HIGH-PERFORMANCE HVAC  
by Carl Ian Graham, PE
Viridian Energy & Environmental, Inc., a Vidaris, Inc. (http://www.vidaris.com/) company
Updated: 11-07-2016

INTRODUCTION
Heating, ventilating, and air-conditioning (HVAC
systems) account for 39% of the energy used in WITHIN THIS PAGE
commercial buildings in the United States. Consequently, Introduction
almost any business or government agency has the Description
potential to realize signi cant savings by improving its Application
control of HVAC operations and improving the ef ciency Relevant Codes and Standards
of the system it uses. Additional Resources

The use of high performance HVAC equipment can result


in considerable energy, emissions, and cost savings (10%–40%). Whole building design coupled with an
"extended comfort zone" can produce much greater savings (40%–70%). Extended comfort includes
employing concepts such as providing warmer, but drier air using desiccant dehumidi cation in summer,
or cooler air with warmer windows and warmer walls in winter. In addition, high-performance HVAC can
provide increased user thermal comfort (/design-objectives/productive/provide-comfortable-
environments), and contribute to improved indoor environmental quality (/design-
objectives/sustainable/enhance-indoor-environmental-quality) (IEQ).

Given the range and complexity of the subject, this information should be viewed as only a starting point
to access information from the many trade associations, agencies, and manufacturers linked throughout
the text.

DESCRIPTION
HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC)

https://www.wbdg.org/resources/high-performance-hvac 1/16
12/23/2018 High-Performance HVAC | WBDG - Whole Building Design Guide

The term HVAC refers to the three disciplines of Heating, Ventilating, and Air-Conditioning. A fourth
discipline, Controls, pervades the entire HVAC eld. Controls determine how HVAC systems operate to
meet the design goals of comfort, safety, and cost-effective operation.

Heating can be accomplished by heating the air within a space (e.g. supply air systems, perimeter
n-tube "radiators"), or by heating the occupants directly by radiation (e.g. oor/ceiling/wall
radiation or radiant panels).

Ventilating maintains an adequate mixture of gases in the air we breath (e.g. not too much CO2),
controls odors, and removes contaminants from occupied spaces. "Clean" air helps keep occupants
healthy (/design-objectives/productive/promote-health-well-being) and productive (/design-
objectives/productive). Ventilation can be accomplished passively through natural ventilation
(/resources/natural-ventilation), or actively through mechanical distribution systems powered by
fans.

Air-conditioning refers to the sensible and latent cooling of air. Sensible cooling involves the control
of air temperature while latent cooling involves the control of air humidity. Room air is cooled by
transferring heat between spaces, such as with a water loop heat pump system, or by rejecting it to
the outside air via air-cooled or water-cooled equipment. Heat can also be rejected to the ground
using geothermal exchange. Cool air is not comfortable if it is too humid. Air is dehumidi ed by
condensing its moisture on a cold surface, such as part of mechanical cooling), or by removing the
moisture through absorption (desiccant dehumidi cation). In dry climates, humidi cation may be
required for comfort instead of dehumidi cation. Evaporative humidi cation also cools the air.
Further, in such climates it is possible to use radiant cooling systems, similar to the radiant heating
systems mentioned above.

Controls ensure occupant comfort, provide safe operation of the equipment, and in a modern HVAC
control system enable judicious use of energy resources. HVAC systems are sized to meet heating
and cooling loads that historically occur only 1% to 2.5% of the time. It is the function of the
controls to ensure that the HVAC systems perform properly, reliably, and ef ciently during those
conditions that occur 97.5% to 99% of the time.

Each HVAC discipline has speci c design requirements and each has opportunities for energy savings. It
must be understood, however, that energy savings in one area may augment or diminish savings in
another. This applies to interactions between components of an HVAC system, as well as between the
HVAC system and the lighting and envelope systems. See WBDG Ensure Appropriate Product/Systems
Integration (/design-objectives/functional-operational/ensure-appropriate-productsystems-integration).
Therefore, understanding how one system or subsystem affects another is essential to making the most of
the available opportunities for energy savings. This design approach is known as whole building design
(/resources/whole-building-design).

IMPACT ON BUILDING ENERGY PERFORMANCE GOALS


Employing high-performance HVAC equipment in conjunction with whole building design can result in
signi cant energy savings. Typically, a 30% reduction in annual energy costs can be achieved with a simple
payback period of about three to ve years. And, if the payback threshold is extended to seven years, the
savings can be about 40%. These gures apply to buildings that offer conventional comfort (e.g., 70°F in
winter, 76°F in summer). (For more information on cost-effectiveness, see WBDG Cost-Effective Branch
(/design-objectives/cost-effective)).

https://www.wbdg.org/resources/high-performance-hvac 2/16
12/23/2018 High-Performance HVAC | WBDG - Whole Building Design Guide

If the comfort zone is extended through natural ventilation and air movement in summer, and through
lower air temperatures in winter (made possible by highly-insulated and, therefore, warmer wall and
window surfaces), even higher savings can be achieved. For example, a typical of ce building minimally
complying with the ASHRAE Standard 90.1 (https://www.ashrae.org/resources--
publications/bookstore/standard-90-1) might use 75,000 Btu/sq.ft./yr. The goal for many federal
buildings is 50,000 Btu/sq.ft./yr. A highly energy-ef cient building using conventional comfort could have
an energy use of 40,000 Btu/sq.ft./yr. or even less. A building designed and operated with extended
comfort strategies might only use 20,000 to 30,000 Btu/sq.ft./yr.

