SOL AR INVERTERS
01
—
ABB string inverters
TRIO-50.0-TL-OUTD
TRIO-60.0-TL-OUTD-480
50 to 60 kW
—
Technical data and types
Type code TRIO-50.0-TL-OUTD TRIO-60.0-TL-OUTD-480
Input side
Absolute maximum DC input voltage (Vmax,abs) 1000 V
Start-up DC input voltage (Vstart) 420...700 V (Default 420 V) 420...700 V (Default 500 V)
Operating DC input voltage range (Vdcmin ...Vdcmax) 0,7xVstart ...950 V (min 300 V) 0,7xVstart ...950 V (min 360 V)
Rated DC input voltage (Vdcr) 610 Vdc 720 Vdc
Rated DC input power (Pdcr) 52000 W 61800 W
Number of independent MPPT 1
MPPT input DC voltage range (VMPPTmin ... VMPPTmax) at Pacr 480-800 Vdc 570-800 Vdc
Maximum DC input current (I dcmax) 108 A
Maximum input short circuit current 160 A
Number of DC input pairs 12 (-SX/-SY), 16 (-SX) 16 (-SX)
PV quick fit connector 3) on -SX and -SY version /
DC connection type
Screw terminal block on Standard and -S version
Input protection
Reverse polarity protection Yes, from limited current source
Input over voltage protection for each MPPT - varistor Yes, 2
Input over voltage protection for each MPPT - plug In modular
Type 2 (-SX version) / Type 1+2 (-SY version)
surge arrester
Photovoltaic array isolation control According to local standard
DC switch rating for each MPPT (version with DC switch) 200 A / 1000 V
Fuse rating (version with fuses) 15 A / 1000 V
Output side
AC grid connection type Three-phase (3W+PE or 4W+PE)
Rated AC power (Pacr @cosφ=1 ) 50000 W 60000 W
Maximum AC output power (Pacmax @cosφ=1) 50000 W 60000 W
Maximum apparent power (S max) 50000 VA 60000 VA
Rated AC grid voltage (Vac,r) 400 V 480 V
AC voltage range 320...480 V 1) 384...571 V 1)
Maximum AC output current (I ac,max) 77 A
Contributory fault current 92 A
Rated output frequency (fr) 50 Hz / 60 Hz
Output frequency range (fmin ...fmax) 47...53 Hz / 57…63 Hz 2)
Nominal power factor and adjustable range > 0.995; 0...1 inductive/capacitive with maximum S max
Total current harmonic distortion <3%
Maximum AC cable section allowed 95 mm2 copper (with TRIO-ALUMINUM-KIT 150 mm2 aluminum)
AC connection type Screw terminal block, cable gland PG42
Output protection
Anti-islanding protection According to local standard
Maximum external AC overcurrent protection 100 A
Output overvoltage protection - varistor Yes, 4
Output overvoltage protection - plug in modular surge
4, Type 2
arrester (-SX version)
Operating performance
Maximum efficiency (ηmax) 98.3% 98.5%
Weighted efficiency (EURO/CEC) 98.0% / - 98.0% / -
Communication
Remote monitoring VSN300 Wifi Logger Card (opt.), VSN700 Data Logger (opt.)
Wireless local monitoring VSN300 Wifi Logger Card (opt.)
User interface LEDs, Display (option)
Communication interface 2 (RS485)
Environmental
-25...+60°C/ -13...14°F -25...+60°C/-13...140°F
Ambient temperature range
with derating above 50°C /140°F with derating above 45°C/113°F
Relative humidity 4%... 100% condensing
Sound pressure level, typical 75 dB(A) @1 m
Maximum operating altitude without derating 2000 m / 6560 ft
Physical
Environmental protection rating IP65 (IP54 for cooling section)
Cooling Forced air
Dimension (H x W x D) 725 mm x 1491 mm x 315 mm / 28.5” x 58.7” x 12.4”
95 kg / 209 lbs overall, 66 kg / 145 lbs electronic compartment,
Weight
15 kg / 33 lbs AC wiring box (full optional), 14kg / 31 lbs DC wiring box (full optional)
Mounting system Wall bracket, horizontal support
P R O D U C T F LY E R F O R T R I O - 5 0 . 0 -T L - O U T D/ T R I O - 6 0 . 0 -T L - O U T D - 4 8 0 A B B S O L A R I N V E R T E R S
—
ABB TRIO-50.0-TL-OUTD/TRIO-60.0-TL-OUTD-480 string inverter block diagram
IN1 L2 L2 L2 N N, S N N, S
- - - -
L3 L3 L3 PE PE
Standard -S version
IN1A(+)
12/16 positive (+) inputs
IN1B(+)
IN1C(+) L1 L1, S
IN1D(+) L2 L2, S
IN1A(-)
12/16 negative (-) inputs
IN1B(-)
- DC/DC DC/AC
IN1C(-) Current reading DSP DSP
contr. contr.
