Janitza Manual UMG512 UL en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 124

Part no. 33.03.

196 (UL)

Power Quality Analyser


UMG 512
Operation manual
and technical data
www.janitza.com
Doc no. 2.054.009.0.p

Janitza electronics GmbH


Vor dem Polstück 1
D-35633 Lahnau
Support Tel. 0049 6441 9642-22
Fax 0049 6441 9642-30
E-mail: [email protected]
Website: http://www.janitza.com
UMG 512

Table of contents

General information 4 Operation 47


Inspection on receipt 7 Meaning of the keys 47
Scope of delivery UMG 512 8 Measured value display 48
Available accessories 8 "Home" measured value display 49
Product description 9 Selecting a measured value display 50
Proper use 9 View additional information 51
UMG 512 features 10 Deleting min./max. values individually 52
Measuring process 11 Transients list 53
Operating concept 11 Event list 54
GridVis network analysis software 11 Configuration 55
Connection variants 12 Connecting the supply voltage 55
Installation 13 Configuration menu 56
Position of installation 13 Language 56
Mounting position 13 Communication 57
Front panel section 13 Measurement 59
Ethernet 14 Measuring transducer 60
Mounting 14 Transients 64
Installation 16 Events 66
Ground wire connection 16 Relevant voltage 68
Supply voltage 16 Nominal frequency 69
Voltage measurement 18 Flicker 70
Three-phase 3-conductor systems 18 Temperature 70
Rated voltages 19 System 71
Frequency measurement 27 Password 72
Current measurement 28 Resetting 73
Residual current measurement inputs (RCM) 32 Display 76
Temperature measurement input 35 Extensions 79
RS485 interface 36 Commissioning the unit 81
Profibus interface 40 Connecting the supply voltage 81
Ethernet interface 42 Connecting the measured voltage 81
Digital outputs 43 Frequency measurement 82

2
UMG 512

Direction of the rotating field 82


Applying the measuring-circuit voltage 83
Applying the residual current 85
Checking the power measurement 87
Checking the communication 87
Measurement range exceeded (overload) 88
RS485 interface 89
Profibus 91
Digital in-/outputs 95
Service and maintenance 100
Service 100
Device calibration 100
Calibration intervals 100
Firmware update 101
Battery 101
Technical data 104
Function parameters 111
Dimension diagrams 116
Configuration menu overview 118
Measured value displays overview 119
Connection example 124

3
UMG 512

General information

Copyright Comments on the manual

This manual is subject to the statutory provisions We welcome your comments. If anything in this manual
of copyright law and may not be photocopied, reprinted, seems unclear, please let us know by sending an e-mail
or reproduced - in whole or in part, by mechanical to: [email protected]
or electronic means - nor otherwise duplicated
or republished, without the binding written permission
of:

Janitza electronics GmbH, Vor dem Polstück 1,


D 35633 Lahnau, Germany.

Trademarks

All trademarks and the resulting rights are the property


of their respective owners.

Disclaimer

Janitza electronics GmbH accepts no responsibility for


errors or deficiencies within this manual, and makes
no commitment to keep the contents of this functional
description up to date.

4
UMG 512

Meaning of symbols

This manual uses the following pictograms:

c Dangerous voltage!
Risk to life or serious injury. Before
commencing work on the system and the
Ground wire connection.

device, they must first be de-energised. Inductive.


The current lags behind the voltage.

m Please note!
Please pay attention to the documentation.
This symbol is intended to warn you
Capacitive.
The voltage lags behind the current.
of potential dangers, which could occur
during installation, commissioning and use.

C Note!

5
UMG 512

Instructions on use

Please read this operation manual as well as all other Additional legal and safety regulations required for
publications that must be consulted for working with the respective application are to be followed during
this product (in particular, for the installation, operation the use of the device.
or maintenance).

Observe all safety instructions and warnings. Failure


to comply with the instructions can result in personal
injuries and/or damage to the product.

Any unauthorised changes or use of this device, which


go beyond the mechanical, electrical or otherwise stated
operating limitations, can result in bodily injury or/and
damage to the product.

Any such unauthorised change constitutes "misuse"


and/or "negligence" according to the warranty for
the product and thus excludes the warranty for covering
possible damage resulting from this.

This device must only be operated and repaired


c If the device is not operated according
to the operation manual, protection
is no longer ensured and hazards can
by specialised personnel. be presented by the device.

Specialised personnel are persons, that based on their


respective training and experience, are qualified
to recognise risks and prevent potential dangers
that can be caused by the operation or maintenance
m Single core conductor must be provided
with sleeves.

of the device.

m Only pluggable screw terminals with


the same number of poles and the same
type of construction are permitted
to be connected together.

6
UMG 512

Concerning this operation manual Inspection on receipt

This operation manual is part of the product. The prerequisites of faultless, safe operation
• Read the operation manual before using the device. of this device are proper transport and proper storage,
• Keep the operation manual instructions throughout set-up and installation, as well as careful operation and
the entire service life of the product and have them maintenance. If it can be assumed that risk-free operation
readily available for reference. is no longer possible, the device must be immediately
• Pass the operation manual on to each subsequent put out of operation and secured against being put back
owner or user of the product. into operation again.
Packing and unpacking must be carried out with
customary care without the use of force and only using
suitable tools. The devices should be visually checked
for flawless mechanical condition.

It can be assumed that risk-free operation is no longer


possible if the device, for example,

• has visible damage


• no longer works despite the mains power supply
being intact
• has been exposed to prolonged adverse conditions
(e.g. storage outside the permissible climate
limits without being adapted to the room climate,
condensation, etc.) or rough handling during

C A l l s c re w - t y p e t e r m i n a l s i n c l u d e d
in the scope of delivery are attached
transportation (e.g. falling from a height, even if there
is no visible external damage, etc.)
to the device. • please check the delivered items for completeness
before you start installing the device.

C All supplied options and versions are


described on the delivery note.

7
UMG 512

Scope of delivery UMG 512

Number Part no. Name


1 52.17.xxx 1) UMG 512
1 33.03.196 Operation manual
1 51.00.116 CD with following content
- GridVis programming software
- GridVis functional description
- UMG 512, GSD file "JAN0EDC.GSD"
1 10.01.855 Screw-type terminal, pluggable, 2-pole (auxilliary power)
1 10.01.847 Screw-type terminal, pluggable, 5-pole (voltage measurement 1-4)
1 10.01.853 Screw-type terminal, pluggable, 8-pole (current measurement 1-4)
1 10.01.873 Screw-type terminal, pluggable, 6-pole (digital inputs/outputs)
1 10.01.888 Screw-type terminal, pluggable, 7-pole (RCM, thermistor input)
1 10.01.859 Screw-type terminal, pluggable, 3-pole (RS 485)
1 08.01.505 Patch cable 2 m, twisted, grey (connection UMG PC/switch)
1 52.19.301 Mounting clips
1)
For the item number, see delivery note

Available accessories
Part no. Name
21.01.102 Lithium battery CR2450, 3V (approval according to i.a.w. UL 1642)
13.10.539 Profibus connector, 9-pole, D-SUB
13.10.543 Profibus connector, 9-pole, D-SUB, angled
29.01.903 Seal, 144 x 144

8
UMG 512

Product description

Proper use
The UMG 512 is intended for the measurement By continuously monitoring the residual currents
of voltage quality according to EN61000-4-30 in building (RCM) of an electrical system via the inputs I5 and I6,
installations, on distribution units, circuit breakers warning pulses can be triggered if a response threshold
and busbar trunking systems. is exceeded. Using these, the system operator can
be alarmed before a protective equipment reacts.
Measured voltages and measured currents must derive The UMG 512 does not provide protection against
from the same network. electric shock!

The UMG 512 is suitable for integration into fixed and The residual current monitoring is performed via
weatherproof switch panels in indoor areas. Conductive the current measurement inputs I5 and I6 via an
switch panels must be earthed. external residual current transformer with a rated current
of 30 mA.
The UMG 512 can be used in 2, 3 and 4-conductor
networks and in TN and TT networks.

The current measurement inputs 1–4 of the UMG 512


are connected via external ../1A or ../5A current
transformers.

Measurements in medium and high-voltage networks are


always performed via current and voltage transformers.

The measurement results can be displayed and read


out and further processed via the interfaces (Ethernet,
Modbus, Profibus).
m Residual current monitoring monitors
residual currents via external current
transformers and can trigger a warning
impulse when a response threshold
The UMG 512 can be used in industrial and domestic is exceeded. The device is thus not an
settings. independent protective device!

9
UMG 512

UMG 512 features

General information • Continuous sampling of the voltage


• Front panel integration device with dimensions and current measurement inputs
144 x 144 mm • Continuous monitoring of residual currents
• Connection via pluggable screw terminals with failure monitoring
• Colour graphic display 320x240, 256 colours • Temperature measurement
• Operation via 6 buttons • Measurement of the power quality in accordance
• 4 Voltage and 4 current measurement inputs with DIN EN61000-4-30, Class A
• 2 Residual current inputs with failure monitoring • Flicker measurement in accordance with DIN
• 1 Temperature measurement input EN61000-4-15:2011, Class F1
• 2 digital outputs and 2 digital inputs • Working measurement, measurement uncertainty
• 16-bit A/D converter, memory 256 Mbyte Flash, in accordance to DIN EN50470-3:
SDRAM 32 Mbyte - Class C for ../5A converter,
• RS485 interface - Class B for ../1A converter,
(Modbus RTU, slave, up to 115 kbps) • Measurement of the harmonics 1st to 63rd in
• Profibus DP/V0 accordance with DIN EN61000-4-7 class 1, for
• Ethernet (web server, e-mail) - Ull, Uln, I, P (cons./del.) and
• Capturing more than 2000 measured values - Q (ind./cap.),
• Clock and battery (with battery monitoring function) • Measurement of the interharmonics 1st to 63rd
• Working temperature range -10°C .. +55°C for (Uln, Ull, I) in accordance with DIN EN61000-4-7
cl.1
Measurement • Analysis and evaluation in accordance with
• Measurement in TN and TT networks DIN EN50160 with the GridVis programming
• Continuous sampling of the voltage and software included in the scope of delivery
current measurement inputs at 25.6 kHz • Programming separate applications in Jasic
• Frequency range of the fundamental oscillation
15Hz .. 440Hz
• Acquisition of transients >39 µs and storage of up
to approx. 330,000 sampling points
• Metering range current 0.001 to 7Arms.
• True RMS (TRMS)

10
UMG 512

Measuring process GridVis network analysis software

The UMG 512 measures continuously and calculates The UMG 512 can be programmed and read out
all effective values over a 200 ms interval. The device using the GridVis network analysis software included
measures the real effective value (TRMS) of the voltages in the scope of the delivery. For this, a PC must be
and currents connected to the measurement inputs. connected to the UMG 512 via a serial interface (RS485/
Ethernet).
Operating concept
GridVis features
You can program and call up the measured values via
many routes using the UMG 512. • Programming the UMG 512
• Configuring recordings
• Directly on the device via 6 buttons and the display • Analysing the read out data according
• Using the GridVis programming software. to EN 61000-2-4.
• Using the device homepage • Reading out recordings
• Using the Modbus protocol. • Saving data to a database
You can modify and call up the data using the • Graphical representation of measured values
Modbus address list. The list can be called up via • Programming customer-specific applications
the device's home page and can be found on the
enclosed CD.

This operation manual only describes how to operate the


UMG 512 using the six buttons.
The GridVis programming software has its own "online
help" system.

11
UMG 512

Connection variants

Connection of a UMG 512 to a PC via an interface converter: Direct connection of a UMG 512 to a PC via Ethernet.

UMG 512 UMG 512


(twisted patch cable)

Connection of a UMG 96RM via a UMG 512 as a gateway Connection of a UMG 512 to a PC via Ethernet.
(twisted patch cable)

UMG 512 UMG 96RM UMG 512

UMG 96RM
(gedrehtes Patchkabel) Switch

(twisted patch cable)

12
UMG 512

Installation

Position of installation

The UMG 512 is suitable for integration into fixed and


weatherproof switch panels in indoor areas. Conductive
switch panels must be earthed.

Mounting position

To ensure adequate ventilation, the UMG 512 must


be installed vertically. There should be separation
above and below of at least 50mm with 20mm space
to the sides.

Front panel section

Cut-out size:
138+0.8 x 138+0.8 mm.

Fig. mounting
position UMG 512
m Failure to meet the minimum clearances
can destroy the UMG 512 at high ambient
temperatures!
(View from rear)

13
UMG 512

Ethernet

The Ethernet connection of the UMG 512 is on the bottom


of the housing.
Depending on the bending radius of the Ethernet cable
and connector type, you must install a connection area
below the UMG 512.

The connection area below the UMG 512 should not


Ethernet connection

50 mm
be smaller than 50 mm.
Patch cable

Mounting

The UMG 512 is mounted in the switchboard with two


mounting clips that are installed at the top and bottom
of the device.