However, note that highly energy-ef cient design (/design-objectives/sustainable/optimize-energy-use)


utilizing high-performance HVAC equipment often requires more effort and more collaboration from the
design team than a conventional, sequential approach.

FUNDAMENTALS OF ENERGY- AND RESOURCE-EFFICIENT HVAC


DESIGN

Consider all Energy-ef cient, climate responsive construction requires a whole building
aspects of the perspective that integrates architectural and engineering concerns early in the design
building process. For example, the evaluation of a building envelope design must consider its
simultaneously effect on cooling loads and daylighting (/resources/daylighting). An energy-ef cient
building envelope, coupled with a state-of-the-art lighting system (/resources/energy-
ef cient-lighting) and ef cient, properly-sized HVAC equipment will cost less to
purchase and operate than a building whose systems are selected in isolation from
each other.

Decide on A building that only meets energy code requirements will often have a different HVAC
design goals as system than one that uses 40% less energy than the code.And the difference is likely
early as to be not only component size, but also basic system type. See WBDG Functional—
possible Meet Performance Objectives (/design-objectives/functional-operational/meet-
performance-objectives).

"Right Size" Safety factors for HVAC systems allow for uncertainties in the nal design,
HVAC systems construction and use of the building, but should be used reasonably.Greatly oversized
to ensure equipment operates less ef ciently and costs more than properly sized equipment.
ef cient For example, oversized cooling systems may not dehumidify the air properly, resulting
operation in cool but "clammy" spaces.It is unreasonable and expensive to assume a
simultaneous worst-case scenario for all load components (occupancy, lighting,
shading devices, weather) and then to apply the highest safety factors for sizing.

Consider part- Part-load performance of equipment is a critical consideration for HVAC sizing.Most
load heating and cooling equipment only operate at their rated, peak ef ciency when fully
performance loaded (that is, working near their maximum output).However, HVAC systems are
when selecting sized to meet design heating and cooling conditions that historically occur only 1% to
equipment 2.5% of the time. Thus, HVAC systems are intentionally oversized at least 97.5% to
99% of the time. In addition, most equipment is further oversized to handle pick-up
loads and to provide a factor of safety. Therefore, systems almost never operate at full
load. In fact, most systems operate at 50% or less of their capacity.

https://www.wbdg.org/resources/high-performance-hvac 3/16
12/23/2018 High-Performance HVAC | WBDG - Whole Building Design Guide

Shift or shave Many electric utilities offer lower rates during off-peak periods that typically occur at
electric loads night. Whenever possible, design systems to take advantage of this situation. For
during peak example, energy management systems can shed non-critical loads at peak periods to
demand prevent short duration electrical demands from affecting energy bills for the entire
periods year. Or, off-peak thermal ice storage systems can be designed to run chillers at night
to make ice that can be used for cooling the building during the next afternoon when
rates are higher.

Plan for A change in building use or the incorporation of new technologies can lead to an
expansion, but increased demand for cooling. But, it is wasteful to provide excess capacity now—the
don't size for it capacity may never be used or the equipment could be obsolete by the time it is
needed. It is better to plan equipment and space so that future expansion is possible.
For example, adequately size mechanical rooms and consider the use of modular
equipment.

Commission Commercial HVAC systems do not always work as expected. Problems can be caused
the HVAC by the design of the HVAC system or because equipment and controls are improperly
systems connected or installed.A part of commissioning involves testing the HVAC systems
under all aspects of operation, revealing and correcting problems, and ensuring that
everything works as intended. A comprehensive commissioning (/building-
commissioning) program will also ensure that O&M personnel are properly trained in
the functioning of all systems.

Establish an Proper performance and energy-ef cient operation of HVAC systems can only be
Operations ensured through a successful O&M (/resources/sustainable-om-practices) program.
and The building design team should provide systems that will perform effectively at the
Maintenance level of maintenance that the owner is able to provide. In turn, the owner must
(O&M) understand that different components of the HVAC system will require different
Program degrees of maintenance to perform properly.

DESIGN RECOMMENDATIONS
Consider all aspects of the building simultaneously. The building should incorporate as many features as
possible that reduce heating and cooling loads, for example:

1. In skin-load dominated structures, employ passive heating (/resources/passive-solar-heating) or


cooling strategies (e.g., sun control and shading devices (/resources/sun-control-and-shading-
devices), thermal mass).
2. In internal-load dominated structures, include glazing (/resources/windows-and-glazing) that has a
high cooling index.
3. Specify exterior wall constructions that avoid thermal bridging.
4. Detail the exterior wall constructions with air retarder systems (/resources/air-barrier-systems-
buildings).
5. Incorporate the highest R-value wall and roof construction that is cost-effective.
6. Design ef cient lighting systems (/resources/energy-ef cient-lighting).
7. Use daylight dimming controls (/resources/electric-lighting-controls) whenever possible.
8. Specify ef cient of ce equipment (e.g., EPA Energy Star® Of ce Equipment)
(https://www.energystar.gov/index.cfm?c=ofc_equip.pr_of ce_equipment).
9. Accept life-cycle horizons (/resources/life-cycle-cost-analysis-lcca) of 20 to 25 years for equipment
and 50 to 75 years for walls and glazings.
https://www.wbdg.org/resources/high-performance-hvac 4/16
12/23/2018 High-Performance HVAC | WBDG - Whole Building Design Guide