IN1D(-) OVP monitoring
-SX version
IN4A(-)
Control circuit
IN4B(-)
IN4C(-)
Current OVP
IN4D(-) reading monitoring
-SX version
1_RS485
+ T/R
IN1A(+)
- T/R
IN1B(+)
12 positive (+) inputs
GND
IN1C(+)
2_RS485
+ T/R
- T/R
2 1 3
IN4A(+)
GND
IN4B(+) +
IN4C(+) Remote control
+ R1
IN1 Expansion slot
+ R2
IN1A(-)
Grid standard setting µP GND
IN1B(-) -
12 negative (-) inputs
Alarm
IN1C(-)
N.C
N.O
C 1 Inverter power module
Aux
IN4A(-) 2 DC wiring box
IN4B(-) N.C
IN4C(-)
Current
N.O 3 AC wiring box
reading C
OVP
Communication and
monitoring control board
-SY version
—
Technical data and types
Type code TRIO-50.0-TL-OUTD TRIO-60.0-TL-OUTD-480
Safety
Isolation level Transformerless
Marking CE
IEC/EN 62109-1, IEC/EN 62109-2, EN 61000-6-2, EN 61000-6-3,
Safety and EMC standard
EN 61000-3-11, EN 61000-3-12
CEI 0-21 4), CEI 0-16, DIN V VDE V 0126-1-1, VDE-AR-N 4105 4), G59/3,
EN 50438 (not for all national appendices) 4), RD 1699 4), RD 413 4), RD 661 4),
Grid standard (check your sales channel for availability)
P.O. 12.3 4), AS 4777 4), BDEW, NRS-097-2-1 4), MEA 4), PEA 4), IEC 61727,
IEC 60068, IEC 61683, VFR-2014, IEC 62116
Available product variants
Inverter power module TRIO-50.0-TL-OUTD-POWER MODULE TRIO-60.0-TL-OUTD-POWER MODULE
DC wiring box options
Input connections with terminal blocks DCWB-TRIO-50.0-TL-OUTD 5) DCWB-TRIO-60.0-TL-OUTD
Input connections with terminal blocks + DC switch DCWB-S-TRIO-50.0-TL-OUTD 5) DCWB-S-TRIO-60.0-TL-OUTD
12 quick input connections + fuses + DC switch + surge
DCWB-SX-TRIO-50.0-TL-OUTD/12 INPUTS 5) -
arresters Type 2
16 quick input connections + fuses + DC switch + surge
DCWB-SX-TRIO-50.0-TL-OUTD/16 INPUTS 5)
DCWB-SX-TRIO-60.0-TL-OUTD/16 INPUTS
arresters Type 2
12 quick input connections + fuses + DC switch + surge
DCWB-SY-TRIO-50.0-TL-OUTD 5)
-
arresters Type 1+2
AC wiring box options
AC output connections with terminal blocks ACWB-TRIO-50.0-TL-OUTD ACWB-TRIO-60.0-TL-OUTD
AC output connections with terminal blocks + AC switch ACWB-S-TRIO-50.0-TL-OUTD ACWB-S-TRIO-60.0-TL-OUTD
AC output connections with terminal blocks + AC switch +
ACWB-SX-TRIO-50.0-TL-OUTD ACWB-SX-TRIO-60.0-TL-OUTD
surge arrester Type 2
1)
The AC voltage range may vary depending on specific country grid standard Valid only for model TRIO-50-TL-OUTD
4)
2)
The Frequency range may vary depending on specific country grid standard DCWB with display is available on request
5)
3)
Please refer to the document “String inverters – Product manual appendix” available at Remark. Features not specifically listed in the present data sheet are not included in
www.abb.com/solarinverters for information on the quick-fit connector brand and
model used in the inverter
— —
Efficiency curves of TRIO-50.0-TL-OUTD Efficiency curves of TRIO-60.0-TL-OUTD
100 100
99 99
98 98
97 97
Efficiency [%]
Efficiency [%]
96 96
95 95
400 Vdc 570 Vdc
93 93
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
— —
For more information please contact We reserve the right to make technical We reserve all rights in this document and
your local ABB representative or visit: changes or modify the contents of this in the subject matter and illustrations
document without prior notice. With contained therein. Any reproduction,
regard to purchase orders, the agreed disclosure to third parties or utilization of
www.abb.com/solarinverters particulars shall prevail. ABB AG does not its contents – in whole or in parts – is
www.abb.com accept any responsibility whatsoever for forbidden without prior written consent of
potential errors or possible lack of ABB AG. Copyright© 2017 ABB
information in this document. All rights reserved