14
UMG 512

15
UMG 512

Installation Fuse Connection point of the


protective conductor
Ground wire connection
Circuit breaker

Use a ring cable lug for connecting the protective Protective conductor
conductor to the UMG 512.

Supply voltage

The UMG 512 needs supply voltage to operate. The type


and amount of the supply voltage required is specified
on the rating plate. The supply voltage is connected
on the rear side of the device via terminal blocks.

Before connecting the supply voltage, ensure that


the voltage and frequency correspond to the details
on the rating plate!

The supply voltage must be connected through a UL/IEC


approved fuse.

c Caution: Risk to life!


The ground wire connection on the device
must be connected with the system
L1 L2 L3 N PE

Fig. connection example of the supply voltage


earthing.
to a UMG 512.

16
UMG 512

c Please note!
The inputs for the supply voltage are
hazardous if touched!

c Please note!
Make sure to observe the specifications
for the supply voltage that are provided
on the rating plate of the UMG 512.

m • If installed in a building, a disconnector


or circuit breaker must be provided for
the supply voltage.
• The disconnector must be installed
near the device and easily accessible
to the user.
• The switch must be marked as the circuit
breaker for this device.
• Voltages which are over the permitted
voltage range can destroy the device.

17
UMG 512

Voltage measurement

Three-phase 4-conductor systems Three-phase 3-conductor systems

The UMG 512 can be used in three-phase 4-conductor The UMG 512 is only suitable to a limited extent for use
systems (TN, TT networks) with an earthed neutral in IT networks, since the measured voltage relative to the
conductor. The bodies of the electrical system are housing potential is measured and the input impedance
earthed. of the device creates residual current against the earth.
The residual current can trigger the insulation monitoring
The voltage measurement in the UMG 512 is designed in IT networks.
for the overvoltage category 600V CAT III (measurement The connection variants with voltage transformers are
voltage surge 6kV). suitable for unlimited use in IT networks.

L1 347V/600V 50/60Hz L1 L1 600V 50/60Hz

L2 240V L2
50/60Hz
L3 L3
N N
PE
Impedance

V4 V1 V2 V3 Vref
V4 V1 V2 V3 Vref AC/DC AC/DC
System
4M

4M

4M
4M
4M

4M

4M

4M
4M
DC earthing 4M DC
System
earthing
Voltage measurement Voltage measurement
UMG 512 Auxilliary power UMG 512 Auxilliary power

Fig. Schematic diagram, UMG 512 in a TN network. Fig. Schematic diagram, UMG 512 in an IT network without N.

18
UMG 512

Rated voltages Three-phase 3-conductor systems, ungrounded.

Lists of networks and their nominal network voltages


in which the UMG 512 can be used.
UL-L

66V
115V
Three-phase 4-conductor systems with earthed 120V
neutral conductor. 127V
200V
220V
UL-N / UL-L 230V
240V
66V / 115V 260V
120V / 208V 277V
127V / 220V 347V
220V / 380V 380V
230V / 400V 400V
240V / 415V 415V
260V / 440V 440V
277V / 480V Maximum system rated 480V
347V / 600V voltage according to UL 500V
400V / 690V 577V
417V / 720V Maximum system rated 600V Maximum system rated
voltage voltage

Fig. Table for network rated voltages i.a.w. EN60664- Fig. Table for network rated voltages i.a.w. EN60664-
1:2003 suitable for the voltage measurement inputs. 1:2003 suitable for the voltage measurement inputs.

19
UMG 512

Voltage measurement inputs

The UMG 512 has four voltage measurement inputs (V1, L1 L2 L3 N PE


V2, V3, V4).

Voltage swell

The voltage measurement inputs are suitable for


measurements in networks where overvoltages
of overvoltage category 600V CATIII can occur.

m For measurement with the supporting


measurement (V4), a voltage must be
connected to the baseline measurement
for frequency determination.

m If the baseline measurement (inputs


V1-V3) is connected to a three-phase
3-conductor network, the supporting Fig. Example connection for measuring voltage.
measurement (input V4) can no longer be
used as a measurement input.

20
UMG 512

When connecting the voltage to be measured,


the following must be observed:

• A suitable circuit breaker must be fitted to


disconnect and de-energise the UMG 512. c Please note!
Voltages that exceed the allow nominal
network voltages must be connected via
• The circuit breaker must be placed in the vicinity a voltage transformer.
of the UMG 512, be marked for the user and easily
accessible.

• Use a UL/IEC approved circuit breaker for the


overcurrent protection and disconnector. c Please note!
The UMG 512 is not suitable for measuring
DC voltages.
• The overcurrent protection must have a rated
value, which is suitable for the short circuit current
at the connection point.
c Please note!
The voltage measurement inputs on
the UMG 512 are dangerous if touched!
• Measured voltages and measured currents must
derive from the same network.

c Please note!
The voltage measurement inputs may not
be used for voltage measurement in SELV
circuits (safe extra low voltage).

21
UMG 512

Baseline measurement, digital inputs 1-3


L1 L1 L1 L1
L2 L2 L2 L2
L1 L1 L1 L1
L3 L3 L3 L3
L2 L2 L2 L2
N N N N
L3 L3 L3 L3
N N N N

S1 S2S1 S1
S2 S2S1 S1
S2 S2S1 S2 S1 S2S1 S1
S2 S2S1 S1
S2 S2S1 S2
4w 3m
4w 3m
4w 3mL1 L1L2 L2L3 L3 N N
4w 3m I1 I1 I2 I2 I3 I3 hv hv L1 L1L2 L2L3 L3 N N I1 I1 I2 I2 I3 I3 4
S1 S2S1 S1
S2 S2S1 S1
S2 S2S1 S2 S1 S2S1 S1
S2 S2S1 S1
S2 S2S1 S2
4w 3m
4w 3m
4w 3mL1 L1L2 L2L3 L3 N N
4w 3m I1 I1 I2 I2 I3 I3 hv hv L1 L1L2 L2L3 L3 N N I1 I1 I2 I2 I3 I3 4
Fig. Measurement in a three-phase 4-conductor network Fig. Measurement via 3 voltage transformers in a three-
with asymmetric loading. phase 4-conductor network with asymmetric loading.

L1 L1 L1 L1
L2 L2 L2 L2
L1 L1 L1 L1
L3 L3 L3 L3
L2 L2 L2 L2
N N N N
L3 L3 L3 L3
N N N N

S1 S2S1 S1
S2 S2S1 S1
S2 S2S1 S2 S1 S2S1 S1
S2 S2S1 S1
S2 S2S1 S2
4w 2u4w 2u
4w 2mL1 L1L2 L2L3 L3 N N
4w 2m I1 I1 I2 I2 I3 I3 hv hv L1 L1L2 L2L3 L3 N N I1 I1 I2 I2 I3 I3 4
S1 S2S1 S1
S2 S2S1 S1
S2 S2S1 S2 S1 S2S1 S1
S2 S2S1 S1
S2 S2S1 S2
Fig.4whv
2u
4w 2u
Measurement via 2 voltage transformers
I1 I1 I2 I2 Iin a three-
Fig.2m
4w 4w 2mL1 L1L2 L2in
Measurement I1 4-conductor
L3 aLthree-phase
3N N I1 I2 I2 I3 I3 network hv L1 L1L2 L2L3 L3 N N 3 I3 4
phase 4-conductor network with asymmetric loading.
with symmetric loading.

22
UMG 512

L1
L2
L1
L3
L2
N
L3
N

S1 S2 S1 S2 S1 S2

4w 2i L1 L2 L3 N I1 I2 I3
S1 S2 S1 S2 S1 S2

4w 2i L1 L2 L3 N I1 I2 I3

Fig. Measurement via 2 voltage transformers in a three-


phase 3-conductor network with symmetric loading.

L1
L2
L1
L3
L2
N
L3
N

S1 S2 S1 S2 S1 S2

4w 2u L1 L2 L3 N I1 I2 I3
S1 S2 S1 S2 S1 S2
Fig.4w Measurement
2u L1 L2 in3 a N three-phase
L I1 I2 4-conductor
I3
network with asymmetric loading.

23
UMG 512

L1 L1 L1 L1 L
L2 L2 L2 L2 L
L1
L3 L1
L3 L1
L3 L1
L3 L
L2 L2 L2 L2 L
L3 L3 L3 L3 L

S1 S2 S1
S1 S2
S2 S1
S1 S2
S2 S1 S2 S1 S2 S1
S1 S2
S2 S1
S1 S2
S2 S1 S2

3w 3m L1
3w 3m LL12 LL23 LN3 N I1 II12 II23 I3 3w 2i3wL2i
1 LL12 LL23 LN3 N I1 II12 II23 I3 3w
S1 S2 S1
S1 S2
S2 S1
S1 S2
S2 S1 S2 S1 S2 S1
S1 S2
S2 S1
S1 S2
S2 S1 S2

3w 3m L1
3w 3m LL12 LL23 LN3 N I1 II12 II23 I3 3w 2i 3wL2i
1 LL12 LL23 LN3 N I1 II12 II23 I3 3w
Fig. Measurement in a three-phase 3-conductor network Fig. Measurement in a three-phase 3-conductor network
with asymmetric loading. with asymmetric loading.

L1 L1 L1 L1 L
L2 L2 L2 L2
L1
L3 L1
L3 L1
L3 L1
L3 L
L2 L2 L2 L2
L3 L3 L3 L3

S1 S2 S1
S1 S2
S2 S1
S1 S2
S2 S1 S2 S1 S2 S1
S1 S2
S2 S1
S1 S2
S2 S1 S2
3w 2u3w 2u
3w 2u3w L
2u1 LL12 LL23 LN3 N I1 II12 II23 I3 hv hvL1 LL12 LL23 LN3 N I1 II12 II23 I3 2w
S1 S2 S1
S1 S2
S2 S1
S1 S2
S2 S1 S2 S1 S2 S1
S1 S2S2 S1
S1 S2S2 S1 S2
3wMeasurement
Fig. 2u3w 2u in a three-phase
Fig. Measurement
3w 2u3w L
2u1 LL12 LLin
23
a three-phase
LN3 N I1 3-conductor
II12 II23 I3network hv hvL1 LL12 LL23 LN3 N I13-conductor
II12 II23 network
I3 2w
with asymmetric loading. with asymmetric loading.

24
UMG 512

L1L1 L1L1
L2L2 L2L2
L1L3
L3L1 L1L3
L3L1
L2L2 L2L2
L3L3 L3L3

S1 S1
S2 S2S1 S1
S2 S2S1 S1
S2 S2 S1 S1
S2 S2S1 S1
S2 S2S1 S1
S2 S2
3w3w
2m2m
3w3w
2m2m L1L1 L2L2 L3L3 N N I1 I1 I2 I2 I3 I3 hvhv L1L1 L2L2 L3L3 N N I1 I1 I2 I2 I3 I3
S1 S1
S2 S2S1 S1
S2 S2S1 S1
S2 S2 S1 S1
S2 S2S1 S1
S2 S2S1 S1
S2 S2
3w3w
2m2m
3w3w
2m2m L1L1 L2L2 L3L3 N N I1 I1 I2 I2 I3 I3 hvhv L1L1 L2L2 L3L3 N N I1 I1 I2 I2 I3 I3

Fig. Measurement in a three-phase 3-conductor network Fig. Measurement in a three-phase 3-conductor network
with asymmetric loading. with asymmetric loading.

L1L1 L1L1

L1L1 L1
L2L1
L2
NN
L2L2
NN

S1 S1
S2 S2S1 S1
S2 S2S1 S1
S2 S2 S1 S1
S2 S2S1 S1
S2 S2S1 S1
S2 S2

2w2w
1m1m L1L1 L2L2 L3L3 N N I1 I1 I2 I2 I3 I3 2w2w
2m2m L1L1 L2L2 L3L3 N N I1 I1 I2 I2 I3 I3
S1 S1
S2 S2S1 S1
S2 S2S1 S1
S2 S2 S1 S1
S2 S2S1 S1
S2 S2S1 S1
S2 S2
Fig. Measurement of one phase
I1 I1 inI2 I2a Ithree-phase Fig. Measurement in single-phase 3-conductor
I1 I1 I2 I2 I3network.
2w2w 1m L1L1 L2L2 L3L3 N N
1m 3 I3 2w2w
2m2m L1L1 L2L2 L3L3 N N I3
4-conductor network. I3 and U3 are not calculated and set to zero.