Decide on design goals as early as possible. It is important that the design team knows where it is headed
long before the construction documents phase.

a. Emphasize communication between all members of the design team throughout the design process
(see WBDG Project Management (/project-management)).
b. Develop a written "Basis of Design" that conveys to all members of the project goals for energy
ef ciency. For example, such a BOD might highlight the intent to incorporate daylighting and the
attendant use of high-performance glazing, suitable lighting controls and interior layout.
c. Establish a quantitative goal for annual energy consumption and annual energy costs.
d. Clarify goals to meet or exceed the minimum requirements of codes or regulations during
schematic design.

"Right Size" HVAC systems to ensure ef cient operation.

a. Accept the HVAC safety factors and pick-up load allowance stated in ANSI/ASHRAE/IES 90.1
(https://www.ashrae.org/resources--publications/bookstore/standard-90-1) as an upper limit.
b. Apply safety factors to a reasonable baseline. It is unreasonable to assume that on the hottest clear
day if no shades are drawn and all lights are on that each room is occupied by the maximum number
of people allowed by re codes (thus, far in excess of the maximum number of people that can be
expected in the building), and then apply safety factors. Safety factors should be applied to a
baseline that was created using reasonable assumptions.
c. Take advantage of the new generation of dependable computerized analysis tools
(/resources/energy-analysis-tools), such as DOE 2.1E, to reduce uncertainty and eliminate excess
oversizing. Hour-by-hour computer simulations can anticipate how building design and operation
affect peak loads. Issues such as diversity, pick-up requirements, and self-shading due to building
geometry can be quanti ed. As uncertainties are reduced, oversizing factors can also be reduced or
at least can be applied to a more realistic baseline.

Consider part-load performance when selecting equipment.

a. Select systems that can operate ef ciently at part-load. For example:


Variable volume fan systems and variable speed drive controls for fan motors;
Variable capacity boiler plants (e.g., step- red (hi/lo) boilers, modular boiler plants,
modulating ame boilers);
Condensing boilers operate more ef ciently (95%–96%) as the part-load decreases to the
minimum turn-down ratio;
Variable capacity cooling plants (e.g., modular chiller plants, multiple compressor equipment,
and variable speed chillers);
Variable capacity cooling towers (e.g., multiple cell towers with variable speed or two speed
fans, reset controls);
Variable capacity pump systems (e.g., primary/secondary pump loops, variable speed pump
motors); and,
Temperature reset controls for hot water, chilled water, and supply air.

Shift or shave the load.

a. Investigate the utility company's rate structure; negotiate for a favorable rate structure.
b. Take advantage of the on-peak and off-peak rate differences.

https://www.wbdg.org/resources/high-performance-hvac 5/16
12/23/2018 High-Performance HVAC | WBDG - Whole Building Design Guide

c. Use energy management controls systems to avoid unnecessary peak demand charges (peak
shaving and demand limiting).
d. Explore thermal storage systems (e.g., thermal ice storage).
e. Examine alternate fuel sources for heating and cooling systems (e.g., district steam vs. natural gas
vs. fuel oil; steam or natural gas chillers; dual fuel boilers).

Plan for future expansion instead of greatly oversizing the equipment. "Right sizing" the systems means
avoiding systems that have more capacity than currently required.This concept extends to
accommodating for planned expansion.Don't provide excess capacity today for a future load that may
never exist, instead:

a. Provide the physical space required for additional equipment: boilers, chillers, pumps, cooling
towers.
b. Design distribution systems that can easily accept additional equipment, and can be expanded to
provide for the requirements of the future expansion.

The result is savings in rst cost and operating cost, and savings in construction cost and down time when
making expansion alterations. See WBDG Productive—Design for the Changing Workplace (/design-
objectives/productive/design-changing-workplace).

Commission the HVAC systems. ASHRAE Guideline 1.1


(http://www.techstreet.com/standards/guideline-1-1-2007-hvac-r-technical-requirements-for-the-
commissioning-process?product_id=1573306) presently recommends a comprehensive commissioning
protocol for HVAC equipment. Many advocates of high-performance buildings are urging that more
general, Total Building Commissioning (TBC) be implemented. More information on commissioning can be
found at:

Building Commissioning Association (http://www.bcxa.org/)


National Institute of Building Sciences—Total Building Commissioning Program
(http://www.nibs.org/?page=councils)
Portland Energy Conservation, Inc. (http://www.peci.org/)
WBDG Building Commissioning (/building-commissioning)

Establish an Operations and Maintenance Program.

a. Specify systems that can be properly maintained by the owner, based on the owner's stated
resources. See WBDG Functional/Operational (/design-objectives/functional-operational).
b. Provide as part of construction, contract system interfaces to allow personnel to easily monitor and
adjust system parameters.
c. Make systems control, operation, and maintenance training part of the construction contract.
d. Include complete documentation regarding operation and maintenance of all equipment and
controls systems as part of the construction contract.
e. Establish a written, comprehensive operation and maintenance program, based on the
requirements of the facility, equipment, and systems installed. See WBDG Sustainable O&M
Practices (/resources/sustainable-om-practices).

