Concrete Column Design Based On ACI 318-14: Input Data & Design Summary

This document summarizes the design of a concrete column based on ACI 318-14 standards. It provides input data such as a concrete strength of 6 ksi and rebar yield stress of 60 ksi. It then details the factored axial and moment loads on the column. The column design is shown to have adequate strength for all factored load combinations based on checks of its flexural and axial capacity as well as shear capacity. Reinforcement requirements are also shown to satisfy code standards.

Uploaded by

gambito escobar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
254 views

Concrete Column Design Based On ACI 318-14: Input Data & Design Summary

This document summarizes the design of a concrete column based on ACI 318-14 standards. It provides input data such as a concrete strength of 6 ksi and rebar yield stress of 60 ksi. It then details the factored axial and moment loads on the column. The column design is shown to have adequate strength for all factored load combinations based on checks of its flexural and axial capacity as well as shear capacity. Reinforcement requirements are also shown to satisfy code standards.

Uploaded by

gambito escobar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 3

PROJECT : PAGE :

CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Concrete Column Design Based on ACI 318-14

INPUT DATA & DESIGN SUMMARY


CONCRETE STRENGTH f c' = 6 ksi, (41 MPa)
REBAR YIELD STRESS fy = 60 ksi, (414 MPa)
SECTION SIZE Cx = 40 in, (1016 mm)
Cy = 36 in, (914 mm)

FACTORED AXIAL LOAD Pu = 1700 kips, (7562 kN)


FACTORED MAGNIFIED MOMENT Mu,x = 1800 ft-kips, (2440 kN-m)
Mu,y = 100 ft-kips, (136 kN-m)
FACTORED SHEAR LOAD Vu,x = 130 kips, (578 kN) THE COLUMN DESIGN IS ADEQUATE.
Vu,y = 150 kips, (667 kN)
COLUMN VERT. REINFORCEMENT 8 # 8 at x dir.
(Total 22 # 8)
3 # 8 at y dir.
LATERAL REINF. OPTION (0=Spirals, 1=Ties) 1 Ties
LATERAL REINFORCEMENT 4 legs,# 4 @ 12 in. (305 mm), o.c., at x dir.
3 legs,# 4 @ 12 in. (305 mm), o.c., at y dir.

ANALYSIS
5000
4500
4000

3500
3000

f Pn (k) 2500
2000

1500
1000
500
0
0 500 1000 1500 2000 2500 3000 3500

f Mn (ft-k)

f Pn (k) f Mn (ft-k) 
2 0.85 f C
'
 '
AT AXIAL LOAD ONLY 4315 0
 o   max or , E c  57 f C , E s  29000ksi
Ec
AT MAXIMUM LOAD 4315 1196
AT 0 % TENSION 3724 1744
       2
 c  c  , for 0 
0.85 f C  2 
'
AT 25 % TENSION 3149 2121    c o
AT 50 % TENSION 2700 2305
fC    o    o  
 '
AT e t = 0.002 2064 2433 0.85 f C , for  c   o

AT BALANCED CONDITION 2043 2457
 s E s , for  s   t

AT e = 0.005 fS
t 1517 2917
 f , for  s   t
AT FLEXURE ONLY 0 1273
 y

CHECK FLEXURAL & AXIAL CAPACITY


f Pmax =F f [ 0.85 fc' (Ag - Ast) + fy Ast] = 4315 kips., (at max axial load, ACI 318-14 22.4)
where f = 0.65 (ACI 318-14 21.2) > Pu [Satisfactory]
F = 0.8 Ag = 1440 in2 Ast = 17.38 in2
0.75 + ( et - 0.002 ) (50), for Spiral
f= = 0.656 (ACI 318-14 21.2)
0.65 + ( et - 0.002 ) (250 / 3), for Ties

where Cb = d ec / (ec + es) = 22.2 in et = 0.0021 ec = 0.003


d = 37.5 in, (ACI 20.6) D = 40.0 in Cover = 1.5 in, (ACI 318 20.6.1)
f Mn = 2757 ft-kips @ Pu = 1700 kips > Mu = 1803 ft-kips [Satisfactory]
r max = 0.08 (ACI 318-14 10.6) rprovd = 0.012
rmin = 0.01 (ACI 318-14 10.6) [Satisfactory]

CHECK SHEAR CAPACITY (ACI 318-14 10 & 22.5)


f Vn = f (Vs + Vc) (ACI 318-11 22.5)
> Vu [Satisfactory]
where f = 0.75 (ACI 318-11 21.2) fy = 60 ksi
d A0 Av Vc = 2 (fc')0.5A0 Vs = MIN (d fy Av / s , 4Vc) f Vn
x 37.5 1240 0.80 192.1 150.0 257
y 33.5 1240 0.60 192.1 100.5 219

smax = 16 (ACI 318-14 25.7) sprovd = 12 in


smin = 1 [Satisfactory]
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Magnified Moment Calculation for Concrete Column Based on ACI 318-14

