Main Protection: Parameter CT F1 CT M1

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 11

Main Protection

Jenis relai : DISTANCE RELAY


Merek/Tipe relai : GE Multilin T60
LOKASI : GI Manggar Sari
PROTEKSI : Bay Trafo 1

 System Setup

Current
PARAMETER CT F1 CT M1
Phase CT Primary 100 A 1000 A
Phase CT Secondary 5A 5A
Ground CT Primary 1A 1A
Ground CT Secondary 1A 1A
Voltage
PARAMETER VT F5 VT M5
Phase VT Primary Wye Wye
Phase VT Secondary 57.7 V 57.7 V
Phase VT Ratio 1500: 1 200:1
Auxiliary VT Connection Vbg Vbg
Auxiliary VT Secondary 57.7 V 57.7 V
Auxiliary VT Ratio 1500:1 200:1

 Transformer

Windings
PARAMETER Winding 1 Winding 2
Source 150 kV (SRC 1) 20 kV (SRC 2)
Rated MVA 20 MVA 20 MVA
Connection Wye Wye
Grounding Within zone Within zone
Angle Wrt Winding 1 0 deg 0 deg
Resistance 10 Ω 10 Ω

Distance
SETTING PARAMETER
Source 150 kV (SRC 1)
Memory Duration 10 cycles
Force Self-Polar OFF
Force Mem-Polar OFF

1/2 Daftar Evaluasi Setelan Rele Proteksi Dibuat : RWH Diperiksa : AW Disetujui : DP
Rev. 00 GI 150 KV Sambutan Tgl : Tgl: Tgl:
RUANG LINGKUP SERTIFIKASI ISO 9001:2000
UP3B SISTEM KALTIM
Phase Distance
PARAMETER Phase Distance Z1 Phase Distance Z2 Phase Distance Z3
Function Disabled Disabled Disabled
Direction Forward Forward Forward
Shape Mho Mho Mho
X fmr Vol Connection None None None
X fmr Current None None None
Connection
Reach 2Ω 2Ω 2Ω
RCA 85 deg 85 deg 85 deg
Rev Reach 2Ω 2Ω 2Ω
Rev Reach RCA 85 deg 85 deg 85 deg
Comp Limit 90 deg 90 deg 90 deg
DIR RCA 85 deg 85 deg 85 deg
DIR Comp Limit 90 deg 90 deg 90 deg
Quad Right Blinder 10 Ω 10 Ω 10 Ω
Quad Right Blinder RCA 85 deg 85 deg 85 deg
Quad Left Blinder 10 Ω 10 Ω 10 Ω
Quad Left Blinder RCA 85 deg 85 deg 85 deg
Supervision 0.2 pu 0.2 pu 0.2 pu
Volt Level 0 pu 0 pu 0 pu
Delay 0.15 s 0.15 s 0.15 s
Block OFF OFF OFF
Target Self-Reset Self-Reset Self-Reset
Event Disabled Disabled Disabled

Ground Distance
PARAMETER GROUND GROUND GROUND
DISTANCE Z1 DISTANCE Z2 DISTANCE Z3
Function Disabled Disabled Disabled
Direction Forward Forward Forward
Shape Mho Mho Mho
Z0/Z1 Mag 2.7 2.7 2.7
Z0/Z1 Ang 0 deg 0 deg 0 deg
ZOM/Z1 Mag 0 0 0
Z0M/Z1 Ang 0 deg 0 deg 0 deg
Reach 2 ohms 2 ohms 2 ohms
RCA 85 deg 85 deg 85 deg
Rev Reach 2 ohms 2 ohms 2 ohms
Rev Reach RCA 85 deg 85 deg 85 deg
POL Current Zero-seq Zero-seq Zero-seq
Non-Homogen ANg 0 deg 0 deg 0 deg
Comp Limit 90 deg 90 deg 90 deg
DIR RCA 85 deg 85 deg 85 deg
DIR Comp Limit 90 deg 90 deg 90 deg
Quad Right Blinder 10 ohms 10 ohms 10 oh,s
Quad Right Blinder 85 deg 85 deg 85 deg
2/2 Daftar Evaluasi Setelan Rele Proteksi Dibuat : RWH Diperiksa : AW Disetujui : DP
Rev. 00 GI 150 KV Sambutan Tgl : Tgl: Tgl:
RUANG LINGKUP SERTIFIKASI ISO 9001:2000
UP3B SISTEM KALTIM
RCA
Quad Left Blinder 10 ohms 10 ohms 10 ohms
Quad Left Blinder 85 deg 85 deg 85 deg
RCA
Supervision 0.2 pu 0.2 pu 0.2 pu
Volt Level 0 pu 0 pu 0 pu
Delay 0.15 s 0.15 s 0.15 s
Block OFF OFF OFF
Target Self-Reset Self-Reset Self-Reset
Events Disabled Disabled Disabled

