Toshiba Technical Handbook Version 14 1 2 PDF
Toshiba Technical Handbook Version 14 1 2 PDF
Toshiba Technical Handbook Version 14 1 2 PDF
Version 14.1.2
Index Page
Make Up of Model Number 3
Mechanical Specifications-RAS R410A Outdoor Units 4
Performance & Electrical Specifications - RAS R410A Single Splits 4
Performance & Electrical Specifications - RAS R410A Multi Splits 4
RAS R410A Multi Split System Combinations 5
Acoustic Data - RAS Indoor Units 5
RAS - Auto Restart Function 6
Fault Codes - RAS “N” Series 6
Mechanical Specifications - DI/SDI R410A Single Splits 7
Performance & Electrical Specifications - DI / SDI R410A Single Splits 7
Electrical Specifications - DI/SDI R410A Multi Splits 8
Acoustic Data – DI/SDI Indoor Units 8
Mechanical & Electrical Data - Air-to-Air Heat Exchangers 9
Digital/Super Digital Replacement Refrigerant Pipe Sizing 10
Digital/Super Digital Inverter Multi Split System Combinations 11
Digital/Super Digital Inverter Twin Splits 12
Digital/Super Digital Inverter Triple Splits 14
Digital Inverter Quad Splits 16
Digital/Super Digital Multi Split System Wiring Schematic 17
VRF System Make Up Chart 18
Electrical Data - VRF Outdoor Units 19
VRF Additional Refrigerant Charge Amount 19
VRF Additional Refrigerant Charge Calculations 20
Acoustic Data - MMY Indoor Units 23
Common Sensor Characteristics 24
Trouble Shooting - RAV Series 25
Apps Store Fault Codes - All Commercial & VRF Systems 28
Fault Codes – All Commercial & VRF Systems 29
Error Detected by TCC-Link Central Controller 43
Step By Step Wiping/Re-addressing Of VRF Systems 44
Priority Mode (SMMSi Only) 44
Outdoor Fan High Static Pressure Setup 44
Compressor or Outdoor Fan Motor Backup Isolation Setting 44
VRF Rotary Dial Data Display SMMSi, SHRMi & Mini SMMS 45
TCC-net Controller Guidelines 46
System Configuration Menu 47
TCCJ Optional Control Accessories 49
TCC-Net Control - Standard Wired Controller 50
Controller Configuration - Remote Controller RBC-AMT32E & RBC-AMS41E 51
Data Retrieval Guide - Remote Controllers RBC-AMT32E, RBC-AMS41E & RBC-AMS51E 52
Simplified Instructions for RBC-AMS41E Remote Controller 54
Time, Temperature & Mode Setting for RBC-AMS41E Remote Controller 55
Simplified Instructions for RBC-AMS51E Remote Controller 56
Fault Code Guide for RBC-AMS51E Remote Controller 57
Data Retrieval Guide - RBC-AMS51E Remote Controller 58
Relocation of Room Temperature Sensing from Return Air to Remote Controller 59
Automatic Restart after Power Failure 60
Condition Setting (Day, Time, Mode & Temperature) 62
Delete Settings for each Day 63
Copy Settings for Previous Day 63
Holiday Day Omit Setting 64
Energy Saving Function 64
VN Air to Air Heat Exchangers 66
VN Air to Air Heat Exchanger Configurations 68
Automatic Zone Registration Using the Central Remote Controller (TCB-SC642TLE) 69
Network Addressing DI/SDI and VRF Systems 70
Integration with AI Network Control 76
Second Controller 76
Temperature Sensing 76
Page 2 of 78
Make Up of Model Number
RAV/RAS Products
RAS - 16 7 S K _ P E
RAV = Light Commercial Range E = CE marked
RAS = Small Office / Domestic
P = Made in Plymouth
Approx Duty (x 1000 = BTU)
Blank = Single Phase Power Supply
Generation 8 = Three Phase Power Supply
RAV use numbers i.e. 0,1,2,3,4,5
RAS use letters i.e. U,E,S,Y H = HP (RAV)
SMMSi/SHRMi
MMYMAP 1204HT8E
E = CE marked
MMY = Modular Multi
Three phase power supply
M = Single module
No mark = Combined model Capacity variable unit (Inverter)
009= 2.8kW 012= 3.6kW 015= 4.5kW 018= 5.6kW 024= 7.1kW 027= 8kW 030= 9kW 036= 11.2kW 048= 14kW 056= 16kW
Page 3 of 78
Mechanical Specifications - RAS R410A Outdoor Units
Page 4 of 78
RAS R410A Multi Split System Combinations Examples
Outdoor Model Type Outdoor Unit Combination of 4-way Air Discharge Cassette
2 - Room Multi outdoor unit RAS-M14GAV-E X X X X
2 - Room Multi outdoor unit RAS-M18UAV-E O O O O
3 - Room Multi outdoor unit RAS-3M26UAV-E O O O O
4 - Room Multi outdoor unit RAS-4M27UAV-E O O O O
5 - Room Multi outdoor unit RAS-5M34UAV-E1 O O O O
O Combination available, X Combination unavailable
Page 5 of 78
RAS – Auto Restart Function
The indoor unit is equipped with an automatic restart facility that allows the unit to restart, at the last set operating conditions, after a power
failure. The operation will resume without warning three minutes after power is restored.
This feature is not set up when these systems are shipped from the factory, therefore it will need to be activated by the installing company.
Generally the process is the same for all RAS products since approx 2001 and is as follows:
Fault codes are displayed through the LEDs flashing at 5 times per second. Note, the green LED will flash once per
second when the system is initially powered.
More specific codes may be obtained, while in the fault mode through the wireless controller
1. Press CHK to enter service mode
2. Navigate through TIMER buttons until all LEDs flash, accompanied by the internal buzzer – compare the
displayed code with the table below
3. Press CLR button to clear the existing fault code (controller displays 7F)
4. Press ON/OFF button to exit service mode.
Initial
Code Description
code/display
0C TA sensor open or short circuit
0d TC sensor open or short circuit
01 11 Indoor fan motor problem
12 Indoor PCB problem
04 Indoor to outdoor communication (includes compressor thermostat)
01 05 Indoor to outdoor communication
14 Inverter low voltage or short circuit protection
16 Compressor position circuit
17 Compressor current detected during off-cycle
18 TE or TS sensor open or short circuit
02 19 Td sensor open or short circuit
1A Outdoor fan motor problem
1b TE sensor fault
1C Compressor drive circuit
07 Indoor to outdoor communication (includes compressor thermostat)
08 Indoor heat exchanger changes temperature – but in wrong direction
03 1d Compressor locked rotor current protection
1E Compressor - high discharge temperature
1F Compressor current remains too high – after current release
Page 6 of 78
Mechanical Specifications - DI / SDI R410A Single Splits
RAV-SM2244AT8-E
1/2 1 1/8 7.5/70 80 5.9 1540x900x320 134
RAV-SM2804AT8-E
RAV-SP404ATP-E 5/30 30 20 1.0 550x780x290 40
1/4 1/2 20
RAV-SP564ATP-E 20 1.4 550x780x290 44
5/50
RAV-SP804ATP-E 40 2.1 890x900x320 63
Ambient
Capacity kW Energy
Model Range °C
Rating Power Soft Max Suggested Interconnect
Cool Heat Cool Heat Cool/Heat Phase To Start Current Fuse Size Cable
Commercial Range
RAV-SP404ATP-E 3.60 4.00 43 to -15 15 to -15 A/A Outdoor Yes 15.00 10 3Core + Earth
Page 7 of 78
Electrical Specifications - DI / SDI R410A Multi Splits
Inter-
Power
Model Outdoor Twin Indoor Triple Indoor Quad Indoor Phase Suggested Connecting
To
Fused Size Cable
RAV-SM80ATP-E RAV-SM40*T(P)-E N/A N/A 1Ph-N Outdoor 16 3C+E
RAV-SM1104ATP-E RAV-SM56*T(P)-E N/A N/A 1Ph-N Outdoor 20 3C+E
Page 8 of 78
Mechanical & Electrical Data - Air-to-Air Heat Exchangers
Page 9 of 78
Digital/Super Digital R410A Replacement Technology Refrigerant Pipe Sizing
Liquid Pipe Size inch" or mm 1/4 - 6.4 (STD) 3/8 - 9.5 (1-size large)
Gas Pipe Size inch" or mm 3/8 - 9.5 (1-size smaller) 1/2 - 12.7 (STD) 5/8 - 15.9 (1-size larger) 1/2 - 12.7 (STD) 5/8 - 15.9 (1-size larger)
Length Pre-charged Length Pre-charged Length Pre-charged Length Pre-charged Length Pre-charged
Maximum Pipe Distance
m m m m m m m m m m
SP404 30 20 30 20 30 20 20 10 20 10
SDI Series 4 SP454 30 20 30 20 30 20 20 10 20 10
SP564 50 20 50 20 20 10 20 10
DI Series 3 SM563 50 20 50 20 20 10 20 10
Liquid Pipe Size inch" or mm 1/4 - 6.4 (1-size smaller) 3/8 - 9.5 (STD) 1/2 - 12.7 (1-size larger)
Gas Pipe Size inch" or mm 1/2 - 12.7 (1-size smaller) 5/8 - 15.9 (STD) 1/2 - 12.7 (1-size smaller) 5/8 - 15.9 (STD) 3/4 - 19.1 (1-size larger) 5/8 - 15.9 (STD) 3/4 - 19.1 (1-size larger)
Length Pre-charged Length Pre-charged Length Pre-charged Length Pre-charged Length Pre-charged Length Pre-charged Length Pre-charged
Maximum Pipe Distance
m m m m m m m m m m m m m m
SP804 30 20 30 20 50 30 50 30 50 30
SDI Series 4 SP1104 75 30 75 30 25 15 25 15
SP1404 75 30 75 30 25 15 25 15
SM804 20 20 20 20 30 20 30 20 30 20
SM1104 50 30 50 30 25 15 25 15
DI Series 4
SM1404 50 30 50 30 25 15 25 15
SM1604 50 30 50 30 25 15 25 15
Liquid Pipe Size inch" or mm 1/2 - 12.7 (STD) 5/8 - 15.9 (1-size larger) Applicable Refrigerants
Gas Pipe Size inch" or mm 7/8 - 22.2 (1-size smaller) 1 1/8 - 28.6 (STD) 7/8 - 22.2 (1-size smaller) 1 1/8 - 28.6 (STD) Existing Plant
Length Pre-charged Length Pre-charged Length Pre-charged Length Pre-charged R22
Maximum Pipe Distance
m m m m m m m m R407C
SM2244 70 30 70 30 50 20 50 20 R417A
SDI Series 4
SM2804 70 30 70 30 50 20 50 20 R404A
R134a
Performance capacity is reduced due to the effect of gas pipe size being smaller than standard connection R12
Page 10 of 78
Digital / Super Digital Inverter Multi Split System Combinations
RAV-SM564UT P-E
RAV-SM564MUT -E
RAV-SM1104ATP-E
RAV-SM567CT P-E
RAV-SP1104AT-E
RAV-SM566BT -E
RAV-SP1104AT8-E
Twin Split Systems
RAV-SM564SDT -E
RAV-SM566K RT -E
RAV-SM804UTP-E
RAV-SM1404ATP-E
RAV-SM807CTP-E
RAV-SP1404AT-E
RAV-SM806BT-E
RAV-SP1404AT8-E
RAV-SM806KRT-E
RAV-SM804UT P-E
RAV-SM1603AT-E RAV-SM807CT P-E
RAV-SP1604AT8-E RAV-SM806BT -E
RAV-SM806K RT -E
RAV-SM1107CTP-E
RAV-SM2244AT8-E RAV-SM1104UTP-E
RAV-SM1106BT-E
RAV-SM1407CTP-E
RAV-SM2804AT8-E RAV-SM1404UTP-E
RAV-SM1406BT-E
1 x Outdoor Unit 3 x Indoor Units
RAV-SM564UTP-E
RAV-SM564MUT-E
Triple Split Systems
RAV-SM1603AT-E RAV-SM567CTP-E
RAV-SP1604AT8-E RAV-SM566BT-E
RAV-SM564SDT -E
RAV-SM566KRT -E
RAV-SM804UTP-E
RAV-SM804BT-E
RAV-SM2244AT8-E
RAV-SM807CTP-E
RAV-SM806KRT -E
RAV-SM804UTP-E
RAV-SM806BT-E
RAV-SM2804AT8-E
RAV-SM807CTP-E
RAV-SM806KRT -E
RAV-SM564UTP-E
RAV-SM564MUT-E
RAV-SM567CTP-E
RAV-SM2244AT8-E
RAV-SM566BT-E
RAV-SM564SDT -E
RAV-SM566KRT -E
RAV-SM804UTP-E
RAV-SM807CTP-E
RAV-SM2804AT8-E
RAV-SM806BT-E
RAV-SM806KRT -E
Page 11 of 78
Digital / Super Digital Inverter Twin Splits
Pipe Specifications
Allowable Piping Length (m) Height Difference (m)
†Branch Piping ‡Subtractive Indoor Unit - Outdoor Unit (H) Indoor Unit Number of
Model *Total Length a or b to Piping Length Outdoor Unit Indoor Unit Height Bent Portions
(RAV-) (L+a or L+b) Furthest Indoor a-b or b-a Higher Higher Difference (Δh) Maximum
Maximum Maximum Maximum Maximum Maximum Maximum or Less
SM804ATP-E 30 10 5 30 30 0.5 10
SM1104ATP-E
SM1404ATP-E
SM1603AT-E
SP804ATP-E 50 15 10 30 30 0.5 10
SP1104AT(8)-E
SP1404AT(8)-E
SP1604AT8-E
SM2244AT8-E
70 20 10 30 30 0.5 10
SM2804AT8-E
Example 2 Example 2
Installed length main pipe L to distributor=40m
Total pipe length L + a 40 + 14= 64m
Installed length branch a=14m
Subtractive pipe length a – b 14 - 2= 12m
Installed length branch b=2m
Page 12 of 78
Example 3 Example 3
Installed length main pipe L to distributor=50m Total pipe length L + a 50 + 12= 62m
Installed length branch a=12m Subtractive pipe length a – b 12 - 10= 2m
Installed length branch b=10m
Example 4 Example 4
Installed length main pipe L to distributor=60m Total pipe length L + a 60 + 14= 74m
Installed length branch a=14m Subtractive pipe length a – b 14 - 2= 12m
Installed length branch b=2m
Additional Charge
Main Pipes Branch Pipes
Model Add Amount
Sizes (“) Sizes (“) Add Amount
(RAV-) Pre-charge (m) Pre-charge (m)
Gas/Liquid (kg/m) – [ ] Gas/Liquid (kg/m) – [ ß ]
SM804ATP-E
5/8 - 3/8 18 0.040 1/2 - 1/4 2 0.020
SP804ATP-E
SM1104ATP-E
5/8 - 3/8 18 0.040 1/2 - 1/4 2 0.020
SP1104AT(8)-E
SM1404ATP-E
5/8 - 3/8 18 0.040 5/8 - 3/8 2 0.040
SP1404AT(8)-E
SM1603AT-E
5/8 - 3/8 28 0.040 5/8 - 3/8 2 0.040
SP1604AT8-E
SM2244AT8-E
1 1/8 - 1/2 28 0.080 5/8 - 3/8 4 0.040
SM2804AT8-E
Gas calculation - [Main pipe] (L-18) x + [Branch Pipe] (a+b - 4) x ß = additional charge
Gas calculation - [Main pipe] (L-28) x + [Branch Pipe] (a+b - 4) x ß= additional charge
Example 1
Installed length main pipe L to distributor=38m
Example 1 using SM1104ATP-E
Installed length branch a=12m
Installed length branch b=10m
Total pipe length L - 18 x 38 - 18 =20 x 0.040= 0.80 +
Branch pipe length a+bxß 12 + 10 - 4 =18 x 0.020= 0.36
Add Amount 1.16 kg
Page 13 of 78
Digital / Super Digital Inverter Triple Splits
Pipe Specifications
Allowable Piping Lengths (m) Height Difference (m)
‡Subtractive Indoor Unit - Outdoor Unit (H)
Model (RAV-) *Total Length †Branch Piping Piping Length Indoor Unit Number of
La + Lb La, Lb or Lc to Lb - La Outdoor Unit Indoor Unit Height Bent portions
La + Lc Furthest Indoor Lb - Lc Higher Higher Difference (∆h) Maximum
Maximum Maximum Maximum Maximum Maximum Maximum or Less
SM1603AT-E
50 15 10 30 30 0.5 10
SP1604AT8-E
SM2244AT8-E
70 20 10 30 30 0.5 10
SM2804AT8-E
Page 14 of 78
Example 3
Installed length main pipe L to distributor=40m
Example 3
Installed length branch a=12m
Installed length branch b=12m Total pipe length L + a 40 + 12= 52m
Installed length branch c=10m Subtractive pipe length a – b 12 - 12= 0m
Subtractive pipe length c – b 12 - 10= 2m
Example 4
Installed length main pipe L to distributor=50m Example 4
Installed length branch a=20m Total pipe length L + a 50 + 20= 70m
Installed length branch b=3m Subtractive pipe length a – b 20 - 3= 15m
Installed length branch c=5m Subtractive pipe length c – b 5 - 3= 2m
Additional Charge
Main Pipes Branch Pipes
Model (RAV-) Sizes (“) Add Amount Sizes (“) Add Amount
Pre-charge (m) Pre-charge (m)
Gas/Liquid (kg/m) – [ ] Gas/Liquid (g/m) – [ ß ]
SM1603AT-E
5/8 – 3/8 28 0.040 5/8 – 3/8 6 0.040
SP1604AT8-E
SM2244AT8-E
1 1/8 – 1/2 28 0.080 5/8 – 3/8 6 0.040
SM2804AT8-E
Gas calculation - [Main pipe] (L-28) x + [Branch Pipe] (a+b+c - 6) x ß = additional charge
Gas calculation - [Main pipe] (L-28) x + [Branch Pipe] (a+b+c - 6) x ß= additional charge
Page 15 of 78
Digital Inverter Quad Splits
Pipe Specifications
Height Difference (m)
Allowable Piping Lengths (m)
Example 1
Installed length main pipe L to distributor=20m Example 1
Installed length branch b=10m Total pipe length L + b + c 20 + 10 + 5= 35m
Installed length branch c=5m Branch length b + d 10 + 5= 15m
Installed length branch d=5m Branch length a + e 10 + 5= 15m
Installed length branch a=10m Branch length a + f 10 + 5= 15m
Installed length branch e=5m Subtractive pipe length c+b - d+b 5+10 - 5+10= 0m
Installed length branch f=5m Subtractive pipe length c+b - e+a 5+10 - 5+10= 0m
Subtractive pipe length c+b - f+a 5+10 - 5+10= 0m
Subtractive pipe length d+b - e+a 5+10 - 5+10= 0m
Subtractive pipe length d+b - f+a 5+10 - 5+10= 0m
Subtractive pipe length e+a - f+a 5+10 - 5+10= 0m
Page 16 of 78
Example 2 Example 2
Installed length main pipe L to distributor=50m Total pipe length L + b +c 50+ 15+ 10 = 75m
Installed length branch b=15m Branch length b + c 15+ 10 = 25m
Installed length branch c=10m Branch length b + d 15+ 6 = 21m
Installed length branch d=6m Branch length a + e 15+ 5 = 20m
Installed length branch a=15m Branch length a + f 15+ 10 = 25m
Installed length branch e=5m Subtractive pipe length c+b - d+b 10+ 15- 6+ 15 = 4m
Installed length branch f=10m Subtractive pipe length c+b - e+a 10+ 15- 5+ 15 = 5m
Subtractive pipe length c+b - f+a 10+ 15- 10+ 15 = 0m
Subtractive pipe length d+b - e+a 6+ 15- 5+ 15 = 1m
Subtractive pipe length d+b - f+a 6+ 15- 10+ 15 = 1m
Subtractive pipe length e+a - f+a 6+ 15- 10+ 15 = 1m
Additional Charge
Main Pipes Branch pipes
Sizes (“) Pre-charge (m) Add amount Sizes (“) Pre-charge (m) Add amount Sizes (“) Add amount
Model
Gas/Liquid
(kg/m) – []
Gas/Liquid (g/m) – [ß] Gas/Liquid (g/m) – [γ]
SM2244AT8-E 1 1/8 – 1/2 28 0.080 5/8 – 3/8 4 0.040 1/2 – 1/4 0.020
SM2804AT8-E 1 1/8 – 1/2 28 0.080 5/8 – 3/8 4 0.040 5/8 – 3/8 0.040
Gas calculation - [Main pipe] (L-28) x + [Branch Pipe] (a + b - 4) x ß + (c+d+e+f) x γ = additional charge
Gas calculation - [Main pipe] (L-28) x + [Branch Pipe] (a + b - 4) x ß + (c+d+e+f) x γ = additional charge
Example 1
Installed length main pipe L to distributor=20m Example 1 using SM2804AT8-E
Installed length branch b=10m
Installed length branch c=5m Total pipe length L - 28 x 20 - 28 =-8 x 0.080= -0.64 +
Installed length branch d=5m Branch pipe length a+b4xß 10+10- 4 =16 x 0.040= 0.64 +
Installed length branch a=10m Branch pipe length c+d+e+fx γ 5+5+5+5 =20 x 0.040= 0.80
Installed length branch e=5m
Installed length branch f=5m Add Amount 0.80 kg
Remote
Controller
Interconnecting Cables
3 Core+Earth Power connected to terminals
2 Core+Earth Power connected to terminals
2 Core Control connected to terminals A + B
Page 17 of 78
VRF System Make Up Chart
Model Cooling Heating Outdoor Unit Combination Max.
