DOW UF Case Study For High Turbid Water
DOW UF Case Study For High Turbid Water
DOW UF Case Study For High Turbid Water
DOW™ Ultrafiltration
Pretreatment with DOW™ Ultrafiltration Membranes Beats Challenge of High Turbidity
Site Information
Location:
JiangShu, China
Capacity:
360 m3/h
Purpose:
Pretreat feed water to RO
system
Time in Operation:
Since August 2007
Performance:
Over 99% reduction in
turbidity; SDI ≤ 3
Skid 2 at the GuanYinShan cogeneration facility, using DOW™ Ultrafiltration SFP-2860 Modules.
(Photo courtesy of Nantong GuanYinShan Environmental Protection Thermoelectricity Co. Ltd.)
Introduction The GuanYinShan cogeneration facility is located in the JiangShu province of China and
supplies heat and electricity for major industries in the city of GuanYinShan. Because of an
increase in demand for energy, the operating company (Nantong GuanYinShan
Environmental Protection Thermoelectricity Co. Ltd.) invested in a second expansion that
added a 12 MW cogeneration system, resulting in a 40 MW co-gen facility providing reliable
and stable energy for the growing community.
To produce boiler feed water, the GuanYinShan facility uses ground water that has high
turbidity, high iron concentration, and high total suspended solids, which poses a challenge
for reverse osmosis (RO) membrane operation. Pretreatment with DOW™ Ultrafiltration
modules facilitates stable RO membrane performance, resulting in product water with
average turbidity of 0.12 NTU and silt density index (SDI) less than 3.
DOW™ The SFP-2860 module is ideal for systems with capacities greater than 50 m3/h (220 gpm).
Ultrafiltration This 8-inch-diameter module offers a high effective membrane area, which contributes to a
Modules more economical membrane system design. At 60 inches long, the SFP-2860 module offers
high efficiencies over a wide range of feed water conditions.
Page 1 of 5 Trademark of The Dow Chemical Company (“Dow”) or an affiliated company of Dow
®TM Form No. 795-00016-1008
DOW™ Ultrafiltration
DOW™ Ultrafiltration DOW™ Ultrafiltration modules are made with high-strength, hollow-fiber membranes that
Modules, cont. have excellent features and benefits:
• 0.03 μm nominal pore diameter for removal of bacteria, viruses, and particulates
(including colloids) to protect downstream processes such as reverse osmosis
• Polyvinylidene fluoride (PVDF) polymeric hollow fibers for high strength and chemical
resistance that lead to long membrane life
• Hydrophilic PVDF fibers for easy cleaning and wettability that help maintain long-term
performance
• Outside-in flow configuration for high tolerance to feed solids that helps reduce the
need for pretreatment processes
• Unplasticized polyvinylchloride (U-PVC) housing that helps eliminate the need for
costly pressure vessels
Water Treatment Table 1 indicates the average raw water analysis. Water treatment challenges included high
Process turbidity (11.1 NTU), high iron (0.22 mg/L), and high total suspended solids (31.8 mg/L).
Sodium bisulfite (NaHSO3) at a dosage of 2–4 ppm is added after the UF modules to remove
residual NaOCl in the UF permeate water. Other additions include an antiscalant (4–5 ppm)
to prevent RO membrane scaling and HCl to reduce pH. A 5-μm cartridge filter is installed
upstream of the RO system as further protection against particulate fouling in the event of
maintenance or operation mishaps.
Cation and anion beds further reduce ions in the water and operate with a decarbonator to
remove excess CO2. A mixed bed polishes the RO water for boiler make-up requirements.
Ammonia (NH3) at a dosage of 1–2 ppm is added to adjust pH to the range required for boiler
make-up water supply.
Page 2 of 5 Trademark of The Dow Chemical Company (“Dow”) or an affiliated company of Dow
®TM Form No. 795-00016-1008
DOW™ Ultrafiltration
Water Treatment Figure 1. Water treatment process
Process, cont.
NaOCl NaHSO3, antiscalant, HCl
Feed Water Self Cleaning Filter Heater DOWTM Ultrafiltration Cartridge Filter
RO Unit Cation Bed Decarbonator Anion Bed Mixed Bed End User
NH3
Table 2 provides the operating parameters for the ultrafiltration, reverse osmosis, and mixed
bed unit operations. Table 3 further describes the ultrafiltration process.
