Bus Duct / Bus Ways (Metabar & Isobar)
Bus Duct / Bus Ways (Metabar & Isobar)
Bus Duct / Bus Ways (Metabar & Isobar)
APPLICATION
SELECTION RANGE:
METABAR ISOBAR
Page 5 Page 27
All the range of busducts are well designed and thoroughly Air Insulated Segregated Phase Busduct
tested in line with IEC 61439-6. Both IPD & C&S Electric are (125~2000A) (3.3kV ~ 33kV)
accredited to ISO 9001:2008. (upto 1.0kV) (upto 5000A)
Busduct is a system of distributing electric power using copper or aluminium busbars with suitable
enclosures to prevent the busducts from getting damaged from foreign bodies.
Busbars are now becoming irreplaceable simply because of the convenience and safety factor. While
using traditional cables, the cost of cabling and trunking and the time taken for installation is much
higher than busbars.
Installing busbars over conventional cabling has a range of advantages some of which are mentioned below:
Apart from these advantages, there are a variety of other benefits that busbars have over cables. With the network and distribution requirement grow-
ing day by day, traditional cables will soon be history and busbars will continue to gain importance.
I Features:
Finishing is superior, hence adds to aesthetics of building. Improper laying of the cables may spoils the aesthetics
of building.
Power feeding to Multiple floor building can be done with Power tap off can be done from the single system installed..
single Bus-trunking system. Incase the load changes we have to just replace the Tap off
boxes of higher rating.
Power tap-off can be achieved from the single system in- Not possible. Additional cables need to be laid up to the
stalled. Incase the load changes, one may simply replace the particular floor.
Tap off boxes to higher ratings.
II Voltage Drop :
The voltage drop of bustrunking is less as compared to The voltage drop is more in cables.
cables.
III Structure :
Example for 3200A(Cu) dimensions : 151(w)x340(h) and Cables and supporting structure example for 700mm wide i.e.,
light in weight. cable tray etc. is very heavy and occupies more space.
Total run is made up of multiple elements which are joined As single lengths of multiple cables are installed, making them
together. Thus making the complete system maintenance maintenance non-friendly.
friendly.
Easy retrofitting of the elements is possible in case the Easy retrofitting of the element is not possible in case the location
location and the consumer load changes. and consumer load.
Totally enclosed, tamper-proof. Fit and forget system. Insulation can wear off with time. Can get damaged by rodents.
Has to be maintained on regular basis.
IV Degree of Protection :
IP54 for plug-in type, IP55/65 for feeder type. No protection as such.
V Enclosure :
It consists of busbars in a protective enclosure, including Cables are simply insulated with multiple layers of PVC.
straight lengths, fittings, devices and accessories.
High Short circuit strength & high fire protection. Low Short circuit strength & low fire protection.
VI Termination :
Direct termination through busbars. The method for cable termination is very cumbersome.
Termination is simple and easy. Additional supports are required to hold the cables inside the
panel.
Have a highly compact structure and can be bent up to 90 Cables are generally installed in bundles & with such cross sec-
degrees. tions they can not be bent tightly.
When sizing busbars the designer only needs to make calcu- It is necessary to protect each cable individually with a fuse and
lations on a single riser which reduces design time and costs. when laying the cables in bundles it is necessary to anchor them
properly so that they can withstand the electrodynamic forces
generated in the event of a short circuit. So, the designers have
to spend more time on calculations.
No extra holes/cutouts required. Holes to be made in the gland plate for fixing cable glands.
No cable tray required, supported on ceilings / walls. Cable tray or the digging of the trench is required to lay the
cables.
No special tools are required. Special tool are required for crimping the cable lugs.
Design verified switchgear assembly, limits defined in the Limits depend on the laying method and cable accumulation.
manufacturer’s catalogue. The derating factor must be determined / calculated.
IX Halogen Free :
Principally free from halogen. PVC cables are not free from halogen. Halogen-free cables are
very expensive.
X Damage by rodents :
Bus-bar systems cannot be damaged by rodents, this is Cables can be damaged by rodents.
prevented by the steel casing.
