REHABILITATION OF
“MISELUK”
TRANSFORMER STATION
20 kV CABLE
TS ALIBEGOVAC – TS MISELUK – TS MOST
Rev 1.1.0
20 kV cable rehabilitation
March 2004
2
20 kV cable rehabilitation
20 kV CABLE
TS ALIBEGOVAC – TS MISELUK – TS MOST
Content:
Section 4: Drawings
3
20 kV cable rehabilitation
4
20 kV cable rehabilitation
1. Code on technical standards for electro energetic plants, nominal voltage over 1000 V,
“Pravilnik o tehničkim normativima za elektroenergetska postrojenja nazivnog napona iznad
1000 V” (Sl. list SFRJ br. 4/74).
2. Code on technical standards for over ground electro energetic lines, nominal voltage
from 1 kV to 400 Kv , “Pravilnik o tehnickim normativima za izgradnju nadzemnih
elektroenergetskih vodova nazivnog napona 1 kV do 400 kV” (Sluzbeni list SFRJ 65/88)
3. Code on changes to the Code on technical standards for overground electro energetic
lines, nominal voltage from 1 kV to 400 Kv , “Pravilnik o izmenama pravilnika o tehnickim
normativima za izgradnju nadzemnih elektroenergetskih vodova nazivnog napona 1 kV do
400 kV” (Sluzbeni list SFRJ 18/92)
4. Code on technical standards for earthing electro energetic plants, nominal voltage over
1000 V, “Pravilnik o tehničkim normativima za uzemljenje elektroenergetskih postrojenja
nazivnog napona iznad 1000 V” (Sl. list SRJ br. 61/95).
5. Code on technical standards for protection of low tension network and belonging
transformer stations, “Pravilnik o tehničkim normativima za zaštitu niskonaponskih mreža i
pripadajućih transformatorskih stanica” (Sl. list SFRJ br. 13/78).
6. Code on changes and addendums to the Code on technical standards for protection of
low tension network and belonging transformer stations, “Pravilnik o izmenama i dopunama
pravilnika o tehničkim normativima za zaštitu niskonaponskih mreža i pripadajućih
transformatorskih stanica” (Sl. list SRJ br. 37/95).
7. Code on technical standards for driving and maintaining electro energetic plants and
leads, “Pravilnik o tehničkim normativima za pogon i održavanje elektroenergetskih
postrojenja i vodova” (Sl. list SRJ br. 41/93).
8. Code on protection of object against atmospheric discharge, “Pravilnik o tehničkim
normativima za zaštitu objekata od atmosferskog pražnjenja” (Sl. list SRJ br. 11/96.).
9. Code on general labour protection against electric power in work areas and sites,
“Pravilnik o opštim merama zaštite na radu od opasnog dejstva električne struje u objektima
namenjenim za rad, radnim prostorima i gradilištima” (Sl. glasnik SRS br. 21/89).
10. Code on technical standards for protection of electro energetic objects and equipment
against fire, “Pravilnik o tehničkim normativima za zaštitu elektroenergetskih postrojenja i
uređaja od požara” ( Sl. list SFRJ br. 74/90).
5
20 kV cable rehabilitation
11. Planning and construction law, “Zakon o planiranju i izgradnji” (Sl. glasnik RS br. 47/03).
12. Law on labour protection, “Zakon o zaštiti na radu” (Sl. glasnik RS br. 42/91, 53/93,
67/93 i 48/94).
13. Law on changes and addendums to the Law on labour protection, “Zakon o izmenama i
dopunama zakona o zaštiti na radu” (Sl. glasnik RS br. 42/98).
14. Law on standardization, “Zakon o standardizaciji” (Sl. list SRJ br. 30/96).
15. Law on measuring units, “Zakon o mernim jedinicama i merilima” (Sl. list SRJ br. 80/94).
16. YU standards referring to this kind of objects. Exact standard will be noted in text
17. Technical recommendations (EPS – Direkcija za distribuciju el. energije Srbije).
18. Code on technical standards for construction of LV overground lines, “Pravilnik o
tehnickim normativima za izgradnju niskonaponskih nadzemnih vodova”, (Sl. list SFRJ 6/92)
19. Code on technical standards for constructing of MV overground lines with self
supporting cables, “Pravilnik o tehnickim normativima za izgradnju srednjenaponskih
nadzemnih vodova samonosecim kablovskim snopom” (Sl. list SRJ 20/92).