Duty
Reference Capacity Capacity Indoor
HP 0401 0501 0601 0804 1004 1204 1404 1604
MMY kW kW Units
Mini SMMS MCY
MAP0401HT 4 12.1 12.5 1 6
MAP0501HT 5 14.0 16.0 1 8
MAP0601HT 6 15.5 18.0 1 9
Note:- MAP0401HT, MAP0501HT & MAP601HT are NOT Modular
SMMSi Heat Pump MMY
MAP0501HT8-E 5 14.0 16.0 1 1 8
MAP0601HT8-E 6 16.0 18.0 10
MAP0804HT8-E 8 22.4 25.0 1 13
MAP1004HT8-E 10 28.0 31.5 1 16
MAP1204HT8-E 12 33.5 37.5 1 20
MAP1404HT8-E 14 40.0 45.0 1 23
MAP1604HT8-E 16 45.0 50.0 1 27
AP1814HT8-E 18 50.4 56.5 1 1 30
AP2014HT8-E 20 56.0 63.0 2 33
AP2214HT8-E 22 61.5 69.0 1 1 37
AP2414HT8-E 24 68.0 76.5 2 40
AP2614HT8E 26 73.0 81.5 1 1 43
AP2814HT8-E 28 78.5 88.0 1 1 47
AP3014HT8-E 30 85.0 95.0 1 1 48
AP3214HT8-E 32 90.0 100.0 2 48
AP3414HT8E 34 96.0 108.0 1 2 48
AP3614HT8-E 36 101.0 113.0 3 48
AP3814HT8E 38 106.5 119.5 1 1 1 48
AP4014HT8-E 40 112.0 127.0 2 1 48
AP4214HT8-E 42 118.0 132.0 1 1 1 48
AP4414HT8-E 44 123.5 138.0 1 2 48
AP4614HT8-E 46 130.0 145.0 1 2 48
AP4814HT8-E 48 135.0 150.0 3 48
SMMSi High Efficiency Heat Pump MMY
AP1624HT8-E 16 45.0 50.0 2 27
AP2424HT8-E 24 68.0 76.5 3 40
AP2624HT8-E 26 73.0 81.5 2 1 43
AP2824HT8-E 28 78.5 88.0 1 2 47
AP3024HT8-E 30 85.0 95.0 3 48
AP3224HT8-E 32 90.0 100.0 4 48
AP3424HT8-E 34 96.0 108.0 3 1 48
AP3624HT8-E 36 101.0 113.0 2 2 48
AP3824HT8-E 38 106.5 119.5 1 3 48
AP4024HT8-E 40 112.0 126.5 4 48
AP4224HT8-E 42 118.0 132.0 3 1 48
AP4424HT8-E 44 123.5 138.0 2 2 48
AP4624HT8-E 46 130.0 145.0 1 3 48
AP4824HT8-E 48 135.0 150.0 4 48
SHRMi Heat Recovery MMY
Model Cooling Heating Outdoor Unit Combination Max.
Reference Duty Capacity Capacity Indoor
0804 1004 1204 1404
MMY HP Kw kW Units
MAP0804FT8-E 8 22.4 25.0 1 13
MAP1004FT8-E 10 28.0 31.5 1 16
MAP1204FT8-E 12 33.5 37.5 1 20
MAP1404FT8-E 14 40.0 45.0 1 23
AP1614FT8-E 16 45.0 50.0 2 27
AP1814FT8-E 18 50.4 56.5 1 1 30
AP2014FT8-E 20 56.0 63.0 2 33
AP2214FT8-E 22 61.5 69.0 1 1 37
AP2414FT8-E 24 68.0 76.5 1 1 40
AP2614FT8-E 26 73.0 81.5 1 1 43
AP2814FT8-E 28 78.5 88.0 2 47
AP3014FT8-E 30 85.0 95.0 3 48
AP3214FT8-E 32 90.0 100.0 2 1 48
AP3414FT8-E 34 96.0 108.0 2 1 48
AP3614FT8-E 36 101.0 113.0 3 48
AP3814FT8-E 38 106.5 119.5 2 1 48
AP4014FT8-E 40 112.0 127.0 1 2 48
AP4214FT8-E 42 118.0 132.0 3 48
Page 18 of 78
Capacity Data – VRF Indoor Units
Page 19 of 78
VRF Additional Refrigerant Charge Calculations
Trim Charge
Mini SMMS SMMS
Condenser Combinations Correction
HP SMMS Base Charge kg HP
1 2 3 4 Factor kg
4 MCY-MAP0401HT 7.2 4 4 -0.8
5 MCY-MAP0501HT 7.2 5 5 -0.4
6 MCY-MAP0601HT 7.2 6 6 0
5 MAP0501HT8-E 8.5 5 5 0
6 MAP0601HT8-E 8.5 6 6 0
8 MAP0801HT8-E 12.5 8 8 1.5
10 MAP1001HT8-E 12.5 10 10 2.5
12 MAP1201HT8-E 12.5 12 12 3.5
14 AP1401HT8-E 21.0 14 8 6 0
16 AP1601HT8-E 25.0 16 8 8 0
18 AP1801HT8-E 25.0 18 10 8 0
20 AP2001HT8-E 25.0 20 10 10 3
22 AP2201HT8-E 33.5 22 8 8 6 0
22 AP2211HT8-E 25.0 22 12 10 5
24 AP2401HT8-E 37.5 24 8 8 8 -4
24 AP2411HT8-E 25.0 24 12 12 7
26 AP2601HT8-E 37.5 26 10 8 8 -4
28 AP2801HT8-E 37.5 28 10 10 8 -2
30 AP3001HT8-E 37.5 30 10 10 10 0
32 AP3201HT8-E 50.0 32 8 8 8 8 -6
32 AP3211HT8-E 37.5 32 12 10 10 1
34 AP3401HT8-E 50.0 34 10 8 8 8 -6
34 AP3411HT8-E 37.5 34 12 12 10 3
36 AP3601HT8-E 50.0 36 10 10 8 8 -6
36 AP3611HT8-E 37.5 36 12 12 12 4
38 AP3801HT8-E 50.0 38 10 10 10 8 -6
40 AP4001HT8-E 50.0 40 10 10 10 10 -5
42 AP4201HT8-E 50.0 42 12 10 10 10 -4
44 AP4401HT8-E 50.0 44 12 12 10 10 -2
46 AP4601HT8-E 50.0 46 12 12 12 10 0
48 AP4801HT8-E 50.0 48 12 12 12 12 2
Total System Charge = Base Charge + Additional Refrigerant Charge + HP Correction Factor
Page 20 of 78
VRF Additional Refrigerant Charge Calculations
Trim Charge
SMMS & SMMSi SMMSi High Efficiency
Condenser Combinations Correction
HP SMMS & SMMSi Base Charge kg HP 1 2 3 4 Factor kg
5 MAP0501HT8-E 8.5 5 5 0
6 MAP0601HT8-E 8.5 6 6 0
8 MAP0804HT8-E 11.5 8 8 1.5
10 MAP1004HT8-E 11.5 10 10 2.5
12 MAP1204HT8-E 11.5 12 12 3.5
14 MAP1404HT8-E 11.5 14 14 8.5
16 MAP1604HT8-E 11.5 16 16 10.5
18 AP1814HT8-E 23.0 18 10 8 0
20 AP2014HT8-E 23.0 20 10 10 3
22 AP2214HT8-E 23.0 22 16 10 5
24 AP2414HT8-E 23.0 24 12 12 7.5
26 AP2614HT8-E 23.0 26 16 10 8.5
28 AP2814HT8-E 23.0 28 16 12 9.5
30 AP3014HT8-E 23.0 30 16 14 11.5
32 AP3214HT8-E 23.0 32 16 16 12.5
34 AP3414HT8-E 34.5 34 12 12 10 3
36 AP3614HT8-E 34.5 36 12 12 12 4
38 AP3814HT8-E 34.5 38 16 12 10 6
40 AP4014HT8-E 34.5 40 16 12 12 7
42 AP4214HT8-E 34.5 42 16 14 12 8
44 AP4414HT8-E 34.5 44 16 16 12 10
46 AP4614HT8-E 34.5 46 16 16 14 12
48 AP4814HT8-E 34.5 48 16 16 16 14
16 AP1624HT8-E 23.0 16 8 8 0
24 AP2424HT8-E 34.5 24 8 8 8 -4
26 AP2624HT8-E 34.5 26 10 8 8 -4
28 AP2824HT8-E 34.5 28 10 10 8 -2
30 AP3024HT8-E 34.5 30 10 10 10 0
32 AP3224HT8-E 46.0 32 8 8 8 8 -6
34 AP3424HT8-E 46.0 34 10 8 8 8 -6
36 AP3624HT8-E 46.0 36 10 10 8 8 -6
38 AP3824HT8-E 46.0 38 10 10 10 8 -6
40 AP4024HT8-E 46.0 40 10 10 10 10 -5
42 AP4224HT8-E 46.0 42 12 10 10 10 -4
44 AP4424HT8-E 46.0 44 12 12 10 10 -2
46 AP4624HT8-E 46.0 46 12 12 12 10 0
48 AP4824HT8-E 46.0 48 12 12 12 12 2
Total System Charge = Base Charge + Additional Refrigerant Charge + HP Correction Factor
Page 21 of 78
VRF Additional Refrigerant Charge Calculations
Trim Charge
SHRM
Condenser Combinations Correction
HP SHRM Base Charge kg
HP 1 2 3 Factor kg
8 MAP0802FT8-E 11.5 8 8 2
10 MAP1002FT8-E 11.5 10 10 2.5
12 MAP1202FT8-E 11.5 12 12 3
16 MAP1602HT8-E 23.0 16 8 8 -1.5
18 MAP1802HT8-E 23.0 18 10 8 0
20 MAP2002HT8-E 23.0 20 10 10 2
24 MAP2402HT8-E 34.5 24 8 8 8 -4.5
26 MAP2602HT8-E 34.5 26 10 8 8 -3
28 MAP2802HT8-E 34.5 28 10 10 8 -1.5
30 MAP3002HT8-E 34.5 30 10 10 10 0
Trim Charge
SHRMi
Condenser Combinations Correction
HP SHRMi Base Charge kg
HP 1 2 3 Factor kg
8 MAP0804FT8-E 11.0 8 8 2
10 MAP1004FT8-E 11.0 10 10 3
12 MAP1204FT8-E 11.0 12 12 8
14 MAP1404FT8-E 11.0 14 14 10
16 AP1614FT8-E 22.0 16 8 8 0
18 AP1814FT8-E 22.0 18 10 8 1.5
20 AP2014FT8-E 22.0 20 10 10 3.5
22 AP2214FT8-E 22.0 22 12 10 7.5
24 AP2414FT8-E 22.0 24 14 10 8.5
26 AP2614FT8-E 22.0 26 14 12 11
28 AP2814FT8-E 22.0 28 14 14 12
30 AP3014FT8-E 33.0 30 10 10 10 2.5
32 AP3214FT8-E 33.0 32 12 10 10 5
34 AP3414FT8-E 33.0 34 14 10 10 6
36 AP3614FT8-E 33.0 36 12 12 12 8
38 AP3814FT8-E 33.0 38 14 12 12 9.5
40 AP4014FT8-E 33.0 40 14 14 12 11
42 AP4214FT8-E 33.0 42 14 14 14 12.5
Total System Charge = Base Charge + Additional Refrigerant Charge + HP Correction Factor
Page 22 of 78
Acoustic Data - MMY Indoor Units
4 Way Compact Cassette High dB(A) Med dB(A) Low dB(A) Ceiling Suspended High dB(A) Med dB(A) Low dB(A)
MMU-AP0074MH-E 36 32 28 MMC-AP0154H-E 35 32 30
MMU-AP0094MH-E 37 33 28 MMC-AP0184H-E 36 33 30
MMU-AP0124MH-E 37 33 29 MMC-AP0244H-E 38 36 33
MMU-AP0154MH-E 40 35 30 MMC-AP0274H-E 38 36 33
MMU-AP0184MH-E 44 39 34 MMC-AP0364H-E 41 38 35
4 Way Cassette High dB(A) Med dB(A) Low dB(A) MMC-AP0484H-E 43 40 37
MMU-AP0094HP-E 30 29 27 High Wall High dB(A) Med dB(A) Low dB(A)
MMU-AP0124HP-E 30 29 27 MMK-AP0073H 35 31 28
MMU-AP0154HP-E 31 29 27 MMK-AP0093H 37 32 28
MMU-AP0184HP-E 32 29 27 MMK-AP0123H 37 32 28
MMU-AP0244HP-E 35 31 28 MMK-AP0153H 41 36 33
MMU-AP0274HP-E 35 31 28 MMK-AP0183H 41 36 33
MMU-AP0304HP-E 38 33 30 MMK-AP0243H 46 39 34
MMU-AP0364HP-E 43 38 32 MMK-AP0074MH-E 35 32 29
MMU-AP0484HP-E 46 38 33 MMK-AP0094MH-E 36 33 29
MMU-AP0564HP-E 46 40 33 MMK-AP0124MH-E 37 33 29
2 Way Cassette High dB(A) Med dB(A) Low dB(A) Concealed Chassis High dB(A) Med dB(A) Low dB(A)
MMU-AP0072WH 34 32 30 MML-AP0074BH-E 36 34 32
MMU-AP0092WH 34 32 30 MML-AP0094BH-E 36 34 32
MMU-AP0122WH 34 32 30 MML-AP0124BH-E 36 34 32
MMU-AP0152WH 35 33 30 MML-AP0154BH-E 36 34 32
MMU-AP0182WH 35 33 30 MML-AP0184BH-E 36 34 32
MMU-AP0242WH 38 35 33 MML-AP0244BH-E 42 37 33
MMU-AP0272WH 38 35 33 Floor Mounted Console High dB(A) Med dB(A) Low dB(A)
MMU-AP0302WH 40 37 34 MML-AP0074H-E 39 37 35
MMU-AP0362WH 42 39 36 MML-AP0094H-E 39 37 35
MMU-AP0482WH 43 40 37 MML-AP0124H-E 45 41 38
MMU-AP0562WH 46 42 39 MML-AP0154H-E 45 41 38
1 Way Cassette High dB(A) Med dB(A) Low dB(A) MML-AP0184H-E 49 44 39
MMU-AP0074YH-E 42 39 34 MML-AP0244H-E 49 44 39
MMU-AP0094YH-E 42 39 34 Bi-Flow Console High dB(A) Med dB(A) Low dB(A)
MMU-AP0124YH-E 42 39 34 MML-AP0074NH-E 38 32 26
MMU-AP0154SH-E 37 35 32 MML-AP0094NH-E 38 32 26
MMU-AP0184SH-E 38 36 34 MML-AP0124NH-E 40 34 29
MMU-AP0244SH-E 45 41 37 MML-AP0154NH-E 43 37 31
Slim Ducted High dB(A) Med dB(A) Low dB(A) MML-AP0184NH-E 47 40 34
MMD-AP0074SPH-E 36 33 30 Floor Mounted Cabinet High dB(A) Med dB(A) Low dB(A)
MMD-AP0094SPH-E 36 33 30 MMF-AP0154H-E 46 43 38
MMD-AP0124SPH-E 38 35 32 MMF-AP0184H-E 46 43 38
MMD-AP0154SPH-E 39 36 33 MMF-AP0244H-E 49 45 40
MMD-AP0184SPH-E 40 38 36 MMF-AP0274H-E 49 45 40
MMD-AP0244SPH-E 49 47 44 MMF-AP0364H-E 51 48 44
MMD-AP0274SPH-E 49 47 44 MMF-AP0484H-E 54 50 46