TECHNICAL SPECIFICATIONS
Busbar Material (Phase/Neutral) Copper 99.9% pure ETP grade Aluminum with high conductivity & strength
Degree of Protection IP54 for plug in type , IP55 for feeder type (IP65 on request)
3 Phase (100%)+ Integral 3 Phase (100%)+100% Neutral 3 Phase+100% Neutral 3 Phase+100% Neutral 3 Phase+200% Neutral+
ground Earth + Integral ground Earth +50% Integral Earth +100% Internal Earth + integral Ground Earth
integral Ground Earth
Rated Current (In) Amps 630 800 900 1000 1100 1250
Product Code -- SBC SBC SBC SBC SBC SBC
040N1 050N1 06N1 070N1 080N1 100N1
Busbar size per phase (No. of busbars) mm 6x40(1) 6x50(1) 6x60(1) 6x70(1) 6x80(1) 6x100(1)
Rated Current (In) Amps 1600 1800 2000 2250 2500 3200
Product Code -- SBC SBC SBC SBC SBC SBC
125N1 150N1 175N1 200N1 230N1 125N2
Busbar size per phase (No. of busbars) mm 6x125(1) 6x150(1) 6x175(1) 6x200(1) 6x230(1) 6x125(2)
Rated Current (In) Amps 3600 4000 4500 5000 6000 6600
Product Code -- SBC SBC SBC SBC SBC SBC
150N2 175N2 200N2 230N2 175N3 200N3
Busbar size per phase (No. of busbars) mm 6x150(2) 6x175(2) 6x200(2) 6x230(2) 6x175(3) 6x200(3)
3 Phase (100%)+ Integral 3 Phase (100%)+100% Neutral 3 Phase+100% Neutral +100% Internal 3 Phase+200% Neutral+
ground Earth + Integral ground Earth Earth + integral Ground Earth integral Ground Earth
Rated Current (In) Amps 400 500 630 700 800 1000
Product Code ---- SBA SBA SBA SBA SBA SBA
040N1 050N1 060N1 070N1 080N1 100N1
Busbar size per phase {No. of busbars) mm 6x40(1) 6x50(1) 6x60(1) 6x70(1) 6x80(1) 6x80(1)
Rated Three phase Peak short time current (lpk) kA 84 105 105 143 105 105
Rated Single Phase RMS Short Time current for 1 Second (lcw) kA 24 30 30 39 30 30
Rated Single phase Peak short time current (lpk) kA 50.4 63 63 81.9 63 63
Rated Current (In) Amps 1250 1350 1600 1800 2000 2250
Product Code ---- SBA SBA SBA SBA SBA SBA
125N1 150N1 175N1 200N1 230N1 125N2
Busbar size per phase {No. of busbars) mm 6x125(1) 6x150(1) 6x175(1) 6x200(1) 6x230(1) 6x125(2)
Rated Three phase Peak short time current (lpk) kA 143 143 220 220 220 264
Rated Single Phase RMS Short Time current for 1 Second (lcw) kA 39 39 60 60 60 72
Rated Single phase Peak short time current (lpk) kA 81.9 81.9 132 132 132 158.4
Rated Current (In) Amps 2500 3200 3600 4000 4500 5000
Product Code ---- SBA SBA SBA SBA SBA SBA
150N2 175N2 200N2 230N2 175N3 200N3
Busbar size per phase {No. of busbars) mm 6x150(2) 6x175(2) 6x200(2) 6x230(2) 6x175(3) 6x200(3)
Rated Three phase Peak short time current (lpk) kA 264 264 264 264 264 264
Rated Single Phase RMS Short Time current for 1 Second (lcw) kA 72 72 72 72 72 72
Rated Single phase Peak short time current (lpk) kA 158.4 158.4 158.4 158.4 158.4 158.4
=Transformer to Panel
=Panel to Panel
=Generator to Panel
=Panel to Rising main
=Panel to Horizontal Distribution Bustrunking
UNIBLOCK JOINT
EDGE ELBOW
FLAT ELBOW
FLAT TEE
FLANGED END
END COVER
=Flange End Box are used for matching the standard Bustrunking flange assembly with the PaneV DG/ Trt. flange.
=Flange Bellow need to be fixed between Flanged End Box and Gen set termination box to avoid impact of vibrations of
Genset being transferred to bustrunking.
REDUCER
These are required to connect two dissimilar rating of bustrunking. Reducer may be designed
with switching or isolating device
SECTIONAL ISOLATOR
These are required to isolate the bustrunking run, in between, for various reasons. Section Isolator Unit can be fitted with Load
Breaker Switches/ SF Us/ MCCBs.