TYPES OF HVAC SYSTEMS


Heating Systems

1. Boilers are used to generate steam or hot water and can be red by natural gas, fuel oil, or coal.
https://www.wbdg.org/resources/high-performance-hvac 6/16
12/23/2018 High-Performance HVAC | WBDG - Whole Building Design Guide

a. The following boilers have combustion ef ciencies between 78% and 86%.
Firetube steel boilers are constructed so that hot gases from the combustion chamber
pass through tubes that are surrounded by water.Typically, retube boilers do not
exceed 25 million Btu/hr (MMBtu/hr), but capacities up to 70 MMBtu/hr are available.
Watertube steel boilers pass hot combustion gases over water- lled tubes.Sizes for
packaged watertube boilers range from small, low pressure units (e.g., around 10
MMBtu/hr) to very large, high-pressure units with steam outputs of about 300
MMBtu/hr.
Cast iron boilers are used in small installations (0.35 to 10 MMBtu/hr) where long
service life is important.Since these boilers are composed of precast sections, they can
be more readily eld-assembled than watertube or retube boilers.At similar
capacities, cast-iron boilers are more expensive than retube or watertube boilers.

b. Condensing boilers achieve higher system ef ciencies by extracting so much heat from the
ue gases that the moisture in the gas condenses. The gases that remain can often be vented
directly to the outside, simplifying and reducing the cost of breeching.They are typically red
with natural gas and operate between 95% and 96% combustion ef ciencies. Theyalso
operate more ef ciently than non-condensing boilers at part-load.Condensing boilers are
available in capacities between 0.3 and 2 MMBtu/hr, and can be connected in modular
installations.

2. Furnaces can be used for residential and small commercial heating systems. Furnaces use natural
gas, fuel oil, and electricity for the heat source.Natural gas furnaces are available in condensing and
non-condensing models. The cooling can be packaged within the system, or a cooling coil can be
added. When direct expansion systems with coils are used, the condenser can be part of the
package or remote.

3. Heat pumps are devices that add heat to or extract heat from a conditioned space. Both
refrigerators and air conditioners are types of heat pumps that extract heat from a cooler,
conditioned space and reject it to a warmer space (i.e., the outdoors). Heating can be obtained if this
cycle is reversed: heat is moved from the outdoors to the conditioned space indoors. Heat pumps
are available in two major types: conventional packaged (air-source) and water-source
(conventional or geothermal).

More information on heat pumps can be found at:

Energy Star—Air-Source Heat Pumps

https://www.wbdg.org/resources/high-performance-hvac 7/16
12/23/2018 High-Performance HVAC | WBDG - Whole Building Design Guide

Geothermal heat pump system on the


Georgia Institute of Technology Campus
Courtesy of U.S. DOE, Craig Miller Productions

(https://www.energystar.gov/products/heating_cooling/heat_pumps_air_source)
Energy Star—Geothermal Heat Pumps
(https://www.energystar.gov/products/heating_cooling/heat_pumps_geothermal)
The Geothermal Exchange Organization (https://www.geoexchange.org/)
International Energy Agency (IEA) Heat Pumping Technologies
(http://heatpumpingtechnologies.org/)
International Ground Source Heat Pump Association (IGSHPA) (http://www.igshpa.okstate.edu/)
U.S. Department of Energy (DOE)—Geothermal Energy Program
(http://energy.gov/eere/geothermal/geothermal-energy-us-department-energy)

HEATING CONTROLS
The rst three controls increase energy ef ciency by reducing on/off cycling of boilers. The fourth
improves the ef ciency during operation.

1. Modulating ame—The heat input to the boiler can be adjusted continually (modulated) up or down
to match the heating load required.Modulating ame boilers have a minimum turn-down ratio,
below which the boiler cycles off.This ratio is 25% for most boilers, but some can be turned down to
as low as 10%.

2. Step- red—The heat input to the boiler changes in steps, usually high/low/off.Compared to steady-
state units, the capacity of the boiler can come closer to the required heating load.

3. Modular boilers—Another energy-ef cient measure is to assemble groups of smaller boilers into
modular plants.As the heating load increases, a new boiler enters on-line, augmenting the capacity
of the heating system in a gradual manner.As the heating load decreases, the boilers are taken off-
line one by one.

4. Oxygen trim systems continuously adjust the amount of combustion air to achieve high combustion
ef ciency. They are usually cost-effective for large boilers that have modulating ame controls.

VENTILATION SYSTEMS
Ventilation systems deliver conditioned air to occupied spaces. Depending on the building type,
ventilation air may be comprised of 100% outside air, such as in a laboratory building, or some mixture of
re-circulated interior air and outside air. In commercial and institutional buildings, there are a number of
different types of systems for delivering this air:

1. Constant air volume (CAV) systems deliver a constant rate of air while varying the temperature of
the supply air. If more than one zone is served by a CAV system, the supply air is cooled at a central
location to meet the need of the zone with highest demand. The other zones get overcooled or, if
comfort is to be maintained, the air is reheated at the terminal units. CAV systems with reheat are
inef cient because they expend energy to cool air that will be heated again. CAV systems with
reheat, however, provide superior comfort in any zone. Constant air ow reduces pockets of "dead"
air, and reheat provides close control of the space temperature.

https://www.wbdg.org/resources/high-performance-hvac 8/16
12/23/2018 High-Performance HVAC | WBDG - Whole Building Design Guide

2. Variable air volume (VAV) systems vary the amount of air supplied to a zone while holding the
supply air temperature constant. This strategy saves fan energy and uses less reheat than in a CAV
system. VAV systems, however, can have problems assuring uniform space temperature at low
air ow rates. At times, the minimum air ow required for ventilation or for proper temperature
control may be higher than is required to meet the space load. When this occurs reheat may be
required.