25
UMG 512

Supporting measurement, input V4


L1 L1
L2 L2
L1 L1
L3 L1 L3
L1
L2 L2
N L2 L2
L3 L3 L3 L3
N N

S1 S2 S1 S2

4w 1m L4 N I4 3w 1m L4 N I4
S1 S2S1 S2 S1 S2S1 S2

4w 1mL4 L4N
4w 1m N I4 I4 3w 1mL4 L4N
3w 1m N I4 I4

Fig. Measurement in a three-phase 4-conductor Fig. Measurement in a three-phase 3-conductor


network with symmetric loading. network with symmetric loading.

m If the baseline measurement (inputs


V1-V3) is connected to a three-phase
3-conductor network, the supporting
N measurement (input V4) can no longer
PE be used as a measurement input.
N N
PE PE

S1 S2
m For measurement with the supporting
measurement (V4), a voltage must
be connected to the baseline measurement
2w 1n L4 N I4
S1 S2S1 S2 for frequency determination.
Fig. Measurement of the voltage between N and PE.
2w 1nL4 L4N N
2w 1n I4 I4
Measurement of the current in the neutral conductor.

26
UMG 512

Frequency measurement

The UMG 512 is suitable for measurements in networks


in which the fundamental oscillation of the voltage
is in the range 15Hz to 440Hz.

To automatically determine (wide range) the mains


frequency, a voltage L1-N of greater than 10Veff must
be applied to voltage measurement input V1.

The mains frequency is only measured


on the measurement inputs of the baseline measurement
(V1,V2,V3).

m Measured voltages and measured currents


must derive from the same network.

27
UMG 512

Current measurement

The UMG 512 is intended for the connection of current L1 L2 L3 N PE


transformers with secondary currents of ../1A and ../5A.
The factory default for the current transformer ratio
is 5/5A and must be adapted to the current transformer
employed if necessary.

Only AC currents can be measured - DC currents cannot.

Any of the current measurement inputs can be loaded


with 120A for 1 second. S1

S2 S1

S2 S1

c Attention!
The current transformer must have basic
insulation per IEC 61010 1:2010, as a
S2 S1

S2
minimum, for the nominal voltage of the
circuit to be measured.

c Please note!
The measurement lines must be suitable
for an operating temperature of at least
80°C!

m Please note!
The UMG 512 is not suitable for measuring
DC voltages.
Load

Fig. Current measurement (I1-I3) via current

m The attached screw-type terminal must be


fixed using the two screws on the device!
transformers (connection example)

28
UMG 512

Current direction

The current direction can be individually corrected via


the existing serial interfaces or on the device for each
phase.

If incorrectly connected, a subsequent re-connection of


the current transformer is not required.

c Please note!
Residual current monitoring is performed
using the terminals I5 and I6. There is no
directional sensitivity of the residual
currents of the network or load sides (not
directionally sensitive).

c Earthing of current transformers!


A secondary connection for each current
transformer must be connected to ground.

c Current transformer connections!


The secondary connection of the current
transformer must be short circuited on this
c Open-circuit current transformers!
High voltage spikes that are dangerous
to touch can occur on current transformers
before the current feed to the UMG 512 that are driven with open-circuit secondary
is disconnected! windings!
If a test switch, which automatically short- With "safe open-circuit current
circuits the secondary wires of the current transformers" the winding insulation
transformer, is available then it is sufficient is rated such that the current transformer
to set this to the "Test" position insofar can be driven open. However, even these
as the short-circuiting device has been current transformers are dangerous to
checked beforehand. touch when they are driven open-circuit.

29
UMG 512

Total current measurement

If the current measurement is done via two current Example:


transformers, the overall transformation ratio The current is measured via two current transformers.
of the current transformers must be programmed into Both current transformers have a transformation ratio
the UMG 512. of 1000/5A. The summation measurement is performed
using a total current transformer 5+5/5A.
UMG The UMG 512 must then be setup as follows:
I
S1 S2
Primary current: 1000A + 1000A = 2000A
Einspeisung 1 Einspeisung 2 Secondary current: 5A
Supply 1 Supply 2
P1 P2

1S1 1S2 2S1 2S2


1P1 1S1 2S1 2P1
(K) (k) (k) (K)
(L) (l) (l) (L)
1P2 1S2 2S2 2P2

Verbraucher A Verbraucher B
Consumer A Consumer B

Fig. Example, current measurement via a total


current transformer

30
UMG 512

Ammeter

If you wish to measure the current not just using


the UMG 512, rather also with an ammeter, the ammeter
must be connected to the UMG 512 in series.

UMG
I
S1 S2

Einspeisung Verbraucher
Supply (k)S1 S2(l) Consumer

(K)P1 P2(L)

31
UMG 512

Residual current measurement inputs (RCM)

The UMG 512 is suitable for use as a residual current


monitoring device (RCM) as well as for monitoring AC,
pulsing DC, and DC.

The UMG 512 can measure type A residual currents


in accordance with IEC/TR 60755 (2008-01)

The connection of suitable external residual current


transformers with a rated current of 30 mA is performed
via the residual current transformer inputs I5 (terminals
4/5) and I6 (terminals 6/7).

Load
PE N L1 L2 L3

Fig. Connection example of residual current monitoring


via current transformers

C Residual current transformer ratio


The GridVis software included in the scope
of the delivery can be used to individually
program the residual current transformer
inputs' transformer ratios.
C It is not necessary to configure a connection
schematic for measurement inputs I5 and I6.

32
UMG 512

c
Failure monitoring
Please note!
Operating equipment connected to the
The UMG 512 monitors the ohmic resistance
analogue inputs (residual current and tem-
at the residual current measurement inputs.
perature measurement) must feature rein-
forced or double insulation to the mains
If the ohmic resistance is greater than 300 Ohm, there
supply circuits!
is a failure (e.g. cable breakage) with the residual current
monitoring.
Example - temperature sensor:
A temperature sensor in close proximity
to non-isolated mains cables should measure
within a 300V CAT III network.
Remedy:
The temperature sensor must be equipped
with reinforced or double insulation for 300V
CAT III.

Example - residual current transformer:


A residual current transformer should measure
on isolated mains cables within a 300V CAT III
network.
Remedy:
The insulation of the mains cables
and the insulation of the residual current
transformer must fulfil the basic insulation
requirements for 300V CAT III.

33
UMG 512

Residual current transformer


L1
L2
L3
PEN
N
PE Residual
current
transformers

L1 L2 L3 N I1 I2 I3 I4 I5 I6
M
UMG 512 3~

Fig. Example UMG 512 with residual current monitoring via measuring inputs I5/I6.

34
UMG 512

Temperature measurement input


VCC
PT100
The UMG 512 has one temperature measurement 10
input. The temperature is measured here via terminals
9
8 through 10.
8

Do not exceed the total resistance load (sensor + cable) GND


of 4kOhm. UMG 512

PT100

m Please note!
Temperature and residual current measure-
ment (RCM) are not galvanically separated
from each other.

m
Fig. Example, temperature
Use a shielded cable to connect the tem-
measurement with a Pt100
perature sensor.

35
UMG 512

RS485 interface Termination resistors

In the UMG 512, the RS485 interface is designed as a The cable is terminated with resistors (120Ohm, 1/4W)
3-pin plug contact, which communicates via the Modbus at the beginning and at the end of a segment.
RTU protocol.
Termination within the device is possible via the S1 DIP
switch of the UMG 512.

Correct

A B
Incorrect
RS485 Bus

Terminal strip in the cabinet.

Device with RS485 interface.


(without termination resistor)

Device with RS485 interface.


(with termination resistor on the device)

36
UMG 512

Screening

Twisted screened cable should be used for connections


via the RS485 interface.

• Earth the screens of all cables that lead to the cabinet


and at the cabinet entry.
• Connect the screens over a generous area and
in a manner that will conduct well, to a low-noise
ON earth.
OFF
• Gather the cables mechanically above the earthing
S1 clamp in order to avoid damage due to cable
movements.
• Use suitable cable glands to feed the cables into
Fig.: Placement in the middle the cabinet, for example, armoured conduit couplings.
of the segment; termination via S1
DIP switch deactivated (OFF)

ON
OFF
S1

Fig.: Placement at the end of


the segment; termination via S1
DIP switch activated (ON)

37
UMG 512

Cable type

The cable used must be suitable for an environmental


temperature of at least 80°C.

Recommended cable types:


C If the bus line is laid in the switch cabinet,
the screen must be connected to functio-
nal earth (PE).
Unitronic Li2YCY(TP) 2x2x0.22 (from Lapp Kabel)
Unitronic BUS L2/FIP 1x2x0.64 (from Lapp Kabel) When laying bus lines in the switch cabinet
it is normally sufficient if the screen of the
bus line is connected at least once to the
functional earth (PE).
Maximum cable length
If there are more significant sources of in-
1200m at a baud rate of 38.4k. terference, such as a frequency converter,
installed in the switch cabinet, the screen
Cable must be connected to the functional earth
(PE) as close as possible to the device.
Strain relief

Screen braid of the cable


Earthing clamp

Noiseless ground

C CAT cables are not suitable for bus wiring.


Use the recommended cable types for this.

Fig. Screening procedure at cabinet entry.

38
UMG 512

Bus structure

• All devices are connected in a bus structure (line) • It is recommended that the master be placed
and each device has its own address within the bus at the end of a segment.
(see also Parameter programming). • If the master is replaced with a bus connection,
• Up to 32 subscribers can be connected together the bus must be switched off.
in a single segment. • Replacing a slave with a bus connection that is either
• The cable is terminated with resistors (bus termination switched on or de-energised can destabilise the bus.
120Ohm, 1/4W) at the beginning and at the • Devices that are not connected to the bus can be
end of a segment. replaced without destabilising the bus.
• With more than 32 subscribers, repeaters (amplifiers)
must be used to connect the individual segments.
• Devices for which the bus connection is switched
on must be under current.

Speisung notwendig / power supply necessary


Master
T Busabschluß eingeschaltet / bus terminator on
T
T

Slave Slave Slave Repeater

T
T

Slave Slave Slave Slave


Fig. Bus structure

39
UMG 512

Profibus interface

This 9-pole D-sub receptacle RS485 interface supports


the Profibus DP V0 slave protocol.

For the simple connection of inbound and outbound


bus wiring, it should be connected to the UMG 512 via a
Profibus connector.

For the connection, we recommend a 9-pole Profibus


connector, e.g. type "SUBCON-Plus-ProfiB/AX/SC"
from Phoenix, item number 2744380. (Janitza item no:
13.10.539)

UMG 512 Profibus connector (external)


Profibus
Terminating resistors
D-sub
receptacle for
D-Sub, D-Sub,
9 pin,
socket
9 pin,
connec- Other
Profibus
tor profibus
stations

Screw-type terminals

Fig. Profibus connector with termination resistors. Fig. UMG 512 with D-sub
receptacle for Profibus
(View from rear).

C When using the device in a Profibus


system, the device address must be set
using the configuration menu.

40
UMG 512

Connection of the bus wiring

The inbound bus wiring is connected to terminals 1A


and 1B of the Profibus connector. The continuing bus
wiring for the next device in line should be connected
to terminals 2A and 2B.

If there are no subsequent devices in the line, then


the bus wiring must be terminated with a resistor (switch
to ON).

With the switch set to ON, terminals 2A and 2B are


switched off for further continuing bus wiring.

Transfer speeds Max.


in Kbit/s segment length
9.6, 19.2, 45.45, 93.75 1200m
187.5 1000m
500 400m
1500 200m
3000, 6000, 12000 100m

Table Segment lengths per Profibus specification.

41
UMG 512

Ethernet interface

m
The Ethernet network settings should be specified by
Please note!
the network administrator and set on the UMG 512
Connection of the UMG 512 to the Ethernet
accordingly.
may only be carried out after consulting
the network administrator!
If the network settings are not known, the UMG 512 may
not be integrated into the network through the patch
cable.

m Please note!
The UMG 512 is factory-set for the dynamic
IP address assignment (DHCP mode).
Settings can be changed as described in
"TCP/IP Configuration" or, for example,
via an appropriate Ethernet connection by
means of GridVis software.

Ethernet connection

Patch cable
PC / switch

42
UMG 512

Digital outputs

The UMG 512 has two digital outputs. These outputs


are galvanically separated from the analysis electronics
using optocouplers. The digital outputs have a joint
reference.

• The digital outputs can switch DC loads.


=
• The digital outputs are not short-circuit proof.
• Connected cables that are longer than 30m must be
shielded when laid.
• An external auxilliary voltage is required.
• The digital outputs can be used as impulse outputs.

Fig. Connection of digital


outputs

43
UMG 512

External
auxilliary voltage

24V DC
C When using the digital outputs as pulse
outputs, the auxilliary voltage (DC) must
+ - have a max. residual ripple of 5%.

C Functions for the digital outputs can be


adjusted clearly in the GridVis software
provided in the scope of delivery.
A connection between the UMG 512
11
and the PC via an interface is required to
DC
Digital Ouput 1 use the GridVis software.
12
K1

Digital Ouput 2
13
DC
m Please note!
Digital outputs are not short-circuit proof!
K2

Fig. Example for two relays connected to the digital


outputs

44
UMG 512

Digital inputs

The UMG 512 has two digital inputs. An input signal Wiring longer than 30m must be screened.
is detected on a digital input if a voltage of at least 18V
and maximum 28V DC (typically at 4mA) is applied. There Note the correct polarity of the supply voltage!
is no input signal for a voltage of 0 to 5V and a current
less than 0.5 mA.