VERTICAL SUPPORT
- Vertical Support is recommended per floor per rising main along with rigid or spring
hanger when the floor height is between 3.5 to 4.5 Mtrs.
- Vertical Support is common for all ratings of Sandwich Rising Mains.
- Vertical Support is installed approximately at 2.0 Mir. Height for floor level.
Spring Hanger
Spring Hanger
These support need to be provided on horizontal feeder run at an interval of 1.5 Meter
(or as per site requirement).
PLUG-IN-BOX
=Plug in box enclosure is made from G.I with side hinged door.
=Plug in contacts are made out of silver plated copper with spring steel backup pressure clips for ensuring uniform pressure and low
contact resistance.
=For cables entry, provision of gland plates are provided on both sides and bottom of Plug in Box.
=Plug in box are suitable for MCB/MCCB’s with rotary handle and door interlocking.
=Plug in boxes are available with Interlocking with bustrunking to ensure “Plug-in” and “PlugOut” possible only in” OFF” Condition.
=Silver Plated contacts are properly shrouded / isolated.
=Plug in boxes can only befitted on to the Busducts with corrected polarity.
=Plug in box shall also be supplied with meters / sockets / lamps etc.
Up to 100V AC
Three phase conductors and/or
50,100% Protective internal & isolated earth
And 100% Neutral
SPECIFICATIONS
Rated Frequency 50 Hz / 60 Hz
Busbar Material (Phase/Neutral) Copper (full round edge),99.9% pure ETP grade Aluminium (full round
edge), 97.5% pure.
Degree of Protection IP 54
Rated Current (In) Amps 125 315 400 500 630 800
Product Code ---- CBC CBC CBC CBC CBC CBC
125 315 400 500 630 800
Busbar size per phase {No. of busbars) mm Dia 6.0 6x20(1) 6x30(1) 6x40(1) 6x50(1) 6x70(1)
Overall Height (H) mm 60 85 85 85 95 115
Rated Three Phase RMS Short Time Current for 1 Second (lcw) kA 5 20 30 35 50 50
Rated Three phase Peak short time current (lpk) kA 7.5 40 63 73.5 105 105
Rated Single Phase RMS Short Time current for 1 Second (lcw) kA 3 12 18 21 30 30
Rated Single phase Peak short time current (lpk) kA 4.5 24 36 44.1 63 63
Rated Current (In) Amps 200 250 315 400 500 630 800 1000 1250
Product Code ---- CBC CBC CBC CBC CBC CBC CBC CBC CBC
200 250 315 400 500 630 800 1000 1250
Busbar size per phase {No. of busbars) mm 6x20(1) 6x30(1) 6x40(1) 6x50(1) 6x70(1) 6x90(1) 6x50(2) 6x70(2) 6x90(2)
Overall Height (H) mm 85 85 85 95 115 135 190 230 270
Rated Three Phase RMS Short Time Cur- kA 10 15 25 30 35 50 50 50 50
rent for 1 Second (lcw)
Rated Three phase Peak short time cur- kA 17 30 52.5 63 73.5 105 105 105 105
rent (lpk)
Rated Single Phase RMS Short Time cur- kA 6 9 15 18 21 30 30 30 30
rent for 1 Second (lcw)
Rated Single phase Peak short time cur- kA 10.2 15.3 30 36 44.1 63 63 63 63
rent (lpk)
ACCESSORIES
Following accessories will be supplied along with the Air insulated busduct system
- Up to 500V AC
- Three phase conductors
- Cu-conductors range up to 63A
=The Lighting Trunking (LB) system is the ideal solution for the lighting and low
power distribution mainly for industrial and commercial applications
=LB systems simplify the accurate and uniform installation of continuous lighting
layouts. Their high degree of flexibility, low fire load and uniform appearance
speak for themselves.
=LB is extremely easy and quick to be installed and shows its flexibility during
the planning of its installation, during the installation and in the everyday
usage.
=LB is optimum solution for fixing the trunking elements to raised floors, over
head and false ceiling due to its IP 55 protection degree.
=C&S LB systems are manufactured using the latest production
technologies available worldwide according to ISO standards and the product
is designed as per the IEC 60439 (1 &2) and IS 8623 (1 &2).
=LB system can be mounted edgewise or flat wise, horizontally or vertically in
any direction.