3. Low- ow air diffusers in VAV systems help maintain uniform air distribution in a space at low
air ows. These devices can be passive or active. Passive low ow diffusers are designed to mix the
supply air with the room air ef ciently at low ow. Active diffusers actually move the outlet vanes of
the diffuser to maintain good mixing at low ow. Active diffusers can also be used as VAV terminal
units.

4. Fan-powered VAV terminal units provide another method to improve air distribution at low load
conditions. These units combine the bene ts of a VAV system, by reducing central fan energy and
reheat energy, with the bene ts of a CAV system, by maintaining good air ow. There are two major
types, series and parallel: Series fan-powered units maintain constant air ow to the zone at all
times; parallel fan-powered units allow the air ow to the zone to vary somewhat, but do not allow
the air ow in the zone to drop below a desired level. Both, however, allow the central fan to throttle
down to the minimum air ow required for ventilation.

5. Raised oor air distribution delivers air low in the space, at low velocity and relatively high
temperature compared to traditional plenum mounted distribution systems. Delivering air through
a series of adjustable oor-mounted registers permits room air to be strati ed with lower
temperatures in the bottom portion of the room where people are located and high temperatures
towards the ceiling. This system type is attracting increasing interest because it has the potential to
save energy and to provide a high degree of individual comfort control. These systems have
historically used constant-volume air delivery. Manufacturers arenow beginning to offer VAV
systems that are more easily designed, installed, and operated with raised oor plenum systems.

Under oor air distribution.

VENTILATION SYSTEM CONTROLS


https://www.wbdg.org/resources/high-performance-hvac 9/16
12/23/2018 High-Performance HVAC | WBDG - Whole Building Design Guide

In recent years, ventilation control systems have become more complex and, if installed and maintained
properly, more dependable. Among the advancements are:

1. Direct digital control (DDC) systems using digital-logic controllers and electrically-operated
actuators are replacing traditional pneumatic controls. Pneumatic systems use analog-logic
controllers and air-pressure actuators. DDC systems are repeatable and reliable,provide accurate
system responses, and can be monitored from a central computer station. DDC systems also
require less maintenance than pneumatic systems. However, pneumatic controllers can be less
expensive than electric actuators. Hybrid systems use a combination of digital logic controllers and
pneumatic actuators.

2. CAV systems should have controls to reset the supply air temperature at the cooling coil to provide
the warmest air possible to the space with the highest cooling load. This reduces reheat throughout
the system. However, the temperature should be no higher than is necessary to properly
dehumidify the air. Another option to reduce reheat is to use a bypass system. Bypass systems work
like variable volume systems at the zones, but have constant air ow across the central fan.

3. VAV systems can now be designed to serve areas with as little as six tons of cooling load.Inlet vanes
or, better yet, variable speed fans should be used to control air volume. In systems that have supply
and return fans, air ow monitoring stations should be used to maintain the balance between supply
and return air ow.

4. CO2-based control systems control the amount of outside air required for ventilation. These
systems monitor the CO2 in the return air and modulate the outside air damper to provide only the
amount of outside air required to maintain desired levels. Since CO2 does not account for
contaminants released by the building materials (e.g., carpets, furniture), there must be a minimum
amount of outside air even when the spaces are unoccupied. Alternately, detectors of volatile
organic compounds (VOC) can supplement the CO2 monitoring system.

AIR-CONDITIONING EQUIPMENT
1. Chillers. In large commercial and institutional buildings, devices used to produce cool water are
called chillers. The water is pumped to air handling units to cool the air. They use either mechanical
refrigeration processes or absorption processes.

a. Mechanical refrigeration chillers may have one or more compressors. These compressors
can be powered by electric motors, fossil fuel engines, or turbines. Refrigeration systems
achieve variable capacity by bringing compressors on or off line, by unloading stages within
the compressors, or by varying the speed of the compressor. The major types of compressors
are described below:
1. Reciprocating compressors are usually found in air-cooled direct expansion (DX)
systems for residential and small commercial systems. They can also be found in chillers
with capacities of 10 through 200 tons. To better match part-load conditions and
achieve higher operating ef ciencies, multiple compressors can be employed in a single
system.
2. Scroll compressors are manufactured in the 1 to 15 ton range. Multiple compressors
can be found in water chillers with capacities of 20 to 500 tons. Scroll compressors
require less maintenance than reciprocating compressors.
3. Rotary screw compressors are found in chillers with capacities of 70 to 500 tons.

https://www.wbdg.org/resources/high-performance-hvac 10/16
12/23/2018 High-Performance HVAC | WBDG - Whole Building Design Guide

4. Centrifugal compressors are used in chillers with typical capacities of 100 to 7,000
tons. Centrifugal chillers are the most ef cient of the large-capacity chillers.

