Instruction Manual: Compact Inverter
Instruction Manual: Compact Inverter
Instruction Manual: Compact Inverter
Compact Inverter
2-3
1/8 FRN0001C2S-6U
1 FRN0005C2S-6U 14/12
DCR: DC reactor
*1 Use crimp terminals covered with an insulated sheath or insulating tube.
*2 Wire sizes are calculated on the basis of input RMS current under the condition that the power supply
capacity and impedance are 50 kVA and 5%, respectively.
*3 Insert the DC reactor (DCR) in either of the primary power input lines. Refer to Chapter 10 for more
details.
2-5
2.3.5 Wiring for main circuit terminals and grounding terminals
Inverter output terminals, U, V, W and grounding terminal ( G)
1) Connect the three wires of the three-phase motor to terminals U, V, and W, aligning phases each other.
2) Connect the grounding wire of terminals U, V, and W to the grounding terminal ( G).
3) If the cable from the inverter to the motor is very long, a high-frequency current may be generated by
stray capacitance between the cables and result in an overcurrent trip of the inverter, an increase in
leakage current, or a reduction in current indication precision.
When a motor is driven by a PWM-type inverter, the motor terminals may be subject to surge voltage
generated by inverter element switching. If the motor cable (with 460 V series motors, in particular) is
particularly long, surge voltage will deteriorate motor insulation. To prevent this, use the following guidelines:
Inverters of 5 HP or below
Motor Insulation Level 1000 V 1300 V 1600 V
460 VAC Input Voltage 66 ft (20 m) 165 ft (50 m) 165 ft (50 m)*
230 VAC Input Voltage 328 ft (400 m)* 328 ft (100 m)* 328 ft (100 m)*
* For this case the cable length is determined by secondary effects and not voltage spiking.
When a motor protective thermal O/L relay is inserted between the inverter and the motor, the
thermal O/L relay may malfunction (particularly in the 460 V series), even when the cable
length is 165 ft (50 m) or less. To correct, insert a filter or reduce the carrier frequency. (Use
function code F26 (Motor sound).)
When wiring the inverter to the power supply of 50 kVA or more, be sure to connect an optional
DC reactor (DCR).
Otherwise, fire could occur.
2-9
Chapter 5 FUNCTION CODES
This chapter sets forth function codes whose setting ranges differ according to the input voltage for
the single-phase 100 V class series (FRN-_ _ _ _C2S-6U).
5.1 Function Code Tables
Change Refer
Incre- Data Default
Code Name Data setting range Unit when to
ment copying setting
running page:
F05 Rated Voltage at Base 0: Output a voltage in proportion to input 1 V N Y2 0 5-23
Frequency 1 voltage
80 to 240: Output an AVR-controlled
voltage (Note 1)
160 to 500: Output an AVR-controlled
voltage (Note 2)
5-2
Table A Fuji Standard Motor Parameters
Nominal rated Nominal rated
Fuji's standard
Nominal current of capacity of
Power torque boost
applied Fuji standard motor Fuji standard motor
supply Inverter type (%)
motor (A) (kW)
voltage
(HP) Function code Function code Function code
F09/A05 F11/A07/E34/E37 P02/A16
5-20
F20 to F22 DC Braking 1 (Braking starting frequency, Braking level, and Braking time)
H95 DC Braking (Braking response mode)
5-37
F30 Analog Output [FMA] (Voltage adjustment)
F31 Analog Output [FMA] (Function)
The reference current is given in the table for F20 to F22 on page 5-37.
According to the conversion result, the output voltage to terminal [FMA] can be
calculated as shown below.
I (A) Output gain (F30)
Analog output voltage (V) = 10 (V)
2 I ref (A) 100
Reference table
To output analog 10 V at 200% of the rated current of any of the single-phase 100 V
class series of inverters, set the output gain at terminal [FMA] (F30) as listed below.