Standard Ducted High dB(A) Med dB(A) Low dB(A) MMF-AP0564H-E 54 50 46
MMD-AP0076BH-E 29 26 23 Fresh Air Intake High dB(A) Med dB(A) Low dB(A)
MMD-AP0096BH-E 30 26 23 MMD-AP0481HFE 45 43 41
MMD-AP0126BH-E 30 26 23 MMD-AP0721HFE 46 45 44
MMD-AP0156BH-E 33 29 25 MMD-AP0961HFE 46 45 44
MMD-AP0186BH-E 33 29 25 Extra
MMD-AP0246BH-E 36 31 27 Air to Air Heat Exchanger High dB(A) High dB(A) Low dB(A)
MMD-AP0276BH-E 36 31 27 MMD-VN502HEXE 37 36 34
MMD-AP0306BH-E 36 31 27 MMD-VN802HEXE 41 40 38
MMD-AP0366BH-E 40 36 33 MMD-VN1002HEXE 43 42 40
MMD-AP0486BH-E 40 36 33 MMD-VNK502HEXE 36 35 33
MMD-AP0566BH-E 40 36 33 MMD-VNK802HEXE 40 39 38
High Static Ducted High dB(A) Med dB(A) Low dB(A) MMD-VNK1002HEXE 42 41 39
MMD-AP0184H-E 40 37 33
MMD-AP0244H-E 44 40 36 Sound Pressure Levels measured in an anechoic chamber in
MMD-AP0274H-E 44 40 36 accordance with JSI B8616
MMD-AP0364H-E 44 40 36
MMD-AP0484H-E 44 40 36
MMD-AP0724H-E 50 49 48
MMD-AP0964H-E 51 50 49
Page 23 of 78
Common Sensor Characteristics
There are eight commonly used sensors in the RAS and RAV systems.
Ta = Return Air Sensor; indoor unit Tc = Coil Sensor; indoor unit
TL = Liquid Pipe Sensor (fan speed); outdoor unit TE = Heat Exchange Sensor (defrost); outdoor unit
Td = Discharge Pipe Sensor; outdoor unit To = Ambient
Ts = Suction Tk = Oil sensor
The Ta,Tc,TL and TE sensors all share the same resistance versus temperature characteristic. They differ however
in electrical connections and sensing head style, therefore it is important to quote the full model type number
when ordering any replacement sensors.
The Td sensor has a different resistance characteristic because its sensing range is that much higher than the
others.
Indoor unit
Distributor
Example for location of Sensors TCJ sensor (Strainer incorporated)
Strainer
Air heat exchanger
TC sensor
TD sensor
Strainer
4-way valve TE
(STF-0213Z TL sensor sensor
Muffler Heat exchanger
Outer side Distributor
Ø8, 2 rows, 20 steps
Ø25 × L210 FP1.3 flat fin
Inner side
Ø25 × L180
Ø9.52 row, 30 steps
Accumulator Twin Rotary
(2500cc) FP1.5 flat fin
compressor
(DA220A2F – 20L)
R410A 2.5kg
Page 24 of 78
Indoor Lamp Indication for Trouble Shooting - RAV Series
: Go off, : Go on, : Flash (0.5 sec.)
Lamp indication Check code Cause of trouble occurrence Lamp indication Check code Cause of trouble occurrence
Page 25 of 78
Indoor Lamp Indication for Trouble Shooting - RAV Series
<I
Check Code List (Indoor)
¡ : Go on, ¥ : Flash, l : Go off ALT (Alternate): Alternate flashing when there are two flashing LED SIM (Simultaneous): Simultaneous flashing when there are two flashing LED
(Indoor unit detected)
Check code indication Indoor Sensor lamp indication Air conditioner operation
TCC-LINK central & Block indication Representative defective position Explanation of error contents Automatic Operation
Wired remote controller Operation Timer Ready Flash reset continuation
P12 l ¥ ¥ ALT Indoor unit, DC fan error Indoor DC fan error (Over-current/Lock, etc.) was detected. × ×
P19 ¥ l ¥ ALT 4-way valve system error In heating operation, an error was detected by temp. down of indoor heat exchanger sensor. ¡ ×
P31 ¥ l ¥ ALT Other indoor unit error Follower unit in group cannot operate by warning from [E03/L03/L07/L08] of master unit. ¡ ×
² When this warning was detected before group construction/address check finish at power supply was turned on, the mode shifts automatically to AUTO address setup mode.
(Remote controller detected)
Check code indication Indoor Sensor lamp indication Air conditioner operation
Block indication Representative defective position Explanation of error contents Automatic Operation
Wired remote controller reset continuation
Operation Timer Ready Flash
E01 ¥ l l No master remote controller, Remote controller
communication (Receive) error
Signal cannot be received from indoor unit. Master remote controller was not set.
(including 2 remote controllers)
— —
E02 ¥ l l Remote controller communication (Send) error Signal cannot be sent to indoor unit. — —
E09 ¥ l l Duplicated master remote controller In 2-remote controller control, both were set as master. (Indoor master unit stops warning
and follower unit continues operation.) ×
NOTE: Even for the same contents of error such as communication error, the display of check code may differ according to detection device.
When remote controller or central controller detects an error, it is not necessarily
related to operation of the air conditioner. In this list, the check codes that outdoor unit detects are not described.
Page 26 of 78
Indoor Lamp Indication for Trouble Shooting - RAV Series
<
Check Code List (Outdoor)
¡ : Go on, ¥ : Flash, l : Go off
ALT (Alternate): Alternate flashing when there are two flashing LED SIM (Simultaneous): Simultaneous flashing when there are two flashing LED
P04 ALT High pressure system error, Power supply voltage error Outdoor outdoor heat exchanger temp. sensor. Power supply voltage error
P05 ¥ l ¥ ALT Power supply error Outdoor Power supply voltage error × ×
P07 ¥ l ¥ ALT Outdoor unit Heat sink overheat Outdoor Abnormal overheat was detected by outdoor heat sink temp. sensor. × ×
P15 ¥ l ¥ ALT Gas leak detection Outdoor Abnormal overheat of discharge temp. or suction temp. was detected. × ×
P20 ¥ l ¥ ALT Outdoor unit High pressure system error Outdoor Error was detected by high release control from indoor/outdoor heat exchanger temp. sensor. × ×
P22 ¥ l ¥ ALT Outdoor unit Outdoor fan error Outdoor Error (Over-current, lock, etc.) was detected on outdoor fan drive circuit. × ×
P26 ¥ l ¥ ALT Outdoor unit Inverter Idc operation Outdoor Short-circuited protective operation of compressor drive circuit element (G-Tr /IGBT) worked. × ×
P29 ¥ l ¥ ALT Outdoor unit Position detection error Outdoor Position detection error of compressor motor was detected. × ×
E01 ¥ l l No remote controller master unit
Remote controller communication error
Remote
controller
Signal was not received from indoor unit.
Main remote controller was not set. (including 2 remote controllers) — —
Page 27 of 78
Indoor Lamp Indication for Trouble Shooting - RAV Series
<
¡ : Go on, ¥ : Flash, l : Go off
ALT (Alternate): Alternate flashing when there are two flashing LED SIM (Simultaneous): Simultaneous flashing when there are two flashing LED
Indoor Sensor lamp part
Remote Automatic Operation
controller Block indication Representative defective position Detection Explanation of error contents
indication reset continuation
Operation Timer Ready Flash
F01 ¥ ¥ l ALT Indoor unit Heat exchanger sensor (TCJ) error Indoor Open/Short of heat exchanger (TCJ) was detected. ¡ ×
F02 ¥ ¥ l ALT Indoor unit Heat exchanger sensor (TC) error Indoor Open/Short of heat exchanger (TC) was detected. ¡ ×
F10 ¥ ¥ l ALT Indoor unit Room temp. sensor (TA) error Indoor Open/Short of room temp. (TA) was detected. ¡ ×
F29 ¥ ¥ l SIM Indoor unit Other indoor P.C. board error Indoor EEPROM error (Other error may be detected. If no error, automatic address is repeated. × ×
P01 l ¥ ¥ ALT Indoor unit Indoor fan error Indoor Indoor AC fan error was detected. (Fan thermal relay worked.) × ×
P10 l ¥ ¥ ALT Indoor unit Overflow detection Indoor Float switch worked. × ×
P12 l ¥ ¥ ALT Indoor unit Indoor fan error Indoor Indoor fan error (Over-current / Lock, etc.) was detected. × ×
P31 ¥ l ¥ ALT Other indoor unit error Indoor Other indoor under condition of warning in group. E03/L07/L03/L08 warning ¡ ×
Sub remote controller error in a group — —
— By unit with warning No. ALT Error in indoor group Network adapter (Details of remote controller are displayed with unit No. Only central control side is displayed.)
Network adapter/ Communication error of central control system signal
— — LAN system communication error Center ∗ Is not displayed on the remote controller ¡ ¡
Network adapter/
L20 ¥ ¡ ¥ SIM LAN system communication error Center Duplicated indoor address of central control system communication ¡ ×
— — There are multiple communication adapters. Network adapter There are multiple communication adapters on remote controller communication line. ¡ ¡
–
Example: 1
Local controller displaying fault code E04
Enter E04 and select Find Fault
Example: 2
Local controller displaying fault code L29
Condenser displaying sub-code 07
Model of condenser MMY-MAP1604HT8-E
Enter L29071604 and select Find Fault
Please note; codes can be entered with or without character spaces, spaces ignored
in text strings.
Page 28 of 78
Fault Codes – All Commercial & VRF Systems
Do Not turn off the power supply before reading the fault codes, doing so will clear the diagnostic memory.
Caution must be taken when removing the access covers, as high voltages are present.
