ASCO 7000 Withstand and Close-On Ratings

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Withstand and Close-On Ratings for

all 7000 Series Products 1, 2


Switch Current
UL 1008 Withstand and Close-On Ratings Recommended
Rating
(Symmetrical RMS, A.) Short Time 4
Fuses
(A)

"Any" Current -
Specific Max Ratings
Transfer Bypass Volts, Volts, Limiting Volts, Duration
Breaker Breaker3 Size, Class (RMS
Switches Switches Max Max Fuse Max Sym) A Cycles
Rating Rating (A)
Rating

30 - N/A - 10,000 600 100,000 480 60 J N/A -


70, 100,
- 22,000 480 10,000 600 200,000 480 200 J N/A -
125, 150
200, 230 - 22,000 480 10,000 480 200,000 480 300 J N/A -
150, 200, 35,000 600 200,000 600 J
260, 400,
230, 260, 42,000 600 600 N/A -
600
400, 600 42,0007 480 200,000 800 L

150, 200, 200,000 600 J


260, 400,
230, 260, 50,000 480 65,000 240 600 N/A -
600 200,000 800 L
400, 600
800, 1000, 800, 1000,
65,000 600 50,000 600 200,000 600 1,600 L 36,000 18
1200 1200
1600, 1600,
125,000 - 100,000 600 200,000 600 3,000 L 65,0006 30
20005 20005
2600, 3000 3000 N/A - 100,000 600 200,000 600 4,000 L 65,0006 30
4000 4000 N/A - 100,000 600 200,000 600 5,000 L 65,0008 18
Notes:

1. All WCR values above are tested in accordance with the requirements of UL 1008. See Publication 1128 for more WCR information.
2. Application requirements may permit higher withstand ratings for certain size switches. Contact ASCO for guidance if available short circuit current

exceeds the WCR ratings shown.

3. "Any" breaker ratings are based on 3 cycles for 260 - 4,000A. and 1.5 cycles for 30 - 230A switches. Applicable to the circuit breakers with

instantaneous trip elements.

4. Short-time ratings are provided for applications involving circuit breakers that do not have instantaneous trips for systems coordination. Applicable to

transfer switch design only.

5. Optional front connected service for 1,600 and 2,000A switches is limited to 85,000A for "Any" Breaker Rating.

6. Withstand (non UL) test only.

7. Limited to 35kA on switches with overlapping neutral.

8. At 480V; does not apply to bypass designs


© Copyright 2001-2009 ASCO Power Technologies, LP