0% found this document useful (0 votes)
167 views2 pages

013A

The Inbal Series 13 Flow Control Unit is used in 2-way hydraulic pilot lines to maintain a constant predetermined flow rate regardless of pressure variations. Model 13-07 is used in resetting deluge valves, while 13-08 is used in adjustable and non-adjustable hydraulic actuators. It works by using a flexible ring within a tapered seat chamber - increasing pressure forces the ring down to reduce the orifice, while decreasing pressure allows the ring to open the orifice and maintain the flow rate. Standard flow rates range from 0.53 to 2.11 gpm.

Uploaded by

Ckaal74
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
167 views2 pages

013A

The Inbal Series 13 Flow Control Unit is used in 2-way hydraulic pilot lines to maintain a constant predetermined flow rate regardless of pressure variations. Model 13-07 is used in resetting deluge valves, while 13-08 is used in adjustable and non-adjustable hydraulic actuators. It works by using a flexible ring within a tapered seat chamber - increasing pressure forces the ring down to reduce the orifice, while decreasing pressure allows the ring to open the orifice and maintain the flow rate. Standard flow rates range from 0.53 to 2.11 gpm.

Uploaded by

Ckaal74
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Flow Control Unit

Series 13

Flow Control Unit model 13-07 is used


in the Inbal 2-way Hydraulically
Controlled, Remote Resetting Deluge
Valve. Model 13-08 is used in the Inbal
2-way type, Adjustable and Non-
adjustable, Hydraulic Pilot Actuator and
in the Inbal 2-way Hydraulically
Actuated, Remote control Valve.

Technical Data

Model 13-08 Flow Rates


Standard
1.32 gpm (0.30 m³/h).
Optional
0.53 gpm (0.12 m³/h) ;
0.79 gpm (0.18 m³/h) ;
1.06 gpm (0.24 m³/h) ;
Model 13-07 1.63 gpm (0.37 m³/h) ;
2.11 gpm (0.48 m³/h) .
Ends
General Description
Model 13-07
The Flow Control Unit series 13 is used The Inbal Series 13 is primarily used in a
to provide a predetermined flow rate 2-way type hydraulic pilot line where the Inlet - ½" NPT, male.
unaffected by line pressure variations. release device could be located in an Outlet - ½" NPT, female.
The Flow Control Unit is used in Inbal extended remote distance. The Flow
Hydraulically Controlled Valves and Control unit prevents an increasing Model 13-08
Remote Resetting Deluge Valves. Its residual pressure when the release Pressed fitting in Hydraulic Pilot
function is to limit the flow introduced to device operates as a result of increasing Actuators models 421-02 and 423-02.
the Inbal Valve control chamber to be line pressure. Thus, the Inbal Valve's
less than the flow released. fully open position is obtained regardless Pressure Rating
Consequently, a fully open position of of the system and wet pilot line Minimum : 15 psi ( 1 bar).
the Inbal Valve is assured. pressures. Maximum: 300 psi (21 bar).

3 2 1
½" NPT

28 mm
½" NPT

11/8"

113/16"
3 2 1 45 mm
Model 13-07

Item Part No. Description Standard Materials Quantity


1 1308118 Flexible Ring Nitrile 1
2 1308108 Flexible Ring Housing Brass 1
3 1307108 Flow Control Fitting Brass 1

F40-02-01
Flow Control Unit
Series 13

Temperature Range HIGH PRESSURE LOW PRESSURE


Water: Max. +1800F (+800C).

Materials
Standard
Brass.
Optional
Stainless Steel.

Weight
13-07 : 0.13 lbs (0.06 kg).
13-08 : 0.22 lbs (0.1 kg).

Operation

The Flow Control Unit is to provide a Upon Pressure increasing, the flexible Pressure is decreasing, the flexible ring is
flow of water at a predetermined rate, ring rolls down the tapered seat to extended upwards to enlarge the orifice
regardless of system pressure changes. decrease the orifice bore. The flow rate bore and to maintain the constant flow
The Inbal series 13 employs a flexible remains constant. rate.
ring housed within a performed tapered
seat chamber. An increase of the flowing
water pressure forces the flexible ring
down the chamber to reduce the size of
the orifice. As the pressure reduces, the
flexible ring returns to its original shape,
enlarging the orifice bore. This motion of
the ring maintains a balance of pressure
and orifice to provide a constant flow
rate.

5
4
3
2
1

Item Part No. Description Standard Materials Quantity


1 1308118 Flexible Ring Nitrile 1
2 1308108 Flexible Ring Housing Brass 1
3 1308008 Flow Control Unit Housing Brass 1
4 210867 O-Ring Buna N 1

Copersa. Eduard Calvet i Pintó 20, 08339 - Vilassar de Dalt, Barcelona. Tel: +34 937 59 25 00, Fax: +34 937 59 50 08, E-mail: [email protected]
March 2000 / F40-02-01-002