Fault diagnosis is available at three locations within the Air Conditioning system. :-
1 Remote Controller - press the check button 2 Multi Controller - rotate the display switch to position 1
3 Central Controller - press the check button (if installed) 4 Outdoor Unit Switch position (variable dependent upon model): –
2 Pipe Super Multi 2, 3 & 8; 3 Pipe Super Multi 2 & 0;
3 Pipe SMI 2 & 0 2 Pipe Modular Multi MMY 1, 1, 1
3 Pipe Modular Multi MMY 1, 1, 1
Page 29 of 78
Code Fault Description
87 Phase missing phase. Detected at outdoor. Likely cause abnormal power supply
88 Multi-Control box does not recognise condenser capacity. Likely cause interconnecting cable damage, outdoor PCB fault
89 Indoor capacity to high. Likely cause loss of combination within group of modularised condensers
93 Indoor coil sensor fault. Detected indoors. Likely cause TC1 sensor condition or indoor PCB fault sensor value 20°c=12.5k ohms
94 Indoor coil sensor fault. Detected indoors. Likely cause TC2 sensor condition or indoor PCB fault sensor value 20°c=12.5k ohms
Communication failure on P&Q network (indoor/outdoor communication). Detected indoors & outdoors. Likely cause network cable condition, PCB
95
failure indoor or outdoor
96 Indoor unit count too high. Detected at outdoor. Likely cause indoor capacity vs. outdoor capacity Incorrect, too many indoor units connected
97 Central control communication error. Detected at central controller & indoors. Likely cause indoor power failure, central address error, cable damage
98 Duplicated zone address. Likely cause incorrectly assigned central control addresses
No communication from indoor to remote controller. Detected by hard-wired remote controller. Likely cause faulty indoor PCB, remote controller or
99
cable damage
Indoor float switch open circuit as result of high condensation levels within drip tray. Detected indoors. Likely cause faulty float switch, faulty lift pump,
0b
debris blocking drain
0c Return air sensor fault. Detected indoors. Likely cause TA sensor condition or indoor PCB fault sensor value 20°c=12.5k ohms
0d Coil sensor fault. Detected indoors. Likely cause TC sensor condition or indoor PCB fault sensor value 20°c=12.5k ohms
1C Outdoor error. Detected indoors (interrogate condenser for additional faults)
1d High Inverter dc current. Detected at outdoor. Likely cause imbalance in compressor voltage, excessive amps by inverter compressor
High compressor discharge temperature. Detected at outdoor. Likely cause low refrigerant, poor refrigerant flow, poor airflows, TD sensor condition
1E
sensor value 20°c=63k ohms
1F High Inverter ac current. Detected at outdoor. Likely cause imbalance in compressor voltage, excessive amps by inverter compressor
Outdoor unit quantity fallen (loss of communication between condensers). Detected at outdoor. Likely cause power interruption, BUS communication
8d
cable condition
8E Outdoor units quantity too high. Detected at outdoor. Likely cause too many condensers connected
8F Outdoor unit address incorrect. Detected at outdoor. Likely cause multiple modularised condenser having SW 9 ON, Interface PCB failure
No temperature change on evaporator. Detected by indoor evaporator sensor TC1. Likely cause miss-wiring, restriction in refrigerant flow, lack of
9A
refrigerant
Insufficient temperature change on evaporator. Detected indoors. Likely cause miss-wiring, restriction in refrigerant flow, lack of refrigerant, TC1,TC2
9F
& TA sensor condition sensor value 20°c=12.5k ohms
A0 Compressor discharge sensor fault. Detected at outdoor. Likely cause TD1/ThD1 sensor condition or Interface PCB sensor value 20°c=63k ohms
A1 Compressor discharge sensor fault. Detected at outdoor. Likely cause TD2/ThD2 sensor condition or Interface PCB sensor value 20°c=63k ohms
A2 Compressor suction sensor fault. Detected at outdoor. Likely cause TS1/ThS sensor condition or interface PCB sensor value 20°c=12.5k ohms
High compressor discharge temperature. Detected at outdoor. by TD1. Likely cause low refrigerant, poor refrigerant flow and airflows & TD2 sensor
A6
condition sensor value 20°c=63k ohms
High compressor suction temperature > 40°C. Detected at outdoor. Likely cause severe gas shortage, TS sensor condition, interface PCB sensor value
A7
20°c=12.5k ohms
Page 30 of 78
Code Fault Description
AA High side pressure sensor fault. Detected at outdoor. (Replace Pd pressure transducer)
Ab Pressure transducer error. Detected at outdoor. Likely cause abnormal running pressures, abnormal PS / Pd characteristics, interface PCB
High compressor discharge temperature @ low inverter speed. Detected at outdoor. Likely cause TD1 sensor condition, insufficient refrigerant sensor
AE
value 20°c=63k ohms
AF Phase rotation incorrect. Detected at outdoor. Likely cause abnormal phase order, missing phase to outdoor unit
Low pressure transducer error or misreading fault. Detected at outdoor. Likely cause incorrect characteristics of suction pressure transducer (PS,
b4
interface PCB faulty
b5 External input activation, refrigerant leak detection system (Call Toshiba's technical helpline for further details 0870 843 0333)
b6 External input activation, refrigerant leak detection system (Call Toshiba's technical helpline for further details 0870 843 0333)
b7 Indoor group follower error. Detected at central controller (interrogate local controller by pressing check for additional fault codes)
b9 Pressure sensor fault. Detected indoors. Likely cause evaporator pressure sensor unplugged, pressure sensor open circuit replace sensor
High compressor discharge temperature. Detected at outdoor. by TD2. Likely cause low refrigerant, poor refrigerant flow and airflows & TD2 sensor
bb
condition sensor value 20°c=63k ohms
Low pressure trip. Detected outdoor by PS transducer. Likely cause suction pressure transducer condition (PS), interface PCB fault restriction in
bE
refrigerant flow, lack of refrigerant
C05 Command sending error. Detected on Central Controller. Likely cause power loss at indoor unit group, network cable condition)
C06 Command receiving error. Detected on Central Controller. Likely cause power loss at indoor unit group, network cable condition)
d1 Master condenser setup alarm. Detected at outdoor. Likely cause multiple inverter outdoor units connected, faulty interface PCB)
d2 Fault within follower condenser. Detected at outdoor. (retrieve additional fault code from follower condensers)
d3 IPDU PCB overheat (inverter board). Detected at outdoor. Likely cause clogged heat-sink fins, poorly secured or faulty IPDU PCB)
d4 Oil sensor fault. Detected at outdoor. Likely cause TK1 sensor condition or outdoor PCB fault sensor value 20°c=63k ohms)
d5 Oil sensor fault. Detected at outdoor. Likely cause TK2 sensor condition or outdoor PCB fault sensor value 20°c=63k ohms)
d6 Oil sensor fault. Detected at outdoor. Likely cause TK3 sensor condition or outdoor PCB fault sensor value 20°c=63k ohms)
d7 Low oil detection. Detected at outdoor. Likely cause TK1, TK2 & TK3 sensor condition, interface PCB, lack of refrigerant sensor value 20°c=63k ohms)
d8 Oil temperature alarm. Detected at outdoor. Likely cause TK1 sensor location or condition, outdoor PCB fault sensor value 20°c=63k ohms
d9 Oil temperature alarm. Detected at outdoor. Likely cause TK2 sensor location or condition, outdoor PCB fault sensor value 20°c=63k ohms
dA Abnormal overheat of heat-sink. Detected at outdoor. Likely cause clogged heat-sink fins, poorly secured or faulty IPDU board
No oil flow detected. Detected at outdoor. Likely cause TK1, TK2 & TK3 sensor location or condition, interface PCB, blockage within SV3C sensor value
db
20°c=63k ohms
High temperature oil alarm. Detected at outdoor. Likely cause TK1 sensor condition, interface PCB fault, high ambient running conditions >43°c sensor
dC
value 20°c=63k ohms
Temperature change when condensers in off cycle. Detected at outdoor. Likely cause PMV passing within condenser, discharge & suction pressure
dd
transducer error (PS & Pd characteristics), interface PCB fault
dE Indoor unit automatic addressing failure. Detected at outdoor. Likely cause indoor PCB configuration error, indoor PCB faulty
dF Outdoor unit automatic address failure. Detected at outdoor. Likely cause interface PCB fault
Page 31 of 78
Code Fault Description
Communication error between indoor unit and remote controller. Detected by remote controller. Likely cause indoor PCB, remote controller, incorrect
E01
switch position on rear of remote controller, all switches normally down
E02 Sending error of local remote controller. Detected by remote controller. Likely cause replace remote controller
Communication error between indoor unit and central remote controller. Detected indoors. Likely cause indoor network adapter, central remote
E03
controller
Communication failure between indoor and outdoor units. Detected indoors. Likely cause split A/C=indoor PCB, outdoor PCB, interconnecting cable
E04
condition, compressor klixon open circuit. VRF system=power loss at condenser, U1/U2 network cable condition
E06 Decrease in quantity of indoor units. Detected indoors. Likely cause power loss at indoor unit, indoor PCB fault, A&B controller cable condition
Communication failure between indoor and outdoor units. Detected at outdoor. Likely cause interconnecting cable condition, outdoor PCB switch
E07
position SW30 bit 1 & 2 must be placed in ON position for test
E08 Duplicated indoor address. Detected indoors. Likely cause incorrect setting of BUS addresses when under central control
E09 Duplicated master remote controllers. Detected indoors. Likely cause two local remote controller connected on A&B network
Activation of high pressure switch on D.O.L (Fixed speed) compressor 1. Detected at outdoor. Likely cause fan motor trouble, poor airflows, restricted
E1
refrigerant flow
e1 80 Multi-Control box 1 Th(A) sensor fault. Likely cause TH(A) sensor or M/C box PCB sensor value 20°c=12.5k ohms
e1 81 Multi-Control box 1 Th(B) sensor fault. Likely cause TH(B) sensor or M/C box PCB sensor value 20°c=12.5k ohms
e1 82 Multi-Control box 1 Th(C) sensor fault. Likely cause TH(C) sensor or M/C box PCB sensor value 20°c=12.5k ohms
e1 83 Multi-Control box 1 Th(D) sensor fault. Likely cause TH(D) sensor or M/C box PCB sensor value 20°c=12.5k ohms
e1 84 Multi-Control box 1 Th(X) sensor fault. Likely cause TH(X) sensor or M/C box PCB sensor value 20°c=12.5k ohms
E10 Communication Error at indoor PCB. Detected indoors. Likely cause replace indoor PCB
Automatic addressing error. Detected at outdoor. Likely cause incorrect self-addressing sequence, repeat self-addressing procedure. Retrieve fault sub-
E12
code from condenser interface PCB by placing rotary dials to position 1 / 1 / 1 for diagnosis.
E12 01 Automatic addressing error. Detected at outdoor. Indoor / Outdoor communication
E12 02 Automatic addressing error. Detected at outdoor. Outdoor / Outdoor communication
Automatic self-addressing failure. Detected at outdoor. Likely cause SW30 bit 1 & 2 in OFF position, switch both ON before self-addressing
E15
commenced, interface pcb failure
Indoor unit count or capacity to high. Detected at outdoor. Likely cause if condenser PCB displays sub code 00=indoor capacity vs. condenser to high.
E16 If sub code at condenser reads 01=indoor unit count/quantity to high. Retrieve fault sub-code from condenser interface PCB by placing rotary dials to
position 1 / 1 / 1 for diagnosis.
E16 00 Indoor unit capacity to high. Detected at outdoor. Likely cause indoor unit capacity to high vs. condenser capacity
E16 01 Indoor unit count to high. Detected at outdoor. Likely cause indoor unit count to high vs. outdoor upper limit
Communication failure between indoor units. Detected indoors. Likely cause indoor power loss, A&B controller cable condition. Twin, triple & Quad
E18
applications E18 can result from E04 fault code
Outdoor header error. Detected at outdoor. Likely cause if condenser PCB displays sub code 00=power loss to indoor units or U1/U2 network cable
E19 condition. If sub code reads 01=incorrect wiring between modularised condensers. Retrieve fault sub-code from condenser interface PCB by placing
rotary dials to position 1 / 1 / 1 for diagnosis.
Page 32 of 78
Code Fault Description
E19 00 Outdoor header error. Detected at outdoor. Likely cause power loss to indoor units, U1/U2 network cable condition, SW30 bit 1 & 2 must be ON to test
E19 01 Outdoor header error. Detected at outdoor. Likely cause incorrect wiring between modularised condensers
e2 80 Multi-Control box 2 Th(A) sensor fault. Likely cause TH(A) sensor or M/C box PCB sensor value 20°c=12.5k ohms
e2 81 Multi-Control box 2 Th(B) sensor fault. Likely cause TH(B) sensor or M/C box PCB sensor value 20°c=12.5k ohms
e2 82 Multi-Control box 2 Th(C) sensor fault. Likely cause TH(C) sensor or M/C box PCB sensor value 20°c=12.5k ohms
e2 83 Multi-Control box 2 Th(D) sensor fault. Likely cause TH(D) sensor or M/C box PCB sensor value 20°c=12.5k ohms
e2 84 Multi-Control box 2 Th(X) sensor fault. Likely cause TH(X) sensor or M/C box PCB sensor value 20°c=12.5k ohms
One or more systems connected on network during self-addressing procedure. Detected at outdoor. Likely cause if condenser PCB displays sub code
01=multiple outdoor systems connected on U3/U4 network, miss-wiring or central control relay connecter in-place. If sub code reads 02=indoor units
E20
from other line connected, miss-wiring or central control relay connecter in-place. Retrieve fault sub-code from condenser interface PCB by placing
rotary dials to position 1 / 1 / 1 for diagnosis.
Multiple indoor system line numbers connected on network during self-addressing procedure. Detected at outdoor. Likely cause miss-wiring of indoor
E20 01
network cable, central control relay connecter together during self-address
Multiple outdoor system numbers connected on network during self-address procedure. Detected at outdoor. Likely cause miss-wiring of outdoor units,
E20 02
central control relay/plug connected during self-address
E23 Communication error between outdoor units. Detect outdoors. Likely cause U5/U6 cable condition, interface PCB fault
E25 Duplicated follower outdoor unit address. Detected at outdoor. Likely cause error in manually assigning addresses, allow system to self-address
E26 Decrease in quantity of outdoor units connected. Detected at outdoor. Likely cause power loss at condensers, U5/U6 cable condition
Outdoor follower fault. Detected at outdoor. Likely cause lead condenser OK, follower condenser has suffered fault, retrieve second fault code from
E28
follower condenser
IPDU/PCB board communication error. Detected at outdoor. Likely cause loss in communication between condenser PCB's. Retrieve fault sub-code
E31
from condenser interface PCB by placing rotary dials to position 1 / 1 / 1 for diagnosis.
Compressor 1 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace Compressor 1
E31 01
IPDU board
Compressor 2 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace Compressor 2
E31 02
IPDU board
Compressor 1 & 2 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
E31 03
Compressor 1 & 2 IPDU board
Communication failure between PCB's within condenser. Detected at outdoor. Fault Code is outdoor model series specific e.g. MMY-MAP###1HT8-E,
E31 04 MMY-AP###2HT8-E or MMY-MAP###4HT8-E therefore example fault code for E3104 will be (MMY-MAP0801HT8-E (series 1), MMY-MAP0802HT8-E
(series 2), MMY-MAP0804HT8-E (series 4) search E31041, E31042 or E31044
E31 04 1 Fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace fan IPDU board
E31 04 2 Fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace fan IPDU board
Compressor 3 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace Compressor 3
E31 04 4
IPDU board
Page 33 of 78
Code Fault Description
Communication failure between PCB within condenser. Fault Code is outdoor model series specific e.g. MMY-MAP###1HT8-E, MMY-AP###2HT8-E or
E31 05 MMY-MAP###4HT8-E therefore example fault code for E3105 will be (MMY-MAP0801HT8-E (series 1), MMY-MAP0802HT8-E (series 2), MMY-
MAP0804HT8-E (series 4) search E31051, E31052 or E31054
Compressor 1 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
E31 05 1
Compressor 1 IPDU & fan IPDU board
Compressor 1 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
E31 05 2
Compressor 1 IPDU & fan IPDU board
Compressor 1 & 3 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
E31 05 4
Compressor 1 & 3 IPDU board
Communication failure between PCB within condenser. Detected at outdoor. Fault Code is outdoor model series specific e.g. MMY-MAP###1HT8-E,
E31 06 MMY-AP###2HT8-E or MMY-MAP###4HT8-E therefore example fault code for E3106 will be (MMY-MAP0801HT8-E (series 1), MMY-MAP0802HT8-E
(series 2), MMY-MAP0804HT8-E (series 4) search E3101, E31062 or E31064
Compressor 2 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
E31 06 1
Compressor 2 IPDU & fan IPDU board
Compressor 2 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
E31 06 2
Compressor 2 IPDU & fan IPDU board
Compressor 2 & 3 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
E31 06 4
Compressor 2 & 3 IPDU board
Communication failure between PCB within condenser. Detected at outdoor. (4 Series Condenser Compressor 1, 2 & 3 IPDU board communication
E31 07
error). (1&2 Series condenser communication error between PCB within condenser) likely cause phase missing on power supply, replace interface PCB
Communication error between PCB within condenser. Detected at outdoor. Likely cause check communication cable linking all PCB's, phase missing on
E31 07 1
power supply, replace interface PCB
Communication error between PCB within condenser. Detected at outdoor. Likely cause check communication cable linking all PCB's, phase missing on
E31 07 2
power supply, replace interface PCB
Compressor 1, 2 & 3 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
E31 07 4
Compressor 1, 2 & 3 IPDU board
E31 08 Fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace fan IPDU board
Compressor 1 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
E31 09
Compressor 1 IPDU & fan IPDU board
Compressor 2 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
E31 0A
Compressor 2 IPDU & fan IPDU board
Compressor 1 & 2 IPDU board & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's,
E31 0B
replace Compressor 1 & 2 IPDU PCB & fan IPDU board
Compressor 3 IPDU board & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's,
E31 0C
replace Compressor 3 IPDU board & fan IPDU board
Compressor 1 & 3 IPDU board & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's,
E31 0d
replace Compressor 1 & 3 IPDU board & fan IPDU board
Page 34 of 78
Code Fault Description
Compressor 2 & 3 IPDU board & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's,
E31 0E
replace Compressor 2 & 3 IPDU PCB & fan IPDU board
Communication error between PCB within condenser. Detected at outdoor. Likely cause check communication cable linking all PCB's, phase missing on
E31 0F
power supply, replace interface PCB
Activation of high pressure switch or internal overheat (klixon on INVERTER compressor only. Detected at outdoor. Likely cause fan motor trouble,
E5
poor airflows, poor refrigerant flow, insufficient refrigerant
Activation of compressor klixon or contactor overload on D.O.L (Fixed speed compressor 1. Detected at outdoor. Likely cause poor refrigerant flow,
E6
insufficient refrigerant, excessive amps by compressor
Resulting from b6 fault code generated at indoor unit. Detected at outdoor. (b6=External input activation, refrigerant leak detection system (Call
Eb
Toshiba's technical helpline for further details 0870 843 0333)
Inverter compressor low voltage. Detected at outdoor. Likely cause AC fuse disconnection, faulty component within compressor inverter circuit,
Er 14
electrical failure of compressor
Er 1d High Inverter dc current. Detected at outdoor. Likely cause imbalance in compressor voltage, excessive amps by inverter compressor
Er 1F High Inverter ac current. Detected at outdoor. Likely cause imbalance in compressor voltage, excessive amps by inverter compressor
Inverter compressor trip. Detected at outdoor. Likely cause activation of high pressure switch 425psi-29bar / internal overheat (klixon) on inverter
Er 21
compressor only
Er A0 Compressor discharge sensor fault. Detected at outdoor. Likely cause TD1/ThD1 sensor condition or Interface PCB sensor value 20°c=63k ohms
Er A1 Compressor discharge sensor fault. Detected at outdoor. Likely cause TD2/ThD2 sensor condition or Interface PCB sensor value 20°c=63k ohms
Er A2 Compressor suction sensor fault. Detected at outdoor. Likely cause TS1/ThS sensor condition or interface PCB sensor value 20°c=12.5k ohms
Er A4 Ambient air sensor fault. Detected at outdoor. Likely cause Th0 sensor condition or interface PCB sensor value 20°c=12.5k ohms
Er A5 Condenser coil sensor fault. Detected at outdoor. Likely cause ThE sensor condition or interface PCB fault sensor value 20°c=12.5k ohms
High compressor discharge temperature. Detected at outdoor. by TD1,TD2,ThD1 & ThD2. Likely cause low refrigerant, poor refrigerant flow and
Er A6
airflows & TD sensor condition sensor value 20°c=63k ohms
High compressor suction temperature > 40°C. Detected at outdoor. Likely cause severe gas shortage, TS sensor condition, interface PCB sensor value
Er A7
20°c=12.5k ohms
Er AA High side pressure sensor fault. Detected at outdoor. (Replace Pd pressure sensor)
Fixed speed compressor trip (D.O.L). Detected at outdoor. Likely cause activation of high pressure switch 425psi-29bar / internal overheat (klixon) /
Er Ad
phase rotation PCB / D.O.L contactor overload trip
Er AE Low Pressure trip < 3 psig. Detected at outdoor. by L.P. switch. Likely cause refrigerant loss, restriction in refrigerant flow
Er AF Phase rotation incorrect. Detected at outdoor. Likely cause abnormal phase order, missing phase to outdoor unit
Activation of high pressure switch on D.O.L (Fixed speed) compressor 2. Detected at outdoor. Likely cause fan motor trouble, poor airflows, restricted
F0
refrigerant flow
F01 TCj Coil sensor fault. Detected indoors. Likely cause TCj sensor condition or indoor PCB fault sensor value 20°c=12.5k ohms
F02 TC2 or TC Coil sensor fault. Detected indoors. Likely cause TC2 / TC sensor condition or indoor PCB fault sensor value 20°c=12.5k ohms
F03 TC1 Coil sensor fault. Detected indoors. Likely cause TC1 sensor condition or indoor PCB fault sensor value 20°c=12.5k ohms
Page 35 of 78
Code Fault Description
F04 Td1 sensor fault. Detected at outdoor. Likely cause compressor discharge sensor condition (Td1) or outdoor PCB fault sensor value 20°c=63k ohms
F05 Td2 sensor fault. Detected at outdoor. Likely cause compressor discharge sensor condition (Td2) or outdoor PCB fault sensor value 20°c=63k ohms
TE or TS Sensor fault. Detected at outdoor. Likely cause Heat exchange sensor condition (TE / TE1 / TE2). Suction line sensor condition (TS) or
F06 outdoor PCB fault sensor value 20°c=12.5k ohms. Retrieve fault sub-code from condenser interface PCB by placing rotary dials to position 1 / 1 / 1 for
diagnosis.