20. Regulations on technical measures for driving and maintaining of electro energetic
plants, “Propisi o tehnickim merama za pogon I odrzavanje elektroenergetskih postrojenja”
(Sl.list SFRJ 19/68)
This design is on MV 20kV cable that connections three transformer station in the
area of Sloboda Bridge and Axcess roads to it: Alibegovac, Miseluk and Most. All
three transformer stations serve for power supplying for public lighting for mentioned
area and for tunnel ventialtion and other consumers connected to them. Route of the
cable is defined in original designs and it will be followed. From TS Alibegovac it is
laid paralell to cables for public lighting. Inside tunnel, cable is laid in concrete cable
channel. From tunnel exit on, route is paralell to cables for tunnel lighting and public
lighting. Through the Bridge cable is laid on existing or renewed cable girders. From
the Bridge on, cable is laid in ground ditch till TS Most. Type of 20kV cable is XHE-
49A, 3x(1x150)mm 2
6
20 kV cable rehabilitation
Cable laying is designed to be on existing route in excavated ditch of 0.8m depth. After
laying, cable is to be covered with fine soil or sand in 20 cm layers with mechanical or
manual tapping. After this, ditch will be covered with upper layer of surrounding soil to:
a) existing ground level if it is grass area and
b) to the bottom level of other constructions (structures) if cable is crossing it or if it is under
it.
1 With excavated soil in 20 cm layers with tamping. Tamping is to be done with hand
. tampers and upper layers by mechanical tamper.
Tamping is to be done until:
a) 100% from natural density of excavated ground
b) modulus of compressibility of final layer must be min 2.5 kN/cm 2 .
2 After refilling with natural soil in one layer of 20 cm (this is necessary because of
. heating and cooling of the cable), ditch could be covered with sand till level beneath
other structure. This job should be done professionally and with care.
If refilling is to be done with sand, rest of soil is to be transported to the place defined by the
employer, but the distance should be shorter than 2 km.
7
20 kV cable rehabilitation
Most dangerous thermo tension could occur in case of short connection on cable beginning.
As equipment in TS 110/20kV, are designed for max. Power of short connection of 500
MVA on 20 kV side, cables will be checked for thermo tension for the same power. Relevant
current of short connection is 14.45 kA.
According to data on selected cable, this cable could stand this current for more than 0.2
sec, on which time protection is designed.
1.10. Remark
8
20 kV cable rehabilitation
This cable serves for electric transport to the places of consumption and consists of all parts
needed for this function to be fulfilled. Those other parts are: conductors, earthing, cable
heads, connections and other cable equipment.
Cables in ground ditch are after laying and refilling, practically unreachable. On open
places, on buildings etc. cable is laid in protective pipes on secured height so there is no
possibility for direct contact.
Where cable is laid in cable channel, that channel must be covered with appropriate covers
preventing unauthorized person from entering (route in the tunnel).
Excavating in cable ditch area is only allowed when there is a need for intervention and that
must be only with skilled personnel and supervision.
During exploitation period, need for intervention could occur. All intervention on cable could
be done under following conditions:
- no current in the cable,
- preventing contact of the cable with other parts under voltage,
- good work preparation and
9
20 kV cable rehabilitation
Every of mentioned items is described in local “list of directions for secured work on electro
energetic objects in exploitation” (“Zbirka uputstava za bezbedan rad na elektroenergetskim
objektima u eksploataciji”) published by local electro distributor - Elektrovojvodina.
All cable ends must be formed in appropriate way and these ends must be in cable
cabinets, or LV and HV assembly blocks.
On occasion of underground short circuit in MV cables there is possibility for transfer of high
voltage out of short circuit spot. By this design, Cu cable coat is connected with TS earthing
on both cable ends. As those earthlings are designed according to relevant regulations, it
could be concluded that there is no danger from danger on high voltage impact.
Electric arc could occur as a result of broken insulation of cable itself. Measures against this
are in choosing appropriate cable and other cable equipment. If electric arc occurs, no other
dangers could occur except power failure. If cable is in opened channels, fire could start. It
should be treated with CO2 fire extinguishers.
10
20 kV cable rehabilitation
BILL OF QUANTITIES
20 Kv Cable Rehabilitation
Item
No Description Unit Quantity Unit rate Amount
1 Preliminary Works
2 Earth works
11
20 kV cable rehabilitation
To Summary:
4 Other works
12
20 kV cable rehabilitation
Summary
Schedule Amount
Description of Works
No. (in Euro)
1 Preliminary Works
2 Earth Works
4 Other Works
PRICE €
SECTION 4: DRAWINGS
13