b. Absorption chillers are heat-operated devices that produce chilled water via an absorption
cycle. Absorption chillers can be direct- red, using natural gas or fuel oil, or indirect- red.
Indirect- red units may use different sources for heat: hot water or steam from a boiler,
steam from district heating, or waste heat in the form of water, air, or other gas. Absorption
chillers can be single-effect or double-effect, where one or two vapor generators are used.
Double-effect chillers use two generators sequentially to increase ef ciency. Several
manufacturers offer absorption chiller/heater units, which use the heat produced by ring to
provide space heating and service hot water.

c. Evaporative coolers, also called swamp coolers, are packaged units that cool the air by
humidifying it and then evaporating the moisture. The equipment is most effective in dry
climates. It can signi cantly reduce the peak electric demand when compared to electric
chillers.

d. Typical full-load operating ef ciencies for chillers are noted below:


Small air-cooled electric chillers have 1.6-1.1 kW/ton (Coef cient of Performance
(COP) of 2.2 to 3.2).
Large and medium-sized air-cooled electric chillers have 0.95-0.85 kW/ton (COP of 3.7
to 4.1).
Similar water-cooled electric chillers have 0.8-0.7 kW/ton (COP of 4.4 to 5.0). Lower
values such as 0.6-0.5 kW/ton chillers (COP of 5.9 to 7.0) may indicate energy ef cient
equipment, but part-load performance should also be examined.
The COP of absorption units is in the range of 0.4-0.6 for single-effect chillers, and 0.8-
1.05 for double-effect chillers.
Engine-driven chillers attain COPs of 1.2 to 2.0.

2. Condensers are heat exchangers that are required


for chillers to reject heat that has been removed from
the conditioned spaces. Condensers can be either
air-cooled or water-cooled. Water-cooled
condensers often rely on rooftop cooling towers for
rejecting heat into the environment; however, it is
possible to reject the heat to the ground or river
water.
a. Air-cooled condensers are offered on smaller,
packaged systems (typically from less than one
ton to 120 tons). They are initially less costly
Cooling tower
than water-cooled condensers, but do not
allow the chiller to operate as ef ciently.

b. Water-cooled condensers use water that is cooled directly from the evaporative condenser
or indirectly via a cooling tower. The lower temperature achieved by evaporating water
allows chillers served by water-cooled condensers to operate more ef ciently.

c. A waterside economizer consists of controls and a heat exchanger installed between the
cooling tower water loop and the chilled water loop. When the outdoor air temperature is low
and/or the air is very dry (i.e., when the wet-bulb temperature is low), the temperature of the

https://www.wbdg.org/resources/high-performance-hvac 11/16
12/23/2018 High-Performance HVAC | WBDG - Whole Building Design Guide

cooling tower water may be low enough to directly cool the chilled water loop without use of
the chiller, resulting in signi cant energy savings.

AIR-CONDITIONING EQUIPMENT CONTROLS


1. Controls that signi cantly affect the energy ef ciency of chillers include:
a. Variable speed drives achieve good part-load performance by matching the motor output to
the chiller load, and by cycling off at a lower fraction of capacity than constant-speed chillers.
b. Multiple compressor achieves a closer match of the load than single-compressor chillers by
sequencing the compressors as needed.
c. Water temperature reset controls raise the water temperature as the demand decreases,
allowing for more ef cient chiller operation.

2. Strategies that signi cantly affect the energy ef ciency of cooling towers include the use of:
a. Variable-speed or multiple-speed fans
b. Wet-bulb reset strategies, where the temperature of the cooling water is adjusted according
to the temperature and humidity of outside air (instead of maintaining it constant)
c. Fans and pumps that use variable frequency drive (VFD) controls to reduce energy use at
part-load

3. Integrated chiller plant controls use monitoring and computational strategies to yield the minimum
combined energy cost for the chillers, cooling towers, fans, and pumps.This approach can be
signi cantly more effective (though more dif cult to implement) than optimizing the operation of
each piece of equipment independently.

HEAT RECOVERY
Air is blown across copper coils to reject heat from this residential air-cooled condenser. Heat Recovery is
an important component of many energy ef cient HVAC systems.

Enthalpy recovery wheel.

Types of heat recovery include:

a. Air-to-air heat exchangers transfer heat or "coolth" from one air stream to another. They are usually
classi ed as one of the following:
Plate heat exchangers, with 60%–75% ef ciencies
Glycol loop heat exchangers, with 50%–70% ef ciencies (including pump energy use)

https://www.wbdg.org/resources/high-performance-hvac 12/16
12/23/2018 High-Performance HVAC | WBDG - Whole Building Design Guide

Heat pipe heat exchangers, with ef ciencies as high as 80%

b. Desiccant wheels retrieve both sensible and latent heat, with ef ciencies as high as 85%. Desiccant
dehumidi cation of the air is achieved by inserting a rotating wheel in the air stream that needs to
be dried. The desiccant extracts moisture from the air stream. The wheel then rotates, exposing the
moist part to another air stream that dries (or regenerates) the desiccant material. Two methods of
regeneration are typical:
Energy (Enthalpy) recovery wheels are located in the outside intake and the exhaust air
streams. The exhaust air regenerates the desiccant.
Gas- red desiccant dehumidi cation packages are located in the outside intake air stream or
in the entire supply air stream. Outside air is heated by the gas furnace and is blown over the
wheel to regenerate the desiccant.

c. Other forms of heat exchange include:


Indirect evaporative cooling (IDEC) uses water-to-air heat exchange to precool air.
Electric heat recovery chillers receive up to 50% of rejected heat, usually though split or
multiple condensers.
Absorption chiller/heaters can use a fraction (typically 50%) of the heat input for cooling and
the rest for heating.
Gas- red, engine driven chillers retrieve much of the heat rejected (usually 20% - 50%).

