45425
103 .06557 .003106 .06868 15.25 .04737 .04523 190 .02228 .024393 .04667 44.85 1.0948 .52270
104 .06530 .003193 .06849 15.31 .04890 .04662 195 .01779 .026957 .04475 56.20 1.5153 .60240
105 .06504 .003283 .06832 15.37 .05048 .04806 200 .01297 .029730 .04270 77.11 2.2923 .69660
106 .06477 .003375 .06814 15.44 .05212 .04953 205 .00782 .032715 .04064 127.9 4.1838 .80500
107 .06451 .003470 .06798 15.50 .05379 .05105 210 .00232 .035942 .03836 431.0 15.493 .93700
108 .06421 .003568 .06778 15.57 .05556 .05264 212 .00000 .037298 .03730 ____ Inf. 1.0000
109 .06394 .003666 .06761 15.64 .05734 .05422
110 .06364 .003766 .06741 15.71 .05917 .05587
Figure N.4 - Weights of Air, Water Vapor, and Saturated Mixture of Air and
Water Vapor at Different Temperatures and 29.92 in. Hg
121
AMCA 203-90 (R2007)
Note: Approximate average decrease in density per 0.1°F rise in dry-bulb temperature equals .000017 lbm/ft3.
122
AMCA 203-90 (R2007)
Note: Approximate average decrease in density per 0.1°F rise in dry-bulb temperature equals .000017 lbm/ft3.
123
AMCA 203-90 (R2007)
OIL 0.075
BAGASSE 0.070
LIGNITE 0.073
WOOD 0.070
The above densities at 70°F and 29.92 in. Hg are based on average fuel analyses and moisture contents
124
AMCA 203-90 (R2007)
BLAST AREA
DISCHARGE DUCT
OUTLET AREA
CUTOFF
25%
50%
75%
CENTRIFUGAL FAN
100% EFFECTIVE DUCT LENGTH
AXIAL FAN
To calculate 100% effective duct length, assume a minimum of 2½ duct diameters for 2500 fpm or less. Add 1 duct
diameter for each additional 1000 fpm.
If the duct is rectangular, with side dimensions equal to a and b, the equivalent duct diameter is equal to (4ab/π)0.5
125
AMCA 203-90 (R2007)
CASING
BACKPLATE
RIM
HUB INLET
MOTOR BLADE
GUIDE VANE
IMPELLER
INLET BELL
CASING
BLADE
DIFFUSER
HUB
MOTOR
IMPELLER
CASING
BLADE
HUB
GUIDE VANE
Vaneaxial Fan-Belt Drive
IMPELLER
MECHANISM FOR
CONTROLLING
INLET BOX BEARINGS GUIDE VANES BLADE ANGLE
FAN
CASING
INNER CYLINDER
IMPELLER
DIFFUSER
Vaneaxial Mechanical Draft Fan
Figure R.1 - Common Terminology for Axial and Tubular Centrifugal Fans
126
AMCA 203-90 (R2007)
HOUSING
DIVERTER
FF
TO
CU
CENTER PLATE
BLAST AREA
DISCHARGE
OUTLET AREA
SIDE SHEET
BACKPLATE
BLADE TO
FF
CU
INLET
SCROLL
IMPELLER
FRAME
RIM
BEARING
SUPPORT
INLET COLLAR
+ +
DRIP TRAY
HOT DECK + +
+
+
COLD DECK
CC
+ + +
FLEXIBLE CONNECTION
AS ACCESS SECTION EXT F & BP EXTERNAL FACE AND BYPASS DAMPER FS FAN SECTION
CS COIL SECTION INT F & BP INTERNAL FACE AND BYPASS DAMPER FB FILTER BOX
CC COOLING COIL ELIM ELIMINATORS MB MIXING BOX
HC HEATING COIL SS SPRAY SECTION
MOTOR DESCRIPTION: Mfgr., Nameplate Data (Ident. No., hp, volts, FLA, . . . ), Performance Data
Reference, . . . . .
DRIVE DESCRIPTION: Type, Mfgr., Ident. No., Size, . . . . .