External
auxilliary voltage 24V DC
- +

- +
UMG 512
Digital inputs 1-2 14

2k21
15
Digital S1
Input 1
2k21

2k21
16
Digital S2
Input 2
2k21

2k21

Fig. Example for the connection of external switch Fig. Connection


contacts S1 and S2 to digital inputs 1 and 2. of digital outputs

45
UMG 512

S0 pulse input

You can connect an S0 pulse transducer per


DIN EN62053-31 to any digital input.

This requires an external auxilliary voltage with an


output voltage in the range 18 .. 28V DC and a resistor
of 1.5kOhm.

External
auxilliary voltage 24V DC

- +
UMG 512
Digital inputs 1-2 14

1.5k
2k21
15
S0 pulse
Digital transducer
Input 1
2k21

2k21
16
Digital
Input 2
2k21

2k21

46
UMG 512

Operation Meaning of the keys

The UMG 512 is operated by six function keys.


Key Function
Depending on the context, the six keys are assigned • Returns to the first screen (home)
with different functions: • Exits selection menu

• Selecting measured value displays.


• Navigation within the menus. • Selects number
• Editing device settings. • Selects main values (U, I, P ...)

• Changes (number -1)


• By-values (select)
• Selects menu item
Display title
• Changes (number +1)
Measured
• By-values (select)
values
• Selects menu item

• Selects number
• Selects main values (U, I, P ...)
Labelling of
the function keys
• Opens selection menu
Function keys
• Confirm selection

47
UMG 512

Measured value display

Main values By-values

Using the 2 and 5 keys, you can scroll between the main Using the 3 and 4 keys, you can select the by-values
values of the measured value displays (see page of a measured value display (see page 120-123).
120-123).

Main values

Display Display Display Display ...


Bar graph Communication Home Voltage L-N
... Voltage Status

Display Display
Bar graph Voltage L-L
By-values

Current

Display
Bar graph
Effective power

48
UMG 512

"Home" measured value display

After the power returns, the UMG 512 starts with


the "Home" measured value display.

This measured value display contains the device


names and an overview of important measured
values. In it delivery condition, the unit name consists
of the device type and the serial number of the device.

Using the "Home - key 1", you navigate


directly to the first "Home" measured value
display from the measured value displays
for the main values.

49
UMG 512

Selecting a measured value display

You would like to switch to a measured value display


with main values.

• Using the 2 and 5 function keys, you can scroll


between the measured value displays of the main
values.
• Using the 1 (home) function key, you always navigate
to the first measured value display.

You would like to switch to a measured value display


with by-values.

• Select the measured value display with the main


values.
• Using the 3 and 4 function keys, select the measured
value display for the by-values.

Display Display
Home Voltage L-N
... ...

Display
Voltage L-L

Example: Selecting the voltage by-values.

50
UMG 512

View additional information

• Using the 2 and 5 keys, scroll to the desired measured


value display.
• Activate the measured value selection using the 6 key
(select).
• The background colours for the measured value
switches from grey to green. The additional information
is displayed in blue window.
• Using the 2 and 5 keys, select the desired measured
value.
• End the procedure using the 1 key (ESC) or select
another measured value with the 2 to 5 keys.

51
UMG 512

Deleting min./max. values individually

• Using the 2 and 5 keys, scroll to the desired measured


value display.
• Activate the measured value selection using the 6 key
(select).
• The background colours for the measured value
switches from grey to green. The additional information
is displayed in blue window.
• Using the 2 and 5 keys, select the desired minimum
or maximum value.
• The time along with the date and time of the occurrence
are displayed as additional information.
• Using the 6 key (reset), you can delete the selected
minimum or maximum value.
• End the procedure using the 1 key (ESC) or select
another minimum or maximum value with the 2 to 5
keys.

C The date and time for the minimum/max-


imum values are specified displayed in
UTC time (Coordinated Universal Time).

52
UMG 512

Transients list

The detected transients are listed in the transients list.


• The transients list consists of 2 pages.
• On page 1, the transients 1 through 8 are listed and
on page 2, the transients 9 through 16 are listed.

Displaying transients

• Using the 2 and 5 keys, scroll to the "Transient" main


value display.
• Select the desired page using the 4 key.
• Navigate to the transients list using key 6 (select)
and select a transient using the 3 or 4 keys.
• Using the 6 key (select), have a transient displayed
in a graph.
• Show or hide the legend using the 6 key (select).
• You can exit the transient graph display using the 1
key (ESC).

Transient voltages are fast impulse transient


effects in electrical networks.
The time when transient voltages occur cannot
be predicted and they have a limited duration.
Transient voltages are caused by lightning strikes,
switching operations or by tripped fuses.

53
UMG 512

Event list

Detected events are listed in the event list.


• The event list consists of 2 pages.
• On page 1, the events 1 through 8 are listed
and on page 2, the events 9 through 16 are listed.

Displaying events

• Using the 2 and 5 keys, scroll to the "Event" main


value display.
• Select the desired page using the 4 key.
• Navigate to the event list using key 6 (select)
and select an event using the 3 or 4 keys.
• Using the 6 key (select), have an event displayed in a
graph.
• Show or hide the legend using the 6 key (select).
• You can exit the result graph display using the 1 key
(ESC).

Events are threshold value violations of effective


current and voltage values.

54
UMG 512

Configuration

The supply voltage must be connected for


the configuration of the UMG 512.

Connecting the supply voltage

• The supply voltage level for the UMG 512 is specified


on the rating plate.
• After applying the supply voltage, a start-up display
appears. Approximately ten seconds later, the UMG
512 switches to the first "Home" measured value
display.
• If no display appears, check whether the applied
supply voltage is within the rated voltage range.
Fig. Example of the "Home" measured value
display

c Please note!
If the supply voltage does not correspond
to the voltage indicated on the rating
plate, this may lead to malfunctions and
severe damage to the device.

55
UMG 512

Configuration menu

After the power returns, the device starts on the "Home"


measured value display.

• Open the Configuration menu using the 1 button.

If you are in a measured value display for main values,


you can navigate directly to the "Home" measured
value display using the 1 button (home). Pressing the 1
key again opens the Configuration menu. Using the 3
or 4 keys, you select the desired submenu that can be
activated using the 6 key (enter).

Language

You can set the language for the measured value displays
and menus directly in the "Configuration" menu.

There are different languages available for selection.


The factory default setting for the language is "English".

If the language field is marked green, then the desired


language can be selected by pressing the key 6 (enter)
and the keys 3 or 4. Pressing the key 6 (enter) again
confirms the selection and changes the language.

56
UMG 512

Communication

The UMG 512 has an Ethernet and a RS485 interface.

Ethernet (TCP/IP)

Select the type of the address assignment for


the Ethernet interface here.

DHCP mode

• Off - The IP address, netmask and gateway are


defined by the user and set directly on the UMG 512.
Select this mode for straightforward networks without
DHCP servers.
• BOOTP - BootP enables the fully automatic
integration of a UMG 512 into an existing network.
However, BootP is an older protocol and does not
provide the scope of functions provided by DHCP.
• DHCP - When started, the UMG 512 automatically
obtains the IP address, the network mask
and the gateway from a DHCP server.

Factory default setting: DHCP

m Connection of the UMG 512 to the


Ethernet may only be carried out after
consulting the network administrator!

57
UMG 512

RS485

You can specify the protocol, device address and baud


rate for operation with the RS485 interface. The device
address must be uniquely assigned within the bus
structure; the baud rate specification must be selected
uniformly.

The corresponding field can be selected via the keys 3 or


4 (green marking). Key 6 (enter) provides you with access
the selection options, which can then be selected with
key 3 or 4.
Pressing the 6 key (enter) again confirms the selection.

Protocol

Selection options:
• Modbus slave
• Modbus master/gateway (default setting)
• Profibus DP V0 (option)

Device address

Setting range: 0 - 255


Factory default setting: 1

Baud rate

Setting range: 9600, 19200, 38400, 57600,


115200 (default setting),
921600 kbps

58
UMG 512

Measurement

The UMG 512 has 4 measurement channels used


to measure the current (I1..I4) and 4 measurement
channels used to measure the voltage (V1..V4 against
Vref).
Measured voltage and measured current for
the measurement channels 1-4 must derive from
the same network.

Baseline measurement

The baseline measurement uses the measurement


channels 1-3. Use the measurement channels 1-3
in three-phase systems.
Configure the following here:

• The measuring transducer for the current and voltage Supporting measurement
measurement
• Recording transients The supporting measurement only uses measurement
• Recording events channel 4. Use measurement channel 4 when measuring
• The relevant voltage in single-phase systems or in three-phase systems with
• The mains frequency symmetrical loads.
• The flicker settings The frequency setting and the setting for the relevant
voltage are pulled automatically from the baseline
measurement settings.

59
UMG 512

Measuring transducer

Current transformer

You can assign current transformer ratios to the baseline


measurement and the supporting measurement.
Select the 5/5A setting when measuring currents directly.

Setting range:
Primary 1 to 1000000
Secondary 1 to 5

Factory default setting:


Primary 5
Secondary 5

Rated current

The rated current defines the value to which


• Overcurrent
• Current transients
• K-factor and the
• Automatic scaling of graphics
refer.

Setting range: 0 to 1000000A

60
UMG 512

Residual current transformer

When using residual current inputs I5 and I6, the


corresponding transformer ratios of the used residual
current transformer must be set.

Setting range:
Primary 1 to 1000000
Secondary 1

Factory default setting:


Primary 127
Secondary 1

Monitoring

Activates or deactivates the failure monitoring of the


corresponding residual current inputs.

• Activated - Switches on the failure monitoring


for residual current monitoring.
• Deactivated - Switches off the failure monitoring
for residual current monitoring.

61
UMG 512

Voltage transformer

You can assign voltage transformer ratios to the baseline


measurement and the supporting measurement.
Select the 400/400V setting when measuring without
a voltage transformer.

Setting range:
Primary 1 to 1000000
Secondary 1 to 999

Factory default setting:


Primary 400
Secondary 400

Rated voltage

The rated voltage corresponding to the "arranged input


voltage Udin" according to EN 61000-4-30. The rated
voltage defines the value to which
• Upward deviation (EN 61000-4-30),
• Downward deviation (EN 61000-4-30),
• Transients,
• Events and the
• Automatic scaling of graphics
refer.

Setting range: 0 to 1000000V


Factory default setting: 230V

62
UMG 512

Accepting AUX / MAIN

The measuring transducer can be configured


for the baseline measurement and supporting
measurement. You can accept the measuring transducer
settings in each case from the supporting or baseline
measurement.
• No - The settings from the supporting and baseline
measurement are not accepted.
• Yes - The settings from the supporting measurement
and baseline measurement are accepted.

Connection

You can select between different connection schemes


(see page 22) for the voltage and current measurement
using the "Connection" selection.

Factory default setting: 4w3m

Fig. Example for the measurement in a three-


phase 4-conductor network with asymmetric
loading

63
UMG 512

Transients

Transient voltages are fast impulse transient effects


in electrical networks. The time when transient voltages
occur cannot be predicted and they have a limited
duration.
Transient voltages are caused by lightning strikes,
switching operations or by tripped fuses.

• The UMG 512 detects transients that are longer than


39µs.
• The UMG 512 monitors the measurement inputs for
transients.
• There are two independent criteria by which transients
are detected.
• If a transient has been detected, the wave form will
be saved to a transient record.
• If a transient has been detected, the threshold value
increases by 20V, both in automatic and in manual Mode (absolute)
mode. This automatic increase of the threshold value
switches off within 10 minutes. If a sampled value exceeds the set threshold value,
• If a further transient is detected within the next 60 a transient is detected.
seconds, it will be recorded with 512 points. • Off - Transient monitoring has been switched off.
• The GridVis event browser can display recorded • Automatic - Factory default setting. The threshold
transients. value is calculated automatically and is 110% of
the current 200ms effective value.
• Manual - The transient monitoring uses
the configurable threshold values under "Peak".

64
UMG 512

Mode (delta) Accepting AUX / MAIN

If the difference between two neighbouring sampled The transient monitoring can be configured for the
points exceeds the set threshold value, a transient baseline measurement and supporting measurement.
is detected. You can accept the settings from the supporting
or baseline measurement.
• Off - Transient monitoring has been switched off.
• Automatic - Factory default setting. The threshold • No - The settings from the supporting and baseline
value is calculated automatically and is 0.2175 times measurement are not accepted.
the current 200ms effective value. • Yes - The settings from the supporting measurement
• Manual - The transient monitoring uses and baseline measurement are accepted.
the configurable threshold values under "Trns U".

Mode (envelop)

If a sampled value exceeds the envelope range,


a transient is detected.

• Off - Transient monitoring has been switched off.