Power Swing Detect

SETTING PARAMETER
Function Disabled
Source 150 kV (SRC 1)
Shape Mho Shape
Mode Two Step
Supv 0.6 pu
Fwd Reach 50 ohms
Quad Fwd Mid 60 ohms
Quad Fwd Out 70 ohms
Fwd RCA 75 deg
Rev RCA 50 ohms
Quad Rev Mid 60 ohms
Quad Rev Out 70 ohms
Rev RCA 75 deg
Outer Limit Angle 120 deg
Middle Limit Angle 90 deg
Inner Limit Angle 60 deg
Outer Rgt Bld 100 ohms
Outer Lft Bld 100 ohms
Middle Rgt Bld 100 ohms
Middle Lft Bld 100 ohms
Inner Rgt Bld 100 ohms
Inner Lft Bld 100 ohms
Delay 1 Pickup 0.03 s
Delay 1 Rest 0.05 s
Delay 2 Pickup 0.017 s
Delay 3 Pickup 0.009 s
Delay 4 Pickup 0.0 s
Seal-In Delay 0.4 s
Trip Mode Delayed
Block OFF
Target Self-Reset
Event Disabled

Load Encroachment
3/2 Daftar Evaluasi Setelan Rele Proteksi Dibuat : RWH Diperiksa : AW Disetujui : DP
Rev. 00 GI 150 KV Sambutan Tgl : Tgl: Tgl:
RUANG LINGKUP SERTIFIKASI ISO 9001:2000
UP3B SISTEM KALTIM
Setting Parameter
Function Disabled
Source 150 kV (SRC 1)
Min Volt 0.25 pu
Reach 1Ω
Angle 30 deg
Pickup delay 0s
Reset Delay 0s
Block Off
Target Self-Reset
Event Disabled

 Transformer

Percent Differential
Setting Parameter
Function Enabled
Pickup 0.3 pu
Slope 1 30 %
Break 1 1 pu
Break 2 8 pu
Slope 2 80 %
Inrush Inhibit Fuction Adapt 2nd
Inrush Inhibit Mode Per Phase
Inrush Inhibit Level 20 %
Overexcitation Inhibit Function Disabled
Overexcitation Inhibit Leve 10%
Block OFF
Target Latched
Event Enabled
Instantaneous Differential
Setting Parameter
Function Enabled
Pickup 0.3 pu
Slope 1 30 %
Break 1 1 pu
Break 2 8 pu
Slope 2 80 %
Inrush Inhibit Fuction Adapt 2nd
Inrush Inhibit Mode Per Phase
Inrush Inhibit Level 20 %
Overexcitation Inhibit Function Disabled
Overexcitation Inhibit Leve 10%
Block OFF
Target Latched
Event Enabled
Hottest Spot

4/2 Daftar Evaluasi Setelan Rele Proteksi Dibuat : RWH Diperiksa : AW Disetujui : DP
Rev. 00 GI 150 KV Sambutan Tgl : Tgl: Tgl:
RUANG LINGKUP SERTIFIKASI ISO 9001:2000
UP3B SISTEM KALTIM
Setting Paramater
Function Disabled
Pickup 140o C
Delay 1 min
Block OFF
Target Self-reset
Events Disabled
Aging Factor
Setting Paramater
Function Disabled
Pickup 2 PU
Delay 10 min
Block OFF
Target Self-reset
Events Disabled
Loss of Life
Setting Paramater
Function Disabled
Pickup 0 hrs
Delay 180000
Block OFF
Target Self-reset
Events Disabled