REFERENCE DRAWINGS OR
SKETCHES OF INSTALLATION: System Configuration with Dimensions, Measurement Plane
Locations, . . . . .
MEASUREMENTS
AMBIENT DATA: Barometric Pressure, Dry-Bulb Temp., Wet-Bulb Temp, . . . . .
FAN SPEED
•
•
•
•
n
TOTAL
AVERAGE
CALCULATIONS: (Refer to the various sections of this publication for the appropriate calculation
procedures.)
130
AMCA 203-90 (R2007)
131
AMCA 203-90 (R2007)
T.4.2 Dry-bulb temperature. The estimated The estimated uncertainty is based on a broad range
uncertainty in measuring dry-bulb temperature is of duct sizes, accessibility, and the rigidity of ducts
between 0.5% of absolute temperature minimum and under pressure.
2.0% of absolute temperature maximum.
T.4.8 Velocity pressure. An allowance of 2.0%
ed = 0.005 (min) to 0.02 (max) minimum to 5.0% maximum of the reading is
estimated for the mental averaging performed on a
The estimated uncertainty range is based on a broad fluctuating reading. An allowance of 1.0% minimum
temeprature range and the likelihood of stratification. to 2.0% maximum of the reading is estimated for
calibrated manometer uncertainty and relocation of
T.4.3 Web-bulb depression. The estimated the instrument after calibration. In addition, an
uncertainty in measuring wet-bulb depression is allowance of 0.5% minimum to 10.0% maximum of
between 5°F minimum and 10°F maximum. the reading is estimated for instrument precision. No
allowance is included for yaw on the assumption that
ew = 5/(td - tw) (min) to 10/(td - tw) (max) the Pitot-static tube is aligned within 10 degrees of
streamlines. A combined uncertainty can be written
The estimated uncertainty range is based on a broad as:
temperature range with the associated difficulties in
determining wet-bulb readings at high or low ef (min) = [(0.02)2 + (0.01)2 + (0.005)2]0.5
temperatures and the likelihood of stratification. = 0.0229
T.4.4 Fan speed. The estimated uncertainty in ef (max) = [(0.05)2 + (0.02)2 + (0.10)2]0.5
measuring fan speed is between 0.5% minimum and = 0.1136
1.0% maximum.
T.4.9 Static pressure. An allowance of 1.0%
eN = 0.005 (min) to 0.01 (max) minimum to 5.0% maximum of the reading is
estimated for the mental averaging performed on a
The uncertainty range in fan speed is estimated on fluctuating reading. An allowance of 1.0% minimum
the basis of portable instrumentation accuracy and to 2.0% maximum of the reading is estimated for
an allowance for fluctuation in fan speed. calibrated manometer uncertainty and relocation of
the instrument after . In addition, a tolerance of 10%
T.4.5 Power input. The estimated uncertainty in minimum to 20.0% maximum of the fan velocity
measuring power input is betwen 3.0% minimum and pressure should cover the influence of Pitot-static
7.0% maximum. tube yaw or velocity influence on static pressure taps
and other possible effects. A combined uncertainty
eh = 0.03 (min) to 0.07 (max) can be written as:
The estimated uncertainty range is based on the eg (min) = {(0.01)2 + (0.01)2 + (0.005)2 +
various measurement methods and their respective [0.1 Pv/(Ps2 - Ps1)]2}0.5
accuracies, estimated drive losses, and the broad = {0.000225 + [0.1 Pv/(Ps2 - Ps1)]2}0.5
horsepower range encountered in the field.
eg (max) = {(0.05)2 + (0.02)2 + (0.02)2 +
T.4.6 Pitot traverse. A properly performed field [0.2 Pv/(Ps2 - Ps1)]2}0.5
traverse is estimated to have an accuracy of 1.5% = {0.0033 + [0.2 Pv/(Ps2 - Ps1)]2}0.5
minimum to 7.5% maximum.