COGENERATION
Cogeneration (/resources/distributed-energy-resources-der) is a process in which electric power is
generated at the facility where the waste heat is recovered to produce service hot water, process heat, or
absorption cooling. Currently, packaged cogeneration systems between about 60-600 kW are widely
available. Extensive research and marketing efforts are underway for smaller systems (as low as 4 kW).

FUEL CELLS
Fuel cells (/resources/fuel-cells-and-renewable-hydrogen) use chemical processes to generate electricity.
The heat generated by fuel cells can also be recovered, as in cogeneration. Currently, the minimum size for
a fuel cell in building applications is 200 kW. Note that fuel cells need continuous, full-load operation.

APPLICATION
The bene ts of high performance, energy-ef cient HVAC systems are universal. Therefore, high
performance HVAC systems can be installed in all different types of buildings, including of ce buildings
(/building-types/of ce-building), schools (/building-types/educational-facilities), hospitals (/building-
types/health-care-facilities), and courthouses (/building-types/federal-courthouse-1).

REPRESENTATIVE EXAMPLE
Sam Nunn Atlanta Federal Center, Atlanta, GA
(http://eber.ed.ornl.gov/pub/blddata/TRANE%20samnunn.pdf) 
Commercial Buildings, Saving Energy with Energy-Ef cient HVAC Systems in Commercial Buildings

https://www.wbdg.org/resources/high-performance-hvac 13/16
12/23/2018 High-Performance HVAC | WBDG - Whole Building Design Guide

RELEVANT CODES AND STANDARDS


Energy Policy Act of 2005 (EPACT) (/ffc/fed/congressional-acts/energy-policy-act-2005)—The
enactment of the Energy Policy Act in 1992 has eased many restrictions of the Public Utility
Holding Company Act of 1935 (PUHCA).Forty-six states in the United States have some form of
deregulation plan for electric utilities. Under the new framework, facility owners can solicit
proposals from utilities, including independent power producers, for their energy services.Thus,
contract negotiations at the pre-design phase could result in signi cantly lower energy cost for the
same energy use. While this is good news for consumers, it does suggest that investments in energy
ef ciency and renewable energy equipment may be harder to justify in the short-term.

For more information on regulations:

ASHRAE Standards and Guidelines


Standard 62.1 Ventilation for Acceptable Indoor Air Quality (https://www.ashrae.org/resources-
-publications/bookstore/standards-62-1--62-2)
ANSI/ASHRAE/IES Standard 90.1 Energy Standard for Buildings Except Low-Rise Residential
Buildings (https://www.ashrae.org/resources--publications/bookstore/standard-90-1)
Guideline 1.1 HVAC&R Technical Requirements for the Commissioning Process
(http://www.techstreet.com/ashrae/standards/guideline-1-1-2007-hvac-r-technical-
requirements-for-the-commissioning-process?product_id=1573306)

Energy Information Administration—Electricity (http://www.eia.gov/electricity/)


PBS-P100 Facilities Standards for the Public Buildings Service (/ffc/gsa/criteria/pbs-p100)

ADDITIONAL RESOURCES
DESIGN AND ANALYSIS TOOLS
Building energy simulations allow the system designer to compare different HVAC systems and control
strategies. These tools vary in their scope and level of complexity. Some tools analyze individual
components of HVAC systems (e.g., motors) under simpli ed assumptions regarding the component use
(e.g., annual hours of operation). Other tools simulate entire buildings, including energy gains/losses
through the building envelope, energy gains from internal loads, and energy used by the HVAC systems to
maintain user-prescribed space conditions (e.g., temperature, humidity, ventilation rates). The latter tools
require expertise and experience to obtain accurate results due to the detailed input required. Some
building simulation packages have reduced input requirements. The trade-off is that these tools are
typically not as accurate, since the programs use defaults or assumptions to replace the user inputs.
However, simpli ed tools can be used early in the design process to investigate the in uence of HVAC
system selection on energy ef ciency strategies such as daylighting.