 Phase Current

Phase TOC
PARAMETER PHASE TOC1 PHASE TOC2 PHASE TOC3 PHASE TOC4
Function Enabled Disabled Disabled Disabled
Signal Source 150 kV (SRC 1) 150 kV (SRC 1) 150 kV (SRC 1) 150 kV (SRC 1)
Input Phasor Phasor Phasor Phasor
Pickup 0.9 pu 1 pu 1 pu 1 pu
Curve Definite Time IEEE Mod Inv. IEEE Mod Inv. IEEE Mod Inv.
TD Multiplier 1.5 1 1 1
Reset Instantaneous Instantaneous Instantaneous Instantaneous
Voltage Restraint Disabled Disabled Disabled Disabled
Block A OFF OFF OFF OFF
Block B OFF OFF OFF OFF
Block C OFF OFF OFF OFF
Target Latched Self-Reset Self-Reset Self-Reset
Events Enabled Disabled Disabled Disabled

Phase IOC
5/2 Daftar Evaluasi Setelan Rele Proteksi Dibuat : RWH Diperiksa : AW Disetujui : DP
Rev. 00 GI 150 KV Sambutan Tgl : Tgl: Tgl:
RUANG LINGKUP SERTIFIKASI ISO 9001:2000
UP3B SISTEM KALTIM
PARAMETER PHASE TOC1 PHASE TOC2 PHASE TOC3 PHASE TOC4
Function Enabled Disabled Disabled Disabled
Source 150 kV (SRC 1) 150 kV (SRC 1) 150 kV (SRC 1) 150 kV (SRC 1)
Pickup 1 pu 1 pu 1 pu 1 pu
Delay 0s 0s 0s 0s
Reset Delay 0s 0s 0s 0s
Block A OFF OFF OFF OFF
Block B OFF OFF OFF OFF
Block C OFF OFF OFF OFF
Target Latched Self-Reset Self-Reset Self-Reset
Events Enabled Disabled Disabled Disabled

Phase Directional
Parameter Phase DIR1
Function Disabled
Source 150 kV (SRC 1)
Block OFF
ECA 30 deg
Pol V Threshold 0.7 pu
Block when V Mem No
Exp
Target Self-Reset
Events Disabled

 Neutral Current

Neutral TOC
Parameter Neutral TOC 1 Neutral TOC 2 Neutral TOC 3 Neutral TOC 4
Function Disabled Disabled Disabled Disabled
Source 150 kV (SRC 1) 150 kV (SRC 1) 150 kV (SRC 1) 150 kV (SRC 1)
Input Phasor Phasor Phasor Phasor
Pickup 1 pu 1 pu 1 pu 1 pu
Curve IEEE Mod Inv IEEE Mod Inv IEEE Mod Inv IEEE Mod Inv
TD Multiplier 1 1 1 1
Reset Instantaneous Instantaneous Instantaneous Instantaneous
Block OFF OFF OFF OFF
Targer Self-Reset Self-Reset Self-Reset Self-Reset
Events Disabled Disabled Disabled Disabled

