Types of Earthing (As Per IEC Standards)
Types of Earthing (As Per IEC Standards)
Introduction
In the preceding article we studied the basics of Earthing and also the basic most Earthing
type where the neutral is grounded at source and optionally grounding is done even at
customer side.
Besides this, International Standard – IEC 60364 formally defines different types of
Earthing arrangements. Let us examine them here in detail.
IEC Standard 60364 specifies a Two Letter Codes to identify type of earthing. It also
defines three families of Earthing arrangements.
The two letter code is based on Source Side – Device Side Earthing.
The First Letter indicates how the Earthing is done on Source side (Generator /
Transformer).
The Second Letter indicates how the Earthing is done on Device side (place
where electricity is consumed at customer premises).
T – (French word “Terre” meaning Earth) – It means direct connection of a point to earth
N – It means that there is direct connection to neutral at the source of installation which is
in turn connected to the ground
Based on a combination of these three letters, there are three families of Earthing
arrangements proposed by IEC as below:
TN Network
TT Network
IT Network
A. TN Network
In TN type of earthing system, one of the points of the source side (Generator or
Transformer) is connected to earth. This point is usually the star point in a three phase
system. The body of the connected electrical device is connected to earth via this earth
point on the source side. See fig. below which depicts this:
In above diagram:
PE – Acronym for “Protective Earth” – is the conductor that connects the exposed
metallic parts of the consumer’s electrical installation to the ground.
N –Also called Neutral. It is the conductor that connects Star point in a 3 phase system to
the earth.
1. TN-S
2. TN-C
3. TN-C-S
TN-S: In this, separate conductors for Protective Earth (PE) and Neutral run from
Consumer’s electrical installation till the source. They are connected together only at the
power source.
TN-C: In this, there is a combined conductor called PEN (Protective Earth-Neutral)
which is connected to earth at the source.
TN-C-S: In this type of earthing, part of the system uses a combined PEN conductor for
earthing, whereas for remaining part of the system uses separate conductor for PE and N.
Usually, the combined PEN conductor is used near the source of the system.
B. TT Network
In TT type of earthing system, consumer employs its own local earth connection in the
premises, which is independent of any earth connection at source side.
In IT type of earthing system, there is either no connection to earth at all, or it is done via
a high impendence earthing connection.
Australia / New Zealand – Also uses TN-C-S type of earthing know as Multiple Earth
Neutral (MEN) system
USA / Canada – Uses TN-C for the feed from Transformer but uses TN-C-S within the
structure at customer premises
France / Japan / Denmark – Uses TT type of earthing and customer must make its own
arrangement for its own earthing connection