More information on a variety of tools, including those listed below, can be found at:

Building Energy Software Tools (BEST) (http://www.buildingenergysoftwaretools.com/) formerly


hosted by the U.S. Department of Energy (DOE)
WBDG Energy Analysis Tools (/resources/energy-analysis-tools)

WHOLE BUILDING ANNUAL ENERGY SIMULATION SOFTWARE


https://www.wbdg.org/resources/high-performance-hvac 14/16
12/23/2018 High-Performance HVAC | WBDG - Whole Building Design Guide

Detailed Input
DOE-2 (http://doe2.com/)
EnergyPlus™ (/additional-resources/tools/energyplus)

INDIVIDUAL COMPONENT ENERGY ANALYSIS


MotorMaster (http://www.energy.gov/eere/amo/downloads/motormaster-software-tool-brochure)
Pumping System Assessment Tool (http://www.energy.gov/eere/amo/articles/pumping-system-
assessment-tool)

GOVERNMENT AGENCIES AND INITIATIVES


Department of Energy (DOE) (http://www.energy.gov/)
Federal Energy Management Program (FEMP) (http://energy.gov/eere/femp/federal-energy-
management-program)—Information on Energy Technologies
Of ce of Energy Ef ciency and Renewable Energy (EERE) (http://energy.gov/eere/of ce-
energy-ef ciency-renewable-energy)
Of ce of Scienti c and Technical Information (OSTI) (http://www.osti.gov/)

Energy Information Administration (EIA) (http://www.eia.doe.gov/)


Environmental Protection Agency (EPA) Energy Star Program (http://www.energystar.gov/)
National Technical Information Service (NTIS) (http://www.ntis.gov/)
National Institute of Standards and Technology (NIST) (http://www.nist.gov/)
U.S. Department of Commerce (http://www.commerce.gov/) NOTE: This is a repository for all
publications by the federal labs and contractors.
U.S. EPA Atmospheric Pollution (https://www.epa.gov/)
USA.gov (https://www.usa.gov/)

NATIONAL LABORATORIES AND RESEARCH CENTERS


Lawrence Berkeley National Laboratories (LBNL) (http://www.lbl.gov/)
National Renewable Energy Laboratory (NREL) (http://www.nrel.gov/)
Oak Ridge National Laboratory (ORNL) (http://www.ornl.gov/)
Paci c Northwest National Laboratory (PNNL) (http://www.pnl.gov/)

PROFESSIONAL AND TRADE ASSOCIATIONS, AND INTEREST


GROUPS
Air-Conditioning and Refrigeration Institute (ARI) (http://www.ahrinet.org/)
American Boiler Manufacturers Association (ABMA) (http://abma.com/)
American Society of Heating, Refrigeration and Air-Conditioning Engineers (ASHRAE)
(http://www.ashrae.org/)
Association of Energy Engineers (AEE) (http://www.aeecenter.org/)
Cooling Technology Institute (http://www.cti.org/)
Electric Power Research Institute (EPRI) (http://www.epri.com/Pages/Default.aspx)
Geothermal Exchange Organization (http://www.geoexchange.com/)
Geothermal Resources Council (GRC) (http://www.geothermal.org/)
International Ground Source Heat Pump Association (IGSHPA) (http://www.igshpa.okstate.edu/)

https://www.wbdg.org/resources/high-performance-hvac 15/16
12/23/2018 High-Performance HVAC | WBDG - Whole Building Design Guide

International Energy Agency (IEA) Heat Pumping Technologies Centre


(http://heatpumpingtechnologies.org/)
Sheet Metal and Air Conditioning Contractors' National Association (SMACNA)
(http://www.smacna.org/)

TRADE PUBLICATIONS
ACHRNEWS—Air-Conditioning, Heating and Refrigeration News (http://www.achrnews.com/)
American Society of Heating, Refrigeration and Air-Conditioning Engineers (ASHRAE) Journal
(https://www.ashrae.org/resources--publications/periodicals/ashrae-journal)
Consulting-Specifying Engineer (http://www.csemag.com/)
Energy User News
Engineered Systems Magazine (http://www.esmagazine.com/)
Heating/Piping/Air-Conditioning HPAC Engineering Magazine (http://hpac.com/air-conditioning)

BOOKS
Building Technology: Mechanical and Electrical Systems, 2nd Edition
(http://www.wiley.com/WileyCDA/WileyTitle/productCd-0471593192.html) by Stein, Benjamin. New
York: John Wiley & Sons, Inc., 1997.
Energy-Ef cient Design and Construction for Commercial Buildings by Steven Winter Associates, Inc.
New York: McGraw-Hill, 1997. ISBN 0-07-071159-3.
Energy-Ef cient Operation of Commercial Buildings: Rede ning the Energy Manager's Job by Herzog,
Peter. New York: McGraw-Hill, 1997. ISBN 0-07-028468-7.
Simpli ed Design of HVAC Systems (http://www.wiley.com/WileyCDA/WileyTitle/productCd-
0471532800.html), by Bobenhausen, William. New York: John Wiley & Sons, Inc., 1994.

ARTICLES
HVAC Characteristics and Occupant Health
(https://search.proquest.com/openview/9104a1dd8a8cba77bde8d0878626a320/1?pq-
origsite=gscholar&cbl=41118) by W.K. Sieber, M.R. Petersen, L.T. Stayner, R. Malkin, M.J. Mendell,
K.M. Wallingford, T.G. Wilcox, M.S. Crandall, and L. Reed. ASHRAE Journal, September 2002.
Ventilation Rates and Health (http://www.osti.gov/scitech/servlets/purl/803802)  by Olli Seppänen,
Fellow ASHRAE, William J. Fisk, P.E., Member ASHRAE, and Mark J. Mendell, Ph.D. ASHRAE Journal,
August 2002.

OTHER
GSA Sustainable Facilities Tool (SFTool) (https://sftool.gov/)—SFTool's immersive virtual
environment addresses all your sustainability planning, designing and procurement needs.

https://www.wbdg.org/resources/high-performance-hvac 16/16