• Automatic - Factory default setting. The envelop
is automatically calculated and is ±5% of the rated
voltage.
• Manual - The transient monitoring uses the
configurable envelop.

65
UMG 512

Events

Events are threshold value violations of set threshold • An event describes a fault due to undervoltages/
values for current and voltage. overvoltages, voltage loss, overcurrent, overfrequency/
underfrequency and rapid frequency changes
Here, threshold values are compared with the half • Monitoring of the threshold values can be switched
wave effective values for current and voltage from off (Off/Manual).
the measurement channels. The event record consists • Threshold values and hysteresis must be set as
of a mean value, a minimum or maximum value, a start a percentage of the nominal value.
time and an end time. • Threshold values can be set for excess voltage,
undervoltage, voltage interruption and overcurrent.
• If an event has occurred, the corresponding measured
value is recorded with the set pre-run and after-run
periods (respectively 0..1000 half waves).
• Event records are configured with the GridVis
and displayed with the event browser.

Measured
value
Event Half wave
effective value
Hysteresis
Limit value
Hysteresis

Start time event


(Trigger time) End time

Event record

Pre-run After-run

Fig. Shows the half wave effective values for an event.

66
UMG 512

Voltage

Drop

A voltage drop is set in % of the rated voltage.

Voltage swell

The voltage swell is set in % of the rated voltage.

Current

Overcurrent

The rapid increase of current is set in % of the nominal


current.

Accepting AUX / MAIN

The event monitoring can be configured for the baseline


measurement and supporting measurement. You can
C Lead time
You can only set the lead time with
accept the settings from the supporting or baseline GridVis.
measurement. Factory default setting: 0
• No - The settings from the supporting and baseline
measurement are not accepted.
• Yes - The settings from the supporting measurement
and baseline measurement are accepted.
C After-run
You can only set the after-run with
GridVis.
Factory default setting: 0

67
UMG 512

Relevant voltage

Depending on the application, the voltage between


the outer conductors (L) or the voltage between the outer
conductor (L) and the neutral conductor (N) is relevant
for analysing the power quality.

We recommend the "L-N" setting for measuring


the power quality in low voltage networks.
You should select the "L-L" setting in medium voltage
networks.

C Flicker values can only be determined


if the relevant voltage L-N is given.

68
UMG 512

Nominal frequency

The UMG 512 determines the mains frequency from


the voltage applied to L1 and uses this for the additional
calculations.

The nominal frequency is required as a reference for


measurement of the voltage quality.

Configure the nominal frequency for the mains


on the UMG 512 prior to starting the measurement.

Select the mains frequency 50Hz or 60Hz


for measuring the power quality in accordance with
EN61000-4-30 and EN50160.

Setting range of the nominal frequency:


• 50Hz (factory default setting)
• 60Hz
• 15Hz to 440Hz (wide range)
C In order to determine the mains
frequency, a voltage L1-N of greater
Set the nominal frequency to "Wide range" for than 10Veff must be applied to voltage
measurements in networks with other nominal measurement input V1.
frequencies e.g. 16 2/3Hz or 400Hz.

69
UMG 512

Flicker

The UMG 512 requires the mains base values in order


to provide voltage and frequency-independent
measurement and calculation of the flicker values
(flicker measurement as per DIN EN61000-4-15:2011).
These values are to be specified by the user and can be
selected from a predefined list:

• 230V/50Hz (factory default setting)


• 120V/50Hz
• 230V/60Hz
• 120V/60Hz

C Flicker values can only be determined


if the relevant voltage L-N is given.

Temperature

When using a temperature measurement,


the corresponding sensor type must be selected from
a predefined list.

• PT100
• PT1000
• KTY83
• KTY84

70
UMG 512

System

Display of the device-specific system settings with:

Firmware version

Serial number of the device

Fixed MAC address of the device

Set IP address

Set gateway address

Date and time

Set password

Reset settings

C You cannot configure the date and time


directly on the device.
You can carry out the settings for the time
synchronisation and date and time with
the GridVis.

71
UMG 512

Password

The user can block access to the configuration with


a password. The configuration can then only be changed
directly on the device by entering the password.

The password consists of a 6-digit code.

Setting range: 1-999999 = With password


000000 = Without password

Password (000000) is not factory-programmed.

• To change a password that has already been set,


you must know the current password.
• Note down the changed password.
• When selecting the "Password" (green marking),
the password can be changed using the 6 key
(enter) and keys 2 to 5. Pressing the 6 key again
confirms the entry.
C Forgot my password
If you no longer remember your password,
• If you no longer want a password prompt, enter you can only delete it using the "GridVis"
the password "000000". PC software.
In order to do so, connect the UMG 512
to the PC with a suitable interface. More
information can be found in the GridVis
assistant.

72
UMG 512

Resetting

Clearing energy meters

You can clear all energy meters in the UMG 512


at the same time using the "Reset" key.
Some specific energy meters cannot be selected.

• Highlight the "Clear energy" button (green marking)


and enable the deletion process using the key 6
(enter).

• Select "Yes" with the 4 key.


• Confirm the selection using the 6 key.
• The "Carried out" message appears in the line,
all energy meters have been cleared.

73
UMG 512

Deleting min. and max. values

You can delete all min. and max. values in the UMG 512
at the same time using the "Reset" key.

The "Deleting minimum/maximum values individually"


section describes how you can individually delete
min. and max. values.

• Highlight the "Min/max values" item (green


marking) and enable the clear process using
the key 6 (enter).

• Select "Yes" with the 4 key.


• Confirm the selection using the 6 key.
• The "Carried out" message appears in the line,
all minimum and maximum values have been
cleared.

C Prior to commissioning potential pro-


duction dependant contents of the ener-
gy counter, min/max values and records
have to be deleted.

74
UMG 512

Delivery status

All settings, such as the configuration and the recorded


data, are restored to the factory default settings
or deleted. Entered activation codes are not deleted.

• Select "Yes" with the 4 key.


• Confirm using the 6 key.
• The "Carried out" message appears in the line,
the delivery status is restored.

Re-initialisation

The UMG 512 is started again.

• Select "Yes" with the 4 key.


• Confirm using the 6 key.
• The device starts again within approx. 10 seconds

75
UMG 512

Display

Brightness

The backlight brightness can be configured. The


brightness set here is used when the UMG 512 is
operated.
Setting range: 0 to 100%
Factory default setting: 70%
(0% = dark, 100% = very bright)

Standby

Time after which the brightness switches to the "Standby


brightness".
Setting range: 60 to 9999 sec.
Factory default setting: 900 sec.

Standby brightness

Brightness level the system switches to after the standby


time expires. The standby time is restarted by using keys
1-6.
Setting range: 0 to 60%
Factory default setting: 40%

Screen Saver

The screen saver prevents a screen image that is not


changed for a longer time period from "burning into"
the LCD.
Setting range: Yes, No
Factory default setting: Yes

76
UMG 512

Screen Update

Here, you can define the speed at which the new


measured values appear in the measured value displays.
Setting range: fast (200ms), slow (1 sec.)
Factory default setting: Fast

Rotate

The measured value displays are automatically shown


one after the other. This does not affect the displays
of the configuration.
Setting range: Yes, No
Factory default setting: No

Rotation interval

Here, you can set the time after which the screen
automatically switches to the next measured value
display.
Setting range: 0 to 255 seconds
Factory default setting: 0 seconds

C The service life of the backlight is


extended if the brightness of the backlight
is lower.

77
UMG 512

Colours

Selection of the colours for displaying the current


and voltage in the graphic representations.

• Using the keys 3 or 4, select the desired coloured


field.
• Confirm the selection using the 6 key.
• Using the keys 3 or 4, select the desired colour.
• Confirm the selection using the 6 key.

78
UMG 512

Extensions

Under "Extensions", you can subsequently activate


functions that are subject to purchase (activation) and
display the status of the Jasic programs (Jasic status).

Activation

The UMG  512 contains functions that are subject


to purchase and can be subsequently activated.
List of the functions that can be activated:

• BACnet

You receive the activation codes from the manufacturer.


The manufacturer requires the serial number of the device
and the name of the function to be activated.

To activate the function, enter the 6-digit activation code


in the corresponding line.

Make sure that the activation code is only valid for one
device.

79
UMG 512

Jasic status

Up to 7 customer-specific Jasic programs (1-7) and


a recording can run in the UMG 512.

The Jasic programs can have the following statuses:

• Stopped
• Running

You cannot change the status of the Jasic programs


on the device.

80
UMG 512

Commissioning the unit Connecting the measured voltage

Connecting the supply voltage • Measurement of voltages in networks with over


500VAC to earth must be connected via voltage
• The supply voltage level for the UMG 512 transformers.
is specified on the rating plate. • After connecting the measured voltages,
• After connecting the supply voltage, a display the measured values displayed by the UMG 512
appears. Approximately 15 seconds later, the UMG for the L-N and L-L voltages must correspond
512 switches to the first measured value display. to those at the voltage measurement input.
• If no display appears, check whether the power • If a voltage transformer factor is programmed,
supply voltage is within the rated voltage range. it must be taken into consideration for
the comparison.

c Please note!
If the supply voltage does not correspond
C Prior to commissioning potential pro-
duction dependant contents of the ener-
to the voltage indicated on the rating gy counter, min/max values and records
plate, this may lead to malfunctions have to be deleted.
and severe damage to the device.

c Please note!
The UMG 512 is only suitable for c Please note!
The UMG 512 is not suitable for
use in networks where overvoltages measuring DC voltages.
of overvoltage category 600V CATIII can
occur.

81
UMG 512

Frequency measurement Direction of the rotating field

The UMG 512 requires the mains frequency for Check the direction of the rotating field voltage
the measurement. The mains frequency can be defined in the measured value display of the UMG 512.
by the user or automatically determined by the device.
A “right” rotation field usually exists.
• For the UMG 512 to automatically determine
the frequency, a voltage L1-N of greater than
10Veff must be applied to voltage measurement
input V1.
• The mains frequency must be in the range from
15Hz to 440Hz.
• If there is no sufficiently high measured voltage UL1-UL2-UL3 = right rotation field
available, the UMG 512 cannot determine UL1-UL3-UL2 = left rotation field
the mains frequency and thus cannot perform any
measurements.

Presentation of the phase sequence according to the


direction of the rotating field.

82
UMG 512

Applying the measuring-circuit voltage

The UMG 512 is designed for the connection of .. /1A


and .. /5A current transformers.
Only AC currents can be measured via the current
measurement inputs - DC currents cannot.

Short circuit all current transformer outputs except for


one. Compare the currents displayed by the UMG 512
with the applied current.

Bearing in mind the current transformer conversion ratio,


the current displayed by the UMG 512 must correspond
with the input current.
The UMG 512 must display approx. zero amperes
in the short circuited current measurement inputs.

The current transformer ratio is factory-set to 5/5A In the Phasor diagram, the voltages are displayed
and must be adapted to the current transformer used with long pointers and the currents with short
if necessary. pointers.

Phase shift angle sign prefix (U/I):


- Positive (+) for capacitive load Voltage
- Negative (-) for inductive load

Current

m Please note!
Voltages and currents that are outside
the permissible measuring range can
damage the device.

83
UMG 512

Phasor diagram, example 1


Predominantly ohmic load.

Voltage and current only have


a minor deviation in the phase
length.

• The current measurement input is assigned to the


correct voltage measurement input.

Phasor diagram, example 2


Predominantly ohmic load.

Voltage and current have


a deviation of about 180° in
the phase position.

• The current measurement input is assigned to the


correct voltage measurement input.
• In the current measurement considered here, the k and
l connections are reversed or there is a return feed
in the mains power supply.

84
UMG 512

Applying the residual current

C
Connect residual current transformer only to the I5
and I6 inputs with a rated current of 30mA! Both residual The UMG 512 requires the mains frequency
current inputs can measure AC currents, pulsing direct for residual current monitoring. For this
currents and DC currents. purpose, the measured voltage should be
applied or a fixed frequency should be set.
Bearing in mind the current transformer ratio, the residual
current displayed by the UMG 512 must correspond with
the input current. C It is not necessary to configure a
connection schematic for residual current
inputs I5 and I6.
The current transformer ratio is factory-set to 5/5A
and must be adapted to the residual current transformer
used if necessary.

Failure monitoring (RCM) for I5, I6

The UMG 512 enables continuous monitoring of the


Modbus addr. Value / Function
connection to the residual current transformer on inputs
I5 and I6. 13793 (I5) Failure monitoring for I5 / I6
13795 (I6) 0 = Deactivate monitoring
Activation of failure monitoring is performed using 1 = Activate monitoring
the corresponding menu item or by setting address
13793 for the residual-current measurement input I5
and 13795 for I6. Modbus addr. Value / Function
13805 (I5) 0 = Connection to the residual
If there is an interruption in the connection to the current 13806 (I6) current transformer on to I5 or I6
transformer, this state is recorded in certain registers error-free
or indicated in the GridVis software. 1 = Error in the current transformer
connection to I5 or I6

85
UMG 512

Alarm status for I5, I6

Using bit-by-bit coding inside the alarm register (addr.