6/2 Daftar Evaluasi Setelan Rele Proteksi Dibuat : RWH Diperiksa : AW Disetujui : DP
Rev. 00 GI 150 KV Sambutan Tgl : Tgl: Tgl:
RUANG LINGKUP SERTIFIKASI ISO 9001:2000
UP3B SISTEM KALTIM
Neutral IOC
Parameter Neutral TOC 1 Neutral TOC 2 Neutral TOC 3 Neutral TOC 4
Function Disabled Disabled Disabled Disabled
Source 150 kV (SRC 1) 150 kV (SRC 1) 150 kV (SRC 1) 150 kV (SRC 1)
Input Phasor Phasor Phasor Phasor
Pickup 1 pu 1 pu 1 pu 1 pu
Delay 0s 0s 0s 0s
Reset Delay 0s 0s 0s 0s
Block OFF OFF OFF OFF
Targer Self-Reset Self-Reset Self-Reset Self-Reset
Events Disabled Disabled Disabled Disabled
Neutral Directional OC
Parameter Neutral TOC 1
Function Disabled
Source 150 kV (SRC 1)
Polarizing Voltage
Polarizing Volt Calculated V0
Op Current Calculated 3I0
POS SEQ 0.063
Restrain
Offset 0Ω
Forward ECA 75o lag
Forward Limit 90 deg
Angle
Forward Pickup 0.05 pu
Reverse Limit 90 deg
Angle
Reverse Pickup 0.05 pu
Block OFF
Target Self-Reset
Events Disable

 Ground Current

7/2 Daftar Evaluasi Setelan Rele Proteksi Dibuat : RWH Diperiksa : AW Disetujui : DP
Rev. 00 GI 150 KV Sambutan Tgl : Tgl: Tgl:
RUANG LINGKUP SERTIFIKASI ISO 9001:2000
UP3B SISTEM KALTIM
Ground TOC
Parameter Ground TOC1 Ground TOC2 Ground TOC3 Ground TOC4
Function Disabled Disabled Disabled Disabled
Source 150 kV (SRC 1) 150 kV (SRC 1) 150 kV (SRC 1) 150 kV (SRC 1)
Input Phasor Phasor Phasor Phasor
Pickup 1 pu 1 pu 1 pu 1 pu
Curve IEEE Mod Inv. IEEE Mod Inv. IEEE Mod Inv. IEEE Mod Inv.
TD Multiplier 1 1 1 1
Reset Instantaneous Instantaneous Instantaneous Instantaneous
Block OFF OFF OFF OFF
Target Self-Reset Self-Reset Self-Reset Self-Reset
Events Disabled Disabled Disabled Disabled

Ground IOC

PARAMETER Ground IOC1 Ground IOC2 Ground IOC3 Ground IOC4


Function Enabled Disabled Disabled Disabled
Source 150 kV (SRC 1) 150 kV (SRC 1) 150 kV (SRC 1) 150 kV (SRC 1)
Pickup 1 pu 1 pu 1 pu 1 pu
Delay 0s 0s 0s 0s
Reset Delay 0s 0s 0s 0s
Block A OFF OFF OFF OFF
Target Latched Self-Reset Self-Reset Self-Reset
Events Enabled Disabled Disabled Disabled

Restricted Ground Fault

PARAMETER RGF 1 RGF 2


Function Enabled Disabled
Source 150 kV (SRC 1) 150 kV (SRC 1)
Pickup 0 pu 0 pu
Slope 40 % 40 %
Pickup Delay 0s 0s
Reset Delay 0s 0s
Block OFF OFF
Target Latched Self-Reset
Events Enabled Disabled

 Voltage Elements

8/2 Daftar Evaluasi Setelan Rele Proteksi Dibuat : RWH Diperiksa : AW Disetujui : DP
Rev. 00 GI 150 KV Sambutan Tgl : Tgl: Tgl:
RUANG LINGKUP SERTIFIKASI ISO 9001:2000
UP3B SISTEM KALTIM
Phase UV
PARAMETER PHASE UV1 PHASE UV2 PHASE UV3
Function Enabled Disabled Disabled
Signal Source 150 kV (SRC 1) 150 kV (SRC 1) 150 kV (SRC 1)
Mode Phase to Ground Phase to Ground Phase to Ground
Pickup 0.9 pu 1 pu 1 pu
Curve Definite Time Definite Time Definite Time
Delay 1s 1s 1s
Minimum 0.1 pu 0.1 pu 0.1 pu
Voltage
Voltage Restraint Disabled Disabled Disabled
Block OFF OFF OFF
Target Latched Self-Reset Self-Reset
Events Disabled Disabled Disabled