F06 01 TE1 Sensor fault. Detected at outdoor. Likely cause Heat exchange sensor condition (TE1) or outdoor PCB fault sensor value 20°c=12.5k ohms
F06 02 TE2 Sensor fault. Detected at outdoor. Likely cause Heat exchange sensor condition (TE2) or outdoor PCB fault sensor value 20°c=12.5k ohms
F07 TL Sensor fault. Detected at outdoor. Likely cause Liquid line sensor condition (TL) or outdoor PCB fault sensor value 20°c=12.5k ohms
F08 TO Sensor fault. Detected at outdoor. Likely cause Ambient air sensor condition (TO) or outdoor PCB fault sensor value 20°c=12.5k ohms
Activation of compressor klixon or contactor overload on D.O.L (Fixed speed compressor 2). Detected at outdoor. Likely cause poor refrigerant flow,
F1
insufficient refrigerant, excessive amps by compressor
F10 TA Sensor fault. Detected indoors. Likely cause Return air sensor condition (TA) or indoor PCB fault sensor value 20°c=12.5k ohms
F12 TS Sensor fault. Detected at outdoor. Likely cause Suction line sensor condition (TS / TS1 / TS2) or outdoor PCB fault sensor value 20°c=12.5k ohms
Compressor IPDU board overheat. Detected at outdoor. Likely cause poor contact to heat-sink, IPDU board fault. Fault sub-code required to determine
F13 which board has suffered overheat 01=IPDU1 overheated 02=IPDU2 overheated 03=IPDU3 overheated. Retrieve fault sub-code from condenser
interface PCB by placing rotary dials to position 1 / 1 / 1 for diagnosis.
F13 01 Compressor 1 IPDU board overheat. Detected at outdoor. Likely cause poor contact to heat-sink, replace compressor IPDU board 1
F13 02 Compressor 2 IPDU board overheat. Detected at outdoor. Likely cause poor contact to heat-sink, replace compressor IPDU board 2
F13 03 Compressor 3 IPDU board overheat. Detected at outdoor. Likely cause poor contact to heat-sink, replace compressor IPDU board 3
Outdoor temperature sensor error. Detected at outdoor. Likely cause VRF equipment=Heat exchange (TE) sensor condition/location or Liquid line (TL)
F15 sensor condition/location, outdoor PCB fault Split equipment=Suction sensor (TS) condition/location Heat exchange sensor (TE) condition/location,
outdoor PCB fault sensor value 20°c=12.5k ohms
Pressure sensors miss-reading. Detected at outdoor. Likely cause incorrect characteristics of compressor discharge (Pd) & compressor suction (PS)
F16
pressure sensor or total loss of refrigerant
F22 Td3 sensor fault. Detected at outdoor. Likely cause compressor discharge sensor condition (Td3) or outdoor PCB fault sensor value 20°c=63k ohms
F23 Compressor suction pressure sensor fault. Detected at outdoor. Likely cause Suction transducer (PS) fault, outdoor PCB fault
F24 Compressor discharge pressure sensor fault. Detected at outdoor. Likely cause Suction transducer (Pd) fault, outdoor PCB fault
F29 Indoor PCB fault. Detected indoors. Likely cause replace indoor PCB
Outdoor EEPROM Error. Detected at outdoor. Likely cause VRF equipment=power interruption, replace interface PCB Split equipment=replace
F31
condenser CDB board
Excessive amps drawn by compressor. Detected at outdoor. Likely cause imbalance in voltage supplied from IPDU board to compressor, compressor
H01 lock / seizure. Retrieve sub-code for VRF from condenser to determine which compressor suffered failure 01=compressor1, 02=compressor2 &
03=compressor3. Retrieve fault sub-code from condenser interface PCB by placing rotary dials to position 1 / 1 / 1 for diagnosis.
Excessive amps drawn by compressor 1. Detected at outdoor. Likely cause imbalance in voltage supplied to compressor 1 from inverter IPDU board 1,
H01 01
compressor 1 lock / seizure
Page 36 of 78
Code Fault Description
Excessive amps drawn by compressor 2. Detected at outdoor. Likely cause imbalance in voltage supplied to compressor 2 from inverter IPDU board 2,
H01 02
compressor 2 lock / seizure
Excessive amps drawn by compressor 3. Detected at outdoor. Likely cause imbalance in voltage supplied to compressor 3 from IPDU board 3,
H01 03
compressor 3 lock / seizure
High amps drawn by compressor on start-up. Detected at outdoor. Likely cause imbalance in voltage supplied to compressor from IPDU board,
H02 compressor locked / seized. For VRF fault sub-code required to determine which compressor suffered failure 01=compressor1 02=compressor2
03=compressor3. Retrieve fault sub-code from condenser interface PCB by placing rotary dials to position 1 / 1 / 1 for diagnosis.
High amps drawn by compressor 1 on start-up. Detected at outdoor. Likely cause imbalance in voltage supplied to compressor 1 from IPDU board 1,
H02 01
compressor 1 locked / seized
High amps drawn by compressor 2 on start-up. Detected at outdoor. Likely cause imbalance in voltage supplied to compressor 2 from IPDU board 2,
H02 02
compressor 2 locked / seized
High amps drawn by compressor 3 on start-up. Detected at outdoor. Likely cause imbalance in voltage supplied to compressor 3 from IPDU board 3,
H02 03
compressor 3 locked / seized
Current detected in compressor off cycle. Detected at outdoor. Likely cause replace compressor IPDU board. For VRF fault sub-code required to
H03 determine which compressor suffered failure 01=compressor1 02=compressor2 03=compressor3. Retrieve fault sub-code from condenser interface
PCB by placing rotary dials to position 1 / 1 / 1 for diagnosis.
H03 01 Current detected in compressor off cycle. Detected at outdoor. Likely cause replace compressor IPDU board 1
H03 02 Current detected in compressor off cycle. Detected at outdoor. Likely cause replace compressor IPDU board 2
H03 03 Current detected in compressor off cycle. Detected at outdoor. Likely cause replace compressor IPDU board 3
Compressor 1 over-heat. Detected at outdoor. Likely cause compressor klixon activation, loss of refrigerant, poor refrigerant flow reducing cooling
H04
effect to compressor
Compressor discharge temperature does not increase while compressor 1 operates. Detected at outdoor. Likely cause compressor discharge sensor
H05
(Td1) condition / location, outdoor PCB fault sensor value 20°c=63k ohms
Low pressure protection operation. Detected at outdoor. Likely cause characteristics of suction pressure transducer (PS), system pump-down, interface
H06
PCB fault)
Abnormal oil level / temperature alarm. Detected outdoor. Likely cause oil balance service valve, refrigerant loss, oil sensor condition (TK1 / TK2 / TK3
H07
/ TK4 / TK5), interface board PCB fault sensor value 20°c=63k ohms)
TK Oil sensor fault. Detected at outdoor. Likely cause oil sensor condition, outdoor PCB fault. Fault sub code required to determine which sensor (TK1 /
H08 TK2 / TK3 / TK4 / TK5 sensor value 20°c=63k ohms). Retrieve fault sub-code from condenser interface PCB by placing rotary dials to position 1 / 1 / 1
for diagnosis.
H08 01 TK1 Oil sensor fault. Detected at outdoor. Likely cause oil sensor condition (TK1), outdoor PCB fault sensor value 20°c=63k ohms
H08 02 TK2 Oil sensor fault. Detected at outdoor. Likely cause oil sensor condition (TK2), outdoor PCB fault sensor value 20°c=63k ohms
H08 03 TK3 Oil sensor fault. Detected at outdoor. Likely cause oil sensor condition (TK3), outdoor PCB fault sensor value 20°c=63k ohms
H08 04 TK4 Oil sensor fault. Detected at outdoor. Likely cause oil sensor condition (TK4), outdoor PCB fault sensor value 20°c=63k ohms
H08 05 TK5 Oil sensor fault. Detected at outdoor. Likely cause oil sensor condition (TK5), outdoor PCB fault sensor value 20°c=63k ohms
Compressor 2 over-heat. Detected at outdoor. Likely cause compressor klixon activation, loss of refrigerant, poor refrigerant flow reducing cooling
H14
effect to compressor
Page 37 of 78
Code Fault Description
Compressor discharge temperature does not increase while compressor 2 operates. Detected at outdoor. Likely cause compressor discharge sensor
H15
(Td2) condition / location, outdoor PCB fault sensor value 20°c=63k ohms
TK oil sensors do not detect temperature change while compressors operate. Detected at outdoor. Likely cause oil line (TK1 / TK2 / TK3 / TK4 / TK5)
H16 sensor condition / location, outdoor PCB fault sensor value 20°c=63k ohms. Retrieve fault sub-code from condenser interface PCB by placing rotary
dials to position 1 / 1 / 1 for diagnosis.
TK1 oil sensor does not detect temperature change while compressor 1 operates. Detected at outdoor. Likely cause oil line (TK1) sensor condition /
H16 01
location, outdoor PCB fault sensor value 20°c=63k ohms
TK2 oil sensor does not detect temperature change while compressor 2 operates. Detected at outdoor. Likely cause oil line (TK2) sensor condition /
H16 02
location, outdoor PCB fault sensor value 20°c=63k ohms
TK3 oil sensor does not detect temperature change while compressor 3 operates. Detected at outdoor. Likely cause oil line (TK3) sensor condition /
H16 03
location, outdoor PCB fault sensor value 20°c=63kΩ
TK4 oil sensor does not detect temperature change while compressors operate. Detected at outdoor. Likely cause oil line (TK4) sensor condition /
H16 04
location, outdoor PCB fault sensor value 20°c=63kΩ
TK5 oil sensor does not detect temperature change while compressors operate. Detected at outdoor. Likely cause oil line (TK5) sensor condition /
H16 05
location, outdoor PCB fault sensor value 20°c=63kΩ
Compressor discharge temperature does not increase while compressor 3 operates. Detected at outdoor. Likely cause compressor discharge sensor
H25
(Td3) condition / location, outdoor PCB fault sensor value 20°c=63k ohms
Two or more lead units within group of indoor units. Detected indoors. Likely cause incorrect addressing, alteration in grouped set-up / wiring, requires
L03
re-addressing
L04 Duplicated outdoor line address. Detected at outdoor. Likely cause failure to correctly set line address before auto addressing
Duplicated priority indoor unit, displayed on priority indoor unit. Detected indoors. Likely cause two units configured as priority units, correct
L05
configuration within engineers menu 04
Duplicated priority indoor unit, displayed on other than priority indoor unit. Detected indoors. Likely cause two units configured as priority units, correct
L06
configuration within engineering menu code 04
L07 Indoor unit group address incorrectly set. Detected indoors. Likely cause alteration of indoor group set-up, re-address required
L08 Indoor group / addresses unset. Detected at outdoor. Likely cause automatic addressing in-completed
L09 Indoor PCB capacity unset. Detected indoors. Likely cause failure to follow instruction accompanying new PCB
L10 Outdoor PCB capacity unset. Detected at outdoor. Likely cause failure to follow instructions accompanying new PCB
L17 Inconsistency of outdoor unit models. Detected at outdoor. Likely cause incorrect selection on outdoor model references
Flow Selector unit error. Detected indoors. Likely cause indoor unit unable to heat on demand. Check power & communication to F/S Box from local
L18
indoor unit. Incorrectly configured indoor group sharing F/S box
L20 Duplicated central controller address. Detected indoors. Likely cause incorrectly set network address. Engineering code 03
L28 Quantity of outdoor units to high. Detected at outdoor. Likely cause to many outdoor units modularised together
IPDU /PCB communication error. Detected at outdoor. Likely cause Split equipment=faulty or overheating inverter PCB. VRF equipment=loss in
L29 communication between condenser PCB's. Retrieve fault sub-code from condenser interface PCB by placing rotary dials to position 1 / 1 / 1 for
diagnosis. Search fault code (without spaces) for diagnosis e.g. L2901
Page 38 of 78
Code Fault Description
Compressor 1 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace Compressor 1
L29 01
IPDU board
Compressor 2 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace Compressor 2
L29 02
IPDU board
Compressor 1 & 2 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
L29 03
Compressor 1 & 2 IPDU board
Communication failure between PCB within condenser. Detected at outdoor. Fault Code is outdoor model series specific e.g. MMY-MAP###1HT8-E,
L29 04 MMY-AP###2HT8-E or MMY-MAP###4HT8-E therefore example fault code for L2904 will be (MMY-MAP0801HT8-E (series 1), MMY-MAP0802HT8-E
(series 2), MMY-MAP0804HT8-E (series 4) search L29041, L29042 or L29044
L29 04 1 Fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace fan IPDU board
L29 04 2 Fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace fan IPDU board
Compressor 3 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace Compressor 3
L29 04 4
IPDU board
Communication failure between PCB within condenser. Detected at outdoor. Fault Code is outdoor model series specific e.g. MMY-MAP###1HT8-E,
L29 05 MMY-AP###2HT8-E or MMY-MAP###4HT8-E therefore example fault code for L2905 will be (MMY-MAP0801HT8-E (series 1), MMY-MAP0802HT8-E
(series 2), MMY-MAP0804HT8-E (series 4) search L29051, L29052 or L29054
Compressor 1 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
L29 05 1
Compressor 1 IPDU & fan IPDU board
Compressor 1 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
L29 05 2
Compressor 1 IPDU & fan IPDU board
Compressor 1 & 3 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
L29 05 4
Compressor 1 & 3 IPDU board
Communication failure between PCB within condenser. Detected at outdoor. Fault Code is outdoor model series specific e.g. MMY-MAP###1HT8-E,
L29 06 MMY-AP###2HT8-E or MMY-MAP###4HT8-E therefore example fault code for L2906 will be (MMY-MAP0801HT8-E (series 1), MMY-MAP0802HT8-E
(series 2), MMY-MAP0804HT8-E (series 4) search L29061, L29062 or L29064
Compressor 2 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
L29 06 1
Compressor 2 IPDU & fan IPDU board
Compressor 2 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
L29 06 2
Compressor 2 IPDU & fan IPDU board
Compressor 2 & 3 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
L29 06 4
Compressor 2 & 3 IPDU board
Communication failure between PCB within condenser. Detected at outdoor. Fault Code is outdoor model series specific e.g. MMY-MAP###1HT8-E,
L29 07 MMY-AP###2HT8-E or MMY-MAP###4HT8-E therefore example fault code for L2907 will be (MMY-MAP0801HT8-E (series 1), MMY-MAP0802HT8-E
(series 2), MMY-MAP0804HT8-E (series 4) search L29071, L29072 or L29074 for diagnosis
Communication error between PCB within condenser. Detected at outdoor. Likely cause check communication cable linking all PCB's, phase missing on
L29 07 1
power supply, replace interface PCB
Page 39 of 78
Code Fault Description
Communication error between PCB within condenser. Detected at outdoor. Likely cause check communication cable linking all PCB's, phase missing on
L29 07 2
power supply, replace interface PCB
Compressor 1, 2 & 3 IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
L29 07 4
Compressor 1, 2 & 3 IPDU board
L29 08 Fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace fan IPDU board
Compressor 1 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
L29 09
Compressor 1 IPDU & fan IPDU board
Compressor 2 IPDU & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's, replace
L29 0A
Compressor 2 IPDU & fan IPDU board
Compressor 1 & 2 IPDU board & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's,
L29 0B
replace Compressor 1 & 2 IPDU PCB & fan IPDU board
Compressor 3 IPDU board & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's,
L29 0C
replace Compressor 3 IPDU board & fan IPDU board
Compressor 1 & 3 IPDU board & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's,
L29 0d
replace Compressor 1 & 3 IPDU board & fan IPDU board
Compressor 2 & 3 IPDU board & fan IPDU board communication error. Detected at outdoor. Likely cause check communication cable linking all PCB's,
L29 0E
replace Compressor 2 & 3 IPDU PCB & fan IPDU board
Communication error between PCB within condenser. Detected at outdoor. Likely cause check communication cable linking all PCB's, phase missing on
L29 0F
power supply, replace interface PCB
L30 Auxiliary interlock in indoor unit. Detected indoors. Likely cause external interlock in CN80 socket on indoor unit
P01 Indoor fan motor error. Detected indoors. Likely cause indoor fan motor or wiring to motor
High compressor discharge temperature. Detected at outdoor. by TD1 @ 115°c. Likely cause low refrigerant, poor refrigerant flow and airflows & TD1
P03
sensor condition sensor value 20°c=63k ohms
High pressure switch activation. Detected at outdoor. Likely cause poor airflows over indoor / out dependant on operation, restriction in refrigerant
P04 flow, non-condensable mixed with refrigerant. Fault sub code required to determine which H.P Switch activated 01=compressor 1 02=compressor 2
03=compressor 3. Retrieve fault sub-code from condenser interface PCB by placing rotary dials to position 1 / 1 / 1 for diagnosis.