Warning: The residual current has exceeded
13921 for I5, 13922 for I6), it is possible to read out
the set warning limit value
different alarm statuses:
Overcurrent: The measurement range has been
Bit: 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 exceeded

00000000 00000000 Alarm: Alarm bit is set for: warning,


overcurrent or connection error
to the transformer.
Unused
The alarm bit must be reset
Alarm or acknowledged manually.
Overcurrent
Warning

Example:
The measurement range has been exceeded. The alarm
bit is also set and must be acknowledged!

Bit: 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

00000000 00000110

Unused

Alarm
Overcurrent
Warning

86
UMG 512

Checking the power measurement

Short-circuit all current transformer outputs except for


one and check the displayed power outputs.
The UMG 512 may only display one power output
in the phase with a non-short-circuited current transformer
input. If this is not the case, check the connection of the
measured voltage and the measuring-circuit current.

If the effective power amount is correct but the sign


of the power output is negative,

• S1(k) and S2(l) could be inverted at the current


transformer
• or they supply effective power back into
the network. In the Phasor diagram, the voltages are displayed
with long pointers and the currents with short
pointers.

Checking the communication

The UMG 512 counts all received (RX), all transmitted


(TX) and all faulty data packages.

Ideally, the number of the error displayed in the Error


column is zero.

Reset:
You can reset the meters for the data package with
the 6 key.
The start time for the new counting process is reset.

87
UMG 512

Measurement range exceeded (overload)

If the measurement range is exceeded, it is displayed


as long as this persists and cannot be acknowledged.
The measurement range is exceeded if at least one
of the four voltage or current measurement inputs lies
outside their specified measuring range.

Threshold values for exceeding the measurement


range (200 ms effective values):

I = 7 Arms
UL-N = 600 Vrms
Indication of values exceeding the measurement
range in voltage circuit L2 and in current path I4

88
UMG 512

RS485 interface

The MODBUS RTU protocol with CRC check Transmission parameters:


on the RS485 interface can be used to access the Data bits: 8
data from the parameter and the measured value lists Parity: None
(see RS485 configuration). Stop bits (UMG 512): 2
External stop bits: 1 or 2
Modbus functions (master)
01 Read coil status Number format: short 16 bit (-215 to 215 -1)
02 Read input status float 32 bit (IEEE 754)
03 Read holding registers
04 Read input registers
05 Force single coil
06 Preset single register
15 (0F Hex) Force multiple coils
16 (10Hex) Preset multiple registers
23 (17Hex) Read/write 4X registers

Modbus functions (slave)


03 Read holding registers
04 Read input registers
06 Preset single register
16 (10Hex) Preset multiple registers
C Broadcast (address 0) is not supported
by the device.
23 (17Hex) Read/write 4X registers

The sequence of bytes is high before low byte (Motorola


format).
C The message length must not exceed
256 bytes.

89
UMG 512

Example: Reading the L1-N voltage


The L1-N voltage is saved in the measured value
list at address 19000. The L1-N voltage is available
in the FLOAT format.
Address = 01 is approved as the UMG 512 device
address.

The Query Message appears as follows:

Name Hex Note


Device address 01 UMG 512, address = 1
Function 03 „Read Holding Reg.“
Start Addr. Hi 4A 19000dez = 4A38hex
Start Addr. Lo 38
Ind. Value Hi 00 2dez = 0002hex
Ind. Value Lo 02
Error Check -

The "Response" of the UMG 512 can appear as follows:

Name Hex Note


Device address 01 UMG 512, address = 1
Function 03
Byte meter 06
Data 00 00hex = 00dez
Data E6 E6hex = 230dez
Error Check (CRC) -

The L1-N voltage read by address 19000 is 230V.

90
UMG 512

Profibus

Profibus profiles Device master file

A Profibus profile contains the data to be exchanged The device master file, abbreviated as GSD file,
between a UMG and a PLC. Four Profibus profiles are describes the Profibus characteristics of the UMG 512.
preconfigured at the factory. The GSD file is required by the configuration program
of the PLC.
A Profibus profile can:
• Retrieve measured values from the UMG, The device master file for the UMG 512 has the file name
• Set the digital outputs in the UMG, "JAN0EDC.GSD" and is included on the data carrier
• Query the status of the digital inputs in the UMG. as part of the scope of the delivery.

Each Profibus profile can hold a maximum of 127 bytes


of data. If more data has to be transferred, simply create Variable definition
additional Profibus profiles. All system variables and global variables1) can
be individually scaled and converted into one
• Every Profibus profile has a profile number. of the following formats:
The profile number is sent by the PLC to the UMG. • 8, 16, 32 bit integer with and without sign prefix.
• Using GridVis, 16 Profibus profiles (profile numbers • 32 or 64 bit float format.
0..15) can be edited. • Big or little endian.
• Additional Profibus profiles (profile numbers • Big endian = High byte before low byte.
16..255) can be created using Jasic programs. • Little endian = Low byte before high byte.
• Factory pre-configured Profibus profiles cannot
be subsequently changed.

1) Global variables are variables that are defined


by the user in Jasic and are available to each interface
in the UMG 512.

91
UMG 512

Example

Using Profibus to retrieve measured values

At least one Profibus profile must be set up with GridVis


software and transferred to the UMG 512.
A Jasic program is not required.

PLC UMG 512


Fetch measured values
for this profile number.

PLC process output box


1st Byte = Profile number (0 to 15) Profile number
2nd Byte = Data to the UMG 512

• Profibus

PLC process input box


1st Byte = Return signal from the profile
Profile number Measured values
number
2nd Byte = Requested by UMG 512 Data

Fig. Block diagram for data exchange


between PLC and UMG 512.

92
UMG 512

Factory pre-configured profiles

Profibus profile number 0 Profibus profile number 1


Byte Value type Value Scaling Byte Value type Value Scaling
index format index format
1 1 Voltage L1-N Float 1 1 1 Voltage L1-N Float 1
2 5 Voltage L2-N Float 1 2 5 Voltage L2-N Float 1
3 9 Voltage L3-N Float 1 3 9 Voltage L3-N Float 1
4 13 Voltage L4-N Float 1 4 13 Voltage L2-L1 Float 1
5 17 Voltage L2-L1 Float 1 5 17 Voltage L3-L2 Float 1
6 21 Voltage L3-L2 Float 1 6 21 Voltage L1-L3 Float 1
7 25 Voltage L1-L3 Float 1 7 25 Current L1 Float 1
8 29 Current L1 Float 1 8 29 Current L2 Float 1
9 33 Current L2 Float 1 9 33 Current L3 Float 1
10 37 Current L3 Float 1 10 37 Effective power L1 Float 1
11 41 Current L4 Float 1 11 41 Effective power L2 Float 1
12 45 Effective power L1 Float 1 12 45 Effective power L3 Float 1
13 49 Effective power L2 Float 1 13 49 Cos phi (math.) L1 Float 1
14 53 Effective power L3 Float 1 14 53 Cos phi (math.) L2 Float 1
15 57 Effective power L4 Float 1 15 57 Cos phi (math.) L3 Float 1
16 61 Cos phi (math.) L1 Float 1 16 61 Frequency Float 1
17 65 Cos phi (math.) L2 Float 1 17 65 Effective power sum L1-L3 Float 1
18 69 Cos phi (math.) L3 Float 1 18 69 Reactive power sum L1-L3 Float 1
19 73 Cos phi (math.) L4 Float 1 19 73 Apparent power sum L1-L3 Float 1
20 77 Frequency Float 1 20 77 Cos phi (math.) sum L1-L3 Float 1
21 81 Effective power sum L1-L4 Float 1 21 81 Effective current sum L1-L3 Float 1
22 85 Reactive power sum L1-L4 Float 1 22 85 Active energy sum L1-L3 Float 1
23 89 Apparent power sum L1-L4 Float 1 23 89 Ind. Reactive energy sum L1-L3 Float 1
24 93 Cos phi (math.) sum L1-L4 Float 1 24 93 THD voltage L1 Float 1
25 97 Effective current sum L1-L4 Float 1 25 97 THD voltage L2 Float 1
26 101 Active energy sum L1-L4 Float 1 26 101 THD voltage L3 Float 1
27 105 Ind. Reactive energy sum L1-L4 Float 1 27 105 THD current L1 Float 1
28 109 THD voltage L1 Float 1 28 109 THD current L2 Float 1
29 113 THD voltage L2 Float 1 29 113 THD current L3 Float 1
30 117 THD voltage L3 Float 1

93
UMG 512

Profibus profile number 2 Profibus profile number 3


Byte Value type Value Scaling Byte Value type Value Scaling
index format index format
1 1 Active energy sum L1-L3 Float 1 1 1 Effective power L1 Float 1
2 5 Rel. Active energy sum L1-L3 Float 1 2 5 Effective power L2 Float 1
3 9 Deliv. Active energy sum L1-L3 Float 1 3 9 Effective power L3 Float 1
4 13 Reactive energy sum L1-L3 Float 1 4 13 Effective power sum L1-L3 Float 1
5 17 Ind. Reactive energy sum L1-L3 Float 1 5 17 Current L1 Float 1
6 21 Cap. reactive energy sum L1-L3 Float 1 6 21 Current L2 Float 1
7 25 Apparent energy sum L1-L3 Float 1 7 25 Current L3 Float 1
8 29 Active energy L1 Float 1 8 29 Current sum L1-L3 Float 1
9 33 Active energy L2 Float 1 9 33 Active energy sum L1-L3 Float 1
10 37 Active energy L3 Float 1 10 37 Cos phi (math.) L1 Float 1
11 41 Inductive reactive energy L1 Float 1 11 41 Cos phi (math.) L2 Float 1
12 45 Inductive reactive energy L2 Float 1 12 45 Cos phi (math.) L3 Float 1
13 49 Inductive reactive energy L3 Float 1 13 49 Cos phi (math.) sum L1-L3 Float 1
14 53 Reactive power L1 Float 1
15 57 Reactive power L2 Float 1
16 61 Reactive power L3 Float 1
17 65 Reactive power sum L1-L3 Float 1
18 69 Apparent power L1 Float 1
19 73 Apparent power L2 Float 1
20 77 Apparent power L3 Float 1
21 81 Apparent power sum L1-L3 Float 1

94
UMG 512

Digital in-/outputs

The UMG 512 has two digital outputs and two digital
inputs. The inputs and outputs can be configured using
the GridVis software (included in the scope of delivery).

The settings of the functions in the configuration menu


must be made using the GridVis software.

+
-
24V = =
DC +
- S1 S2
K1 K2

11 12 13 14 15 16
Digital Outputs Digital Inputs

Fig.: Digital inputs and outputs

Fig.: GridVis software, configuration menu

95
UMG 512

Pulse output

The digital outputs can be used for the output


of pulses for the computation of power consumption.
For this purpose, a pulse of defined length is applied
on the output after reaching a certain, adjustable amount
of power.

You need to make various adjustments


in the configuration menu using the GridVis software
to use a digital output as a pulse out.

• Digital output,
• Measured value selection,
• Pulse length,
• Pulse value.

Fig.: GridVis software, configuration menu

96
UMG 512

Pulse length

The pulse length applies to both pulse outputs and is set The values​in the table are based on the minimum pulse
using the GridVis software. length and the minimum pulse interval for the maximum
number of pulses per hour.
The typical pulse length of S0 pulse is 30ms.

Pulse length Pulse interval Max. pulse/h


Pulse interval
10 ms 10 ms 180 000 pulses/h
The pulse interval is at least as large as the selected 30 ms 30 ms 60 000 pulses/h
pulse length. 50 ms 50 ms 36 000 pulses/h
The pulse interval depends on the measured power, for
example, and can take hours or days. 100 ms 100 ms 18 000 pulses/h
500 ms 500 ms 3600 pulses/h
1 s 1 s 1800 pulses/h
Pulse interval
Pulse length 10 s 10 s 180 pulses/h
10ms .. 10s >10ms
Examples of the maximum possible number of pulses
per hour.

C Pulse interval
The pulse interval is proportional to the
C Measured value selection
When programming with GridVis you
have a selection of work values ​​which are
power output within the selected settings. derived from the power output values.

97
UMG 512

Pulse value

The pulse value is used to indicate how much power


(Wh or varh) should correspond to a pulse.
The pulse value is determined by the maximum
connected load and the maximum number of pulses per
hour.

If you check the pulse value with a positive sign,


the pulses will only be emitted when the measured value
has a positive sign.

If you check the pulse value with a negative sign,


the pulses will only be produced when the measured
value has a negative sign.

max. connected load


Pulse value = [Pulse/Wh]
max. number of pulses/h

C Since the effective power meter operates


with a backstop, pulses will only
be generated when drawing electricity.

C Since the reactive power meter operates


with a backstop, pulses will only
be generated with inductive load applied.