132
AMCA 203-90 (R2007)
Where the denominator in the final term in each Assuming Δ70.73 and ΔR are both zero:
equation will involve Ps2 or Ps5 and Ps1 or Ps4,
whichever are measured. eρ = (eb2 + ev2 + ed2)0.5
V = 1.0 - 0.378 {(pe/pb) - [(td - tw)/2700]} T.5.3 Fan static pressure. Fan static pressure
directly involves static pressure measurements.
Uncertainties in density will produce a first-power
For random and independant uncertainties in
uncertainty in fan static pressure while uncertainties
products, the combined uncertainty is determined as
in fan speed will produce a second-power uncertainty
follows:
in fan static pressure when making fan law
conversions. Combining:
Δρ/ρ = {(Δ70.73/70.73)2 + (Δpb/pb)2 + (ΔV/V)2 +
(ΔR/R)2 + [Δtd/(td + 460)]2}0.5 ep = [eg2 + eρ2 + (2eN)2]0.5
Table T.1
eb 0.003 0.007
ed** 0.005 0.020
eW 5/(td - tw) 10/(td - tw)
eN 0.005 0.010
eh 0.030 0.070
ec 0.015 0.075
eA 0.010 0.020
ef 0.0229 0.1136
eg {0.000225 + [0.1 Pv/(Ps2 - Ps1)]2}0.5 {0.0033 + [0.2 Pv/(Ps2 - Ps1)]2}0.5
* These uncertainties do not account for the effect of swirl at the fan inlet. This situation must be corrected in order
to produce acceptable fan-system performance (see Section 5).
133
AMCA 203-90 (R2007)
In order to simplify the application of this uncertainty The uncertainty calculations lead to absolute
analysis to the results of field tests, the above uncertainties in fan flow rate, fan static pressure, and
equation was developed on the basis of tests in fan power input that can be applied directly to the
which static pressure measurements are made at a corresponding test results. The uncertainty results
single plane, as would be the case in which a fan is can then be plotted as rectangles around the test
ducted on one side only. However, the equation is point. Intersection of the rectangles with the quoted
reasonably accurate for all other fan-system fan performance within the limitations of a field test.
configurations. See the examples in Section T.7.
T.6 Summary
134
AMCA 203-90 (R2007)
135
AMCA 203-90 (R2007)
GRAPHICAL PRESENTATION
ΔQ = 158 cfm
Hc = 18.90 hp
ΔH = 0.64 hp
Qc + ∆Q
Qc - ∆Q
Qc
QUOTED FAN
Q, FAN FLOW RATE
PERFORMANCE
CURVES
Hc + ∆H
Hc
H, FAN POWER INPUT
Hc - ∆H
Qc - ∆Q Qc + ∆Q
Qc
Q, FAN FLOW RATE
Figure T.1
136
AMCA 203-90 (R2007)
137
AMCA 203-90 (R2007)
GRAPHICAL PRESENTATION
TEST POINT
MAXIMUM UNCERTAINTY RANGE
Qc = 25964 cfm
ΔQ = 2526 cfm
Psc + ∆P
Psc = 2.54 in. wg
Psc ΔP = 0.20 in. wg
Ps, FAN STATIC PRESSURE
Hc = 17.11 hp
Psc - ∆P ΔH = 1.36 hp
Qc - ∆Q
Qc + ∆Q
Qsc
Q, FAN FLOW RATE QUOTED FAN
PERFORMANCE
CURVES
Hc + ∆H
H, FAN POWER INPUT
Hc
Hc - ∆H
Qc - ∆Q Qc + ∆Q
Qsc
Q, FAN FLOW RATE
Figure T.2
138
AIR MOVEMENT AND CONTROL
ASSOCIATION INTERNATIONAL, INC.
30 West University Drive
Arlington Heights, IL 60004-1893 U.S.A.
Tel: (847) 394-0150 Fax: (847) 253-0088
E-Mail : [email protected] Web: www.amca.org
The Air Movement and control Association International, Inc. is a not-for-profit international association of the
world’s manufacturers of related air system equipment primarily, but limited to: fans, louvers, dampers, air
curtains, airflow measurement stations, acoustic attenuators, and other air system components for the industrial,
commercial and residential markets.