Compressor 1 high pressure switch activation. Detected at outdoor. Likely cause poor airflows over indoor / out dependant on operation, restriction in
P04 01
refrigerant flow, non-condensable mixed with refrigerant
Compressor 2 high pressure switch activation. Detected at outdoor. Likely cause poor airflows over indoor / out dependant on operation, restriction in
P04 02
refrigerant flow, non-condensable mixed with refrigerant
Compressor 3 high pressure switch activation. Detected at outdoor. Likely cause poor airflows over indoor / out dependant on operation, restriction in
P04 03
refrigerant flow, non-condensable mixed with refrigerant
Phase-missing detection / phase order error, compressor inverter High Voltage. Retrieve fault sub-code from condenser interface PCB by placing rotary
P05
dials to position 1 / 1 / 1 for diagnosis. Search fault code (without spaces) for diagnosis e.g. P0501
P05 00 Phase-order incorrect or phase missing. Detected at outdoor. Likely cause issue with power supply to condenser, or phase order wrong, swap L2 & L3
Page 40 of 78
Code Fault Description
Phase-missing detection (series 1 & 2) or High D.C. inverter voltage (series 4). Detected at outdoor. Fault Code is outdoor model series specific e.g.
P05 01 MMY-MAP###1HT8-E, MMY-AP###2HT8-E or MMY-MAP###4HT8-E therefore example fault code for P0501 will be (MMY-MAP0801HT8-E (series 1),
MMY-MAP0802HT8-E (series 2), MMY-MAP0804HT8-E (series 4) search P05011, P05012 or P05014
P05 01 1 Phase-missing detection. Detected at outdoor. Likely cause error on power supply to condenser
P05 01 2 Phase-missing detection. Detected at outdoor. Likely cause error on power supply to condenser
P05 01 4 High D.C. inverter voltage. Detected at outdoor. Likely cause compressor 1 IPDU board overheat or failure
Phase-order incorrect (series 1 & 2) or High D.C. inverter voltage (series 4). Detected at outdoor. Fault Code is outdoor model series specific e.g. MMY-
P05 02 MAP###1HT8-E, MMY-AP###2HT8-E or MMY-MAP###4HT8-E therefore example fault code for P0502 will be (MMY-MAP0801HT8-E (series 1), MMY-
MAP0802HT8-E (series 2), MMY-MAP0804HT8-E (series 4) search P05011, P05012 or P05014
P05 02 1 Phase-order incorrect. Detected at outdoor. Likely cause issue with power supply to condenser, swap L2 & L3 to correct
P05 02 2 Phase-order incorrect. Detected at outdoor. Likely cause issue with power supply to condenser, swap L2 & L3 to correct
P05 02 4 High D.C. inverter voltage. Detected at outdoor. Likely cause compressor 2 IPDU board overheat or failure
P05 03 High D.C. inverter voltage. Detected at outdoor. Likely cause compressor 3 IPDU board overheat or failure
Overheating compressor IPDU / inverter board. Detected at outdoor. Likely cause poorly secured inverter PCB to heat-sink, faulty IPDU. Fault sub code
P07 required to determine which IPDU overheated 01=IPDU1 02=IPDU2 03=IPDU3. Retrieve fault sub-code from condenser interface PCB by placing
rotary dials to position 1 / 1 / 1 for diagnosis.
P07 01 Overheating compressor 1 IPDU / inverter board. Detected at outdoor. Likely cause poorly secured inverter PCB to heat-sink, faulty IPDU board 1
P07 02 Overheating compressor 2 IPDU / inverter board. Detected at outdoor. Likely cause poorly secured inverter PCB to heat-sink, faulty IPDU board 2
P07 03 Overheating compressor 3 IPDU / inverter board. Detected at outdoor. Likely cause poorly secured inverter PCB to heat-sink, faulty IPDU board 3
Indoor float switch open circuit as result of high condensation levels within drip tray, detected indoors. Likely cause faulty float switch, faulty lift pump,
P10
debris blocking drain
P12 Indoor fan motor trouble. Detected indoors. Likely cause fan motor locked, incorrectly configured PCB, indoor PCB fault
Outdoor liquid back detection in condenser while in OFF cycle. Detected at outdoor. Likely cause increase in pressure within dormant condenser,
P13
possible PMV valves passing
High compressor suction or discharge temperature. Detected at outdoor. Likely cause sensor condition (TS1 or TD1, 2 or 3), interface PCB fault, loss of
P15 refrigerant TS1 sensor value 20°c=12.5k ohms TD1,2 & 3 sensor value 20°c=63k ohms. Retrieve fault sub-code from condenser interface PCB by
placing rotary dials to position 1 / 1 / 1 for diagnosis.
High compressor suction temperature. Detected at outdoor. Likely cause suction sensor condition (TS1), interface PCB fault, loss of refrigerant sensor
P15 01
value 20°c=12.5k ohms
High compressor discharge temperature. Detected at outdoor. Likely cause discharge sensor condition (TD1, TD2 or TD3), interface PCB fault, loss of
P15 02
refrigerant sensor value 20°c=63k ohms
High compressor discharge temperature. Detected at outdoor. by TD2 @ 115°c. Likely cause low refrigerant, poor refrigerant flow and airflows & TD2
P17
sensor condition sensor value 20°c=63k ohms
High compressor discharge temperature. Detected at outdoor. by TD3 @ 115°c. Likely cause low refrigerant, poor refrigerant flow and airflows & TD3
P18
sensor condition sensor value 20°c=63k ohms
Incorrect temperature / pressure reading at condenser. Detected at outdoor. Likely cause check characteristics of pressure transducers (PS & Pd) and
P19
temperature sensors (TS1, TE1 & TL), interface PCB fault sensor value 20°c=12.5k ohms
Page 41 of 78
Code Fault Description
High pressure protection detected by discharge pressure transducer reading @ 36bar. Detected at outdoor. Likely cause characteristics of discharge
P20
pressure transducer (Pd), interface PCB, poor airflows across condensers
Outdoor fan motor error. Detected at outdoor. Likely cause Split equipment, locked / faulty fan motor, faulty PCB VRF Equipment. Retrieve fault sub-
P22 code from condenser interface PCB by placing rotary dials to position 1 / 1 / 1 for diagnosis. Search fault code (without spaces) for diagnosis. e.g.
P2203
Outdoor fan motor error. Detected at outdoor. Likely cause locked / faulty fan motor, faulty fan IPDU PCB. Fan motor has 3 ohms resistance on any 2
P22 03
wires
Outdoor fan motor error. Detected at outdoor. Likely cause locked / faulty fan motor, faulty fan IPDU PCB. Fan motor has 3 ohms resistance on any 2
P22 34
wires
Outdoor fan motor error. Detected at outdoor. Likely cause locked / faulty fan motor, faulty fan IPDU PCB. Fan motor has 3 ohms resistance on any 2
P22 37
wires
P22 E1 Fan IPDU board error. Detected at outdoor. Likely cause error on DC supply voltage to fan IPDU PCB or problem with mains voltage onto condenser
P22 E2 Fan IPDU board error. Detected at outdoor. Likely cause error on DC supply voltage to fan IPDU PCB or problem with mains voltage onto condenser
P22 E3 Fan IPDU board error. Detected at outdoor. Likely cause error on DC supply voltage to fan IPDU PCB or problem with mains voltage onto condenser
Compressor IPDU PCB Short circuit. Detected at outdoor. Likely cause electrical fault on compressor, faulty compressor inverter board. Before replacing
P26
PCB prove compressor is good. Retrieve fault sub-code from condenser interface PCB by placing rotary dials to position 1 / 1 / 1 for diagnosis.
Compressor 1 IPDU PCB Short circuit. Detected at outdoor. Likely cause electrical fault on compressor 1, faulty compressor 1 inverter board. Before
P26 01
replacing PCB prove compressor is good
Compressor 2 IPDU PCB Short circuit. Detected at outdoor. Likely cause electrical fault on compressor 2, faulty compressor 2 inverter board. Before
P26 02
replacing PCB prove compressor is good
Compressor 3 IPDU PCB Short circuit. Detected at outdoor. Likely cause electrical fault on compressor 3, faulty compressor 3 inverter board. Before
P26 03
replacing PCB prove compressor is good
Compressor position detection error. Detected at outdoor. Likely cause fault on compressor, faulty compressor inverter board. Before replacing inverter
P29
PCB prove compressor is good. Retrieve fault sub-code from condenser interface PCB by placing rotary dials to position 1 / 1 / 1 for diagnosis.
Compressor 1 position detection error. Detected at outdoor. Likely cause fault on compressor 1, faulty compressor 1 inverter board. Before replacing
P29 01
inverter PCB prove compressor is good
Compressor 2 position detection error. Detected at outdoor. Likely cause fault on compressor 2, faulty compressor 2 inverter board. Before replacing
P29 02
inverter PCB prove compressor is good
Compressor 3 position detection error. Detected at outdoor. Likely cause fault on compressor 3, faulty compressor 3 inverter board. Before replacing
P29 03
inverter PCB prove compressor is good
Indoor unit other than lead indoor suffering fault. Detected on central controller. Likely cause to diagnose retrieve fault code from local remote
P30
controller to indoor group
Indoor unit other than lead indoor suffering fault. Detected indoors. Likely cause to diagnose retrieve fault code from local remote controller to indoor
P31
group
Page 42 of 78
Error Detected by TCCLink Central Controller
Judging
Check Code Wireless Remote
Device
Central Outdoor 7 Segment Display Sensor Block Display Check Code Name
AI Central
Control
Device
Auxiliary Code Controller O T R F
C05 --- --- --- --- Sending error in TCC-Link central control device TCC-LINK
C06 --- --- --- --- Receiving error in TCC-Link central control device TCC-LINK
Batch alarm of general purpose equipment HA control interface
C12 --- --- --- ---
control interface I/F
Differs according to error contents of unit with occurrence of alarm Group control follower unit error
P30 --- TCC-LINK
--- (L20 is displayed) Duplicated central control addresses
Page 43 of 78
Step By Step Wiping/Re-addressing Of VRF Systems
SW11
Operation
Bit 1 Bit 2
OFF OFF Heating priority (Factory setting)
ON OFF Cooling priority
OFF ON Percentage (60%)
ON ON Specific indoor unit
Page 44 of 78
VRF Rotary Dial Data Display - SMMS(i), SHRM(i) & Mini SMMS
Model SW01 SW02 SW03 Display Data
Common 1 1 1 Error data
Common 1 1 2 Pd pressure data
Common 1 2 2 Ps pressure data
Common 1 2 3 System capacity
Common 1 2 16 Latest error code of follower unit No.1 (U2)
Common 1 3 2 PL pressure conversion data
Common 1 3 3 No. of outdoor units
Common 1 3 16 Latest error code of follower unit No.2 (U3)
Common 1 4 1 Outdoor unit HP capacity
Common 1 4 2 TD1 sensor data
Common 1 4 3 No. of connected indoor units / No. of units with cooling thermo ON
Common 1 5 2 TD2 sensor data
Common 1 5 3 No. of connected indoor units / No. of units with heating thermo ON
Common 2 3 1 Indoor PMV forced full open function
Common 2 4 1 Indoor remote controller discriminating function
Common 2 5 1 Cooling test operation function
Common 2 6 1 Heating test operation function
Common 2 16 1 Error clear function
SHRM 1 8 2 TE sensor data
SHRM 1 11 2 TK1 sensor data
SHRM 1 12 2 TK2 sensor data
SHRM 1 13 2 TK3 sensor data
SHRM 1 14 2 TK4 sensor data
SHRM 1 9 2 TL sensor data
SHRM 1 10 2 TO sensor data
SHRM 1 6 2 TS1 sensor data
SHRM 1 7 2 TS2 sensor data
SHRMi 3 8 1 to 2 Compressor 1 operating current
SHRMi 3 9 1 to 2 Compressor 2 operating current
SHRMi 3 10 1 to 2 Compressor 3 operating current
SHRMi 3 11 1 to 2 Fan operating current
SHRMi 1 6 2 TD3 sensor data
SHRMi 1 9 2 TE1 sensor data
SHRMi 1 10 2 TE2 sensor data
SHRMi 1 1 5 TK1 sensor data
SHRMi 1 2 5 TK2 sensor data
SHRMi 1 3 5 TK3 sensor data
SHRMi 1 4 5 TK4 sensor data
SHRMi 1 5 5 TK5 sensor data
SHRMi 1 11 2 TL sensor data
SHRMi 1 12 2 TO sensor data
SHRMi 1 7 2 TS1 sensor data
SHRMi 1 8 2 TS2 sensor data
SMMS 1 4 16 Latest error code of follower unit No.3 (U4)
SMMS 1 7 2 TE sensor data
SMMS 1 11 2 TK1 sensor data
SMMS 1 12 2 TK2 sensor data
SMMS 1 13 2 TK3 sensor data
SMMS 1 14 2 TK4 sensor data
SMMS 1 9 2 TL sensor data
SMMS 1 10 2 TO sensor data
SMMS 1 6 2 TS sensor data
SMMSi 3 8 1 to 3 Compressor 1 operating current
SMMSi 3 9 1 to 3 Compressor 2 operating current
SMMSi 3 10 1 to 3 Compressor 3 operating current
SMMSi 3 11 1 to 3 Fan operating current
SMMSi 1 4 16 Latest error code of follower unit No.3 (U4)
SMMSi 1 6 2 TD3 sensor data
SMMSi 1 8 2 TE1 sensor data
SMMSi 1 9 2 TE2 sensor data
SMMSi 1 12 2 TK1 sensor data
SMMSi 1 13 2 TK2 sensor data
SMMSi 1 14 2 TK3 sensor data
SMMSi 1 15 2 TK4 sensor data
SMMSi 1 16 2 TK5 sensor data
SMMSi 1 10 2 TL sensor data
SMMSi 1 11 2 TO sensor data
SMMSi 1 7 2 TS sensor data
Mini SMMS 1 6 2 TE sensor data
Mini SMMS 1 7 2 TL sensor data
Mini SMMS 1 8 2 TO sensor data
Mini SMMS 1 5 2 TS sensor data
CN30 - Force open all outdoor PMV's short CN30 out and kill
power within 2 minutes to ensure valves stay in fully open position
Page 45 of 78
TCC-net Controller Guidelines
RBC-AMT32-E RBC-AMS41-E
RBC-AMS51-ES
Page 46 of 78
System Configuration Menu
A number of items are configurable by the wired controller – if an indoor unit without a wired controller requires configuration, it
may be temporarily connected for the procedure to be undertaken. In order to access the menu
TEST
Press + SET + CL for 4 seconds
The indoor units to be configured will be chosen by pressing the UNIT button.
