A. DBR For Cooling Tower, Rev.0

This document provides design details for sizing a counter-flow induced draft cooling tower. It specifies key parameters like the wet bulb temperature of 28.5°C, an inlet temperature of 42°C and outlet of 32°C, with a design approach of 3.5°C. The total required cooling capacity is calculated to be 2400 cubic meters per hour based on the needs of the condenser, oil cooler, alternator and other auxiliary equipment. The cooling tower will have 3 cells of 800 cubic meters per hour capacity each. Materials of construction include reinforced concrete, PVC, polypropylene, galvanized steel and others.

Uploaded by

SumitBhaumik
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
544 views2 pages

A. DBR For Cooling Tower, Rev.0

This document provides design details for sizing a counter-flow induced draft cooling tower. It specifies key parameters like the wet bulb temperature of 28.5°C, an inlet temperature of 42°C and outlet of 32°C, with a design approach of 3.5°C. The total required cooling capacity is calculated to be 2400 cubic meters per hour based on the needs of the condenser, oil cooler, alternator and other auxiliary equipment. The cooling tower will have 3 cells of 800 cubic meters per hour capacity each. Materials of construction include reinforced concrete, PVC, polypropylene, galvanized steel and others.

Uploaded by

SumitBhaumik
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

DESIGN BASIS REPORT FOR SIZING OF RCC COOLING TOWER

SL.NO DESCRIPTION UNITS PARAMETERS Remarks

A DESIGN DATA

1 Type of cooling tower tph Induced Draft, Counter Flow

2 Wet Bulb Temperature (design) °C 28.5

3 Inlet temperature of Cooling tower °C 42

4 Outlet temperature of cooling tower °C 32

5 Design Approach temperature °C 3.5

B CAPACITY OF COOLING TOWER

1 Condenser for one unit m3/hr 2000 Assumed

2 Oil cooler for one unit m3/hr 90 Assumed

3 Alternator for one unit m3/hr 70 Assumed

4 Sample coolers (SWAS) for 3 boilers m3/hr 50 Assumed

5 Boiler feed water pumps (2nos) m3/hr 4 Assumed

6 Ash handling system for 3 boilers m3/hr 60 Assumed

7 Flow required m3/hr 2274

8 Margin % 5

9 Total flow m3/hr 2387.70

10 Say m3/hr 2400

11 No. of cells nos 3

12 Flow per cell m3/hr 800

C MATERIAL OF CONSTRUCTION

1 Cold water basin RCC

2 Frame work / Members / Supporting structure RCC

3 Fills PVC (splash bar)

4 Louvers RCC

5 Sprayers Poly propylene

6 Drift eliminators PVC (Wave type)

7 Drain valves CI

8 Hot water pipe MS Epoxy coated / RCC

9 Fan deck RCC

SL.NO DESCRIPTION UNITS PARAMETERS Remarks

10 Fan stack GRP / FRP


11 Fan blades FRP

12 Fan hub MS Galvanised

13 Fan hub cover FRP

14 Drive shaft SS304

15 Staircase / Cage ladder HDG steel

16 Structural connectors / Fasteners / Washers / Anchor bolts HDG steel

17 Sluice gate CI

18 Pre & post Screen HDG frame with SS304 mesh