Function (F31)
F31 specifies what is output to analog output terminal [FMA].
5-40
F43, F44 Current Limiter (Mode selection, Level)
(Example) Setting the current limiting level Ilimit at 4.2 A for 1 HP standard motors
4.2 (A)
Setting (%) = 100 84
5.0 (A)
The reference current is given in the table for F20 to F22 on page 5-37.
5-42
10% ED models
Continuous braking Intermittent braking
Braking resistor
Power (100% braking torque) (Period: 100 s or less)
Resistance
supply Inverter type Discharging Braking Allowable
( ) Duty
voltage Type Qty. capacity time average
(%ED)
(kWs) (s) loss (kW)
Single- FRN0003C2S-6U 250 37
phase DB0.75-2C 1 100 50 0.075
100 V FRN0005C2S-6U 133 20
5-43
Chapter 8 SPECIFICATIONS
8.1 Standard Models
8.1.4 Single-phase 100 V class series
Item Specifications
Type (FRN_ _ _ _C2S-6U) 0001 0002 0003 0005
Nominal applied motor (HP) *1 1/8 1/4 1/2 1
Rated capacity (kVA) *2 0.26 0.53 0.95 1.6
Output Ratings
(Note) When driven by 100 VAC, the single-phase 100 V class series of inverters limit their shaft output and
maximum output torque as listed below. This is to prevent their output voltage from decreasing when
load is applied.
8-3a
8.3 Terminal Specifications
8.3.2 Connection diagram in operation by external signal inputs
8-7
8.4 External Dimensions
8.4.1 Standard models
Unit: inch [mm]
Power Dimensions
supply Inverter type inch [mm]
voltage D D1 D2
FRN0001C2S-6U 3.94 0.39
Single- [100] 3.54 [10]
FRN0002C2S-6U
phase
100 V 4.53 [90] 0.98
FRN0003C2S-6U
[115] [25]
Power Dimensions
supply Inverter type inch [mm]
voltage D D1 D2
Single-
5.47 3.90 1.57
phase FRN0005C2S-6U
[139] [99] [40]
100 V
8-9
8.5 Protective Functions
LED Alarm
Name Description monitor output
displays [30A,B,C]
Overvoltage The inverter stops the inverter output upon During Yes
protection detecting an overvoltage condition (400 VDC for acceleration
three-phase 200 V, single-phase 200 V, and During
single -phase 100 V class series; 800 VDC for deceleration
three -phase 400 V class series) in the DC link
bus. During running
at constant
This protection is not assured if excess AC line speed
voltage is applied inadvertently. (Stopped)
Undervoltage Stops the inverter output when the DC link bus voltage drops below Yes
protection the undervoltage level (200 VDC for three-phase 200 V, (Note)
single-phase 200 V, and single-phase 100 V class series; 400 VDC
for three-phase 400 V class series).
However, if data "4 or 5" is selected for F14, no alarm is output even
if the DC link bus voltage drops.
(Note) No alarm output depending upon the data setting of the function code.
8-11
Chapter 9 LIST OF PERIPHERAL EQUIPMENT AND OPTIONS
Name of
peripheral Function and application
equipment
Molded case MCCBs are designed to protect the power circuits between the power control
circuit breaker board and inverter’s main terminals (L1/R, L2/S and L3/T for three-phase
(MCCB) power, L1/L and L2/N for single-phase power) from overload or short-circuit
Residual-current- which in turn prevents secondary disasters caused by the inverter
operated malfunctioning.
protective device RCDs/ELCBs function in the same way as MCCBs. Use the MCCBs and
(RCD) RCDs/ELCBs that satisfy the recommended rated current listed below.
/Earth leakage
circuit breaker Nominal Recommended rated current (A) of
Power
(ELCB)* applied MCCB and RCD/ELCB
Main peripheral equipment
Select the MCCB or RCD/ELCB with appropriate rated current and breaking
capacity according to the power supply capacity.
