Z1170 Engineered
Z1170 Engineered
Z1170 Engineered
PURPOSE
For nearly a hundred years, grease interceptors have been used in plumbing wastewater systems to permit free flow of drainage
from sinks and similar equipment. They have played an important role in preventing grease accumulations from clogging waste
pipes and sewer lines. They also help to improve operations at wastewater treatment facilities and prevent environmental problems
caused by grease.
INSTALLATION The flow control device must be properly vented to permit air
Installation Considerations to mix with the fluid entering the interceptor. Air facilitates
Install the interceptor as close as practical to the fixture(s) being separation and, more importantly, is necessary to maintain
served. The interceptor may be placed on the floor, partially the proper pressure, thus, the proper operating level within
recessed in the floor, recessed with top flush with the floor, the separation chamber.
or fully recessed below the floor, in order to accommodate Air intake for the flow control device may terminate under the
piping and structural conditions. sink drain board, as high as possible, to prevent overflow or
Anticipate sufficient clearance for removal of the interceptor terminate in a return bend at the same height outside of the
cover and baffle for cleaning. Also, take into consideration the building. When a fixture is individually trapped and back-vented,
possibility of pipelines becoming clogged with congealed air intake may intersect the vent stack. All installation recom-
grease that may collect before reaching the grease interceptor. mendations are subject to approval of code authority.
Do not install the grease interceptor in a waste line from Venting
a garbage grinder. Garbage grinder waste must bypass the Grease interceptors must have a vented waste, sized in
interceptor because rapid accumulation of solid matter will accordance with code requirements for venting traps,
greatly reduce the grease interceptor efficiency, preventing to retain a water seal and to prevent siphoning.
operation in compliance with its rated capacity. Solid material
Multiple Fixture Installation
should not be permitted to enter the grease interceptor. In an
application where solids are present, a solids interceptor One interceptor to serve multiple fixtures is recommended only
should be used. where fixtures are located close together. In such installations,
each fixture should be individually trapped and back-vented.
A separate grease interceptor is recommended for each
commercial dishwasher. The size of the interceptor is MAINTENANCE
determined by the discharge rate of the dishwasher as General Considerations
specified by the manufacturer. Design and installation are key factors to the operation of a
grease interceptor. However, without disciplined maintenance,
Placement of the interceptor in a high traffic area is an most performances are lost. For a manual interceptor to perform
important concern. If the interceptor is to be installed flush as designed, a strict maintenance schedule must be adhered
with the floor, it is necessary to determine whether or not the to. If adequate maintenance is not performed, excessive grease
interceptor will experience heavy-duty load traffic. The standard buildup will occur until water ladened with grease passes
grease interceptor is designed for foot and light traffic only. directly through the unit. Therefore, no matter how efficient
If a greater load rating is required, the interceptor must be the design or how proper the installation, grease interceptors
constructed accordingly to accept the higher load. perform only as well as the maintenance routine allows.
Caution: Z1171 installations using indirect piping to unit
could result in standing water in floor sink or flooding if Cleaning
line blockage occurs. All grease interceptors must be cleaned regularly. The frequency
of grease removal is dependent upon the capacity of the inter-
Flow Control ceptor and the quantity of grease in the wastewater. Grease
The use of a flow control device (Z1108), furnished with all removal intervals may therefore vary from once a week to once
grease interceptors, is an important factor in the operation of in several weeks. When the grease removal interval has been
the interceptor. The flow control device should be installed in determined for a specific installation, regular cleaning at that
the waste line upstream of the grease interceptor. It should be interval is necessary to maintain the rated efficiency of the
placed beyond the last connection from the fixture(s) and as interceptor. After the accumulated grease and waste material
close as possible to the underside of the lowest fixture. When has been removed, the interceptor should be thoroughly checked
two or more sinks or fixtures are combined and served by one to make certain the inlet, outlet, and air relief ports are clear
interceptor, a single flow control fitting can be used. of obstructions.
MAINTENANCE, continued
Cleaning can easily be performed by following the steps listed 6. Remove the clean-out plug on the outlet portion of the body.
below: Using a clean water supply, hose down and wipe the inside
1. Loosen and remove the fastener(s) securing the cover to of the body.
the interceptor body. 7. Replace the cleaned baffle assembly back into the unit.
2. Remove the cover. 8. Ensure that the cover gasket material is intact and in good
3. Remove the flow diffusing baffle and/or sediment tray working condition. Replace gasket material if it is damaged.
assembly from the body. 9. Securely refasten the cover and the clean-out plug back
4. Wipe down the baffle assembly, disposing of grease in a onto the trap.
proper waste container.
5. Clean out any liquid grease by skimming it from the top
surface. Remove any remaining solid material with a spade
or shovel.
Page 2
GENERAL PRODUCT INFORMATION, continued Trap Flow Rate Standard Size
Size/GPM Orifice/Inches
Need for a Flow Control Device 4 5/8
A grease interceptor, correctly designed to separate light density substances from 7 5/8
wastewater, will not by itself govern or regulate the flow of water through the inter- 10 15/16
ceptor at all times to sufficiently assure the “flotation” separation of the substances 15 15/16
20 1-1/4
which are to be intercepted at maximum efficiency. 25 1-1/4
35 1-1/2
The flow control fitting is designed with an integral orifice to give a predetermined 50 1-3/4
optimum flow rate, thus eliminating turbulence in the interceptor, which could 75 2-1/4
otherwise occur from sudden surges in the drainage line. 100 2-1/4
125 2-5/8
The orifice openings are related to the size and flow rating of the grease interceptor. 150 2-5/8
Standard orifice sizing is for gravity flow conditions where no pressure buildup is 200 3-1/4
considered. If an interceptor is operating at maximum flow levels, a head may 250 3-1/4
develop, in which case overload conditions may still exist. 300 4
400 4-1/2
450 4-7/8
500 4-7/8