DESIGN BASIS REPORT FOR SIZING OF RCC COOLING TOWER
SL.NO DESCRIPTION UNITS PARAMETERS Remarks
A DESIGN DATA
1 Type of cooling tower tph Induced Draft, Counter Flow
2 Wet Bulb Temperature (design) °C 28.5
3 Inlet temperature of Cooling tower °C 42
4 Outlet temperature of cooling tower °C 32
5 Design Approach temperature °C 3.5
B CAPACITY OF COOLING TOWER
1 Condenser for one unit m3/hr 2000 Assumed
2 Oil cooler for one unit m3/hr 90 Assumed
3 Alternator for one unit m3/hr 70 Assumed
4 Sample coolers (SWAS) for 3 boilers m3/hr 50 Assumed
5 Boiler feed water pumps (2nos) m3/hr 4 Assumed
6 Ash handling system for 3 boilers m3/hr 60 Assumed
7 Flow required m3/hr 2274
8 Margin % 5
9 Total flow m3/hr 2387.70
10 Say m3/hr 2400
11 No. of cells nos 3
12 Flow per cell m3/hr 800
C MATERIAL OF CONSTRUCTION
1 Cold water basin RCC
2 Frame work / Members / Supporting structure RCC
3 Fills PVC (splash bar)
4 Louvers RCC
5 Sprayers Poly propylene
6 Drift eliminators PVC (Wave type)
7 Drain valves CI
8 Hot water pipe MS Epoxy coated / RCC
9 Fan deck RCC
SL.NO DESCRIPTION UNITS PARAMETERS Remarks
10 Fan stack GRP / FRP
11 Fan blades FRP
12 Fan hub MS Galvanised
13 Fan hub cover FRP
14 Drive shaft SS304
15 Staircase / Cage ladder HDG steel
16 Structural connectors / Fasteners / Washers / Anchor bolts HDG steel
17 Sluice gate CI
18 Pre & post Screen HDG frame with SS304 mesh