UF System Figure 2 shows the dramatic decrease in turbidity through the DOW™ Ultrafiltration
Performance membranes, with turbidity being reduced 99% from 11.1 NTU to an average of 0.12 NTU.
Minor turbidity spikes shown in the graph were caused by system maintenance. However,
none of the spikes exceeded 0.2 NTU.
Figure 3 shows the expected rise in transmembrane pressure (TMP) values between
cleanings. Off-line Clean In Place (CIP) was performed in November 2007 and in January
2008, as indicated by the sudden drop in transmembrane pressure. Other TMP spikes were
caused by system maintenance and changes in the raw water source. Implementing a CIP
effectively restores the operating TMP. The feed water iron concentration has not affected
the performance of the UF membranes, and no fouling has been observed.
Page 3 of 5 Trademark of The Dow Chemical Company (“Dow”) or an affiliated company of Dow
®TM Form No. 795-00016-1008
DOW™ Ultrafiltration
UF System Figure 2. Product water turbidity versus time.
Performance, cont.
0.2
0.18
0.16
Turbidity (NTU)
0.14
0.12
0.1
0.08
0.06
0.04
0.02
0
07/10/10
07/10/22
07/11/15
07/11/27
07/12/21
08/1/2
08/5/5
07/11/3
07/12/9
08/1/14
08/1/26
08/2/17
08/2/29
08/3/12
08/3/24
08/4/05
08/4/17
08/5/17
08/7/20
Date
0.15
0.1
0.05
0
07/8/1
07/8/19
07/9/4
07/9/19
07/10/4
07/10/19
07/11/3
07/11/18
07/12/3
07/12/18
08/1/2
08/1/17
08/2/3
08/2/26
08/3/12
08/3/27
08/4/11
08/5/2
08/5/17
08/8/5
Date
Page 4 of 5 Trademark of The Dow Chemical Company (“Dow”) or an affiliated company of Dow
®TM Form No. 795-00016-1008
DOW™ Ultrafiltration
UF System The UF permeate SDI has an average value of 2.6 and meets the requirement of SDI less
Performance, cont. than 3 for optimal RO feed water. Higher SDI values shown in Figure 4 occurred as a result
of downtime and maintenance of other facility unit operations.
SDI
3.0
2.5
2.0
1.5
1.0
07/8/5
07/8/11
07/8/17
07/8/23
07/7/29
07/9/4
07/9/10
07/9/16
07/9/22
07/9/28
07/10/4
07/10/10
07/10/16
Summary Using a ground water source with high turbidity, high iron, and high suspended solids has not
prevented GuanYinShan from producing desirable RO feed water. DOW™ Ultrafiltration
membranes have successfully treated this water without other pretreatment processes. The
UF product water has an average turbidity of 0.12 NTU and SDI less than 3. DOW™
Ultrafiltration provides an economic and reliable water treatment system for this ground water
source.
DOW™ Ultrafiltration Notice: The use of this product in and of itself does not necessarily guarantee the removal of cysts and pathogens from water.
For more information about DOW™ Effective cyst and pathogen reduction is dependent on the complete system design and on the operation and maintenance of
Ultrafiltration, call the Dow Water the system.
Solutions business:
North America: 1-800-447-4369 Notice: No freedom from any patent owned by Seller or others is to be inferred. Because use conditions and applicable laws
Latin America: (+55) 11-5188-9277 may differ from one location to another and may change with time, Customer is responsible for determining whether products
Europe: (+32) 3-450-2240 and the information in this document are appropriate for Customer’s use and for ensuring that Customer’s workplace and
Japan: (+81) 3-5460-2100
disposal practices are in compliance with applicable laws and other governmental enactments. Seller assumes no obligation or
Australia: (+61) 3-9226-3545
liability for the information in this document. NO WARRANTIES ARE GIVEN; ALL IMPLIED WARRANTIES OF
http://www.dowwatersolutions.com
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE EXPRESSLY EXCLUDED.
Page 5 of 5 ®TM Trademark of The Dow Chemical Company (“Dow”) or an affiliated company of Dow Form No. 795-00016-1008