Phase OV

PARAMETER Phase OV1


Function Disabled
Source 150 kV (SRC 1)
Pickup 1 pu
Delay 1s
Reset Delay 1s
Block A OFF
Target Self-Reset
Events Disabled

Neutral OV
PARAMETER PHASE UV1 PHASE UV2 PHASE UV3
Function Disabled Disabled Disabled
Source 150 kV (SRC 1) 150 kV (SRC 1) 150 kV (SRC 1)
Pickup 0.3 pu 0.3 pu 0.3 pu
Curve Definite Time Definite Time Definite Time
Pickup Delay 1s 1s 1s
Reset Delay 1s 1s 1s
Block OFF OFF OFF
Target Self-Reset Self-Reset Self-Reset
Events Disabled Disabled Disabled

Auxilary UV
Parameter Auxilary UV 1 Auxilary UV 2
9/2 Daftar Evaluasi Setelan Rele Proteksi Dibuat : RWH Diperiksa : AW Disetujui : DP
Rev. 00 GI 150 KV Sambutan Tgl : Tgl: Tgl:
RUANG LINGKUP SERTIFIKASI ISO 9001:2000
UP3B SISTEM KALTIM
Function Disabled Disabled
Source 150 kV (SRC 1) 150 kV (SRC 1)
Pickup 0.7 pu 0.7 pu
Curve Definite Time Definite Time
Delay 1s 1s
Minimum 0.1 pu 0.1 pu
Voltage
Block OFF OFF
Targer Self-Reset Self-Reset
Events Disabled Disabled
Auxilary OV
Parameter Auxilary OV 1 Auxilary OV 2
Function Disabled Disabled
Source 150 kV (SRC 1) 150 kV (SRC 1)
Pickup 0.3 pu 0.3 pu
Pickup Delay 1s 1s
Reset Delay 1s 1s
Block OFF OFF
Targer Self-Reset Self-Reset
Events Disabled Disabled

Volts Per Hertz


Parameter Auxilary OV 1 Auxilary OV 2
Function Disabled Disabled
Source 150 kV (SRC 1) 150 kV (SRC 1)
VHZ Voltage Phase to Ground Phase to Ground
Mode
Pickup 0.8 pu 0.8 pu
Curve Definite Time Definite Time
TD Multiplier 1 1
T Reset 1s 1s
Block OFF OFF
Targer Self-Reset Self-Reset
Events Disabled Disabled

Back-Up Protection Protection

10/2 Daftar Evaluasi Setelan Rele Proteksi Dibuat : RWH Diperiksa : AW Disetujui : DP
Rev. 00 GI 150 KV Sambutan Tgl : Tgl: Tgl:
RUANG LINGKUP SERTIFIKASI ISO 9001:2000
UP3B SISTEM KALTIM
Jenis relai : DISTANCE RELAY
(Overcurrent & Earth Fault)
Merek/Tipe relai : Areva /MICOM P442
LOKASI : Sambutan
PROTEKSI : Line Muara Badak

GROUP 1 BACK UP I>

ROW MENU TEXT VALUES


35.01 I>1 Function IEC S Inverse
35.02 I>1 Directional Non Directional
35.04 I>1 Current Set 2.5 A
35.07 I>1 TMS 0.25
35.0A I>1 tReset 0s
35.0B I>2 Function Disabled
35.15 I>3 Status Disabled
35.18 I>4 Status Disabled

GROUP 1 EARTH FAULT

ROW MENU TEXT VALUES


35.01 IN>1 Function IEC S Inverse
35.02 IN>1 Directional Non Directional
35.04 IN>1 Current Set 1A
35.07 IN>1 TMS 0.45
35.0A IN>1 tReset 0s
35.0B IN>2 Function Disabled
35.15 IN>3 Status Disabled
35.18 IN>4 Status Disabled

11/2 Daftar Evaluasi Setelan Rele Proteksi Dibuat : RWH Diperiksa : AW Disetujui : DP
Rev. 00 GI 150 KV Sambutan Tgl : Tgl: Tgl:
RUANG LINGKUP SERTIFIKASI ISO 9001:2000
UP3B SISTEM KALTIM

You might also like