98
UMG 512

Determine the pulse value

Set the pulse length External 230V AC


Set the pulse length in accordance with the requirements supply voltage
of the connected pulse receiver.
24V DC
At a pulse length of 30 ms, for example, the UMG 512 + -
generates a maximum number of 60,000 pulses UMG 512
(see Table "maximum number of pulses" per hour. Switch and pulse outputs
11
+24V=
Data logger
Determining the maximum connected load
Example: 12

1.5k
Current transformer = 150/5A
Voltage L-N = max. 300 V
13
Power per phase = 150 A x 300 V
= 45 kW
Power at 3 phases = 45kW x 3
Max. connected load = 135kW Fig.: Connection example for the circuit as pulse
output.

Calculating the pulse value

max. connected load


Pulse value = [Pulse/Wh]
max. number of pulses/h

Pulse value = 135kW / 60,000 Imp/h


C When using the digital outputs as pulse
outputs, the auxilliary voltage (DC) must
Pulse value = 0.00225 pulse/kWh have a max. residual ripple of 5%.
Pulse value = 2.25 pulses/Wh

99
UMG 512

Service and maintenance

The device underwent various safety checks before We will need the following information from you
delivery and is marked with a seal. If a device is open, to answer any questions:
then the safety checks must be repeated. Warranty
claims will only be accepted if the device is unopened. - Device name (see rating plate),
- Serial number (see rating plate),
Repair and calibration - Software release (see measured value display),
- Measured voltage and power supply voltage,
Repair work and calibration can be carried out - Precise description of the error.
by the manufacturer only.
Device calibration
Front film
The devices are calibrated by the manufacturer
The front film can be cleaned with a soft cloth at the factory - it is not necessary to recalibrate
and standard household cleaning agent. Do not use the device providing that the environmental conditions
acids and products containing acid for cleaning. are complied with.

Disposal Calibration intervals

The UMG 512 can be reused or recycled as electronic We recommend having the device recalibrated
scrap in accordance with the legal provisions. by the manufacturer or an accredited laboratory every
The permanently installed lithium battery must 5 years approximately.
be disposed of separately.

Service

Should questions arise, which are not described in this


manual, please contact the manufacturer directly.

100
UMG 512

Firmware update Battery

If the device is connected to a computer via Ethernet, The internal clock is fed from the supply voltage.
then the device firmware can be updated via the GridVis If the supply voltage fails then the clock is powered by the
software. battery. The clock provides date and time information,
for the records, min. and max. values and events, for
The new firmware is transferred by selecting a suitable example.
update menu (Tools/Upgrade Devices menu)
and the device. The life expectancy of the battery is at least 5 years
with a storage temperature of +45°C. The typical life
expectancy of the battery is 8 to 10 years.

The battery (type CR2450 / 3V) can be replaced


by the user.

Fig. GridVis firmware update assistant

C Firmware may NOT be updated via the


RS485 interface.
Fig. Replacing the battery using long-nose pliers

101
UMG 512

Procedure in the event of faults

Possible fault Cause Remedy


No display External fuse for the power supply voltage has Replace fuse.
tripped.
No current display Measured voltage Connect the measured voltage.
is not connected.
Measurement current is not connected. Connect measuring-circuit current.
Current displayed is too large Current measurement in the wrong phase. Check connection and correct if necessary.
or too small. Current transformer factor is incorrectly Read out and program the CT ratio at the current
programmed. transformer.
The current peak value at the measurement input Install current transformer with a larger CT ratio.
was exceeded by harmonic components.
The current at the measurement input fell short Install current transformer with a smaller current
of. transformer ratio.
Voltage displayed is too large Measurement in the wrong phase. Check connection and correct if necessary.
or too small. Voltage transformer incorrectly programmed. Read out and program the voltage transformer
ratio at the voltage transformer.
Voltage displayed is too small. Measurement range exceeded. Use voltage transformers.
The peak voltage value at the measurement input Please note! Ensure the measurement inputs are
has been exceeded by the harmonics. not overloaded.
Phase shift ind/cap. A current path is assigned to the wrong voltage Check connection and correct if necessary.
circuit.
Effective power, consumption/supply At least one current transformer connection Check connection and correct if necessary.
reversed. is mixed up/reversed.
A current path is assigned to the wrong voltage Check connection and correct if necessary.
circuit.

102
UMG 512

Possible fault Cause Remedy


Effective power too large The programmed CT ratio is incorrect. Read out and program the CT ratio at the current
or too small. transformer
The current path is assigned to the wrong Check connection and correct if necessary.
voltage circuit.
The programmed voltage transformer ratio Read out and program the voltage transformer
is incorrect. ratio at the voltage transformer.
An output is not responding. The output was incorrectly programmed. Check the settings and correct if necessary.
The output was incorrectly connected. Check connection and correct if necessary.
Measurement range exceeded Voltage and current measurement input outside Check connection and correct if necessary.
display (overload) the measurement range
Use suitable voltage and current transformers.
(See section Measurement range exceeded)
Read out and program the voltage or current
transformer ratio at the transformer.
No connection with the device. RS485
- Device address is incorrect. - Adjust the device address.
- Different bus speeds - Adjust speed (baud rate).
(Baud rate).
- Wrong protocol. - Select the correct protocol.
- Termination missing. - Terminate bus with termination resistor.
Ethernet
- IP Device address is incorrect. - Adjust IP device address.
- Incorrect addressing mode - Adjust the IP address assignment mode
Device still does not work despite Device defective. Send the device to the manufacturer for
the above measures. inspection and testing along with an accurate
fault description.

103
UMG 512

Technical data
General
Net weight (with attached connectors) approx. 1080g
Device dimensions approx. l = 144mm, w = 144mm, h = 75mm
Battery Type Li-Mn CR2450, 3V (approval i.a.w. UL 1642)
Clock (in temperature range -40°C to 85°C) +-5ppm (corresponding to approx. 3 minutes p.a.)

Transport and storage


The following information applies to devices which are transported or stored in the original packaging.
Free fall 1m
Temperature -25°C to +70°C

Ambient conditions during operation


The UMG 512 is intended for weather-protected, stationary use.
The UMG 512 must be connected to the protective current connection! Protection class I in acc. with IEC 60536 (VDE 0106, Part 1).
Working temperature range -10°C to +55°C
Relative humidity 5 to 95% RH (at 25°C without condensation)
Operating altitude 0 to 2000m above sea level
Pollution degree 2
Mounting position vertical
Ventilation Forced ventilation is not required.
Protection against ingress of solid foreign bodies and water
- Front side IP40 i.a.w. EN60529
- Rear side IP20 in acc. with EN60529

104
UMG 512

Supply voltage
Installations of overvoltage category 300V CAT III
Protection of the supply voltage (fuse) 6A Char. B (approved i.a.w. UL/IEC)
230V option: - Nominal range 95V .. 240V (50/60 Hz) or DC 80V .. 300V
- Operating range +-10% of nominal range
- Power consumption max. 7W / 14VA
24V option: - Nominal range 48V .. 110V (50/60 Hz) or DC 24 .. 150V
- Operating range +-10% of nominal range
- Power consumption max. 9W / 13VA

Terminal connection capacity (supply voltage)


Connectable conductors. Only one conductor can be connected per terminal!
Single core, multi-core, fine-stranded 0.2 - 2.5mm2, AWG 24 - 12
Terminal pins, core end sheath 0.25 - 2.5mm2
Tightening torque 0.5 - 0.6Nm
Stripping length 7mm

Current measurement
Rated current 5A
Resolution 0.1mA
Metering range 0.001 to 7 Arms
Measurement range exceeded (overload) From 7 Arms
Crest factor 1.41
Overvoltage category 230V option: 300V CAT III 24V option: 300V CAT II
Measurement surge voltage 4kV
Power consumption approx. 0.2 VA (Ri=5mOhm)
Overload for 1 sec. 120A (sinusoidal)
Sampling frequency 25.6kHz / phase

105
UMG 512

Voltage measurement
The voltage measurement inputs are suitable for measurements in the following power supply systems:
Three-phase 4-conductor systems with rated voltages up to 417V/720V
347V / 600V UL listed
Three-phase 3-conductor systems with rated voltages up to 600V
From a safety and reliability perspective, the voltage measurement inputs are designed as follows:
Overvoltage category 600V CAT III
Measurement surge voltage 6kV
Fuse protection for voltage measurement 1-10 A

Metering range L-N 01) to 600Vrms


Metering range L-L 01) to 1000Vrms
Resolution 0.01V
Crest factor 1.6 (related to 600Vrms)
Impedance 4MOhm/phase
Power consumption approx. 0.1VA
Sampling rate 25.6kHz / phase
Transients 39μs
Udin2) i.a.w. EN61000-4-30 100 to 250V
Flicker range (dU/U) 27.5%
Frequency range of the fundamental oscillation 15Hz to 440Hz
- Resolution 0.001Hz
1)
The UMG 512 can only determine measured values, if at least a voltage L-N greater than 10Veff or a voltage
L-L of greater than 18Veff is present at one voltage measurement input.
2)
The Udin = arranged input voltage according to DIN EN 61000-4-30

Terminal connection capacity (voltage and current measurement)


Connectable conductors. Only one conductor can be connected per terminal!
Single core, multi-core, fine-stranded 0.2 - 2.5mm2, AWG 24-12
Terminal pins, core end sheath 0.25 - 2.5mm2
Tightening torque 0.5 - 0.6Nm
Stripping length 7mm

106
UMG 512

Residual current monitoring (RCM)


Rated current 30mArms
Metering range 0 to 40mArms
Triggering current 100µA
Resolution 1µA
Crest factor 1.414 (related to 40mA)
Burden 4 Ohm
Overload for 1 sec. 5A
Sustained overload 1A
Overload for 20 ms 50A
Residual current monitoring i.a.w. IEC/TR 60755 (2008-01), type A

Maximum external burden 300 Ohm (for cable break detection)

Terminal connection capacity (residual current monitoring)


Connectable conductors. Only one conductor can be connected per terminal!
Rigid/flexible 0.14 - 1.5mm2, AWG 28-16
Flexible with core end sheath without plastic sleeve 0.20 - 1.5mm2
Flexible with core end sheath with plastic sleeve 0.20 - 1.5mm2
Stripping length 7mm
Tightening torque 0.20 - 0.25Nm
Cable length up to 30m unshielded, from 30m shielded
Potential separation and electrical safety
- The RCM measurement inputs are double-insulated from the current and voltage measurement inputs as well as the supply voltage.
- There is no insulation from the thermistor input.
- There is only a functional insulation from the Ethernet, Profibus and RS485 interfaces and the digital I/Os.
- The residual current transformer connected and the lines to be measured must each have at least one additional or a basic insulation
per IEC61010-1:2010 for the mains voltage present.

107
UMG 512

Temperature measurement input


3-wire measurement
Update time 1 second
Connectable sensors PT100, PT1000, KTY83, KTY84
Total burden (sensor + cable) max. 4 kOhm
Cable length up to 30m unshielded, from 30m shielded

Sensor type Temperature range Resistor range Measurement uncertainty


KTY83 -55°C to +175°C 500Ohm to 2.6kOhm ± 1.5% rng
KTY84 -40°C to +300°C 350Ohm to 2.6kOhm ± 1.5% rng
PT100 -99°C to +500°C 60Ohm to 180Ohm ± 1.5% rng
PT1000 -99°C to +500°C 600Ohm to 1.8kOhm ± 1.5% rng

Terminal connection capacity (temperature measurement input)


Connectable conductors. Only one conductor can be connected per terminal!
Single core, multi-core, fine-stranded 0.08 - 1.5mm2
Terminal pins, core end sheath 1mm2
Potential separation and electrical safety
- The thermistor input is double-insulated from the current and voltage measurement inputs as well as the supply voltage.
- There is no insulation from the RCM measurement input.
- There is only a functional insulation from the Ethernet, Profibus and RS485 interfaces and the digital I/Os.
- The external temperature sensor must be double insulated from the system parts that carry voltages that are dangerous to
the touch (per IEC61010-1:2010).

108
UMG 512

Digital inputs
2 Digital inputs with a joint earth
Maximum counter frequency 20Hz
Response time (Jasic program) 200ms
Input signal present 18V to 28V DC (typical 4mA) (SELV or PELV supply)
Input signal not present 0 to 5V DC, current less than 0.5mA
Cable length up to 30m unshielded, from 30m shielded

Digital outputs
2 Digital outputs with a joint earth; opto-coupler, not short-circuit proof
Supply voltage 20V - 30V DC (SELV or PELV supply)
Switching voltage max. 60V DC
Switching current max. 50mAeff AC/DC
Response time (Jasic program) 200ms
Switching frequency max. 20Hz
Cable length up to 30m unshielded, from 30m shielded

Terminal connection capacity (digital inputs and outputs)


Rigid/flexible 0.14 - 1.5mm2, AWG 28-16
Flexible with core end sheath without plastic sleeve 0.25 - 1.5mm2
Flexible with core end sheath with plastic sleeve 0.25 - 0.5mm2
Tightening torque 0.22 - 0.25Nm
Stripping length 7mm
Potential separation and electrical safety
- The digital inputs and outputs are double-insulated from the current and voltage measurement inputs as well as the supply voltage.
- There is only a functional insulation from the Ethernet, Profibus and RS485 interfaces and the digital I/Os, and from one another.
- The external auxiliary voltage to be connected must be compliant with SELV or PELV.

