Experion Series C Platform Specifications and Technical Data
Experion Series C Platform Specifications and Technical Data
Experion Series C Platform Specifications and Technical Data
Table of Contents
Product Introduction Summary ......................................................................... 2
Features............................................................................................................ 2
Detailed Specifications – Environmental Characteristics ...........................3
Approval Bodies................................................................................................ 5
Series-C Power System.................................................................................... 7
- Environmental characteristics
- Approvals
- Power system
Features
All Series C components feature an innovative design
that improves heat management. This unique look
provides a significant reduction in overall size for the
equivalent function.
Environmental Characteristics
This section relates to the physical characteristics applicable to all Series C components. Where applicable,
specifications state limits within an approved cabinet and to the cabinet skin.
Relative Humidity (3) 5 to 95% (non condensing) (4) 5 to 95%, (non condensing) (4)
Barometric Pressure
Altitude -300 to +3000 m any
Notes:
(1) If Lithium Batteries are used, some Government regulations may prohibit air transport of batteries.
(2)This rating applies to the external ambient temperature of the enclosure with doors closed.
(3)This rating applies to the internal ambient temperature of the enclosure with the doors closed.
(4) The maximum relative humidity spec applies up to 40°C. Above 40°C the RH spec is de-rated to
55% to maintain constant moisture content.
(5) Measured with field strength meter near the surface of the electronics with doors open. This is a
goal for the entire contents of the cabinet and may be a stretch for some items.
(6) Applied to items that are likely to be in contact with discharge sources (e.g. human body) during
typical maintenance actions.
(7) 10 Hz is approximate – exact crossover freq. is determined by the intersection of the displacement
and acceleration.
(8) Composite Transportation Test Curve--encompassing maximum Random Vibration power
spectral density values associated with ground, air, and sea transportation environments.
The transportation portion of the vibration specification in the vertical direction adheres to ASTM D4169–96
Standard Practice for Performance Testing of Shipping Containers and Systems for Truck and Air at Quality
Assurance Level II, and in the longitudinal and transverse axes MIL-STD_810F, Category 4 – Truck
Transportation over US Highways. The transportation shock adheres to ASTM D4169-96 Standard Practice for
Performance Testing of Shipping Containers for “Mechanical Handling: Fork Lift Truck Handling for items over
500 lbs [226.8 kgs] Quality Assurance Level II.
Approval Bodies
Factory Mutual
Division 2 Approvals
All models are approved as non-incendive for use in Class I, Division 2, Group A, B, C, D hazardous (classified)
locations.
Selected low voltage AO, AI and DI models will also have additional approval as having non-incendive field wiring
for connection to Class I, Division, 2, Group A, B, C and D hazardous (classified) locations.
Zone 2 Approvals
All models are approved as normally non-sparking apparatus for use in Class I, Zone 2, AEx nA IIC hazardous
(classified) locations.
Selected low voltage AO, AI and DI models will also have additional approval as having non-incendive field wiring
connections to Class I, Zone 2, Group IIC hazardous (classified) locations.
Temperature rating of all individual models as well as cabinet configurations is rated T4.
Division 2 Certifications
All models are certified as suitable for use in Class I, Division 2, Group A, B, C, D hazardous locations.
Zone 2 Certifications
All models are certified as normally non-sparking apparatus, Ex nA IIC, for use in Zone 2 hazardous locations.
Selected low voltage AO, AI and DI models will also have additional certification as having energy limited circuits,
Ex nA [L] IIC, for field wiring connections within Class I, Zone 2, Group IIC hazardous (classified) locations.
Temperature rating of all individual models as well as cabinet configurations is not to exceed T4.
ATEX Certification
Zone 2 Certifications
All models are certified as normally non-sparking apparatus, II 3 G EEx nA IIC, for use in Zone 2 hazardous
locations.
Selected low voltage AO, AI and DI models will also have additional certification as having energy limited circuits,
II 3 G EEx nA [L] IIC, for field wiring connections within Zone 2, Group IIC hazardous locations.
Temperature rating of all individual models as well as cabinet configurations are rated T4.
CE
• EN 61326:1998 Electrical equipment for measurement, control and laboratory use - EMC requirements.
• EN 50082-2:1995 Electromagnetic Compatibility - Generic Immunity Standard, Part 2: Industrial Environment.
• EN 55011:1991 Limits and Methods of Measurement of Radio Disturbance Characteristics of Industrial, Scientific
and Medical (ISM) Radio-Frequency Equipment
• EN 61010-1:1993 Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory Use.
• Part 1: General Requirements
C-Tick
Australian Radio communications Act of 1997, Section 182
Cabinet:
Class I, Division 2, Grp. ABCD, T4
Class I, Zone 2, AEx/Ex nC[nL] IIC T4
ATEX II 3G EEx nC [nL] IIC T4
Field Wiring:
Nonincendive & [nL] field wiring
The Series C power system provides optionally redundant 24VDC primary power at 20
amps for Series C devices. The power system allows for reserve (battery) power when
disconnected from the power mains.
The power system also provides capabilities to support integral field power. This
eliminates the need for additional power sources as well as the additional wiring, fusing,
marshalling and documentation costs.
Notable Features
• Modular design
• Space efficient design
• Designed specifically for Series C
• Power supply is removable and insert-able under power
• Redundant power supply
• Optional battery backup for a minimum of 30 minutes
• Seamless switch operation between either of the power supplies or battery backup
system
• Visual and point contact alarms on all power system components
Relative Humidity
(non-condensing) 10-70% 5-95% 5-95%
Vibration 0.1 in. (Max) D.A. 0.1 in. (Max) D.A. 0.2 in. (Max) D.A.
Disp, 10-24 Hz, Disp, 10-24 Hz, Disp, 5-18 Hz, 3.5g
3.0g (0-peak) @ 24- 3.0g (0-peak) @ (0-peak) @ 18-200
60 Hz 24-60 Hz Hz
Shock
(a) Acceleration (g) 1 5 20
(1) – Holdup time is the time the power system will continue to operate after power has been
removed. This allows for at least one full AC cycle for UPS systems to engage.
(2) – Inrush for one input line cycle maximum.
® ®
TotalPlant and Experion are registered trademarks of Honeywell International Inc. All other products and brand and product names shown herein are
trademarks of their respective owners. FOUNDATION is a trademark of the Fieldbus Foundation. HART is a trademark of the HART Communication
Foundation.
While this information is presented in good faith and believed to be accurate, Honeywell disclaims the implied warranties of merchantability and fitness for
a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customer. In no event is
Honeywell liable to anyone for any indirect, special or consequential damages. The information and specifications in this document are subject to change
without notice