The indoor unit being configured runs its fan and swings its louvers (if possible).
Use SET TEMPERATURE up/down buttons to scroll through the configurable items Use TIMER up/down buttons to choose the
configuration value for Use
SET to confirm configuration value Use CL to undo an incorrect setting (provided that configurable item has not been changed)
Use CHECK to return to normal operation
Item Description Value Default
0000: Inactive 0001: 150 H
Filter sign displayed after selected time has elapsed – or by 0002: 250 H 0003: 500 H
01 Filter alarm time 0004: 1000 H
0004
external pressure switch (CN70)
0005: External switch
Allows filter alarm time to be halved if used in a dirty
02 Dirty environment 0000: Standard 0001: Dirty 0000
environment
0099: Unset
03 Network address When under network control. 0001 to 0064 available 0099
Priority Setting for 0 = Normal 1= Priority (This remote has priority of mode
04 0000 = Standard 0001 = Priority 0000
Remote Controller setting
0002; +2oC
Increases effective return air temperature setting in heating
06 Stratification control 0000 to 0010 (Floor type 000;
mode (0 to 10 K) 0oC)
0F Heat Mode Enable or disable Heat Mode 0000 = available 0001 = unavailable 0000
11 Indoor unit capacity 0000 will generate a (L09) fault Air to air heat exchanger
Type
0001= 150m3/h
0002= 250m3/h
0003= 350m3/h
0004= 500m3/h
0005= 650m3/h
0006= 800m3/h
0007= 1000m3/h
Page 47 of 78
System Configuration Menu
1b Compressor on time Compressor minimum on time 0 = 5 minutes 1 = 4 minutes 0000: 0 – 5 min., 0001: 1 - 4 min. 0000
1E Dead band - auto Changeover sensitivity in automatic mode. 1 to 10 k adjustable 0000: 0 K, 0010: 10 K 0003
o o
0018 = 18 C 0020 = 20 C
1F Max. Setting Cooling mode maximum temperature setting (18 – 29) 0029 = 29 o C
29 o C
0000: Usual
29 Humidifier condition Operating condition of humidifier 0001: Condition ignored
0000
45 Anti smudge 4 way cassette – anti smudge effect via louver position 0000 = enabled, 0001 = disabled 0000
60 Timer lock Locks timer in wired local controller – maintaining last setting 0000: unlocked, 0001: locked 0000
62 Anti smudge 4 way cassette – ant smudge via fan speed (Coanda effect) 0001
8b Heating Correction Heating output reduction split systems only 0000: None, 0001: Correction 0000
Run group in HEAT mode after setting defrost is conducted 0000 = disabled
8C Forced Defrost
automatically. Value is reset automatically back to 0000 0001 = enabled
0000
Fan and pump operation during oil retrieval mode (VRF 0000 = fan off, pump on
A0 Fan & Pump
cassettes ONLY) 0003 = fan on, pump on
0003
Page 48 of 78
TCCJ Optional Control Accessories
Operation Control
Night Set Back Control, Snowfall Fan Control and
TCB-PCMO4E Operation Control
External Master On/Off
Peak Power Cut and Noise Reduction. Output for
TCB-PCOS1E2 * Outdoor Control Compressor Operation (*not applicable to all units)
TCB-PCNT30TLE2 Network Adapter U3/U4 TCC Link Connects a RAV Unit to the TCC Link Network
TCB-PCNT20E Network Adapter XY AI Network Connects a RAV Unit to the Old AI Network
Enclosure for the PCNT30TLE2 when used with all
TCB-PX30MUE Terminal Box
RAV Cassette Units
Interface to Provide An Output to Enable An
RBC-SMF1 Fan Interface
external Fan From the Unit
Interface to Indicate the Mode of Unit Operation
RBC-SMIM2 Indicator Module Mode
Output For Cool, Heat and Fan Only
Indicator Module ON/OFF and Interface to Indicate Unit Operation and Stopping
Boards
Indoor
RBC-SMIM3 Fault
Stopping Fault
Indicator Module ON/OFF, Stopping Interface to Indicate Unit Operation and Stopping
RBC-SMIM4 Fault and Unit Enable Fault. It Also Has Connections to Enable the Unit
Interface to Connect to a 0-10v or Resistance Based
RBC-FDP3-PE BMS Interface
BMS This Also Has Modbus Functionality
Interface to Accept a 240v Input from a Timer for
RBC-IT2-PE Timer Interface
R22 and R407C Systems
RBC-IT3-PE Daiseikai/AvAnt 240v Timer Interface Connects to “HA” Socket for RAS Units
TCB-PCM03E External Input PCB Interface to Switch the Estia Unit On or Off
TCB-PCIN3E Output PCB Interface Provides an Output for Estia Fault and Run
RBC-FSEX15 Flow Selector Lead 15m Extension Lead Kit for the Flow Selector
RBC-SMCN61 On/Off and Locking Lead Remotely Switches Unit ON/OFF and Locks Function
Accessories
Page 49 of 78
TCC-Net Control
Features
2 wire, screened, non-polarised controller connection
Infra red control available for cassette models
Remote temperature sensing available
Wired controller
Infra red controller
Separate room sensor
Automatic addressing of groups and twins
Optional control of external fan
High ceiling compensation
Time for filter warning is configurable
Each mode of operation (auto – heat – cool – dry) may have a different temperature set point
Auto restart is configurable
Louver TA TCJ TC
Wired controller
1. Set data – displayed 6. Filter alert 12. Displayed when using the
when setting timer 7. Not used remote sensor
2. Operating mode 8. External fan active 13. Preheat defrost
3. Alarm alert 9. Louver position 14. Not used
4. Timer/check code 10. Louver swinging 15. Fan speed
5. Choice of timer mode 11. Set temperature 16. Displayed during test run
Page 50 of 78
A-B A-B
Automatic addressing
This takes place when power is applied and can last up to 5 minutes – the address will be selected automatically. If a
replacement indoor PCB is fitted, the missing address will be re-applied.
The powered controller screen shows the demarcation lines – and does not indicate that the system is either
configuring itself – or is ready to use. If the remote temperature sensor is selected (configuration item 32), the
associated symbol will appear when the system is ready for use. If a 9 th indoor unit (which can be a protocol
converter) is added to a group, the controller will continue to show the demarcation lines.
Adding a system to an existing group (or powering a group up at different times) will require manual configuration
(the fault codes will provide guidance).
Test operation
System must be stopped
Press TEST for 4 seconds
Controller displays TEST
Press the ON/OFF button to start operation
Select MODE of operation
HEAT or COOL
Press the ON/OFF button to stop test
System will automatically revert to normal operation after 1 hour
Press the TEST button to leave TEST function
Page 51 of 78
System Data
System data can be obtained by pressing “TEST & CL” together and holding
for 4 seconds. Codes are displayed on the right of the remote display.
To scroll through the codes use the “TEMP” buttons. Data is displayed on the left of
the remote controller. Data is available for “0, 1, 2, 3 & 4 Series” Digital/Super Digital
inverter and VRF equipment (Mini SMMS, SHRM, SHRMi, SMMS & SMMSi).
VRF Outdoor Data For Mini SMMS / SMMS & SHRM Equipment
Code Outdoor Data Code Outdoor Data
*0 Td1 Compressor 1 Discharge Temp (°C) *8 TU Low Pressure Saturated Temp (°C)
*1 Td2 Compressor 2 Discharge Temp (°C) *9 Compressor 1 Current (A)
*2 Pd High Pressure Sensor (MPa) *A Compressor 2 Current (A)
*3 Ps Low Pressure Sensor (MPa) *b PMV1 + 2 Opening (0-100)
*4 TS Suction Temp (°C) *d Compressor 1, 2 ON/OFF
*5 TE Outdoor Heat Exchanger Temp (°C) *E Outdoor Fan Mode (0-31)
*6 TL Liquid Temp (°C) *F Outdoor Unit Size (HP)
Note * Would be replaced with 1, 2, 3 or 4 to obtain data from respective outdoor unit.
Page 52 of 78
VRF Outdoor data for SMMSi equipment
Code Outdoor Data Code Outdoor Data
*0 Pd – High Pressure Sensor (MPa) #0 Compressor 1 Revolutions (rps)
*1 Ps – Low Pressure Sensor (MPa) #1 Compressor 2 Revolutions (rps)
*2 Td1 – Compressor 1 Discharge Temp (°C) #2 Compressor 3 Revolutions (rps)
*3 Td2 – Compressor 2 Discharge Temp (°C) #3 Outdoor Fan Mode
*4 Td3 – Compressor 3 Discharge Temp (°C) #4 Compressor IPDU 1 Heat Sink Temp (°C)
*5 TS – Suction Temp (°C) #5 Compressor IPDU 2 Heat Sink Temp (°C)
*6 TE1 – Outdoor Coil Temp (°C) #6 Compressor IPDU 3 Heat Sink Temp (°C)
*7 TE2 – Outdoor Coil Temp (°C) #7 Outdoor Fan IPDU Heat Sink Temp (°C)
*8 TL – Liquid Temp (°C) #8 Heating / Cooling Recovery Controlled
*9 TO – Outdoor Ambient Temp (°C) #9 Pressure release
*A PMV 1 + 2 Opening #A Discharge Temp. Release
*B PMV 4 Opening #B Follower Unit Release
*C Compressor 1 Current (A) #F Outdoor Unit Size (HP)
*D Compressor 2 Current (A) Note; * Is replaced with 1, 2, 3 or 4 to obtain data from
*E Compressor 3 Current (A) respective outdoor unit.
*F Outdoor Fan Current (A) # Is replaced with either 5, 6, 7, 8 to obtain data from
outdoor units 1, 2, 3 or 4
*Accessed using Toshiba hard wired remote controller RBC-AMT32E and RBC-AMS41E
Relocation of Room Temperature Sensing from Return Air to Remote Controller Sensor
Press and hold the ”TEST, SET & CL“ Buttons simultaneously for 4 seconds
The Engineering Menu is accessed at item code 10
Use the “TEMP” Buttons to navigate to item code 32
Use the “TIMER” Buttons to adjust the value from 0000 to 0001
Press SET to acknowledge the change
Press TEST to exit the Engineering Menu
The display will go blank and then flash SETTING whilst the system reconfigures
When SETTING stops flashing press ON/OFF Button to restart the operation
Page 53 of 78
Simplified Instructions for RBC-AMS41E Remote Controller
Press and hold the SCHEDULE for 4 seconds SETTING appears on screen
Press DAY until the correct day of the week is indicated
Press TIME up and down keys to set current time
Press SET to confirm entries. Day and time now set
The bar now underlining MONDAY indicates that times have now been entered
Page 54 of 78
Time Temp & Mode Setting for RBCAMS41E Remote Controller
The bar now underlining MONDAY indicates that times have now been entered
Page 55 of 78
Simplified Instructions for RBC-AMS51EES Remote Controller
Controller Layout
Room A 12:00
24
Cool
Mode Fan Speed
5
8 6
The button LED lights while the air conditioning unit is
4 running.
1
7
Temperature sensor
▼ Icon list
Shows the Energy saving operation is activated Shows a timer function is activated.
Shows the remote controller sensor is activated Shows the Louver lock is activate
Shows the use of remote controller is prohibited ! Shows the filter needs to be cleaned.
Page 56 of 78
Fault Code Guide for RBC-AMS51EES Remote Controller
Fault codes are displayed automatically at the top of the LCD display
Code: *** Unit : #-#)
Main power switch flashes “Green”.
Fault code history can be accessed by “Field Setting Menu”
A list of the latest 10 alarm codes along with date, time and unit are
displayed. The oldest data is deleted in order to record the newest.
The date and time when the error occurred for the first time are
displayed for any repeated alarms.
Press the button Reset
Reset to reset alarm codes
Refer to Technical Handbook for fault code diagnosis and descriptions or use Smart Phones to download Toshiba Fault Codes from
your Apps Store or go to web page Toshiba-calc.co.uk/fault-codes/
Page 57 of 78
Data Retrieval Guide RBC-AMS51EES Remote Controller
Page 58 of 78
Relocation of Room Temp Sensing from Return Air to Remote Controller
Page 59 of 78
Automatic Restartafter Power Failure
Page 60 of 78
Automatic Restart after Power Failure
Initial setting(1/2)
1.Clock
2.Name of room
3.Screen contrast
Select "1 Clock" then press Set
4.Backlight
5.Key lock
Return
Set
Clock
∨][ ∧ ] buttons to select year, month, date
Date 01
Presss the [
Month 01
and time. Press the or buttons to set the value Year 2010
Hour 00
Press the [ MENU ] button to return to "Menu" screen
Minute 00
Return Fix
– +
Schedule timer
1.Schedule timer
Press the to turn On or ON / OFF
2.Condition setting
press the to turn Off the "Schedule timer" 3.Holiday setting
Return Fix
Page 61 of 78
Condition Setting (Day, Time, Mode & Temperature)
Schedule timer
1.Schedule timer
ON / OFF
Presss the [ ∨][ ∧ ] buttons to scroll through settings 2.Condition setting
3.Holiday setting
to select option "2 Condition setting" then press Set
Return Fix
Set
Schedule timer(1/3)
Day : Monday
The current settings are displayed 1. -- --:-- --°C
Press the 2. -- --:-- --°C
Day to confirm the day settings
3. -- --:-- --°C
Press the Next to confirm setting, 8 settings appear 4. -- --:-- --°C
Return Set
Day Next
Schedule timer(1/3)
Day : Monday
Press the [ MENU ] button 1. -- --:-- --°C
Presss the [ ∨][ ∧ ] buttons to select the day to set 2. -- --:-- --°C
3. -- --:-- --°C
Press the 4. -- --:-- --°C
Return Fix
Reset
Schedule timer
Press the [ MENU ] button
Schedule timer confirm?
Press the Yes to confirm
Page 62 of 78
Delete Settings for each Day
Schedule timer(3/3)
Day : Monday
Press the Day button to select day 5. ON 13:00 25°C
6. OFF 17:00 --°C
Press the [ MENU ] button 7. ON 22:05 25°C
8. OFF 23:45 --°C
Return Set
Day Next
Schedule timer(1/3)
Day : Tuesday
Press the [ MONITOR ] button on day selection screen 1. -- --:-- --°C
2. -- --:-- --°C
Press the Reset button 3. -- --:-- --°C
Schedule for the day selected is deleted 4. -- --:-- --°C
Return Fix
Reset
Schedule timer
Press the Yes to delete the day setting Delete the day setting?
Press the No to return to Schedule timer screen
Return
Yes No
Schedule timer(3/3)
Day : Monday
5. ON 13:00 25°C
Press the Day button to select day 6. OFF 17:00 --°C
Press the [ MENU ] button 7. ON 22:05 25°C
8. OFF 23:45 --°C
Return Set
Day Next
Schedule timer(1/3)
Day : Tuesday
1. -- --:-- --°C
Press the [ MONITOR ] button on day selection screen 2. -- --:-- --°C
3. -- --:-- --°C
4. -- --:-- --°C
Return Fix
Reset
Schedule timer
Page 63 of 78
Holiday Day Omit Setting
Press the [ MENU ] button to display the "Menu" screen Schedule timer
1.Schedule timer
Presss the [ ∨][ ∧ ] buttons to scroll through settings ON / OFF
& select option "5 Scheduled timer" then press Set 2.Condition setting
3.Holiday setting
Presss the [ ∨][ ∧ ] buttons to scroll through settings
to select option "3 Holiday setting" then press Set Return Fix
Set
Holiday setting
Press the Day button to select the day to omit Mon Tue Wed Thu Fri Sat Sun
Press the Set button to set day to omit
Press the [ MENU ] button to "Fix" the setting
Return Fix
Day Set
(QHUJ\6DYLQJ)XQFWLRQ
Menu(2/3)
MENU ] button to display the "Menu" screen 6.Night operation
Press the [
7.Filter sign reset
Presss the [ ∨][ ∧ ] buttons to scroll through settings & 8.Auto grille
select option " (QHUJ\sDYLQJ operation" 9.Energy saving
10.Initial setting
Press the button to set Energy saving operation Return
Set
Press the %+ button to increase % ratio (max 100%) Energy saving ratio
Energy saving ratio
Press the % button to decrease % ratio (min 50%)
75%
The lower the value is set, the higher the power saving effect becomes
Press the [ MENU ] button to "Fix" the setting
" Setting" appears on the screen, then the screen returns to Return Fix
the “Energy saving operation” screen %+ %–
Page 64 of 78
(QHUJ\6DYLQJTemperature
Menu(2/3)
Press the [ MENU ] button to display the "Menu" screen 6.Night operation
7.Filter sign reset
Presss the [ ∨][ ∧ ] buttons to scroll through settings & 8.Auto grille
select option " (QHUJ\sDYLQJ operation" 9.Energy saving
10.Initial setting
Press the Set button to set Energy saving operation Return
Set
Energy saving
1.Energy saving operation
Presss the [ ∨][ ∧ ] buttons to scroll through settings & <ON>
2.Set temp. range limit
select option "2.Set temp. range limit" Set
3.Return back
Press the Set button to set <OFF>
Return
Set
Press the button to select temperature settings Set temp range limit
Minimum ~ Maximum
Press the button to select temperature settings Cool 18.0°C ~ 29.0°C
Return Fix
The time of the schedule setting for the Save operation can be set within the range from 0:00 to 23:50 at 10 minute intervals.