109
UMG 512

RS485 interface
3-wire connection with GND, A, B
Protocol Modbus RTU/slave, Modbus RTU/master,
Modbus RTU /Gateway
Transmission rate 9.6kbps, 19.2kbps, 38.4kbps, 57.6 kbps, 115.2kbps, 921.6kbps
Termination resistor Can be activated by micro switch

Profibus interface
Connection SUB D 9-pole
Protocol Profibus DP/V0 as per EN 50170
Transmission rate 9.6k baud to 12 MBaud

Ethernet interface
Connection RJ45
Function Modbus gateway, embedded web server (HTTP)
Protocols CP/IP, EMAIL (SMTP), DHCP client (BootP),
Modbus/TCP, Modbus RTU over Ethernet, FTP,
ICMP (Ping), NTP, TFTP, BACnet (option), SNMP,

Potential separation and electrical safety for the interfaces


- The Ethernet, Profibus and RS485 interfaces are double-insulated from the current and voltage measurement inputs as well as the
supply voltage.
- There is only a functional insulation from the RCM measurement inputs and thermistor inputs as well as from the digital I/Os, and
from one another.
- The interfaces of the externally connected equipment must have double or reinforced insulation against mains voltages (acc. to
IEC 61010-1:2010).

110
UMG 512

Function parameters
• Measurement via current transformer ../5A
• Measurements with 50/60 Hz

Function Symbol Precision class Metering range Display range


Total effective power P 0.25) (IEC61557-12) 0 to 15.3kW 0 W to 9999 GW *
Total reactive power QA 6), Qv 6) 1 (IEC61557-12) 0 to 15.3 kvar 0 varh .. 9999 Gvar *
Total apparent power SA, Sv 6) 0.25) (IEC61557-12) 0 to 15.3 kVA 0 VA to 9999 GVA *
Total effective energy Ea 0.2S5) 7) (IEC61557-12) 0 to 15.3 kWh 0 Wh to 9999 GWh *
Total reactive energy ErA , ErV
6) 6)
1 (IEC61557-12) 0 to 15.3 kvarh 0 varh .. 9999 Gvarh *
Total apparent energy EapA,EapV6) 0.25) (IEC61557-12) 0 to 15.3 kVAh 0 VAh to 9999 GVAh *
Frequency f 0.05 (IEC61557-12) 40 to 70 Hz 40 Hz to 70 Hz
Phase current I 0.1 (IEC61557-12) 0.001 to 8.5 Arms 0 A to 9999 kA
Measured neutral conductor current IN 0.1 (IEC61557-12) 0.001 to 8.5 Arms 0 A to 9999 kA
Residual currents I5, I6 IDIFF 1 (IEC61557-12) 0 to 40 mArms 0 A to 9999 kA
Computed neutral conductor current INc 0.5 (IEC61557-12) 0.001 to 25.5 A 0 A to 9999 kA
Voltage U L-N 0.1 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV
Voltage U L-L 0.1 (IEC61557-12) 18 to 1000 Vrms 0 V to 9999 kV
Power factor PFA, PFV 0.5 (IEC61557-12) 0.00 to 1.00 0 to 1
Short-term flicker, long-term flicker Pst, Plt Cl. A (IEC61000-4-15) 0.4 Pst to 10.0 Pst 0 to 10
Voltage drops Udip 0.2 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV
Voltage increases Uswl 0.2 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV
Transient overvoltages Utr 0.2 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV
Voltage interruptions Uint Duration +- 1 cycle - -
Voltage unbalance 1) Unba 0.2 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV
Voltage unbalance 2)
Unb 0.2 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV
Voltage harmonics Uh Cl. 1 (IEC61000-4-7) up to 2.5 kHz 0 V to 9999 kV

111
UMG 512

THD of the voltage 3) THDu 1.0 (IEC61557-12) up to 2.5 kHz 0% to 999%


THD of the voltage 4) THD-Ru 1.0 (IEC61557-12) up to 2.5 kHz 0% to 999%
Current harmonics Ih Cl. 1 (IEC61000-4-7) up to 2.5 kHz 0 A to 9999 kA
THD of the current 3)
THDi 1.0 (IEC61557-12) up to 2.5 kHz 0% to 999%
THD of the current 4) THD-Ri 1.0 (IEC61557-12) up to 2.5 kHz 0% to 999%
Mains signal voltage (interharmonics MSV IEC 61000-4-7 class 1 10% – 200% of 0 V to 9999 kV
voltage) IEC 61000-2-4
class 3

• Measurements in the range 15 to 440 Hz


Function Symbol Precision class Metering range Display range
Total effective power P 2 (IEC61557-12) 0 to 15.3kW 0 W to 9999 GW *
Total reactive power QA 6), Qv 6) 2 (IEC61557-12) 0 to 15.3 kvar 0 varh .. 9999 Gvar *
Total apparent power SA, Sv 6)
1 (IEC61557-12) 0 to 15.3 kVA 0 VA to 9999 GVA *
Total effective energy Ea 2 (IEC61557-12) 0 to 15.3 kWh 0 Wh to 9999 GWh *
Total reactive energy ErA 6), ErV 6) 2 (IEC61557-12) 0 to 15.3 kvarh 0 varh .. 9999 Gvarh *
Total apparent energy EapA,EapV6) 1 (IEC61557-12) 0 to 15.3 kVAh 0 VAh to 9999 GVAh *
Frequency f 0.05 (IEC61557-12) 15 to 440 Hz 15 Hz to 440 Hz
Phase current I 0.5 (IEC61557-12) 0.001 to 8.5 Arms 0 A to 9999 kA
Measured neutral conductor current IN 0.5 (IEC61557-12) 0.001 to 8.5 Arms 0 A to 9999 kA
Residual currents I5, I6 IDIFF 1 (IEC61557-12) 0 to 40 mArms 0 A to 9999 kA
Computed neutral conductor current INc 1.5 (IEC61557-12) 0.001 to 25.5 A 0 A to 9999 kA
Voltage U L-N 0.5 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV

112
UMG 512

Function Symbol Precision class Metering range Display range


Voltage U L-L 0.5 (IEC61557-12) 18 to 1000 Vrms 0 V to 9999 kV
Power factor PFA, PFV 2 (IEC61557-12) 0.00 to 1.00 0 to 1
Short-term flicker, long-term flicker Pst, Plt - - -
Voltage drops Udip 0.5 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV
Voltage increases Uswl 0.5 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV
Transient overvoltages Utr 0.5 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV
Voltage interruptions Uint Duration +- 1 cycle - -
Voltage unbalance 1)
Unba 0.5 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV
Voltage unbalance 2) Unb 0.5 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV
Voltage harmonics Uh Cl. 2 (IEC61000-4-7) up to 2.5 kHz 0 V to 9999 kV
THD of the voltage 3) THDu 2.0 (IEC61557-12) up to 2.5 kHz 0% to 999%

Declarations
1) In relation to the amplitude.
2) In relation to phase and amplitude.
3) In relation to fundamental oscillation.
4) In relation to effective value.
5) Precision class 0.2 with.../ 5A converter.
Precision class 0.5 with.../ 1A converter.
* The display returns to 0 W once the max.
total working value range has been reached.
6) Calculation from fundamental oscillation.
7) Precision class 0.2S according IEC62053-22

113
UMG 512

UMG512 specifications as per IEC 61000-4-30

Characteristic Uncertainty Metering range


5.1 Frequency ± 10 mHz 42.5 Hz – 57.5 Hz,
51Hz – 69 Hz
5.2 Supply voltage level ± 0.1% of Udin 10% – 150% of Udin
5.3 Flicker ± 5% of measured value 0.2 – 10 Pst
5.4 Drops and excessive increases Amplitude: ± 0.2% of Udin N/A
Duration: ± 1 period
5.5 Voltage interruptions Duration: ± 1 period N/A
5.7 Unbalance ± 0.15% 0.5% – 5% u2
0.5% – 5% u0
5.8 Harmonics IEC 61000-4-7 class 1 10% – 200% of
class 3 of IEC 61000-2-4
5.9 Interharmonics IEC 61000-4-7 class 1 10% – 200% of
class 3 of IEC 61000-2-4
5.10 Mains signal voltage In the range 3%-15% of Udin, ± 5% of Udin. 0% – 15% of Udin
In the range 1%-3% of Udin, ± 0.15% of Udin.
There are no uncertainty requirements for values
< 1% of Udin.
5.12 Downward/upward deviation ± 0.1% of Udin 10% – 150% of Udin

The UMG 512 meets the requirements according to IEC 61000-4-30 class A for:
• compensation, time uncertainty, marking concept, transient influence quantities.

m To ensure that two measurement devices achieve the same measurement results in a 10 minute
compensation interval, we recommend synchronising time measurement in the UMG 512 using
an external time signal.

114
UMG 512

115
UMG 512

Dimension diagrams

Cut-out size: 138+0.8 x 138+0.8 mm

Rear side

Patch cable

116
UMG 512

Side view View from below

117
UMG 512

Configuration menu overview

Display ... Additional main values


Display Display
Home
Communication Voltage L-N
(Measured value
Status
Additional main values ... overview)

(config)

Configuration
Language, communication, measurement, system
Display, colours, extensions

Communication Measurement Display System Colours Extensions


Ethernet Measuring transducer information U, I Activation
Field bus Transients Reset L1...L4 Jasic status
Events password
Rel. Voltage
Nominal frequency
Flicker
Thermistor input

Measuring Transients Events Clear Activation


transducer -> MAIN -> MAIN energy BACnet
-> MAIN -> AUX -> AUX Min./Max. values
-> AUX Delivery status
I Diff1 / I Diff2 Re-initialisation
Jasic status

U pim./sec. Mode Drop U


I prim./sec. Peak Voltage swell
I nom Trns Overcurrent
U nom Envelop
Connection

118
UMG 512

Measured value displays overview

Main values

Device name Voltage Current Effective power Effective power


Overview L-N L1 to L4 L1 to L4 Overview
Measured (Power sum L1 (Tariff 1, tariff 2)
values to L3)

(config)

Configuration Voltage Residual current Reactive power Reactive power


L-L L5,L6 Overview
(Power sum
(Tariff 1, tariff 2)
L1 to L3)

By-values
K-factor
L1..L4 Apparent power Apparent power
Overview
(Power sum L1
to L3)

THD-I
L1..L4

Current
Sum

119
UMG 512

Main values

Effective power Harmonics Voltage Transients Events


Monthly values of voltage L1 progression L1 1 to 8 1 to 8
Bar diagram (L2, L3, L4) (L2, L3, L4) (9 to 16) (9 to 16)

Apparent power Harmonics Current


Monthly values of current L1 progression L1
Bar diagram (L2, L3, L4) (L2, L3, L4)

Reactive power Effective power


Monthly values progression L1

By-values
Bar diagram (L2, L3, L4,
L1 to L3, L1 to L4)

Peak Demand Reactive power


Bar diagram progression L1
(L2, L3, L4,
L1 to L3, L1 to L4)

Residual current External


progression temperature
I Diff1 progression
(I Diff2) (Internal)

120
UMG 512

Main values

Phasor diagram Oscilloscope Flicker Voltage bar Communication


L1 L-N graph status
L-N

Oscilloscope Current bar


L2 graph
L3 L-N
L4

Oscilloscope Effective power


ULN1 to 3 bar graph

By-values
ULN1 to 4 L-N

Oscilloscope Residual current


IL1 to 3 bar graph
IL1 to 4 I Diff1
I Diff2

External
temperature bar
graph
(Internal)

121
UMG 512

122
UMG 512

123
UMG 512

Connection example

IDIFF IPE PT100 1 2


Data GND

A K1
- +
K2
B + -
0-30
mA

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

10/100Base-T
A B I5 I6

Ethernet

RJ45
Switch
RS485 RCM Temp. Digital Digital
Outputs Inputs

PC PC
UMG 512

Profibus
DSUB-9
SPS
Hilfsenergie Strommessung 1-4 Spannungsmessung 1-4
Auxiliary Supply Current Input 1-4 Voltage Input 1-4
L/+ N/- I1 I2 I3 I4 V1 V2 V3 V4 VN SPS
S1 S2 S1 S2 S1 S2 S1 S2
17 18 PE 19 20 21 22 23 24 25 26 27 28 29 30 31

PE PE
N N S1 S2

Verbraucher
L1 L1

Loads
S1 S2

L2 S1 S2

L3 S1 S2

124

You might also like