MVS25N3MW6L: Product Data Sheet

This document provides product specifications for an EP MVS CB 2500A 50kA 3P MDO ET6 drawout manual circuit breaker. It is a 3-pole circuit breaker with a rated current of 2500A and breaking capacity of 50kA. It has microprocessor-based trip controls for protection functions like overload, short circuit, and earth fault protection.

Uploaded by

Murali Subramani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
63 views2 pages

MVS25N3MW6L: Product Data Sheet

This document provides product specifications for an EP MVS CB 2500A 50kA 3P MDO ET6 drawout manual circuit breaker. It is a 3-pole circuit breaker with a rated current of 2500A and breaking capacity of 50kA. It has microprocessor-based trip controls for protection functions like overload, short circuit, and earth fault protection.

Uploaded by

Murali Subramani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Product data sheet MVS25N3MW6L

Characteristics EP MVS CB 2500A 50kA 3P MDO ET6


drawout manual Circuit breaker

Main
Commercial Status Commercialised
Range of product EasyPact MVS
Circuit breaker name MVS25N
Device short name MVS25N
Circuit breaker applica- Standard
tion
Poles description 3P
Protected poles de- 3P 3d
scription
Network type AC
Breaking capacity code N - 50 kA
Suitability for isolation Yes conforming to IEC 60947-2

It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Utilisation category Category B
Trip unit name ET6G
Trip unit technology Micro-processor based
Trip unit rating 2500 A (-5...70 °C)

Complementary

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Network frequency 50/60 Hz

Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Control type Manually operated
Mounting mode Drawout
Mounting support Base plate
Rail
Connection position Horizontal
Vertical
Location of connection Rear
[In] rated current 2500 A (40 °C)
[Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 12 kV conforming to IEC 60947-2
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
Circuit breaker CT rating 2500 A
Breaking capacity 50 kA (Icu) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity 50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 10000 cycles (without maintenance) conforming to IEC 60947-2
20000 cycles (with maintenance) conforming to IEC 60947-2
Electrical durability 2500 cycles (without maintenance), category B at 690 V AC 50/60 Hz, conform-
ing to IEC 60947-2
5000 cycles (without maintenance), category B at 440 V AC 50/60 Hz, conform-
ing to IEC 60947-2
Connection pitch 115 mm (without spreader)
Contact position indicator Yes
[Icm] rated short-circuit making capacity 105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
[Icw] rated short-time withstand current 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2
50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit protection functions LSIG
Protection type Earth fault
Instantaneous short-circuit protection
Overload protection (long time)
Short time short-circuit protection

Nov 19, 2015


1
Fault indication Overload
Short-circuit
Internal fault
Earth fault
Long time pick-up adjstment type Ir Adjustable 9 settings
Long time pick-up adjustment range 0.4...1 x In
Long time delay adjustment type Adjustable 9 settings
[Tr] long-time delay adjustment 0.5...24 s (6 x Ir)
Short-time pick-up adjustment type Isd Adjustable 9 settings
[Isd] short-time pick-up adjustment range 1.5...10 x Ir
Short-time delay adjustment type Adjustable 5 settings
[Tsd] short-time delay adjustment range 100...400 ms
Instantaneous pick-up adjustment type Ii Adjustable 9 settings
Instantaneous pick-up adjustment range 2...15 x In
Off
Ground-fault pick-up adjustment type Adjustable 9 settings
Ground-fault time delay adjustment type -tg Adjustable 5 settings
[Tg] ground-fault time delay adjustment range 100...400 ms
[Ig] ground-fault pick-up adjustment range 500...1200 A
Zone selective interlocking ZSI With
Current sensor rating range 1000/4000 A
Maximum breaking time 25 ms
Closing response time < 70 ms
Height 439 mm
Width 441 mm
Depth 395 mm
Product weight 90 kg

Environment
Standards IEC 60947-2
Product certifications CCC
GOST
IEC
CCS
IP degree of protection IP40
Pollution degree 4 conforming to IEC 60664-1
Ambient air temperature for operation -5...70 °C
Ambient air temperature for storage -25...85 °C (with control unit)
-40...85 °C (without control unit)