Notes:-: Structural Consultants

This document provides specifications for concrete mix design and reinforcement detailing for column and foundation construction. It specifies a M25 concrete mix with a minimum cement content of 300 kg/cum. Reinforcement bars are to be thermo-mechanically twisted bars of grade 500D. Lap splices are only permitted in the central half of members and not more than 50% of bars can be spliced at one section. Hoops/stirrups must be provided over the entire splice length at a maximum spacing of 150mm. Hooks for ties/stirrups should be 13.5 times the bar diameter. IS 456-2000 and IS 13920 must be referred to for reinforcement detailing and ductility requirements.

Uploaded by

Harbhajan Singh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
169 views1 page

Notes:-: Structural Consultants

This document provides specifications for concrete mix design and reinforcement detailing for column and foundation construction. It specifies a M25 concrete mix with a minimum cement content of 300 kg/cum. Reinforcement bars are to be thermo-mechanically twisted bars of grade 500D. Lap splices are only permitted in the central half of members and not more than 50% of bars can be spliced at one section. Hoops/stirrups must be provided over the entire splice length at a maximum spacing of 150mm. Hooks for ties/stirrups should be 13.5 times the bar diameter. IS 456-2000 and IS 13920 must be referred to for reinforcement detailing and ductility requirements.

Uploaded by

Harbhajan Singh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

REGD.No.

1173
NOTES:-
TP TECH PECIFIC
STRUCTURAL CONSULTANTS
1. ALL DIMENSIONS ARE IN mm, UNLESS OTHERWISE SPECIFIED.
JOINT Morth No:-RW/NH-34054/1/2014-S&R(B)
2. M25 CONCRETE MIX FOR ALL. Category=II(17)
ROOF LVL. 3. THE ENGINEER-IN-CHARGE MAY GET THE CONCRETE MIX Office: Plot No.-307, Sector-79, Mohali
Mob. No.- +91-8968012763
DESIGNED BUT CEMENT CONTENT SHOULD NOT BE LESS
THAN E-mail: [email protected]
300 Kg/Cum FOR M25 MIX.
4. P.C.C UNDER FOOTING IS 1:4:8 .
5. MINIMUM CLEAR COVER TO THE REINFORCEMENT IS TO BE
PROVIDED AS FOLLOWS:
FOUNDATION 50mm NOTE-
COLUMNS 40mm A.S.P- AS PER SITE
BEAMS 25mm N.F.L- NORMAL FLOOR
SLAB 20mm LEVEL
P.L -PLINTH LEVEL
6. REINFORCEMENT BARS TO BE USED SHALL BE TMT BARS
(THERMO MECHANICALLY TWISTED BARS) OF GRADE 500D

CONFORMING TO IS 1786 .
DETAILS AS PER 7. IS 456-2000 , IS 13920 SHALL BE REFERRED FOR DETAILING OF
DUCTILE DETAILS REINFORCEMENT AND TO MEET DUCTILITY REQUIREMENTS.
8 (a) LAP SPLICES TO BE PROVIDED ONLY IN THE
CENTRAL HALF OF THE MEMBER LENGTH AND
NOT MORE 50% OF THE BARS SHALL BE SPLICED
all over lap in

AT ONE SECTION.
middle half

(b) HOOPS/STIRRUPS SHALL BE PROVIDED OVER THE


ENTIRE SPLICE LENGTH AT THE SPACING NOT
EXCEEDING 150mm. a
H

9. HOOKS FOR TIES/STIRRUPS = 13.5D

COLUMN

N.F.L
600
SECTION A-A

COLUMN DETAIL
COL DIA OF COL. LENGTH OF
150 150 NO. (D) COLUMN (L) CLIENT-
P1 600 mm 11 m
150
2000

PEDESTAL
REINFORCEMENT
SCHEDULE PROJECT-
BAR
D

DESCRIPTION SHAPE
Ld Ld NO.
536

b DRAWING TITLE-
100

P.C.C 1:4:8

100 LxB 100 DRAWING NO-


ASB D
FOUNDATION LXB Ast
DUCTILE DETAILING OF 3000 x 3000 650 SHEET NO. REVISION-
COLUMN & FOUNDATION AS PER IS13920 R0