INPUT DATA & DESIGN SUMMARY


EFFECTIVE LENGTH FACTOR k = 1.6 , (ACI 6.2.5)
COLUMN UNSUPPORTED LENGTH Lu = 12 ft
LARGER FACTORED MOMENT M2 = 200 ft-k
SMALLER FACTORED END MOMENT M1 = 100 ft-k, (positive if single curvature.)
CONCRETE STRENGTH fc' = 4 ksi
COLUMN DIMENSIONS h = 20 in
b = 20 in
FACTORED AXIAL LOAD Pu = 400 k
SUMMATION FOR ALL VERTICAL LOADS IN THE STORY S Pu = 1200 k
SUMMATION FOR ALL CRITICAL LOADS IN THE STORY S Pc = 13600 k, (ACI 6.6.4)

THE MAGNIFIED MOMENT: Mu = 236.7 ft-k , Sway

ANALYSIS
MAGNIFIED MOMENT - NONSWAY
r = 0.3 h = 6.0 in, ACI 6.2.5.1
k Lu / r = 38.4 > 34 - 12(M1 / M2) = 28 < = = Slenderness effect must be considered. (ACI 6.2.5)
Ec = 57000 (fc')0.5 = 3605.0 ksi, ACI 19.2.2
Ig = b h3 / 12 = 13333 in4

0.4 E c I g 0.4 E c I g
EI    0.25 E c I g  1.2E+07 k-in2 , ACI 6.6.4.4.4
1  d 1  0.6

 2EI 
Pc  2234.18 k-in2 , ACI 6.6.4.4.4
 k Lu 
2

M2,min = MAX[ M2 , Pu (0.6+0.03 h) ] = 200 ft-k, ACI 6.6.4


Cm = MAX[ 0.6 + 0.4 (M1 / M2, min) , 0.4 ] = 0.8 , ACI 6.6.4.5

 
 
 Cm 
  MAX , 1.0 1.05 , ACI 6.6.4.5.2
 1  Pu 
 0.75P c 
 

Mu, ns = d M2, min = 210.2 ft-k, ACI 6.6.4.5.1 > 1.05 M2 = 210.0 ft-k [Unsatisfactory] ,(ACI 6.6.4.3)
The column is sway. See calculation as follows.

MAGNIFIED MOMENT - SWAY


k Lu / r = 38.4 > 22 < = = Slenderness effect must be considered. ACI 6.2.5)

   
   
1
 s  MIN  MAX  , 1.0  , 2.5  1.13 , ACI 6.6.4
   Pu  
  1  0.75 P  
  c  

Ag = b h = 400 in2
Lu / r = 24.00 < 35 / [Pu / (fc' Ag)]0.5 = 70.00 [Satisfactory]
M2s = M2 = 200.0 ft-k, as given
M2ns = 5% M2s = 10.0 ft-k, assumed conservatively
Mu, s = M2ns + ds M2s = 236.7 ft-k, ACI 6.6.4.6

Note: For column subject to bending about both principal axis, the moment about each axis shall be magnified separately based
on the conditions corresponding to that axis.
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Rectangular Concrete Column Design

INPUT DATA
f 'c = 4 ksi
fy = 60 ksi
x = 48 in
y = 32 in
Bar Size ==> # 11
No. of Asx = 8 8 # 11
No. of Asy = 9 9 # 11
Total Bars ==> # 30 # 11
r = 3.0%
Pu = 1700 k
Mux = 2900 ft-k ex = 20.5 in
Muy = 1200 ft-k ey = 8.5 in

CHECK COLUMN CAPACITY BY THE BRESLER METHOD


1
P u   0.80   0.70  P o Pn  1 1 1 M nx  M ny  1.0
  M nox M noy
P ox P oy Po
1700.0 < 4407.9 ok 2428.6 < 2953.0 ok 1.270 > 1.0 NG

ANALYSIS
x DIRECTION y DIRECTION
u = 0.003 d = 45.295 in 29.295 in
d' = 2.705 in 2.705 in
As = 12.48 in2 14.04 in2
 = 0.70 b = 32 in 48 in

Mn = 4142.9 ft-k 1714.3 ft-k


1 Mno
= 0.85 = 5237.1 ft-k 3581.1 ft-k
Po = 3626.1 k 5265.9 k

MOMENT STRENGTH (Pn=0)

 As f y  A's u E s 
2
'
A s f y  As  u E s 
'
 3.4  1 f cb As'  u E s d '
c 
1.7  1 f 'cb 4.100781 in 3.701729 in

'  c d'
f s  E s u   29612.16 psi 23425.65 psi
 c 

  1c 
M n  0.85 f c  1cb  d 
'
 As' f 's  d  d '  
2 
4034.011 ft-k 3052.887 ft-k

AXIAL LOAD STRENGTH (Mn=0)

'
P o  0.85 f c( A g  A st )  A st f y  7871.28 k = 7871.28 k

BALANCED CONDITION

 u E s  1d
ab  
 uEs  f y 22.78616 in 14.73718 in

'  d   u E s  f y 
'
f sb   u E s 1     60000 psi 60000 psi
 d   u E s 
' '
P b  0.85 f cb a b  As f sb  A s f y 
'
2479.134 k 2405.108 k

'  h ab  ' h ' h 


M b  0.85 f cb a b     A s f sb   d   A s f y   d   5262.137 ft-k 3596.574 ft-k
'

2 2  2  2 