SPECIFICATIONS
Busbar Material (Phase/Neutral) ETP grade copper 99.9% Pure (Tin Plated)
Degree of Protection IP 54
STRAIGHT LENGTH
=Aluminum enclosure 1.0 mm thick serves as a protective earthing.
=Joint between two section is made through push fit joints ensure electrical continuity (PE) after tightening 2 joint cover screws.
PLUG IN BOX
ISOBAR range covers Isolated Phase Busduct, Segregated Phase Busducts and Non-Segregated Phase Busducts.
Today, C&S have an enviable track record of having associated with 6 units of 800 MW, 45 units of 660 MW, 33 units of 500 MW, 100 units of 250
MW, 50 units of 150 MW Thermal Power Stations, Hydro Power Plants and Nuclear Power Plants, besides many Captive/Private Power Projects of
capacity less than 100 MW.
ISOBAR Busduct have been successfully type tested for various type tests Viz Short circuit tests, temperature rise tests, d ielectric Voltage withstand test ,
earthquake resistant tests, degree of protections tests at renowned laboratories at KEMA Netherlands, Czech Republic, EDF-France
CPRI- Bangalore/ Bhopal , IIT-Roorkee etc.
C&S offers a wide range of natural air cooled Isolated Phase Busducts
from 11 to 38 kV up to 30000 A with Short Circuit Current withstand
capacity reaching test values even up to 312 kA RMS for 1 sec. and 844
kA peak. These IPB’s have applications in all type of generating stations
between 60 MW to 1000 MW.
SALIENT FEATURE
=Excellent shielding under short circuit conditions, near elimination of forces.
=Eliminates phase-to-phase faults.
=Reduces proximity effect between the main current carrying conductors of the
adjacent phase to almost zero due to magnetic shielding, on the one hand,
and large center spacing, on the other.
=It provides complete protection for operating personnel from high touch or step
voltages across the enclosure and the metallic structure.
=Best suitable for adverse climatic and Highly polluted atmospheric conditions.
=The bus system is easy to manufacture, bend, handle and install.
CONFORMITY TO STANDARDS
Isolated Phase Busducts are designed, manufactured and tested as per the International Standards BIS 8084, ANSI/ IEEE C37.23-2003, IEC 62271
etc.
CONDUCTORS
The Bus conductor in tubular form is manufactured from aluminum alloy plates/ sheets by rolling Into standard cylinders and successive
standard cylinders are welded together to form shipping lengths for higher current ratings. Aluminum alloy extruded tubes are also used as bus
conductor for lower current ratings up to appx. 6000 A. To facilitate and improve the heat dissipating capacity and to reduce temperature rise
on the bus bars, matt black paint is always applied on its external surface.
ADVANTAGES
=Impossible to have Phase to phase fault.
=Excellent shielding to the busbars under short circuit conditions and near elimination of forces.
=Voltage rise in enclosure is very low due to its resistive origin and hence free access to the personnel.
=Provides excellent degree of protection- IP65.
=Undesirable current loops are avoided beyond a regular pattern, due to electrical isolation form structures and hence heating in
the supporting beams is eliminated.
C&S offers a wide range of Segregated Phase Busducts for medium voltage applications from 3.3 kV
to 33 kV up to 5000 A with short circuit capacity of 50 kA for 3 sec.
Segregated Phase Busducts are widely used in power generating stations and industrial or distribution
plants for lower capacity generator connections, inter-connections between switchgear and transformers.
SALIENT FEATURES
=Excellent shielding under short circuit condition.
=Minimizes phase to phase faults.
=Designed for degree of protection of IP-55 for outdoor and IP-54 for indoor Busducts.
CONSTRUCTION
Segregated Phase Busducts are designed, manufactured and tested as per the National / International Standards BIS 8084, ANSI/IEEE C37.23,
IEC 62271 etc.
C&S offers a wide range of Non-Segregated Phase Busducts for Low Voltage applications from 415 V to 1.1 kV up to 6500 A with a short
circuit capacity 80 kA for 1 sec.
Non-Segregated Phase Busducts are commonly used in industrial utilities, power plants for interconnection between switchgear and
transformers and also for lower capacity of generator
(viz DG sets).
SALIENT FEATURES
=Reduced proximity effect by virtue of using flat Busbars.
=Designed for degree of protection of IP555 for outdoor and IP54 for indoor Busducts.
CONSTRUCTION
Non-Segregated Phase Busducts are designed, manufactured and tested as per IEC-61439/ BIS-8623.