Gate Questions Bank EE Power System
Gate Questions Bank EE Power System
QUESTION BANK
1. A cylindrical rotor generator delivers 0.5 pu power (a) 0.87 (b) 0.74
in the steady-state to an infinite bus through a (c) 0.67 (d) 0.54
transmission line of reactance 0.5 pu. The
generator no-load voltage is 1.5 pu and the infinite Common Data Questions 4 & 5:
bus voltage is 1 pu. The inertia constant of the A generator feeds power to an infinite bus through
generator is 5 MW-s/MVA and the generator a double circuit transmission line. A 3-phase fault
reactance is 1 pu. The critical clearing angle, in occurs at the middle point of one of the lines. The
degrees, for a three-phase dead short circuit fault infinite bus voltage is 1 pu, the transient internal
at the generator terminal is voltage of the generator is 1.1 pu and the
(a) 53.5 (b) 60.2 equivalent transfer admittance during fault is 0.8
(c) 70.8 (d) 79.6 pu. The 100 MVA generator has an inertia constant
2. A 500 MVA, 21 kV, 50 Hz, 3-phase, 2-pole of 5 MJ/MVA and it was delivering 1.0 pu power
synchronous generator having a rated p.f. 0.9, has prior of the fault with rotor power angle of 30º.
a moment of inertia of 27.5 × 103 kg–m2. The system frequency is 50 Hz.
The inertia constant (H) will be
4. The initial accelerating power (in pu) will be
(a) 2.44 (b) 2.71
(c) 4.88 (d) 5.42 (a) 1.0 (b) 0.6
3. Consider a synchronous generator connected to (c) 0.56 (d) 0.4
an infinite bus by two identical parallel transmission
5. If the initial accelerating power is X pu, the initial
lines. The transient reactance X of the generator
acceleration in elect deg/sec, and the inertia
is 0.1 pu and the mechanical power input to it, is
constant in MJ-sec/elect deg respectively will be
constant at 1.0 pu. Due to some previous
disturbance, the rotor angle () is undergoing an (a) 31.4 X, 18 (b) 1800 X, 0.056
undamped oscillation, with the maximum value of (c) X/1800, 0.056 (d) X/31.4, 18
(t) equal to 130º. One of the parallel lines trip due
to relay maloperation at an instant when (t) = 6. A generator with constant 1.0 p.u. terminal voltage
130º as shown in the figure. The maximum value supplies power through a step-up transformer of
of the per unit line reactance, X such that the 0.12 p.u. reactance and a double- circuit line to an
system does not loss synchronism subsequent to infinite bus bar as shown in the figure. The infinite
this tripping is bus voltage is maintained at 1.0 p.u. Neglecting
1.00º the resistances and susceptances of the system,
the steady state stability power limit of the system
X
X = 0.1pu is 6.25 p.u. If one of the double-circuit is tripped,
then resulting steady state stability power limit in
X
p.u. will be
1.0
1.9696 1.0
= 1.64 P.u.
1.2
C By keeping active power fixed if the excitation is
min 0
reduced, then the critical excitation corresponding
to operation at stability limit be E1
Initially
Mechanical Input (PS1) = Electrical output E1V
0.8 = sin 90
(Pel) = 0.5 Pmax Xd
c = 23.578º
1.1 1.0
= 0.15 0.3 || 0.3 3.67 p.u.
0
0 min 0.4 = sin d
min