The save ratio of the schedule setting for the Energy saving operation can be selected only from "Random (random is the value set
at Energy saving ratio)" 50% or 0%
Adjust the clock before setting the energy saving schedule.
The lower save ratio is applied when the different save ratios are set at the same hours on the schedule.
Page 65 of 78
VN AirAir Heat Exchangers
Impossible o
\ appears on screen if a ventilation unit is not connected Return
Set
Ventilation
1.ON/OFF
Presss the [ ∨][ ∧ ] buttons to scroll through settings & <OFF>
2.Fan speed <L>
select option "1.ON/OFF" Set
3.Mode
Press the Set button to set 4.24H ventilation off
Return
Set
Return Fix
NOTE
• “Impossible” appears on the display when no ventilation unit is connected or the individual operation for the ventilation
unit is not activated.
• “2. Fan speed” or “3. Mode”, “4. 24H ventilation off” is available only for the air conditioning system using the Toshiba
Air to Air Heat Exchanger VN-M*HE series. Refer to the Owner’s Manual supplied with the Air to Air Heat Exchanger
for details.
• “ ” appears on the detailed display during the ventilation operation when the ventilation unit other than the Toshiba
Air to Air Heat Exchanger VN-M*HE series is used and the individual operation for the ventilation unit is activated.
Page 66 of 78
VN AirAir Heat Exchangers
Controller
Energy Save operation (RBC-AMS51EES/RBC-AMT32E/RBC-AMS41E)
The method to control power consumption by limiting the peak of the compressor's electric current.
= To control peak current by limiting **% of the current release
RBC-AMS51E-ES RBC-AMT32E/RBC-AMS41E
O 0%, 50%, Option 50-100% per 1% Option 50-100% per 1%
X NA NA
0000: Normal
Adjusting this setting is necessary
Imbalanced Fan speed 0001: SA (High) > EA (Low) active
48 ventilation 0002: SA (Low) < EA (High) active * “High” may be
0000: Normal for all the Air to Air Heat
Exchangers in the group.
“Extra High”.
Adjusting this setting is necessary
49 24-hour ventilation 0001: Invalid 0002: Valid 0001: Invalid for all the Air to Air Heat
Exchangers in the group.
Setting of the 0000: Exhausting fan run Adjusting this setting is necessary
0001: Exhausting fan stop 0000: Exhausting
4D exhausting fan operation
*The supplying fan stops when the temperature is fan run
for all the Air to Air Heat
below -15 °C (OA) Exchangers in the group.
below −15 °C. (OA)
0000: ON/OFF linked
Adjusting this setting is necessary
0001: ON linked 0002: OFF linked
Setting of the linked for an Air to Air Heat Exchanger to
*Specifies whether the ON/OFF 0000: ON/OFF
4E operation with external
operation of the Air to Air Heat linked
which an adapter for remote
devices ON/OFF control (sold separately)
Exchanger is linked with the external
is connected.
device operation
0001: Bypass mode
0002: Heat Exchange mode
Changing the ventilation 0003: Automatic
EA mode
0003: Automatic mode
mode
*1
*Compatible with systems without a
remote controller and RBC-AMT32E
0002: High
0003: Low
Changing the ventilation
EB Fan speed
0004: Imbalanced 0002: High *1
*“High” may be “Extra High”.
*Compatible with systems without a
remote controller and RBC-AMT32E
Page 67 of 78
VN AirAir Heat Exchanger Configurations
Fig.1 Fig.2
SW-702
NO CHANGE SW-702/703
A/C NO CHANGE
VN UNIT INDOOR UNIT
VN UNIT
SW-703 BIT 4 ON
A & B NETWORK
NRC-01HE NRC-01HE
Fig.3
SW-702/703 SW-702 BIT 1 ON
A/C NO CHANGE SW-703 NO CHANGE
INDOOR UNIT VN UNIT VN UNIT
A & B NETWORK
NRC-01HE
U3 & U4 NETWORK
RBC-AMT31-E NO NO NO
RBC-AMT32-E YES NO NO
Page 68 of 78
Automatic Zone Registration Using the Central Remote Controller (TCB-SC642TLE2)
1) Press the and buttons at the same time for more
than 4 seconds.
and CODE No. C! will flash.
2) Select CODE. No. C” by pressing and ( ) button
and press the button.
C2 changes from flashing to ON state and automatic zone
Registration will start.
3) Registered GROUP No. will be disappeared all.
4) Central address will be assigned from small indoor unit
address to large one in numerical order automatically.
Finishing automatic zone registration, changes from
Flashing to OFF.
5) If an error occurs, the “CHECK” starts flashing and
zone registration finishes at this time. Press the button.
6) Finally, complete automatic zone registration mode by
pressing the button.
Flashes for a few minutes, then OFF.
When setting up a central remote controller, which includes more than one outdoor system, each outdoor
system needs to have a system address set, factory setting is 1.
Additional systems may be addressed up to a system number of 28. This is achieved via “Dip switches” SW13 & 14
Page 69 of 78
Network Addressing DI/SDI and VRF Systems
Definition of address
Indoor unit address
“Indoor unit address” This enables the outdoor unit to recognize each individual indoor unit.
An unique address is allocated to every indoor unit within a refrigeration system.
Header Follower Header Follo wer
Line address
Code 12 0001 0001 0001 0001
Outdoor
Indoor unit
Remote
controller
Indoor unit 0001 0002 0003 0004 0001 0002 0003 0004
Code 13 address
Group address (VRF) in case of DI/SDI, please refer to Address setup procedure (when using DI/SDI only or using DI/SDI and VRF) page 75
“Group address” This is the address that recognizes the group control and determines the header indoor unit and follower indoor unit.
Group address and the header indoor unit is decided automatically when the automatic address setting is performed.
(Which indoor unit becomes the header unit is indefinite when automatic address setting is performed.)
Indoor unit of individual control : Group address = 0
Header indoor unit of group control : Group address = 1
Follower indoor unit of group control : Group address = 2
Header Follower Header Follower
Line address
Code 12 Outdoor 0001 0001 0001 0001
Indoor unit
Remote
controller
Indoor unit 0001 0002 0003 0004 0001 0002 0003 0004
Code 13 address
Group
Code 1 4 0000 0000 0001 0002 0000 0002 0001 0002
address
Indoor unit
Remote
controller
Page 70 of 78
Network Addressing DI/SDI and VRF Systems
Central control address
“Central control address” is used to make the central control devices recognize each indoor unit.
Address can be set from the central control devices either automatically or manually, or from wired remote controller devices manually.
In the case of group control in the VRF systems, one central control address is allocated to each indoor unit in a group control.
Line 1 Line 2
(Refrigerant system 1) (Refrigerant system 2)
Line address
Code 12 Outdoor 0001 0002
Indoor unit
Remote
controller
99 Not set up
Zone 1 Zone 2
Zone 1 2
Central Central
Zone 1 RC* Zone 2 RC*
Indoor unit
Remote
controller
Central
Code 03 control 0001 0002 0003 0004 0017 0018 0019 0020 0021
address
* RC: Remote controller
When using BMS-CM1280TLE or BMS-CM1280FTL, you can allocate a zone to each of the 64 central control addresses.
Page 71 of 78
Network Addressing DI/SDI and VRF Systems
Terminology
Terms for explaining DI/SDI used in section are redefined to:
Indoor Unit No. N-n =outdoor unit line address N (Max30) –indoor unit address n (max64)
Group address 0=single (not group control)
1=Master unit in group control
2=sub unit in group control
Master unit:
The representative of multiple indoor units in group operation sends/receives signal to/from the remote controllers and sub
indoor units. It has no relation with an indoor unit which communicates serially with the outdoor units. Also this unit
communicates with the central controller. The operation mode and setup temperature range are reflected on the remote
controller LCD. (Except air direction adjustment of louver)
Sub unit:
Indoor units other than master unit in group operation. Basically, sub units do not send/receive signals to/from the remote
controller.
Header unit (Representative unit) (Master twin):
This unit communicates with the indoor unit (follower) which serial-communicates with the outdoor units and sends/receives
signal (command from compressor) to/from the outdoor units as the representative of the cycle control in the outdoor units of
the identical line address within the minimum unit which confugures one of the refrigerating cycles of twin.
Follower unit (Subordinate unit) (Sub twin):
Indoor units excluding the header unit in Twin. This unit communicates with Header indoor unit in the identical line address
and performs control synchronized with Header unit. This unit does not perform the signal send /receive operation with the
outdoor units. No judgement for serial signal error.
Basic configuration
The basic DI/SDI connection configuration of each type of model is shown below.
Single Twin Triple Double Twin
Outdoor Outdoor Outdoor Outdoor
unit unit unit unit
Page 72 of 78
Network Addressing DI/SDI and VRF Systems
Group configuration (single only)
In this case, address setting can be made by using auto addressing.
Single Single Single Single Single
Outdoor Outdoor Outdoor Outdoor Outdoor
unit unit unit unit unit
Max. 8 units
Remote
controller
Max. 8 units
Remote Example of after Automatic address setting
controller
* Each line address shall be set for each refrigerating cycle Max. 8 units
Remote
controller
* Mater address shall be set to one indoor unit in a group.
* Max. 8 indoor units in a group.
U3 U4 U3 U4
A B A B A B A B A B
Remote Remote
controller controller
Page 73 of 78
Network Addressing DI/SDI and VRF Systems
A central control connection example of a system where both VRF and DI/SDI are used is shown below. The VRF and DI/SDI
subsystems are connected through the central control wiring and to the central control devices.
Central Control Central Control
Device1 Device2
U1 U2 U1 U2
U3 U4 U3 U4
central control wiring
Header Follower Header Follower
U3 U4 U3 U4 U3 U4 U3 U4
ODU ODU
ODU ODU ODU ODU
123 123
U1 U2 U5 U6 U1 U2 U5 U6 U1 U2 U5 U6
U1 U2 U5 U6 Sub/Follower
VRF DI/SDI
After automatic address setup, it is necessary to change the line address from the wired remote controller for each system.
Reason : After automatic address setup, all of the line addresses will become “1” except in a group control and then a
duplicated address error “E08” will be outputted.
* TCB-PCNT30TLE
No change
Need to change line address3 Need to change
line address
* A wired remote controller (RBC-AMT21E
or RBC-AMT32(31)E, RBC-AMS41E) is
required for address change.
Page 74 of 78
Network Addressing DI/SDI and VRF Systems
When the central control is performed for indoor units using twin control in a group operation, it may be required to change the
group address. (Adapter is attached to the Master indoor unit.)
Reason : The central control device communicates with each individual indoor unit, the Master indoor unit of the group
control and the Master indoor unit of the twin control. However, as the address is automatically set up, which unit
will become the Master unit is indefinite. Therefore if the unit attached with adapter does not become the Master
indoor unit, the central control function will become unavailable.
*TCB-PCNT30TLE
Code 12 Line address outdoor 0001 0002 0003 0004 0005 0006
Code 13 Indoor unit address 0001 0001 0001 0001 0001 0001
Code 14 Group address 0001 0002 0002 0002 2 0002 0002 0002 0000
Address setup procedure (when using DI/SDI only, or using DI/SDI and VRF)
When an outdoor unit and an indoor unit are connected, or when an outdoor unit is connected to each indoor unit
respectively in the group operation even if multiple refrigerant lines are provided, the automatic address setup completes
with power -ON of the outdoor unit after group construction check (refer to the note below). The operation of the remote
controller is not accepted while automatic address works. (Approx.4 to 5 minutes)
CAUTIONS
1. Set up address after the wiring has been completed.
2. “1:1Model” Connection Interface TCB-PCNT30TLE2 is necessary for DI/SDI for central control. Some Hi-wall
Type do not need “1:1Model” Connection Interface. Please refer to the installation manual of each model.
Connect the central control devices to U3/U4 wires of the central control system.
3. When “1:1Model” Connection Interface is used for the group control or twin, triple or quad system, the interface
must be connected to the Master unit of the indoor unit. (Connection to Sub unit is unavailable). One “1:1Model”
Connection Interface per one group.
4. In group operation, be sure to turn on power supplies to all indoor units in group control within 3 minutes. When
power supply of the Master unit is not turned on, there is a possibility that the Master unit exchanges with Sub
unit. (If Master unit is exchanged, the central control is unavailable.)
Note)
If group construction is abnormal, the automatic address sequence starts automatically. Normal
condition is below.
1. There is no duplicated indoor unit address.
2. There is no invalid indoor unit address.
3. Individual unit and master/sub units are not intermingled.
4. Only a unit for Individual.
5. A master indoor unit and 1 or more sub indoor units for group.
Page 75 of 78
Integration with AI Network Control
TCC-net models use a different language to AI – however a TCC-net group can be linked to an AI network, by the use of
a protocol converter. This device is not standard and should be fitted on site – a group requires Network
only one protocol converter to communicate with a network. controller
Second Controller
Options available
2 x wired controllers
1 wired + 1 infra red controller
Full group control from either
Connection may be anywhere within group
Changes updated
The sub-controller must be set – this can be done from either controller. The choice of sub-controller makes little
difference unless it is required to act as the temperature sensor
Temperature Sensing
Both infrared and wired controllers are able to supply a temperature value to the indoor unit. This may be more
representative than the standard, return air sensor but is not available from sub controllers of either type. To set the
room sensor:
Infrared controller – press MAIN SENSOR
Wired controller – selected from configuration menu
Room sensor
A-B A-B
Remote sensor
Should the infrared controller lose contact with the indoor unit, return air temperature control will automatically resume.
A further option for remote sensing is available – the remote sensor. This is connected to terminals A-B whether or not a
wired controller is used. The indoor unit must, in this case, be set to use the standard, return air sensor – this sensor
automatically takes over in this case. This value will be used to provide control to all indoor units within the group.
Page 76 of 78
Toshiba
Air Conditioning
Our vision is to be the No 1 supplier in the UK of the most technologically innovative,
energy efficient and environmentally friendly comfort cooling solutions, combined with a
first class level of customer support.
Providing a number of key services to our customers, these include the following:
• Spare Parts Availability - Large stock, European warehouse based in the UK offering a 24hr turnaround from point
of order, including online parts availability check and ordering.
• Pre-Sales Support - Offering project support and assistance, equipment schedules, mechanical and electrical
schematics and equipment selection.
• Technical Support - We have the industry’s only 24/7/364 technical helpline where you can speak to a trained
engineer for support as well as offering full fault code text back service or download Toshiba Fault Codes from your
Apps Store or go to web page toshibacalc.co.uk/faultcodes/
• Post-Sales Support - Peace of mind with the industry’s most comprehensive warranty support package. Up to 7
year warranty with full labour content support.
• Dedicated Training Sessions - Training sessions are offered to our customers throughout the year and cover all
elements from design and application, installation through to servicing and fault finding.
• Controls - Full support including bespoke controls and full site support functions to maximise efficiency.
• Additions Loyalty Scheme - The original and best scheme in the industry that sets the bar in terms of support.
The information shown in this Technical Book is based on the following data:
• Nominal capacities are based on Eurovent - Cooling: indoor air temperature 27OC db/19OC wb, outdoor air
temperature 35OC db/24OC wb. Heating: indoor air temperature 20OC db, outdoor air temperature 7OC db
• The sound pressure levels are based on - Outdoor units at 1 m distance, indoor units at 1.5 m distance
• The maximum running current is based on 230 V, 1 phase and 380 V, 3 phase in the cooling mode.
Tel: 01372 220240 Tel: 0870 843 0333 Tel: 0870 843 0333
Fax: 01372 220241 Fax: 01752 784574 Fax: 0161 794 4743
[email protected] [email protected] [email protected]
www.toshiba-aircon.co.uk
24 Hour Technical Helpline: 0870 843 0333
Fault & DN Code Apps: Android & iPhone
Web Page toshiba-calc.co.uk/fault-codes/
Fault Code Text Service: 07624 803 017
[email protected]
www.toshiba-aircon.co.uk