Tutorial Power System Analysis - Power Flow Analysis-Solution
Tutorial Power System Analysis - Power Flow Analysis-Solution
1) A power system network is shown in Figure 1. The values marked are impedances in per unit on
a base of 100 MVA. Convert network impedances to admittances and determine the bus
admittance matrix.
Solution
2) In the power system network shown in Figure 2 below, bus 1 is a slack bus with V1 = 1.00 per
unit and bus 2 is a load bus with S2 = 280 MW + j60 Mvar. The line impedance on a base of 100
MVA is Z = 0.02+j0.04 per unit.
a) Using Gauss-Seidel method, determine V2. Use an initial estimate of V2(0) = 1.0+j0.0 and
perform three iterations.
b) If after several iterations voltage at bus 2 converges to V2 = 0.90-j0.10, determine S1 and
the real and reactive power loss in the line.
3) Figure 3 shows the single-line diagram of a simple three-bus power system with generation at
buses 1 and 3. The voltage at bus 1 is V1 = 1.0250 per unit. Voltage magnitude at bus 3 is fixed
at 1.03 per unit with a real power generation of 300 MW. A load consisting of 400 MW and 200
Mvar is taken from bus 2. Line impedances are marked in per unit on a 100 MVA base. Line
resistances and line charging susceptances are neglected.
a) Using Gauss-Seidel method and initial estimates of V2(0) =1.0+j0 and V3(0) =1.03+j0 and
keeping V3 = 1.03 pu, determine the phasor values of V2 and V3. Perform two iterations.
b) If after several iterations the bus voltages converge to
V2 1.001243 2.1 1.000571 j 0.0366898pu
V3 1.031.36851 1.029706 j 0.0246pu
Determine the line flows and the line losses and the slack bus real and reactive power
c) Construct a power flow diagram and show the direction of the line flows
Solution
4) In the two-bus system shown in Figure 4, bus 1 is a slack bus with V1 =1.00 pu. A load of 150
MW and 50 Mvar is taken from bus 2. The line admittance is y12 = 10-73.74 pu on a base of
100 MVA. The expression for real and reactive power at bus 2 is given by
Using Newton-Raphson method, obtain the voltage magnitude and phase angle of bus 2. Start
with an initial estimate of V2(0) = 1.0 pu and 2(0) = 0. Perform two iterations.
Solution
5) Figure 5 shows the single-line diagram of a simple three-bus power system with generation at
buses 1 and 2. The voltage at bus 1 is V =1.00 per unit. Voltage magnitude at bus 2 is fixed at
1.05 pu with a real power generation of 400 MW. A load consisting of 500 MW and 400 Mvar is
taken from bus 3. Line admittances are marked in per unit on a 100 MVA base. Line resistances
and line charging susceptances are neglected.
a) Show that the expression for the real power at bus 2 and real and reactive power at bus 3
are:-
P2 40V2 V1 cos(90 2 1 ) 20V2 V3 cos(90 2 3 )
P3 20V3 V1 cos(90 3 1 ) 20V2 V3 cos(90 3 2 )
Q3 20V3 V1 sin(90 3 1 ) 20V3 V2 sin(90 3 2 ) 40V3
2
b) Using Newton-Raphson method, start with the initial estimates of V2(0) =1.0+j0 and V3(0)
=1.0+j0 and keeping V2 = 1.05 pu, determine the phasor values of V2 and V3. Perform
two iterations.
6) From Figure 5, obtain the power flow solution using the fast decoupled algorithm. Perform two
iterations.