9-1
Chapter 10 APPLICATION OF DC REACTORS (DCRs)
Since the "Japanese Guideline for Suppressing Harmonics in Home and General-purpose
Appliances" issued by the Ministry of International Trade and Industry (Currently the Ministry of
Economy, Trade and Industry) was revised in January 2004, the general-purpose inverters have no
longer been subject to the guideline. Individual inverter manufacturers have voluntarily employed
harmonics suppression measures. It is recommended that DC reactors (DCRs) specified in Table
10.1 be connected to the FRENIC-Mini series of inverters.
P1 P(+)
P1 P(+)
L1/L U
M
V
3
L2/N W
Power
supply G
G Motor
FRENIC-Mini
10-1
Chapter 11 COMPLIANCE WITH STANDARDS
11.1 Compliance with UL Standards and Canadian Standards (cUL certification)
11.1.1 General
Originally, the UL standards were established by Underwriters Laboratories, Inc. as private criteria
for inspections/investigations pertaining to fire/accident insurance in the USA. Later, these standards
were authorized as the official standards to protect operators, service personnel and the general
populace from fires and other accidents in the USA.
cUL certification means that UL has given certification for products to clear CSA Standards. cUL
certified products are equivalent to those compliant with CSA Standards.
Integral solid state short circuit protection does not provide branch circuit protection. Branch
circuit protection must be provided in accordance with the National Electrical Code and any
additional local codes.
1. Solid state motor overload protection (motor protection by electronic thermal overload relay)
is provided in each model.
Adjust function codes F10 to F12 and H89 to set the protection level.
2. Connect the power supply satisfying the characteristics shown in the table below as an input
power supply of the inverter. (Short circuit rating)
3. Use 75 C Cu wire only.
4. Use Class 1 wire only for control circuits.
Power
Power supply max. voltage Power supply current
supply Inverter type
A (Volts) B (Amperes)
voltage
FRN0001C2S-6U
Single- FRN0002C2S-6U
phase 120 VAC 65,000 A or less
100V FRN0003C2S-6U
FRN0005C2S-6U
11-1
Conformity to UL standards and Canadian standards (cUL certification) (Continued)
5. Install UL certified fuses rated 600 Vac between the power supply and the inverter, referring to
the table below.
Class J fuse
Ib-in (N·m) AWG or kcmil (mm2)
current (A)
Power
Control circuit Control circuit
supply Inverter type *3
voltage Main *2 *2
*1 Main *1
terminal TERM2-1 TERM2-1
TERM1 terminal TERM1
TERM2-2 TERM2-2
FRN0001C2S-6U 6
Single- FRN0002C2S-6U 10.6 3.5 1.8 20 10
phase 14
(1.2) (0.4) (0.2) (0.5)
100 V FRN0003C2S-6U 15
FRN0005C2S-6U 30
*1 Denotes the relay contact terminals for [30A], [30B] and [30C].
*2 Denotes control terminals except for [30A], [30B] and [30C].
*3 Values in [ ] mean the size (AWG) of Grounding wires if exist.
6. To comply with CSA for 100 VAC input models, transient surge suppression shall be
installed on the line side of this equipment and shall be rated 120 V (phase to ground), 120 V
(phase to phase), suitable for overvoltage category 3, and shall provide protection for a rated
impulse withstand voltage peak of 2.5 kV.
7. Maximum surrounding air temperature rating of 50ºC.
11-2
Compact Inverter
Instruction Manual
Supplement to Single-phase 100 V Input Series
The purpose of this instruction manual is to provide accurate information in handling, setting up and
operating of the FRENIC-Mini series of inverters. Please feel free to send your comments regarding
any errors or omissions you may have found, or any suggestions you may have for generally
improving the manual.
In no event will Fuji Electric Co., Ltd. be liable for any direct or indirect damages resulting from the
application of the information in this manual.