Product Data Sheet: Micrologic 6.0 A Trip Unit - LSIG - For NT, NW

The document describes the Micrologic 6.0 A trip unit, which provides earth fault, short circuit, and overload protection for Schneider Electric's Masterpact NT and NW circuit breakers. The trip unit comes in ratings from 630A to 6300A and offers adjustable settings for long time pickup, short time pickup, instantaneous pickup, and ground fault pickup. It provides protection functions for distribution networks operating at 50/60Hz.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
183 views2 pages

Product Data Sheet: Micrologic 6.0 A Trip Unit - LSIG - For NT, NW

The document describes the Micrologic 6.0 A trip unit, which provides earth fault, short circuit, and overload protection for Schneider Electric's Masterpact NT and NW circuit breakers. The trip unit comes in ratings from 630A to 6300A and offers adjustable settings for long time pickup, short time pickup, instantaneous pickup, and ground fault pickup. It provides protection functions for distribution networks operating at 50/60Hz.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Product data sheet 33073

Characteristics Micrologic 6.0 A trip unit - LSIG - for NT, NW

Main

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Range of product Masterpact NT
Masterpact NW
Product or component type Control unit
Range compatibility Masterpact NT06...16
Masterpact NW08...40
Masterpact NW40b...63
Device application Distribution
Poles description 3P
4P
Network type AC
Network frequency 50/60 Hz
Trip unit name Micrologic 6.0 A
Trip unit technology Electronic
Trip unit protection functions Selective + earth-fault protection
Trip unit rating 630 A ( 50 °C )
800 A ( 50 °C )
1000 A ( 50 °C )
1250 A ( 50 °C )
1600 A ( 50 °C )
2000 A ( 50 °C )
3200 A ( 50 °C )
5000 A ( 50 °C )
6300 A ( 50 °C )
2500 A ( 50 °C )
4000 A ( 50 °C )
Protection type Earth fault
Instantaneous short-circuit protection
Overload protection (long time)
Short time short-circuit protection

Complementary
Long time pick-up adjustment type Ir Adjustable 9 settings
Long time pick-up adjustment range 0.4...1 x In
Long time delay adjustment type Adjustable
[Tr] long-time delay adjustment range 11 s 7.2 x Ir
16 s 6 x Ir
400 s 1.5 x Ir

Feb 5, 2019
1
0.69 s 7.2 x Ir
0.7 s 6 x Ir
0.7 s 7.2 x Ir
1 s 6 x Ir
1.38 s 7.2 x Ir
100 s 1.5 x Ir
12 s 6 x Ir
12.5 s 1.5 x Ir
13.8 s 7.2 x Ir
16.6 s 7.2 x Ir
2 s 6 x Ir
2.7 s 7.2 x Ir
20 s 6 x Ir
200 s 1.5 x Ir
24 s 6 x Ir
25 s 1.5 x Ir
300 s 1.5 x Ir
4 s 6 x Ir
5.5 s 7.2 x Ir
50 s 1.5 x Ir
500 s 1.5 x Ir
600 s 1.5 x Ir
8 s 6 x Ir
8.3 s 7.2 x Ir
Thermal memory 20 mn
Short-time pick-up adjustment type Isd Adjustable 9 settings
[Isd] short-time pick-up adjustment 1.5...10 x Ir
range
Short-time delay adjustment type Adjustable 5 settings
[Tsd] short-time delay adjustment 0.02...0.5 s
range
Instantaneous pick-up adjustment type Adjustable 8 settings
Ii
Instantaneous pick-up adjustment 2...15 x In
range
Ground-fault time delay adjustment Adjustable 5 settings
type -tg
Ground-fault pick-up adjustment type Adjustable 9 settings
[Tg] ground-fault time delay 0.02...0.5 s
adjustment range
[Ig] ground-fault pick-up adjustment 0.2...1 x In 400 A < In < 1250 A
range 0.3...1 x In In <= 400 A
0.4...1 x In In >= 1250 A
Display type Digital display
Type of measurement Ammeter

Contractual warranty
Warranty period 18 months